Air System Sizing Summary for UE-17

Project Name: CAPILLA LIMATAMBO 09/29/2020


Prepared by: 09:55AM

Air System Information


Air System Name .............................................. UE-17 Number of zones ........................................................... 1
Equipment Class ............................................ UNDEF Floor Area .............................................................. 116.3 ft²
Air System Type ............................................. SZCAV Location ........................................................ Lima, Peru

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ........... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 0.7 Tons Load occurs at ................................................. Jan 1300
Total coil load ........................................................ 8.0 MBH OA DB / WB ................................................... 84.7 / 74.7 °F
Sensible coil load ................................................... 6.5 MBH Entering DB / WB ........................................... 76.8 / 66.1 °F
Coil CFM at Jan 1300 ........................................... 358 CFM Leaving DB / WB ............................................ 60.0 / 59.0 °F
Max block CFM .................................................... 358 CFM Coil ADP .................................................................. 58.1 °F
Sum of peak zone CFM ........................................ 358 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 0.813 Resulting RH ............................................................... 56 %
ft²/Ton ................................................................. 174.2 Design supply temp. ................................................. 58.0 °F
BTU/(hr-ft²) ........................................................... 68.9 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 1.60 gpm Max zone temperature deviation ................................ 0.0 °F

Supply Fan Sizing Data

Actual max CFM ................................................... 358 CFM Fan motor BHP ........................................................ 0.00 BHP
Standard CFM ...................................................... 357 CFM Fan motor kW .......................................................... 0.00 kW
Actual max CFM/ft² ............................................... 3.08 CFM/ft² Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................ 27 CFM CFM/person ............................................................. 6.74 CFM/person
CFM/ft² ................................................................. 0.23 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 3


Air System Design Load Summary for UE-17
Project Name: CAPILLA LIMATAMBO 09/29/2020
Prepared by: 09:55AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.7 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 116 ft² 1717 - 116 ft² 529 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 116 ft² 0 - 116 ft² 0 -
Partitions 465 ft² 3 - 465 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 130 W 442 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3412 - 0 0 -
People 4 980 820 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6554 820 - 529 0
Zone Conditioning - 6263 820 - -270 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 358 CFM 0 - 358 CFM 0 -
Ventilation Load 27 CFM 248 677 27 CFM 283 0
Supply Fan Load 358 CFM 0 - 358 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6511 1497 - 13 0
Central Cooling Coil - 6511 1497 - 0 0
>> Total Conditioning - 6511 1497 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 2 of 3


Space Design Load Summary for UE-17
Project Name: CAPILLA LIMATAMBO 09/29/2020
Prepared by: 09:55AM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2P-210 SALA COMPUTO '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.7 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 116 ft² 1717 - 116 ft² 529 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 116 ft² 0 - 116 ft² 0 -
Partitions 465 ft² 3 - 465 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 130 W 442 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3412 - 0 0 -
People 4 980 820 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6554 820 - 529 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2P-210 SALA COMPUTO '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
H EXPOSURE
ROOF 116 0.350 - 1717 - 529

Hourly Analysis Program v4.90 Page 3 of 3