INSTRUCTION MANUAL

FOR
FRIOLOGICA
RSW/HP

-1–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
1 General
Table of contents
1 General .................................................................................................................................. 2
1.1.1 Address ......................................................................................................................... 3
1.1.2 Support: ........................................................................................................................ 3
2 FrioLogica ............................................................................................................................. 4
2.1 Main picture (process) ................................................................................................... 5
2.2 Starting the plant ............................................................................................................ 7
3 Settings .................................................................................................................................. 8
3.1 Settings ............................................................................................................................ 8
3.2 Heating ............................................................................................................................ 9
3.3 Cooling ........................................................................................................................... 10
3.3 Timer settings ............................................................................................................... 11
3.4 Limitations .................................................................................................................... 12
3.5 Limitation LP ................................................................................................................. 13
3.6 Controller pumps M6 (M7+M8) .................................................................................. 14
3.7 Cooling medium valve .................................................................................................. 15
3.8 Condenser ..................................................................................................................... 16
3.9 Language settings ......................................................................................................... 17
4 Advanced settings ............................................................................................................. 18
5 Factory settings ................................................................................................................. 19
6 Scaling analog inputs ........................................................................................................ 20
6.1 Scaling analog inputs .................................................................................................... 20
6.1.1 Scaling analog inputs ............................................................................................. 21
6.1.2 Suction pressure ........................................................................................................ 22
6.2 Input temperatures ..................................................................................................... 23
6.2.1 Temperature outlet chiller ....................................................................................... 24
6.3 Compressor Ampere..................................................................................................... 25
6.4 Condenser Level ........................................................................................................... 26
6.5 Capacity indicator ......................................................................................................... 27
6.6 Flow inlet chiller 1 ........................................................................................................ 28
7 Scaling analog outputs ..................................................................................................... 29
7.1 Scaling analog outputs ................................................................................................. 29
7.2. Cooling medium valve ................................................................................................. 30
8 Alarm settings .................................................................................................................... 31
8.1 Alarm settings oil filter................................................................................................. 32
8.2 Alarm setting oil pressure............................................................................................ 33
9 Init hardware ..................................................................................................................... 34
10 Adjust time and date ...................................................................................................... 35
11 Edit running hours.......................................................................................................... 36
12 Cooling medium data ..................................................................................................... 37
13 Advanced compressor adjustment.............................................................................. 38
14 Alarm (active) .................................................................................................................. 39
14.1 Alarm (history) ........................................................................................................... 40
15 Alarmlist ............................................................................................................................. 41
16 Remote access .................................................................................................................... 43
16.1 Nettwork ....................................................................................................................... 43
16.2 Access ........................................................................................................................... 44

-2–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
1.1 Contact information

1.1.1 Address
FrioNordica AS
Holamyra 24
6445 Malmefjorden
Norway

Phone: (+47) 71 20 68 00
Fax: (+47) 71 20 68 01
E-mail: aquaterm@frionordica.com
Home page: www.frionordica.com

1.1.2 Support:

TECHNICAL: technical@frionordica.com

ELECTRICAL: electrical@frionordica.com

The office is served from Monday to Friday at 08.00 - 16.00.

-3–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
2 FrioLogica

Start page with selection of language.

-4–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
2.1 Main picture (process)

The main picture shows the general status of the plant. Here you can see temperatures,
pressures, motors running etc.

