Table of Contents
Introduction........................................................................1
Specifications....................................................................2
Configurations...................................................................3
Labelling............................................................................7
Principle of Operation.......................................................7
Installation and Overpressure Protection........................7
Commissioning.................................................................9
Maintenance....................................................................12
Parts List.........................................................................13
Dimensions and Weights...............................................15 Type VS110 Type VS120
! Warning
Introduction
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion Scope of the Manual
and/or fire causing property damage and
This Instruction Manual provides installation,
personal injury or death.
maintenance and parts ordering information for the
Fisher™ slam-shut device must be VS100 Series slam-shut device. Refer to VSX4
installed, operated and maintained and VSX8 Series Controller Instruction Manual,
in accordance with federal, state and Form 5867 included with the VS100 Series for
local codes, rules and regulations and additional VSX4 and VSX8 Series information.
Emerson Process Management Regulator Instructions for other equipment used with
Technologies, Inc. (Emerson) instructions. the VS100 Series can be found in separate
Only a qualified person must install Instruction Manuals.
or service the VS100 Series slam-shut
device. If a leak develops or if the slam- Product Description
shut device continually vents gas,
service to the unit may be required. The VS100 Series slam-shut device is designed to
Failure to correct trouble could result in a shut off the flow of gas to the downstream system
hazardous condition. in the event of outlet pressure rising above or falling
Installation, operation and maintenance below the predefined levels.
procedures performed by unqualified The VS100 Series consists of the following:
personnel may result in improper
adjustment and unsafe operations which • A body with a removable orifice, enclosed by
may result in equipment damage or a bonnet.
personal injury. • A VSX4 or VSX8 Series controller.
VS100 Series
Specifications
The Specifications section lists the specifications for the VS100 Series slam-shut device. The following information
is stamped on the label of VS100 Series: Type and Class, Maximum Outlet Pressure and Spring Range. Additional
operating information is located on the slam-shut device label.
2
VS100 Series
3
VS100 Series
4
VS100 Series
Table 5c. North American Overpressure and Underpressure Shut-off OPSO/UPSO Ranges
5
VS100 Series
Under Over
Pressure Pressure
Factory Set
Shut-off Shut-off
Typical Type (UPSO) (OPSO)
Setpoint (Maximum Spring Part Spring Part
Type Spring Color Set Range Spring Color Adjusted
Operating Number Number
Inlet) Set Range Over UPSO UPSO OPSO
OPSO Range
Setpoint
200 FA142869X12 Orange Stripe 114 to 261 GF02170X012 Orange 100 214 to 361 330
300 100 to 500 FA142869X12 Orange Stripe 179 to 386 GF02171X012 Pink 150 329 to 536 440
500 FA142869X12 Orange Stripe 241 to 565 GF02172X012 Green 250 491 to 815 700
1200 FA142869X12 Orange Stripe GF02171X012 Pink 600 1650 to 2170 1600
1050 to 1570
1500 FA142869X12 Orange Stripe GF02171X012 Pink 750 1800 to 2320 1900
VS112 VSX4L 500 to 2000
VS122 2000 VSX8H FA142869X12 Orange Stripe GF02172X012 Green 1000 2250 to 3300 2400
(16 bar) 1250 to 2300
3000 FA142869X12 Orange Stripe GF02172X012 Green 2000 2250 to 4300 4000
4000 500 to 2800 T14171T0012 Olive 2100 to 3750 GF02173X012 Silver 2000 4100 to 5750 5000
6
VS100 Series
TEMPERATURE
TS
CLASS
VS121 VS122 VSX4L VSX4H
-20/60°C 2
VS111 VS112 -20/66°C / VSX8L VSX8H
Manufacturing site
527 = Cluj IS 6 bar
R
SHUTOFF SERIAL NO. LOC DS 16 bar
527 Manufacturing date LP 1.5 bar
TS TEMP JJ MM AN HP 5.5 bar
DOM JJ MM AN
CLASS
O 19 A Min, Min and
PS PS SEAT FLUID
GROUP
1 CAT IV
Max installation
IS 6 bar Steel (WCC) B Max installation
DN BODY
DS 20 bar PN MATL Iron (GS) only
Figure 2. PED VS100 Series Label Figure 3. EN 14382 VSX4 and VSX8 Series Label
FRANCEL SAS
Chartres FRANCE
2 GT
TYPE
No de Série An
SERIAL No. YEAR
Utilisation
INTENDED USE
7
VS100 Series
OVERPRESSURE
SHUTOFF (OPSO)
SPRING
CAM
RESET
STEM
RESET
BUTTON CLOSING
SPRING
VALVE PLUG
To outlet side of
Pressure Regulator (see
M1200 Figure 7)
INLET PRESSURE, Pu
ATMOSPHERIC PRESSURE, Pb
8
VS100 Series
9
VS100 Series
Control line
V3
V4
V1 4D
V2
Pu D Pd
Regulator
V5
Pu - Inlet Pressure
Pd - Outlet Pressure
10
VS100 Series
11
VS100 Series
12
VS100 Series
13
VS100 Series
14
VS100 Series
D C
Type VS110
A/2
RESET TRIP CLEARANCE 25 mm / 1 in.
15
VS100 Series
L2 L2 L2
43 40 103
L1
38 50 51 TORQUE: 71 TORQUE:
80 0.9 - 1.4 Nm / 14 - 16 Nm /
8 - 12 IN-LBS 10 - 12 FT-LBS
41
84
70
(152.5)
48
73 L1
(206.5)
75
74
MODULE A
VSX4L
TORQUE: 34 36 46 33 61 60 L2
14 - 16 Nm /
TORQUE:
10 - 12 FT-LBS
L1 L1 47 - 61 Nm /
L1
35 - 45 FT-LBS
(255)
GF04352
16
VS100 Series
L2 L2 L2
43 40 103
L1
38 50 51 TORQUE: 71 TORQUE:
80 0.9 - 1.4 Nm / 14 - 16 Nm /
8 - 12 IN-LBS 10 - 12 FT-LBS
41
84
70
(152.5)
48
73 L1
(206.5)
75
74
MODULE A
VSX4H
TORQUE: 34 36 46 33 61 60 L2
14 - 16 Nm /
10 - 12 FT-LBS TORQUE:
L1 L1 L1 47 - 61 Nm /
35 - 45 FT-LBS
(255)
GF04352
17
VS100 Series
L1
L2 L2
84
38
48 70
(152.5)
41
(248)
73 L1
75
74
64 L1
34 36 46 33 61 60
TORQUE:
14 - 16 N•m / L1 L1 L1
10 - 12 FT-LBS
(295)
ERCA03227_AD
18
VS100 Series
L2 L2 L2 L1
41 70
84
(152.5)
48
73 L1
(247.8)
75
74
MODULE A, VSX8H
LIMIT SWITCH OPTIONAL TORQUE:
63 L2
34 - 47 N•m /
25 - 35 FT-LBS
64 L1
TORQUE: 34 36 46 33 61 60
14 - 16 N•m /
10 - 12 FT-LBS
L1 L1 L1
(295.8)
ERCA03228_AA
19
VS100 Series
Webadmin.Regulators@emerson.com Facebook.com/EmersonAutomationSolutions
Fisher.com LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation