LORD COCHARNE-Ventiladores-291020 - Submittal
Model: BSQ-180-30
Belt Drive Centrifugal Inline Fan
Dimensional
Quantity 1
Weight w/o Acc's (lb) 193
Weight w/ Acc's (lb) 212
Max T Motor Frame Size 184
Performance
Requested Volume (CFM) 4,648
Actual Volume (CFM) 4,648
Total External SP (in. wg) 1.5
Fan RPM 1490
Operating Power (hp) 2.45
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 4.6
Tip Speed (ft/min) 7,219
Static Eff. (%) 47
Motor
Motor Mounted Yes
Size (hp) 3
Voltage/Cycle/Phase 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 9.6
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2017. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 83 82 87 82 75 73 69 67 84 72 21 licensed by AMCA International
Radiated 86 83 83 76 67 58 51 51 78 66 14.6 Sones - calculated using AMCA 301 at 5 ft
AIRFLOW
AIRFLOW
TOP VIEW
13.25 MAX
40.38
Model: BSQ-180-30
Belt Drive Centrifugal Inline Fan
Dimensional
Quantity 1
Weight w/o Acc's (lb) 193
Weight w/ Acc's (lb) 212
Max T Motor Frame Size 184
Performance
Requested Volume (CFM) 4,648
Actual Volume (CFM) 4,648
Total External SP (in. wg) 1.4
Fan RPM 1469
Operating Power (hp) 2.34
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 4.6
Tip Speed (ft/min) 7,113
Static Eff. (%) 46
Motor
Motor Mounted Yes
Size (hp) 3
Voltage/Cycle/Phase 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 9.6
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2017. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 83 82 86 82 75 73 69 66 83 72 20 licensed by AMCA International
Radiated 86 83 82 76 67 58 51 50 78 66 14.3 Sones - calculated using AMCA 301 at 5 ft
AIRFLOW
AIRFLOW
TOP VIEW
13.25 MAX
40.38
18.25
21.25 21.25
24.25
ELEVATION VIEW
Performance
Requested Volume (CFM) 2,324
Actual Volume (CFM) 2,324
Total External SP (in. wg) 0.8
Fan RPM 1263
Operating Power (hp) 1.14
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 5.8
Tip Speed (ft/min) 3,286
Static Eff. (%) 27
Motor
Motor Mounted Yes
Size (hp) 1 1/2
Voltage/Cycle/Phase 230/60/3
Enclosure TEFC
Motor RPM 1725
Efficiency Rating Standard
Windings 1
NEC FLA* (Amps) 6
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2017. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 74 84 74 71 72 74 73 66 80 68 17.6 licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
18.25
21.25 21.25
24.25
ELEVATION VIEW
Performance
Requested Volume (CFM) 2,324
Actual Volume (CFM) 2,324
Total External SP (in. wg) 1
Fan RPM 1331
Operating Power (hp) 1.24
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 5.7
Tip Speed (ft/min) 3,464
Static Eff. (%) 31
Motor
Motor Mounted Yes
Size (hp) 1 1/2
Voltage/Cycle/Phase 230/60/3
Enclosure TEFC
Motor RPM 1725
Efficiency Rating Standard
Windings 1
NEC FLA* (Amps) 6
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2017. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 74 85 74 71 72 74 74 66 80 69 18.4 licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
Model: SS1-8-440-D
Sidewall Direct Drive Fan
Motor Access From Int. of Bldg.
Dimensional
Quantity 3
Weight w/o Acc's (lb) 18
Weight w/ Acc's (lb) 19
Wall Opening (in.) 10.5 x 10.5
INTERIOR EXTERIOR
SUPPLY AIRFLOW
Performance
Requested Volume (CFM) 165
Actual Volume (CFM) 165
Total External SP (in. wg) 0.25
Fan RPM 1544
Operating Power (hp) 0.03
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Tip Speed (ft/min) 3,234
Static Eff. (%) 21
Motor
Motor Mounted Yes
Size (hp) 1/30 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO
Motor RPM 1550
Efficiency Rating Standard
Windings 1
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 68 71 59 56 54 50 47 43 61 49 5.6
Model: SS1-8-440-D
Sidewall Direct Drive Fan
Motor Access From Int. of Bldg.
Dimensional
Quantity 4
Weight w/o Acc's (lb) 18
Weight w/ Acc's (lb) 19
Wall Opening (in.) 10.5 x 10.5
INTERIOR EXTERIOR
SUPPLY AIRFLOW
Performance
Requested Volume (CFM) 165
Actual Volume (CFM) 165
Total External SP (in. wg) 0.15
Fan RPM 1319
Operating Power (hp) 0.02
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Tip Speed (ft/min) 2,763
Static Eff. (%) 20
Motor
Motor Mounted Yes
Size (hp) 1/30 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO
Motor RPM 1550
Efficiency Rating Standard
Windings 1
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 59 60 52 49 49 47 39 35 54 42 3.2
Model: SS1-10-428-P
Sidewall Direct Drive Fan
Motor Access From Int. of Bldg.
