You are on page 1of 3

PCU/inverter capacity with detailed specifications

1. INVERTER

The salient features of the inverter are as under:


- DSP based design

- Pure sine wave

- High efficiency and high reliability

- Noiseless operation

- User friendly display

- High efficiency

The technical specification of the inverter is as under:

Capacity 100 kVA


Mains AC input range 160V – 280 V (P-N)
Mains AC low cut 160V+/- 5V (P-N)
Mains AC low cut recovery 170V+/- 5V (P-N)
Mains AC high cut 280V+/- 5V (P-N)
Mains AC high cut recovery 270V+/- 5V (P-N)
Max. mains to inverter <2 sec.
changeover time
Max. inverter to mains <1 sec
changeover time
Max. output at inverter mode 230V+/-2% (P-N), 400V+/-2% (P-P)
Output frequency in inverter 50Hz+/- 0.1 Hz
mode
Full load 80 kW resistive load (0.8 P.F.)
Peak efficiency in inverter >92%
mode
Total Harmonic distortion <5% for linear load (resistive load)
Overload handling capacity 110% for 8 minutes
125% for 1 minute
150% for 15 seconds
200% for 3 seconds
300% for 2 seconds
Short circuit protection >300% load (1 sec)
Nominal battery voltage 360 V
Charger 3- phase
Max charging current 8 Amp- 40 Amp depending upon
battery AH
Battery low cut warning 320V+/-2V
Battery High protection 450V+/- 2V
Features - Battery charging on even if one
phase completely off or low upto
120V
- Battery charging on even if 2
phase low upto 140V.

2. SOLAR CHARGE CONTROLLER:

REIL shall use 8 nos. of 360V/ 30 Amp rating solar charge controllers for each100 kWp SPV Power Plant.
Solar charge controller is equipped with Digital Signal Processing. The charge controller is fully protected

against lightening, transient over voltage and reverses current flow.

The salient features of the charge controller are as under:

- Intelligent microprocessor.

- Silent, solid state PWM charging process.

- Electronic over current protection.

- Communication interface with PC or LCD modular for data logging or parameter display.

Protections:

- Solar / battery reverse polarity.

- Reverse current flow battery to solar array during night.

- Over chage and short circuit.

- Output over voltage.

- Excessive temperature of heat sink.

The technical specifications of each solar Charge controller are as under:


Rating 360V/ 30 Amp
Input - 530V to 750V as per Solar PV array
- 30 Amp max input current
Common terminal Negative
Output > with 360V lead acid battery bank connected to
charge controller.
Bulk stage 422+/- 3 Vv (adjustable from 408V to 436 V)
Float stage 408V+/- 3V (with 14 V below from bulk setting
level.)
Low battery indication 324V+/- 3 V
Low battery indication recovery 365V+/- 3 V
Charger high battery protection Charging cut off – 445V+/- 3 V
Charging reconnect – 390+/- 3 V
Cooling fan operation Fan ON – 50 Deg +/- 5 Deg
Fan off – 40 Deg +/- 5 Deg
Operating temperature 0-40 Deg Cent.
Protection - Reverse current flow from battery to solar
array during night.
- Self protection against excessive
temperature on heat sink.
- Solar/battery reverse.
- Output over voltage.
- High Current.
Enclosure MS powder coated enclosure, rugged in
construction and suitable for wall mounting.

LED indications: Following indications shall be provided on the solar charge controller:

LED STATUS REPRESENTATION


GREEN Continuous ON Bulk Mode Charging
Equal interval Blinking Float Mode Charging
RED Continuous ON High Temperature
Equal interval Blinking High Current
RED Continuous ON Low Battery
Equal interval Blinking High Battery
RED Continuous ON Solar / Battery Reverse Polarity