You are on page 1of 39

2/22/2021

Fluke Webinar:

Operation, Maintenance and Testing in power transmission and distribution.

This webinar will start at 10am sharp.

Stay connected and engaged with us on the platform!

1
2/22/2021

To open the chat box, click on


this icon. Use the chat box to
communicate with the panelist on
audio issues.

You should see a Q&A box here.


You can key in any technical
questions you have to the panelist
anytime during the webinar.

Address your question to


“All Panelist”

If you are unable to see the


Q&A panel, click on this icon
to activate the Q&A.

2
2/22/2021

During a polling session,


the poll will appear here.

Simply select your answer


and submit it!

If you are unable to see the


polling panel, click on this icon
to activate the poll.

We look forward to your participation for a fruitful webinar!

3
2/22/2021

Fluke Webinar:

Operation, Maintenance and Testing in power transmission and distribution.

This webinar will start at 10am sharp.

Fluke Total Solution for Utility Sector

Partial Discharge Thermal Imaging Power Quality


Detect High voltage

Electrical signal

Underground Tracer

Backup
Earth / Ground Battery

4
2/22/2021

High Voltage segment SOLUTION

How did it occur?

Over the years, studies


have shown that more cost of the
than 85% of disruptive PD have led to transformer:
failures in both medium the fire of the 2,500,000$
voltage (MV) and high transformer
voltage (HV) equipment
and machinery are Partial
Discharge related.

loss of opinion
the cost of on the reliability
replacing the of nuclear
transformer power plants
500,000$

Source: thesunnews

10 © 2020 | Fluke Industrial Group

10

5
2/22/2021

Types of Partial Discharge


4 Types of Partial Discharge:
❑ Internal Discharge
- Occurs within a void in insulation such as gaps in solid
or gas bubbles in oil
❑ Surface discharge
- Occur when there is a degradation of the surface of
the insulator caused by contamination
- Electrical Treeing
• Insulator contains a carbon-based compound → Electrical Treeing
carbonization and form carbon track on surface
❑ Arcing
- An electric arc, or arc discharge, is an electrical
breakdown of a gas that produces a
prolonged electrical discharge or plasma discharge
❑ Corona
- Occurs when the air surrounding a conductor is
ionized, causing an electrical discharge.
- Discharge to air
Corona Discharge
11 © 2020 | Fluke Industrial Group

11

Can You Hear The Partial Discharge?

But we can’t see it…


12 © 2020 | Fluke Industrial Group

12

6
2/22/2021

Fluke ii900 – A Method Combining Acoustic and Optical

13 © 2020 | Fluke Industrial Group

13

What is acoustic sound imaging?

• A technique to create an image of the scene based on the sounds in the scene
• The sound image is then overlaid onto a visible image
14 © 2020 | Fluke Industrial Group

14

7
2/22/2021

Preventive Maintenance on Transmission Lines & Switchyards

Detection of Corona on High Voltage towers and switchyards

❑ Easy to use
❑ Safety: able to detect from safe distances
❑ Less depending on external conditions (visual
limitations of UV Cam, noise limitations of
ultrasonic tools).
❑ Accordable price vs. UV camera
❑ Better documenting with pictures

15 © 2020 | Fluke Industrial Group

15

Switchyard

16 © 2020 | Fluke Industrial Group

16

8
2/22/2021

Switchyard

17 © 2020 | Fluke Industrial Group

17

Transmission Lines

18 © 2020 | Fluke Industrial Group

18

9
2/22/2021

Preview of New Fluke ii910 Precision Acoustic Imager

19 © 2020 | Fluke Industrial Group

19

POLL QUESTION No. 1

? What is the technology Fluke ii900 use to detect Partial Discharge?


(Click only one answer)

A. Thermal imaging
B. Acoustic imaging
C. Ozone monitoring
D. All above

20 © 2020 | Fluke Industrial Group

20

10
2/22/2021

Overhead and underground electric safety

• In the last 24 months, 173 accidents have occurred involving electrical systems
or equipment in the public and private sector
• 132 accidents involving contact with energized power lines/conductors (overhead,
underground and ground level)
• 31 accidents involving contact with energized transformers (or its components)
• 10 involving contact with high voltage switch gears
• Accidents were triggered by arc flashes and electrocution by contact
(Source, OSHA)

• Around 30,000 arc flash accidents occur every year in the US, leaving 7000
burn injuries and 400 fatalities
• Every 6 minutes an underground electric utility is damager because someone
digs without the right info
(Source, Industrial Safety & Hygiene News)

21 © 2020 | Fluke Industrial Group

21

Overhead safety with amprobe TIC 300

• CFR 29.1926.964 (OSHA 29) Overhead lines and live-line


barehand work
• Employer shall provide the protective measures when employees
are working close enough to energized conductors
• Minimum approach distances should be kept when approaching
energized areas
• These distances can be defined by the end-user
• All equipment should be insulated

Amprobe High Voltage Non-Contact Detector

22 © 2020 | Fluke Industrial Group

22

11
2/22/2021

Underground safety risks

1. Incorrect estimation of depth


• Excavate with wrong depth
• Come in contact with kV energized lines

2. Overlapping of electrical wires


• Intersection of two underground wires with different directions a different depts
• User confusing which wire is energized

3. Old circuit designs


• Underground circuit designed not updated in a long time
• Contractors’ works impact directions and depths not reflected on plans

4. Ground faults / Cable faults


• Wire damages (faults) impacting the cable’s resistance
• This can lead to a voltage breakdown

23 © 2020 | Fluke Industrial Group

23

Underground safety

• CFR 29.1926.965 (OSHA 29) Underground Electrical


Installations Guidelines
• Provides additional requirements for work on underground electrical
installations

• Cables with abnormalities are stated as a risk of fault or indication of


an impeding fault

• Employee shall de-energize the conductor


• Cables retain energy, even de-energized (particularly long cables)
Underground Cable Locator
• OSHA never clarified until 2003 what is an underground utilities with Fault Finding Capability

locating mean

24 © 2020 | Fluke Industrial Group

24

12
2/22/2021

UAT-620 underground cable tracer

• It can search an area from the surface to locate buried lines.


• It can measure depth from the surface.
• It can find cable faults and monitor pipeline coating condition and locate
water leaks in plastic pipes.
• It can pinpoint the position of joints in iron gas pipes.
• The technique works in all soil conditions

Underground Cable Locator/Tracer


with EM Induction Technology

25 © 2020 | Fluke Industrial Group

25

Multiple tracing mode methods

1. Passive
• 50/60 Hz: On energized wire
• Radiofrequency: detects reflected RF waves from utility

2. Active (Non-contact or contact signal inject)


• Induction: Propagates unique 8kHz/ 33kHz signal
• Signal Clamp (Traces particular cable )
• Direct Connection (any hot line below 600V, accurate)

26 © 2020 | Fluke Industrial Group

26

13
2/22/2021

POLL QUESTION No. 2

?
Which of the following is not an advantage of the EM Induction Technology
for tracing? (Click only one answer)

A. It can find cable faults


B. It can work in all soil conditions
C. It can measure temperature from surface
D. It can pinpoint position of joints in iron gas pipes

27 © 2020 | Fluke Industrial Group

27

Importance of Grounding

• Good grounding not only for safety, its also prevent damage to industrial
plants and equipment.

• Good grounding system will improve the reliability of equipment and reduce
the damage due to lightning or fault current .

• To provide a safe path for the dissipation of fault currents, lightning strikes,
static discharges, EMI and RFI signals and interference.

• National Fire Protection Association (NFPA ) and IEEE have recommended a


ground resistance value should be 5ohm or less

28 © 2020 | Fluke Industrial Group

28

14
2/22/2021

Methods of Testing (Transmission / Distribution)

Selective Testing method Selective Testing method

29 © 2020 | Fluke Industrial Group

29

Transmission Earth Testing

30 © 2020 | Fluke Industrial Group

30

15
2/22/2021

Distribution lines with concrete base

- Stakeless method (only 2 clamps): the result is 2.912 ohm.

