Air System Sizing Summary For UE
Air System Sizing Summary For UE
Calculation Months .................................... Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ........... Individual peak space loads
Total coil load ........................................................ 0.7 Tons Load occurs at ................................................. Jan 1300
Total coil load ........................................................ 8.0 MBH OA DB / WB ................................................... 84.7 / 74.7 °F
Sensible coil load ................................................... 6.5 MBH Entering DB / WB ........................................... 76.8 / 66.1 °F
Coil CFM at Jan 1300 ........................................... 358 CFM Leaving DB / WB ............................................ 60.0 / 59.0 °F
Max block CFM .................................................... 358 CFM Coil ADP .................................................................. 58.1 °F
Sum of peak zone CFM ........................................ 358 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 0.813 Resulting RH ............................................................... 56 %
ft²/Ton ................................................................. 174.2 Design supply temp. ................................................. 58.0 °F
BTU/(hr-ft²) ........................................................... 68.9 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 1.60 gpm Max zone temperature deviation ................................ 0.0 °F
Actual max CFM ................................................... 358 CFM Fan motor BHP ........................................................ 0.00 BHP
Standard CFM ...................................................... 357 CFM Fan motor kW .......................................................... 0.00 kW
Actual max CFM/ft² ............................................... 3.08 CFM/ft² Fan static ................................................................. 0.00 in wg
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2P-210 SALA COMPUTO '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.7 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 116 ft² 1717 - 116 ft² 529 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 116 ft² 0 - 116 ft² 0 -
Partitions 465 ft² 3 - 465 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 130 W 442 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3412 - 0 0 -
People 4 980 820 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6554 820 - 529 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2P-210 SALA COMPUTO '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
H EXPOSURE
ROOF 116 0.350 - 1717 - 529