Utility Communications

TEBIT for FOX515/512


Teleprotection and binary interface

Teleprotection is a key application demanded by any utility The TEBIT Teleprotection interface module provides four com-
communications system. Distance protection relays need mand inputs and outputs for distance protection applications
to exchange information in order to operate correctly and and guaranties highest reliability and dependability of the com-
provide fast reaction times in case of any fault on the power munications channel. Continuous supervision of the availability
line. Reaction times within milliseconds are essential to of the data channel, fastest switchover from main to protecting
prevent damage to industrial assets worth millions of invest- channel (< 5 ms) and automatic loop test for delay measurement
ment. make the TEBIT interface the ideal solution for distance protection
signal transmission. Accordingly the FOX515 can be directly inter-
The relays exchange trip signals between each other which connected with the protection relay and be used for teleprotec-
allows the relays to localize a fault faster and more selectively. tion signal transmission via WAN network.
Such critical applications ask for very fast signal transmission on
one hand and for very high dependability (probability to miss a FOX515 can be used as a combined communication/teleprotec-
command) and security (probability of a false, unwanted com- tion equipment and thus provides a unique solution optimised for
mand) on the other. power utilities. The FOX515/TEBIT solution helps to save costs by
providing several benefits such as less space requirements, fully
The communications service needs to be guaranteed at any integrated solution with one configuration tool and management
time, so accordingly highest availability of the teleprotection inter- system for all services.
faces and communications channel needs to be ensured.
TEBIT – outstanding features for ABB's demanding customers

Specially designed for utilities An 8 bit command addressing scheme ensures correct cross
The TEBIT interface has been specifically designed for distance connection and the very fast 1+1 switchover in case of link failure
protection applications. Therefore it provides exactly the fea- ensures highest reliability of the communication channel.
tures required by power utilities. Having a fibre optic multiplex-
er integrated solution allows to provide optimized end to end An wrongly rerouted channel will be detected by means of the SFC address
solutions for your mission critical application. Besides, TEBIT
also saves space and ensures full supervision by the network
management system (FOXMAN).
TEBIT TEBIT
TEBIT
TEBIT at a glance
FOX 515 Network
– 4 x command inputs for trip signals
TEBIT
– 4 x outputs for solid state trip signals TEBIT
TEBIT
– 2 x programmable auxiliary relay which can be used e.g.
for alarm outputs
– 8 x inputs and outputs for binary signal transmission
– Nonvolatile event recorder with GPS synchronization and
trip counter SFC’s addressing scheme prevents false tripping due to rerouted
channels
– All inputs and outputs are galvanically isolated and with
high EMC immunity for harsh environment
TEBIT architecture
– 1+1 path protection with very fast switchover time (< 5 ms)
The TEBIT is part of a large complement of interface modules
– Supports point to point and Tee-line configuration
which can be plugged into a FOX515 shelf. Like all FOX515
modules TEBIT is:
The command inputs of TEBIT have been designed for direct
connection to the protection relay. They are software configu-
– powered from the FOX515 shelf
rable for trip voltage levels from 24 to 250 VDC.
– configured by UCST and
– supervised by FOXMAN-Management system
TEBIT complies to Teleprotection standard IEC 60834-1 and
can be configured for:
– Permissive tripping Two front connectors provide access to the teleprotection and
– Intertripping binary inputs and outputs.
– Blocking / non-blocking
– Tee-lines (normal or inverse) Alarm states are displayed by LEDs. TEBIT includes a non
– Security, dependability and transmission speed volatile event recorder with an outstanding accuracy, syn-
programmable as per requirements chronizable with the GPS system and trip counter. Cyclic loop
– Continuous performance monitoring for each command tests allow permanent channel monitoring, and add / drop fea-
channel tures allow efficient use of bandwidth. All Teleprotection inputs
– 4 x protection signals per 64 kbit/s channel and outputs are galvanically isolated and provide highest EMC
– Trip transmission time measurement immunity for harsh environment. The TEBIT has an integrated
cross connect with drop and insert functionality for single com-
mands.

Binary data channels


– 8 x opto-coupler inputs 24 to 60 VDC
– 8 x solid-state relay outputs
– All inputs and outputs galvanically isolated
– Cross-connect and drop-and-insert facilities for each binary
signal
– Point-to-multipoint operation
– Transmission of slow data up to 20 bd
– 1+1 path protection
– Integrated galvanically isolated 24 V auxiliary supply
– 8 x binary signals per 64 kbit/s channel

2 TEBIT for FOX515/512


TEBIT – optimised teleprotection solution

It is possible to protect more than one power line using one ration. Trip signals (Trip signal 1 and 2) are broadcast to the
TEBIT module (e.g. if only two commands are used per power two opposite stations. Trip-signal 3 and 4 are configured in
line). Station C of the picture below shows such a configura- a point-to-point connection. A GPS receiver provides an ac-
tion. Station A, B and C are connected in a Tee-line configu- curate time reference for the event recorder.