- Differences from 3-pole method is only 0.162 ohm.

31 © 2020 | Fluke Industrial Group

31

Summary of the earth ground testing

Fall of potential method Selective method Stakeless method Building Grounding test method

32 © 2020 | Fluke Industrial Group

32

16
2/22/2021

Safe and Early detection of problems in Utility

Transformer A transformer operating at just 10C above


its rating will reduce its life by 50%! Transformer
Cooling Tubes

Common failures
• Loose connection
• Harmonics
• Unbalance
• Overloading
• Cooling issue

Transformer normal
thermal pattern

Cold thermal pattern in 4th bank of cooling tubes indicates


the oil isn’t circulating

33 © 2020 | Fluke Industrial Group

33

Key Electrical Applications in Utility

UPS Batteries The optimum ambient air temperature around


a VRLA battery is 22C +/-5C. Every 1C
increase in operating temperature will reduce
5% of battery life

Battery terminal connection problem Whole battery cell overheat could be due to Elevated heating pattern on a UPS battery
poor air circulation cell, most likely caused by an internal short
causing high resistance
34 © 2020 | Fluke Industrial Group

34

17
2/22/2021

What can be done at hard-to-reach area?

Fluke Telephoto lens

35 © 2020 | Fluke Industrial Group

35

Fluke CV400 IR Window

• Highest arc blast safety rating—63kA

• IP67 for years of maintenance free

• Rugged construction

• AutoGround™ technology instantly grounds


window to enclosure upon installation

• Quick installation

36 © 2020 | Fluke Industrial Group

36

18
2/22/2021

Low Voltage Segment SOLUTION

37

Low Voltage Application

Grounding
Power Back up
for
Quality Power ( UPS)
substation

Power and Battery


harmonic testing Earth
application Application Grounding

Electrical
UPS transfer
Partial Cable tracer
time
discharge

AC /DC testing

38

38

19
2/22/2021

Power Quality

39

Where is it used – Customer Workflows?

Power & Energy Value


Stream 3

4
1
2 5
Utility Power Gen Utility Distribution Utility Distribution Industrial & Commercial
<50MW, Renewable sources & Substation Power Quality Branch circuits, last mile PQ Energy & PQ Monitoring
energy storage Monitoring and energy services

Workflows where monitoring power quality is integral to Utility management and QA or Industry
operations uptime and Opex spend
• Utility system planning, demand management and PQ analysis.
– The task of understanding power consumption to ensure the distributed power meets the ever-growing needs of industry
and the consumer.
• Industrial and commercial facility electrical infrastructure, m onitoring power at main service entrance and critical
branch circuits
– Mitigate power quality issues that disrupt company operations
– Trend energy consumption trends, identify waste and savings opportunities
40

40

20
2/22/2021

Standards – EN50160
What is EN50160?
• The EN50160 standard is used across Europe to describe the allowable levels of power quality provided by electricity
distributors, it includes a range of measured variables and the allowable level for each individual measured parameter,
these include:
– Frequency
The power quality is measured at the point where the
– Short interruptions utility transfers power to the consumer, at the point of
– Long interruptions common coupling (PCC), where the utilities revenue meter
– Flicker PST is typically located.
– Flicker PLT The EN50160 has some serious limitations, it includes a
significant amount of time during the any seven days
– Interharmonic voltage period when power quality does not have to meet the
– Temporary overvoltages allowed level for many hours per week.
– Voltage dips The described levels are useful for all users as a basic
– Voltage variations description of the power quality state of health.
– Harmonic voltages
Applies to HV, MV and LV networks with different
– Mains signaling voltage
allowable levels at each voltage
– Rapid voltage change
– Voltage unbalance EN50160 is used more as the starting point of negotiation with the power utility and
consumer rather than a minimum quality standard the utility agrees to.