Dimensional
Quantity 4
Weight w/o Acc's (lb) 22
Weight w/ Acc's (lb) 22
Wall Opening (in.) 12.5 x 12.5
INTERIOR EXTERIOR
SUPPLY AIRFLOW
Performance
Requested Volume (CFM) 300
Actual Volume (CFM) 297
Total External SP (in. wg) 0.236
Fan RPM 1650
Operating Power (hp) 0.04
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Tip Speed (ft/min) 4,320
Static Eff. (%) 27
Motor
Motor Mounted Yes
Size (hp) 1/20 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO Static Pressure Calculations
Motor RPM 1650 External SP 0.24 in. wg
Direct Drive RPM Adjustment -0.004 in. wg
Efficiency Rating Standard
Total External SP 0.236 in. wg
Windings 1
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 81 80 66 61 59 55 50 43 67 56 9.0
Model: SE1-12-432-D
Sidewall Direct Drive Fan
Motor Access From Int. of Bldg.
12.38
Dimensional
Quantity 4
Weight w/o Acc's (lb) 25
Weight w/ Acc's (lb) 26
Wall Opening (in.) 14.5 x 14.5
INTERIOR EXTERIOR
EXHAUST AIRFLOW
Performance
Requested Volume (CFM) 450
Actual Volume (CFM) 450
Total External SP (in. wg) 0.24
Fan RPM 1096
Operating Power (hp) 0.06
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Tip Speed (ft/min) 3,444
Static Eff. (%) 29
Motor
Motor Mounted Yes
Size (hp) 1/8 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO
Motor RPM 1550
Efficiency Rating Standard
Windings 1
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 78 70 45 45 48 47 41 34 58 46 4.8
Model: SS1-10-428-P
Sidewall Direct Drive Fan
Motor Access From Int. of Bldg.
Dimensional
Quantity 4
Weight w/o Acc's (lb) 22
Weight w/ Acc's (lb) 23
Wall Opening (in.) 12.5 x 12.5
INTERIOR EXTERIOR
SUPPLY AIRFLOW
Performance
Requested Volume (CFM) 300
Actual Volume (CFM) 300
Total External SP (in. wg) 0.15
Fan RPM 1375
Operating Power (hp) 0.02
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Tip Speed (ft/min) 3,601
Static Eff. (%) 31
Motor
Motor Mounted Yes
Size (hp) 1/20 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO
Motor RPM 1650
Efficiency Rating Standard
Windings 1
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 68 66 55 53 51 47 41 35 57 45 4.0
Model: SE1-12-432-D
Sidewall Direct Drive Fan
Motor Access From Int. of Bldg.
12.38
Dimensional
Quantity 4
Weight w/o Acc's (lb) 25
Weight w/ Acc's (lb) 26
Wall Opening (in.) 14.5 x 14.5
INTERIOR EXTERIOR
EXHAUST AIRFLOW
Performance
Requested Volume (CFM) 450
Actual Volume (CFM) 450
Total External SP (in. wg) 0.15
Fan RPM 930
Operating Power (hp) 0.03
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Tip Speed (ft/min) 2,923
Static Eff. (%) 31
Motor
Motor Mounted Yes
Size (hp) 1/8 (or greater)
Voltage/Cycle/Phase 230/60/1
Enclosure TEAO
Motor RPM 1550
Efficiency Rating Standard
Windings 1
Notes:
All dimensions shown are in units of in.
*Please consult factory for actual motor amp draw
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones licensed by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 67 67 51 50 52 50 43 36 57 46 4.1
Dimensional
Quantity 1
Weight w/o Acc's (lb) 36
Weight w/ Acc's (lb) 37
Performance
Requested Volume (CFM) 530
Actual Volume (CFM) 530
Total External SP (in. wg) 0.7
Fan RPM 1466
* FLA (A) 2.2
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Sones 2.5
Motor
Motor Mounted Yes
** Input Watts (W) 355
Voltage/Cycle/Phase 220/60/1
Enclosure ODP
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is approximate and may vary between motors.
Dimensional
Quantity 1
Weight w/o Acc's (lb) 36
Weight w/ Acc's (lb) 37
Performance
Requested Volume (CFM) 400
Actual Volume (CFM) 400
Total External SP (in. wg) 0.7
Fan RPM 1288
* FLA (A) 2.2
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Sones 1.5
Motor
Motor Mounted Yes
** Input Watts (W) 355
Voltage/Cycle/Phase 220/60/1
Enclosure ODP
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is approximate and may vary between motors.
Dimensional
Quantity 1
Weight w/o Acc's (lb) 36
Weight w/ Acc's (lb) 37
Performance
Requested Volume (CFM) 400
Actual Volume (CFM) 400
Total External SP (in. wg) 0.8
Fan RPM 1343
* FLA (A) 2.2
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Sones 2.0
Motor
Motor Mounted Yes
** Input Watts (W) 355
Voltage/Cycle/Phase 220/60/1
Enclosure ODP
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is approximate and may vary between motors.
Dimensional
Quantity 1
Weight w/o Acc's (lb) 11
Weight w/ Acc's (lb) 11
Performance
Requested Volume (CFM) 180
Actual Volume (CFM) 179
Total External SP (in. wg) 0.596
Fan RPM 1040
* FLA (A) 0.94
Elevation (ft) 43
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Sones 2.0
Motor
Motor Mounted Yes
** Input Watts (W) 155
Voltage/Cycle/Phase 220/60/1
Enclosure ODP
Notes:
All dimensions shown are in units of in.
*FLA is approximate and will vary slightly with the motor.
Sones - calculated using AMCA 301 at 5 ft
** Wattage is approximate and may vary between motors.