Labels
Temp out chiller Temperature of water at the outlet of the chiller
Temp in chiller Temperature of water at the inlet of the chiller
Evaporator temp Shows evaporating temperature of refrigerant
RSW pump RSW pump motor status. Pump symbol lights up when motor running
Suction pressure Shows evaporating temperature in Bar
Motor current Compressor motor current consumption
Capacity decrease coil Lights up when capacity decrement valve is acting
Capacity increase coil Lights up when capacity increment valve is acting
Oil temp Shows oil temperature after the oil cooler
Oil pressure Oil pressure at compressor inlet in Bar
Pressure loss filter Oil pressure loss in oil filter
Set point Shows the actual set-point
Liming active Lights up when a capacity limiter is active
Condenser pump Condenser-pump motor status. Pump symbol lights up when motor
running

-5–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
Expansion valve Shows ICAD motor valve opening % in a graph
Oil rectifier heater Lights up when the heater is on
Evap spray pressure Shows the evaporator pump pressure lift
Evap spray pump Evaporator spray-pump motor status. Pump symbol lights up when
motor running
RSW water flow Lights up when flow switch is activated
switch
Condensing pressure Shows condensing pressure in Bar
Delivery temp Temperature of refrigerant gas at the compressor outlet
Oil heater Lights up when the oil heater is on
Water in Water temperature at condenser inlet
Water out Water temperature at condenser outlet
Cond temp Condensing temperature of refrigerant
Refr level Refrigerant level in the condenser 0-100%
Oil pump Oil spray-pump motor status. Pump symbol lights up when motor
running

Buttons

Pressing this button starts the process. The pumps will start before the
compressor.

Pressing this button activates the manual control

Pressing this button gives access to the settings screen

Pressing this button gives access to the alarms screen

-6–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
2.2 Starting the plant
The plant can be started in two ways:

Automatic start

Press to start automatic starting sequence:


Water pumps starts
Compressor capacity is reduced to minimum
Timer for minimum resting time runs out
Sending request to PMS system (if used)
Receiving ”start ready” from PMS
Compressor starts
Refrigerant pump starts

The plant is now running and capacity control is acting depending of selected principle

auto/manual

Manual start-up
Pumps can be started manually by pressing pump symbol on the screen. A window like
this is showing:

The pump symbol shifts to blue when a pump is running in manual.

Manual capacity control


The compressor capacity is adjusted by pressing symbols for capacity increase/decrease
solenoids on the screen.
Limiting and alarm functions are functioning as normal.

-7–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3 Settings

3.1 Settings

Capacity control parameters heating mode

Capacity control parameters cooling mode

Timer settings

Limiting function parameters

Alarm parameter settings

Refrigerant level control parameters

Condenser pump control parameters

Advanced parameters. Protected by password

Language

-8–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.2 Heating

Compressor capacity settings


The compressor's capacity is controlled by two relay outputs, which enable compressor
power to be increased or reduced, varying the capacity of the compression chamber.
Compressor power is controlled by sending pulses to the capacity control solenoids.
These pulses command the compressor to load or unload. These pulses are at a constant
frequency, adjustable, and of variable duration between two minimum and maximum
limits.
C: Set point
B/D Decreasing pulse max/min
H/F: Increasing pulse max/min
E: Neutral zone
G-E : Increase zone
A: Decrease zone
Cycle time: Time between capacity controlling pulses

If the plant is delivering warmer water than “C” oC for a long period (settable in timer
settings) the compressor will stop, and not start before the minimum compressor
standstill timer and the outlet temperature is higher than C+E oC.

-9–
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.3 Cooling

Compressor capacity settings


The compressor's capacity is controlled by two relay outputs, which enable compressor
power to be increased or reduced, varying the capacity of the compression chamber.
Compressor power is controlled by sending pulses to the capacity control solenoids.
These pulses command the compressor to load or unload. These pulses are at a constant
frequency, adjustable, and of variable duration between two minimum and maximum
limits.
Points C,E and G are set as a temperature offsets and calculated from setpoint.
The regulator has the following parameters:
A: Set point
B/D Decreasing pulse max/min
H/F: Increasing pulse max/min
E-C: Neutral zone
Cycle time: Time between capacity controlling pulses.

If the plant is delivering colder water than “A” oC for a long period (adjustable in timer
settings) the compressor will stop, and not start before the minimum compressor
standstill timer and the outlet temperature is higher than A+E oC.