41

41

Standards – IEEE519
What is IEEE519-2014?
• The IEEE519 relates to the distortion requirements when installing harmonic loads on the power network.
• The standard details the allowable voltage and current distortion limits allowable at the point of common
coupling
• Different voltage distortion limits apply at separate voltage levels of:
1kV, 1kV to 69kV, 69kV to 161kV and over 161kV:
• The current distortion limits apply at a different set of voltage levels:
120V to 69kV, 69kV to 161kV and over 161kV
• During testing the load is operated to discover the level of distortion created during typical operating cycles.

Harmonic loads within this context are non-linear loads such as static power converters, arc discharge devices, saturated magnetic
devices, and, to a lesser degree, rotating machines. Nonlinear loads change the sinusoidal nature of the ac power current (and
consequently the ac voltage drop), thereby resulting in the flow of harmonic currents in the ac power system that can cause
interference with communication circuits and other types of equipment.

42

42

21
2/22/2021

IEEE519 – Limit Examples

Voltage harmonic limits for all voltage level

Bus voltage V at PCC Individual Harmonic (%) Total Harmonic Distrortion THD (%)
V ≤ 1.0kV 5.0 8.0
1kV < V ≤ 69kV 3.0 5.0
69kV < V ≤ 161kV 1.5 2.5
161kV < V 1.0 1.5
Current harmonic limits at 69kV to 161kV:
Maximum harmonic current distortion in percent of IL
Individual harmonic order (odd harmonics) a, b
ISC/IL 3≤ h <11 11≤ h < 17 17≤ h < 23 23 ≤ h < 35 35≤ h ≤50 TDD
<20 2.0 1.0 0.75 0.3 0.15 2.5
20 < 50 3.5 1.75 1.25 0.5 0.25 4.0
50 < 100 5.0 2.25 2.0 0.75 0.35 6.0
100 < 1000 6.0 2.75 2.5 1.0 0.5 7.5
>1000 7.5 3.5 3.0 1.25 0.7 10.0

The IEEE519/Report software module direct compares the measured values with the limits of the
standard to produce detailed reports in the minimum time.
43

43

IEC61000-4-7 - Harmonics

• The IEC61000-4-7 standard is a general guide on harmonics and interharmonic measurement and
instrumentation for power networks
• It describes in detail the methods that should be used for measurement and classification of the measured
values of harmonics and interharmonics
• In addition to the main standard there are two additional annex documents that describe the measurement
of interharmonics and harmonics in the frequency range above 9kHz.
• These two documents are informative, that is that are not strictly part of the standard.
• The standard does include a variety of limits that other standards specify in a number of examples to show
how the standard is used but nominally does not have built-in limits. These standards include:
• IEC 60038
• IEC 61000-2-2
• IEC 61000-3-12
• IEC 61000-3 series (various standards)

The purpose of this standard is to ensure that measurements of harmonics are consistent by various
measurement instrument so that results can easily be compared when multiple instruments are
used.
44

44

22
2/22/2021

IEC61000-4-15 / IEEE1453 Flicker

• The IEC61000-4-15 and IEEE1453 describe the methods of measurement of flicker in power systems.
• Flicker is caused by fluctuations in the power system voltage which result in observable changes in the light output
of electric lamps. It can be an annoyance and hindrance to workplace productivity and visually affect susceptible
individuals.
• The fluctuation may also cause detrimental effects to electrical equipment such as nuisance tripping of breakers,
unwanted switchover in UPS systems and problems with sensitive electronic equipment that need constant
voltage (e.g. medical equipment)
• The basic measurement of flicker is PST, short term flicker and PLT, long term flicker. Short term is considered over a
10 minute period and long term over a 2 hour period.
• A PST value of 1.0 for flicker represents a figure that 50% of people would perceive flicker in a 60W incandescent
bulb. Although incandescent bulbs are used less frequently the overall effect of flicker remains present on other
lighting and equipment.
• The two standards are almost identical, the IEC standard refers to 230V operated system and the IEEE refers to
120V operated systems.

