UTILITIES - STEAM

Extra High Pressure Steam - EHP


High Pressure Steam - HP
Medium Pressure Steam - MP
Low Pressure Steam - LP
TYPE EHP HP MP LP servic
e
steam
LP
*
VGB RATING kg/cm2a > 60 30-60 10-30 3-10 3-10
Normal Pressure kg/cm2a 106 45 12 2.1 12 4.8
Normal Temperature ・C 482 365 278 243 187 151
* ex new LP boiler 1550
UTILITIES - AIR
TYPE COMBUSTION
AIR
INSTRUMENT
AIR
PLANT/
SERVICE
AIR
Quality oil-free dust/oil-free oil-free
Composition
N2 vol. %
78.11 78.11 78.11
O2 vol.
%
20.95 20.95 20.95
A vol.
%
0.94 0.94 0.94
Relative Humidity % 65/ 85 - 65
Dew point ・C -12
Minimum Pressurekg/cm2a * 100 mmwc 7.0 2
Normal Pressure kg/cm2a * 170-180
mmwc
84
Maximum Pressurekg/cm2a * 535 mmwc 11 10
* Pressure is measured at fan discharge 

You might also like