- 10 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.3 Timer settings

Timer settings
Description of timers
Start delay compressor: When pressing process start in main page the
process starts first and runs for a settable time
before the compressor starts.
Resting time compressor: Minimum time before compressor restart.
Limit decreasing pulse: Pulse length of forced decrement pulse when a
capacity limiter is active
Refrigerant pump time before stop: Time before stopping the spray pump when
cavitation occurs.
Refrigerant pump stop time: Time for allowing gas bubbles to be vented out
of spray pump suction
Regulation stop time: If the plant is delivering colder water than
setpoint for a period set in this parameter, the
compressor will stop.
Pre-lubrication pump: Pre-lubrication of compressor before
compressor start.

- 11 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.4 Limitations

The compressor capacity can be limited if process values is passing threshold values
given in the limits page.

High pressure limit:


If the high pressure is over high pressure limit set point - NZ, then the capacity
increasing solenoid is blocked from operating.
If the high pressure is over high pressure limit set point, a forced decrementing pulse is
activated.

Motor current limit:


If the motor current is over motor current limit set point - NZ, then the capacity
increasing solenoid is blocked from operating.
If the motor current is over high pressure limit set point, a forced decrementing pulse is
activated.

Refrigerant spray pump pressure limit


If the refrigerant pump cavitation occurs, then the delivery pressure of the pump will
drop. If the pump pressure is below the limit for the preset period, the pump stops and
start again when the timer is finish. This allows refrigerant gas to ventilate from pump
suction. This will normally solve cavitation problems.

- 12 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.5 Limitation LP

Suction pressure limit:


If the suction pressure is below suction pressure limit set point + NZ the capacity
increasing solenoid is blocked from operating.
If the suction pressure is below suction pressure limit set point, a forced decrementing
pulse is activated

This regulator allows the cooler to work at a lower setpoint at high water temperature
and increases the setpoint linear against the falling outlet temperature.

- 13 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.6 Controller pumps M6 (M7+M8)

In this picture you can see a typical regulator for pumps / valves.
Used on a pump you normally have 50 Hz max. this will give the range
“min out limit” 30% =15Hz and “max out limit” 100%=50Hz.

- 14 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.7 Cooling medium valve

Settings for the ICAD expansion valve:


Set point: Wanted level in condenser, typically 20%
P-gain: Regulator gain for a deviation from the set point. Normally between
1 and 2. A high P-gain value gives a nervous behaviour of the icad
valve. A low P-gain gives a large difference between set point and
measured value.
I-gain: Integral gain. Normally set to 0
Offset: Offset value for output to valve to compensate for fixed deviation
between set point and condenser level. Normal value is 0 - 20%
Min out limit: Minimum opening of ICAD valve. Normal value is 0 %
Max out limit: Maximum opening of ICAD valve. Normal value is 100%

- 15 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.8 Condenser

Some plants are delivered with a frequency inverter for the condenser pump.
This control is used on plants without an oil pump, and thus requiring a certain
condensing pressure to get sufficient oil pressure.
The correct differential pressure (HP/LP) is calculated in the plc.
Parameters:

P-Gain: Regulator
Pressure req offset: Normally set to 0 but its possible to get an higher differential
pressure when increasing this one.
Minimum out limit: Lowest allowed speed of condenser pump.
Max out limit: Highest allowed speed of condenser pump.

- 16 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
3.9 Language settings

In the Friologica you have the option to choose between 3 different languages.

- 17 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
4 Advanced settings

The Advanced setup menu is protected by a password.

- 18 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
5 Factory settings

This page is to take a factory set up of the system and all the basic settings will be
automatic put in to the program.
Before starting up all the settings need to be checked and sensors calibrated.
The final adjustments had to be done during start up.

- 19 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6 Scaling analog inputs

6.1 Scaling analog inputs

The main page on analog inputs. Here you will find all inputs used in the system.
It’s possible so rescale and calibrate all the analog inputs.

- 20 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.1.1 Scaling analog inputs

The main page if you choose input pressures. All of this pressure transducers can be
calibrated.