The typical source of voltage flicker comes from randomly operating loads such as arc furnaces,
welding machines, intermittently starting and stopping induction motors.
45

45

IEC61000-4-30

• The IEC61000-4-30 standard describes the measurement and testing methods to be used by power quality
measurement instruments. It allows two classes of instruments, Class A and Class S.

• Class A offers the best accuracy and Class S is considered to be acceptable for regular power quality surveys.

• The main differences in accuracy are in the measurement of voltage and time. For Class A, voltage accuracy of 0.1
% of declared input voltage UDIN over the range of 10% to 150% of UDIN is required

• For time accuracy, ± 20 ms for 50 Hz and ± 16.7 ms for 60 Hz is required regardless of the total time interval.
Achieving this accuracy requires either a GPS clock via a GPS receiver or NTP (Network Time Protocol) via Ethernet

• The standard describes the method required for measurement (as per IEC61000-4-7 and -15) and dictates the
methods used for classification and flagging of specific items to enable consistent reporting.

• The Fluke 1740 series will be independently verified to comply with Class A by an external agency.

Class A is particularly useful in dispute resolution between the power supplier and the consumer,
the higher accuracy requirements for Class A analyzers enables both user in the dispute to make
measurements that will be identical.
46

46

23
2/22/2021

Class A Data

Aggregation:
• Data is specified to aggregate at multiple rates depending upon the logged value. The primary aggregation periods
are:
• 150/180 cycles (150 cycles for 50Hz and 180 cycles for 60Hz)
• 10-minute interval
• 2-hour interval (note that the 10 minute and 2-hour periods are those specified for flicker in IEC61000-4-15)
• The 10-minute interval is the one which most data is represented by, each 10-minute interval is made up multiple
150/180 cycle periods

Event Capture
• The identification of the time stamp of events (any significant change in the voltage) is made based on the
occurrence of the event with a half-cycle trigger – that is a half cycle RMS voltage outside of limit will be classified as
an event.
• To identify the occurrence of an event each part of the event is ‘flagged’ to indicate that item is part of one event –
this is to ensure that the effects of the event are consolidated into one for simplicity of analysis.

47

47

Measurement Standard Summary

• The prevailing standard for power quality can be split into two areas:
• Measurement and evaluation (for equipment)
• IEC61000-4-7 (Harmonics)
• IEC61000-4-15 (Flicker)
• IEC61000-4-30 (Methods)
• Evaluation of logged data against limits
• EN50160
• IEEE519
• GOST (Russian standard)
• This is not a comprehensive list of standards for power quality, but these are most frequently quoted standards.
• In many cases there a geographical adaptation of the standards which evaluate against limits which use locally
defined limits, the Fluke 1740 series have adjustable limits to adapt the instrument and reporting to these
situations.
• There are also localized reporting standards that can be configured within the instrument and in reports in the
application software.

The purpose of any standard is to ensure that repeatable results are being created every time,
whether that be in the measurement and evaluation of data or whether that is in the evaluation of
data against allowable limits.
48

48

24
2/22/2021

What are the harmonics ?


• In a normal ac power system, voltage
varies sinusoidal
• With non-linear loads such a rectifiers
and switches, the current draw is not
necessarily sinusoidal
• The waveform is then complex
• The complex waveform can
be decomposed into individual
sinusoidal components
• These harmonic components impact
motors, transformers, cabling and other
electrical components

49

Identifying harmonics waste


Power quality analyzers display a spectrum graph of harmonic components present in a system, but the graph on its own
does not quantify the amount of energy wasted by harmonics.

Harmonics cause:
• unusable power, drawn from utility but not
converted to actual work
• high current to flow in neutral conductors
• motors and transformers to run hot, decreasing
efficiency and shortening lifespan
• increased susceptibility to voltage sags
• reduced transformer efficiency — or, a larger
unit is required to accommodate harmonics.

