You are on page 1of 7

P1-1 P1-4 P1-6 P2-1 P1-2 P2-23 P1-16

5 7 9 9A 102 704

J1 14

DWG. NO.
P3-1 KM1004-3 KM1004-7 KM1004-9 KM1004-11
CB CB
CB CB
CLOSE BLOCKER SWITCH AUX READY NOT READY
CLOSED BB3
LOCATED IN THE TRUCK CLOSED
KM1004-4 KM1004-8 KM1004-10 KM1004-12 52b
***- SEE NOTE
P3-4 **- SEE NOTE
J4 J5

J3
KM1005-1
KM1005-11
KM1003-2 KM1005-3 KM1005-5 13A

Constant Close Blocking Virtual Close Coil 2nd


Control Circuit * SEE NOTE Virtual Open Coil * SEE NOTE
Virtual Open Coil
* SEE NOTE
Power
J2 P3-2
KM1005-2 KM1005-4 KM1005-6
CLOSE BLOCKER SWITCH
KM1003-3 KM1005-12 LOCATED IN THE TRUCK

P3-3

13

103 6 10 10A 303 705

P1-3 P1-5 P1-7 P2-2 P1-24 P2-24


P1-17
2ND READY NOT READY PIN
Constant Control Power CLOSE TRIP/OPEN TRIP/OPEN CONTACT CONTACT MONITOR

P1-8 P1-10 P1-12 P1-14 P1-18 P1-20 P1-22 P2-5 P2-7 P2-9 P2-11 P2-13 P2-15 P2-17 P2-19 P2-21 NOTES:
All contacts are shown with the breaker in the OPEN POSITION & READY
15 51 55 59 53 57 61 815 851 855 859 863 813 853 857 861
unless otherwise specified .
52a 52a 52a 52a 52b 52b 52b 52a 52a 52a 52a 52a 52b 52b 52b 52b
* Coil Monitoring Devices cannot be used and will be recognized
16 52 56 60 54 58 62
816 852 856 860 864 814 854 858 862
as a Close or Open Signal.
** READY Contact is CLOSED when the breaker is ready for operation.
P1-9 P1-11 P1-13 P1-15 P1-19 P1-21 P1-23 P2-6 P2-8 P2-10 P2-12 P2-14 P2-16 P2-18 P2-20 P2-22
"READY" monitors control power, capacitor voltage, Close & Open Coils & uP Watchdog.
AUXILIARY CONTACT -BB8 TYPE 24 AUXILIARY CONTACT -BB3 TYPE 19 AUXILIARY CONTACT -BB2 - TYPE 24 AUXILIARY CONTACT -BB1 - TYPE 19 *** NOT READY Contact is CLOSED when the breaker is not ready for operation.
AUXILIARY AVAILABLE FOR CUSTOMER USE

AO1 SCHEMATIC WIRING DIAGRAM - OPTIONAL

AMVAC WIRING DIAGRAM


MODEL 4

Power Technology 1B11971 2


Inc. Medium Voltage REV
SIZE B SHT 02 CONT ON 03

NEXT ASSY: BY: R HOLMES CHD: S BOUNSAV APP:E DULLNI SHOP ORDER:
DATE: 7/1/09 DATE: 7/1/09 DATE: 7/1/09
2 ADDED "MODEL 4" TO TITLE
MULTIPLE CHANGES TO SCHEMATICS
EG MM
2/2/11 2/2/11 2/2/11
BG
TYPE PROD CLASS THIS DRAWING IS THE PROPERTY OF ABB Inc. POWER TECHNOLOGY MEDIUM
VOLTAGE AND CONTAINS CONFIDENTIAL INFORMATION WHICH MUST NOT BE
NO. REVISIONS
BY
DATE
CHD.
DATE
APP.
DATE
NO. REVISIONS
BY
DATE
CHD.
DATE
APP.
DATE
A 26 G DUPLICATE USED, OR DISCLOSED OTHER THAN EXPRESSLY AUTHORIZED BY ABB Inc.
SoftSource C 1986

SoftSource C 1986

THIS IS AN AUTOCAD DRAWING - MANUAL CHANGES ARE NOT ALLOWED FORM ANSIB-3/01/02