- 21 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.1.2 Suction pressure

Above: Analog input scaling page example

Similar pages for suction pressure, spray pump pressure, oil pressure before filter, oil
pressure after filter, capacity indicator, refrigerant level, compressor motor current
consumption. They are all set up in the same way. Standard settings for a FrioLogica
system:

Sensor X0 Y0 X1 Y1
High pressure sensor 0 -1 6000 34
Low pressure sensor 0 -1 6000 12
Oil pressure before filter sensor 0 -1 6000 34
Oil pressure after filter sensor 0 -1 6000 34
Refrigerant pump pressure sensor 0 -1 6000 12
Capacity indicator 0 0 6000 100
Compressor ampere 0 0 6000 Comp,curr
Refrigerant level 0 0 6000 100

The compressor ampere will have an Y1 value according to the size of the motor.
Capacity indicator have to be calibrated after start up.

- 22 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.2 Input temperatures

The main page for scaling temperatures.

- 23 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.2.1 Temperature outlet chiller

Similar pages for all temperature inputs. Standard settings:


X0= 0, X1=10
Y0= 0, Y1=1
Typical setting for filter is 250, which means that the temperature input is an average of
the last 250 scans.

To calibrate the sensor:

1: take a thermos with fresh water and ice, put the sensor into this mix.
2: after some time the reading will become stabil then read out the value in X(raw
value) and put it in X0. Y0 should stay on 0(that’s the temp of the ice/water).
3: put water of apprx. 20 C in the thermos and check the temperature with an accurate
instrument. Repeat point 2 and put this values in X1 / Y1.

- 24 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.3 Compressor Ampere

Typical settings:
X0=0 Y0=0
X1=6000 Y1=compressor max scaling amp .

When using Danfoss inverter the value in Y1 can be read out in parameter 4.51.

- 25 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.4 Condenser Level

Scaling for the condenser level that controls the Icad valve.

- 26 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.5 Capacity indicator

Scaling capacity indicator compressor.


This has to be calibrated after start up or replacement.

Calibration of the indicator:


1 : after startup put the unit in manual capacity and push the decrease button until its in
minimum. Read out the x ( raw value) and put this value in X0.
2 : run the unit manual up to maximum capacity and again read out the x(raw value).
Take the unit down to minimum before you put this value in X1.

- 27 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
6.6 Flow inlet chiller 1

To calibrate the flow transmitter you need to put the maximum range of the transmitter
in Y1.
Y1 will typical correspond to the flow in m3 / h.

- 28 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
7 Scaling analog outputs

7.1 Scaling analog outputs

The main page on the analog outputs. Which buttons you have here depends on what
kind of installation you have.

- 29 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
7.2. Cooling medium valve

Typical settings:
X0=0 X1=100
Y0=0 Y1=6000

This is the control block for the Icad valve.

- 30 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
8 Alarm settings

Suction pressure: Suction pressure alarm set point. The compressor can be
restarted when the suction pressure is higher than the set
point , the alarm is resetted and the standstill timer has run
out.
High pressure: High pressure alarm set point. Manual reset of alarm before
the compressor can be restarted.
Oil pressure: Oil pressure alarm set point. Manual reset of alarm before
the compressor can be restarted.
Oil temperature: High oil temperature alarm set point. Manual reset of alarm
before the compressor can be restarted.
Pressure pipe temperature: High pressure pipe temperature alarm set point. Manual
reset of alarm before the compressor can be restarted.
Minimum flow chiller If a flow transmitter is used.

Time before alarm oil flow switch: Time allowed to run with too low oil flow
Minimum temp outlet evaporator: Used in HP applications.

- 31 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
8.1 Alarm settings oil filter

This is the setpoint for the monitoring of the oil filter. Its only the warning setpoint that
is adjustebal, the other are just readings.
If the differential pressure gets to high replace the filter.

- 32 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
8.2 Alarm setting oil pressure

Time before oil pressure alarm.