50

25
2/22/2021

The insidious 3rd harmonic

Technical lesson 400


300
200
100

On a three-phase / four-wire system, triplen (zero 0


-100 0 90 180 270 360

sequence) harmonics will add up in the neutral. -200


-300
-400

This is true for all triplen harmonics including 6th, 9th, 12th,
15th 400
300
200
100

3rd Harmonics are created 0


-100 0 90 180 270 360
-200
from Non-linear loads: -300
-400

•Diodes
400
•Transistors 300
200
•Electric motors 100

•SMPSs (switch-mode
0
-100 0 90 180 270 360
-200
power supply) -300
-400

The third harmonics are all in phase


and create unbalance

51

Harmonic sequences

Technical lesson

Positive, negative, zero sequence

Sequence Rotation Effects (from skin effect, eddy currents, etc.)


Positive Forward Heating of conductors, circuit breakers, etc.

Negative Reverse Heating as above + motor problems

Zero None Heating + neutral current in wye systems

Effects of harmonic sequences


Name F 2nd 3rd 4th 5th 6th 7th 8th 9th

Frequency 50 100 150 200 250 300 350 400 450

Sequence + - 0 + - 0 + - 0

Note: If the waveform has no dc offset then it has no even harmonics

52

26
2/22/2021

Fluke 438 Series II: Power Quality And Motor Analyzer

Energy Wastage in Cable Very


Energy Wastage through Reactive Load Important
Energy Wastage through unbalance load
distribution
Energy Wastage through Harmonics issues
Energy Wastage through High Neutral current

Benefits of Fluke 438 Series II Power Quality And Energy Analyzer


• Quantify Energy wastage in your Power System for effective identify Utilities Saving
• Efficiently detects ”Root Causes” of Power Quality Issues
• Effective Predictive Maintenance tools to enhance equipment lifespan and have a
good understanding of the condition of your control system.

53

Partial Discharge

54

27
2/22/2021

What is acoustic imaging?

• A technique to create an image of the scene based on the sounds in the scene
• The sound image is then overlaid onto a visible image

55

55

Why does Power Transmission/Distribution Plant


need ii910?
56

56

28
2/22/2021

Why Do People Care About Partial Discharge?

• Unplanned downtime/outage caused by PD can lead to loss


of revenue and impact the community at large
• Eg. Loss of generated electricity of approx. 1,000 USD per
minute for a medium sizes power generation facility.

• Additional costs for repairs and equipment damage


• Energy waste
• High penalty from government

• Undetected PD will cause arch flash or even explosion →


Safety risk for human and equipment

57

Ii910 Real Application – Detecting PD in Transformer

58

58

29
2/22/2021

Ii910 Real Application - Inspecting PD in Electrical Distribution System


Detection of Partial Discharges and Arcing in HV/MV electrical cabinets and on busbars

❑ Safety: able to detect from safe distances


❑ Effective and fast in location of PD
❑ Easy to use with minimum training required
❑ Documenting with pictures

59

Ii910 Real Application - Inspecting PD in Electrical


Distribution System
Detection of Partial Discharges (and Corona) on Distribution Lines and Switchgears

❑ More effective in outdoors than ultrasonic tools


❑ Fast routing
❑ Easy for untrained users
❑ Documenting with pictures

Inside of the cabinet with severe PD

60

30
2/22/2021

Battery Health Prediction

61

• Power protection systems in medical institutions have higher standards than those for commercial or industrial use

Under most circumstances, a hospital losing power could be the difference between life
and death for any number of patients who are reliant on its systems functioning at
optimum levels.

• Batteries operate by converting chemical energy into electrical energy


through electrochemical discharge reactions.
• Batteries are composed of one or more cells, each containing a
positive electrode, negative electrode, separator, and electrolyte
• Batteries are rated in terms of their nominal voltage and ampere-hour
capacity
Type of Battery

62

62

31
2/22/2021

Meter mode
+ = for quick ad-hoc battery
test

RSOB operation Dual mode combines the simplicity of DMM and


functionality of string data management. Will be
Switch with one button and easy to get going for both entry level user and
continue at break point
sophisticated user.