FOX515 FOX515

A C GPS
Power Line Tee-line receiver

Trip 1
Trip 2
Trip 3
Trip 4 FOX
FOX515 FOX515
Powerline
Binary 3
Binary 2
Binary 1

B D
Trip 1

Binary 2
Trip 2 TEBIT
FOX 515 FOX 515 FOX515 Trip 1
Trip 2
TEBIT Trip 3
Trip 4
TEBIT Binary 1
Trip 1
Trip 2

Trip 3
TEBIT Trip 4

FOX515

Binary 3
TEBIT in Tee-off configuration

The TEBIT module provides two different operation modes which should be chosen depending on the protection scheme. Table
1 and 2 show the applicable delay times.

Operation mode ‘Speed optimized’


Recommended for use with teleprotection schemes: Permissive tripping (blocking/unblocking)
Delay times for point-to-point transmission (excluding line propagation delay):
min. typ. max.
Input voltage 24 – 125 V 220/250 V 24 – 125 V 220/250 V 24 – 125 V 220/250 V
Trip immunity time 0.5 ms 1.4 ms 0.7 ms 1.6 ms 1.0 ms 1.8 ms
Transmission delay time 1.9 ms 1.9 ms 2.4 ms 2.4 ms 3.1 ms 3.1 ms
Propagation delay time 2.4 ms 3.3 ms 3.1ms 4.0 ms 4.1 ms 4.9 ms
Table 1: Delay times operation mode speed optimized’

Operation mode ‘Security optimized’


Recommended for use with teleprotection schemes: Intertripping (direct transfer tripping)
Delay times for point-to-point transmission (excluding line propagation delay):
min. typ. max.
Input voltage 24 – 125 V 220/250 V 24 – 125 V 220/250 V 24 – 125 V 220/250 V
Trip immunity time 1.5 ms 2.4 ms 2.1 ms 3.0 ms 3.0 ms 4.8 ms
Transmission delay time 3.0 ms 3.0 ms 3.6 ms 3.6 ms 3.8 ms 3.8 ms
Propagation delay time 4.5 ms 5.4 ms 5.7 ms 6.6 ms 6.8 ms 7.8 ms
Table 2: Delay times operation mode security optimized’

TEBIT for FOX515/512 3


Technical data

Teleprotection inputs / outputs


Command inputs 4
Nominal input voltage 24 VDC up to 250 VDC configurable with UCST
Threshold 60% of nominal input voltage
Command outputs 4 (PowerMosFET normally open)

© ABB Switzerland Ltd. June 2011. The right to modifications or deviations due to technical progress is reserved.
Tripping command 250 VDC, ≤ 2 A, Ton/Toff ≤ 1/3;
Ton ≤ 5 min
Continuous command 250 VDC; ≤ 1 A
Aux. outputs 2 relays, NO/NC contacts
Contact load 16 ... 250 VAC or DC; max. 150 W
≤ 10 A (max. 100 ms) ≤ 50 A (max. 1 ms)
2 A continuous
Propagation delay time Typical 3.5 ms
(optimized for speed 24 ... 125 VDC)
Standard compliance IEC 60834–1
Binary signal inputs / outputs
Binary inputs 8 (Opto coupler)

1KHA - 000 590 - SEN 1000 - 06/11 - Printed in Switzerland


Nominal input voltage 24, 48, 60 VDC; low -72 ... +9 VDC;
high +18 ... +72 VDC
Input current low ≤ 1.5 mA; high 3 ... 12.5 mA
Binary outputs 8 (PhotoMOS, normally open)
Nominal output voltage 24, 48, 60 VDC
Contact load low ≤ 1.5 mA;
≤ 0.5 A for max. 100 ms;
≤ 0.2 A continuous
On-resistance ≤6Ω
Aux. voltage supply 24 VDC +5% ... -20%
≤ 40 mA continuous, short circuit protected
GPS synchronization input IRIG-B DC-level (unmodulated)
List of abbreviations
Isolation 3,000 Vrms 1 min between protection
GPS Global Positioning System
circuit and equipment
NC Normally closed
1,500 Vrms 1 min between protection
circuits and earth NO Normally open
708 Vrms 1 min for binary circuits SFC Secure Frame Concept
500 Vrms 1 min for aux voltage UCST Configuration tool for
EMC IEC61000-4-2 / 3 / 4 / 5 / 6 / 12 FOX515/512
IEC01255-5 / -22-1 WAN Wide Area Network