Minimum difference will only show up if the unit is supplied with oil pump.

- 33 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
9 Init hardware

Select safety and control functions for the unit.

- 34 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
10 Adjust time and date

This function is password protected.

- 35 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
11 Edit running hours

If for some reason you have to correct the running hours its possible to do so here.
For example if you replace an electric motor / pump.

- 36 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
12 Cooling medium data

This parameters are used by the plc to calculate pressure and temperature on the
refrigeration cycle. The parameters will be different depending on type of refrigerant.

- 37 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
13 Advanced compressor adjustment

Maximum capacity before start is to protect that the system don’t start with to high
capacity on the compressor.

On this side its also possible to choose either cooling or heating function on the unit.

- 38 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
14 Alarm (active)

Alarm page
Resetted alarms will change color to green when marked
Active alarms cant be resetted, they will only change color from red to purple .
To move alarms into history just press the bottom left button on the screen after they
are hooked out.

- 39 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
14.1 Alarm (history)

Here will all resetted alarms be marked blue and still active ones be red.

- 40 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
15 Alarmlist

All alarms and possible causes :

Low battery PLC


- Battery needs to be replaced, plc contact your dealer.
Compressor failed to start
- Check inverter and/or motor protection.
Refrigerant pump failed to start
- Check motor protection.
RSW pump failed to start
- Check inverter and/or motor protection
Condenser pump failed to start
- Check inverter and/or motor protection
Oil pump failed to start
- Check motor protection
M6 pump failed to start
- Check motor protection
Alarm HP switch
- Reset switch and check condenser pump.
Alarm, flow evaporator
- Check sensor and rsw pump
Alarm, flow raw water
- Check sensor and pump.
Oil flow switch
- Check oil level and filter.
High pressure loss oil filter
- Replace filter.
Warning low suction pressure
- Check water flow but normal at low water temperature.
Alarm high pressure
- Reset and check condenser pump/valve regulation
Alarm oil pressure
- Check filter, oilpump or condenser pump/valve settings.
Alarm oil temperature
- Check waterflow oilcooler.
Alarm pressure pipe temperature
- Check oilflow, oilcooler and condenser.
Alarm temperature outlet chiller
- Factory set 0,3 degrees C. only when operated as heatpump
Alarm softstarter / inverter
- Check if there are alarms on softstarter / inverter display.
Sensor fault T1
- Bad connection or defect sensor
Sensor fault P1
- Bad connection or defect sensor
Sensor fault S6 (Level Condenser)
- Bad connection or defect sensor

- 41 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
Sensor fault S7 (Capacity indicator Compressor)
- Bad connection or defect sensor
Sensor fault S1 (Current Compressor)
- Bad connection or defect sensor
Alarm thermistor M1
- Check electrical motor, overheating.
Alarm EKC
- Check readings on display EKC unit.
Emergency stop activated
- Check reason, reset.
Cavitation refrigerant pump (to many restarts)
- Check level of refrigerant.

- 42 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
16 Remote access

16.1 Nettwork

It is possible to accsess Friologica from web browser (explorer, crome, firefox++). To accsess
the panel you have to be in the same network. To be in the same network you can use router,
extra network card, vpn, wifi router. Your it manager can help you to find the best solution for
your company.

- 43 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
16.2 Access

To access the panel you type the ip address in browser. If all connection are correct you
should be asked for username and password.
Username = default
Password = default

You use “Monitor” if you only want to see Friologica. If you want access to control the
system you shod chose Operation.

- 44 –
FrioNordica AS, Finsam Dept.: Jon Lilletunsvei 3, 4879 Grimstad, NORWAY
Tel.+47 37 25 65 00, Fax: + 47 37 25 65 01, e-mail: finsam@frionordica.com, www.frionordica.com
FrioNordica AS. Head Office: 6445 Malmefjorden, NORWAY
Enterprise no.: 962 369 804
You are then connected to the panel and can control the same settings that you can do directly