= Sequence Mode

+ Maintenance tasks with multiple


power systems and battery
strings

63

63

Step 2: Internal Resistance + Voltage + Temperature

Even more accurate


• The spot of the IR sensor is focused on the battery
negative post during measurement. So, the battery
internal temperature can be tested accurately through
the negative post.

64

64

32
2/22/2021

• Coaxial probe
– One pole carries current
– One pole senses voltage
– Insulator
• The rugged probes are sharp to ensure good contact with metal parts.
• Each type of test probe has the same Kelvin arrangement

Probe breaking testing

Fluke done 17000 times press test and result the


Kelvin probe no breaking and its proven.
The probe its strengthens and very robust

65

• Most battery manufacturers specify <0.5% AC ripple voltage of


the DC voltage

• High ripple voltage will produce


ripple current battery temperature
and resulting energy loss
• Temperature conversion rate
is about: 4.6 W/m²/ °C

• Damage to the battery life of battery


temperature increases

• High ripple voltage may be due poor quality or poorly performing


charging equipment
• Up to 20 ripple voltage readings can be saved in one profile .

66

66

33
2/22/2021

Historical trend data of batteries


Histogram of a battery string with user
defined threshold

Multiple rounds of discharge voltage

67

67

Transfer time identification

68

34
2/22/2021

Impact Of UPS Transfer Time (ScopeMeter)

Is this going to charge up? Zoomed detail of a failed switchover Zoomed detail of a correct switchover

69

AC and DC testing

70

35
2/22/2021

Transformer Application
Customer Name – ABB (Low Voltage Drives Division) Fluke Norma 6004
Application – To measure the Output efficiency of Low Voltage Drives -- Quality check before dispatch
Model sold – Fluke Norma 6004 & 6004+ (Value – 20 KUSD)

Customer Pain Points Fluke Offered Values


• Measurements on Output side of VFD • 3 Phase V-pwm and Arms Signals measurements at
Output of drive
• Unable to measure waveforms
(Vpwm, Arms & Hz, THD V/A) • More than 15 parameters visible in a single screen
(Vpwm, Arms, THD & Power etc...)
• Need to measure above 50th Order Harmonics LV – Drives
• Measurement upto 100th Harmonic & Wider
• Requirement of portable product (Battery Bandwidth of 500KHz
Operated)
• Portability & Battery operation (10 Hours Backup &
• Memory issue @ field usage Avoids additional power supply in field)

• Safety concern on field usage • 32GB in-built memory

• CAT-III & CAT-IV rated product for field testing

Other features Considered by ABB :


• Synchronizing 2 instruments for comparing the efficiency of the drives (input & out put)
• Measuring Torque & Speed in 6004+ for verification of motors
• Reliable results
• Simple in Operation

71

EV battery application

Customer: LG Chemical (EV Battery)

Application: DC measurement when EV is in operation


• Battery output DC current & voltage
• Inverter output
• Log data for DC current & voltage trend and DC Transient (instantaneous
DC impulse or current out-flow exceeding the proper load.

Fluke Solution: Norma 6004 with 2000A clamp (70% probability in 2021)

Fluke Offered Values:


• Portability with battery power supply in field
• 32GB in-built memory
• CAT-III & CAT-IV rated product for field testing

72

36
2/22/2021

POLL QUESTION No. 3

? What is the measurement parameter can capture using Fluke 6004+?


(Click only one answer)

A. Harmonic . AC+DC measurement , Motor analysis, inverter efficiency


B. Signal injection and signal verification
C. Network analysis

73

Q&A

74

37
2/22/2021

Thanks!!!

75

DEMO POLL QUESTION

? Do you wish to know more about the following products?


(Click all that apply)

▪ Fluke 438-II Power Quality Analyzer & Motor


▪ Fluke ii910 Precision Acoustic Imager
Analyzer
▪ Fluke TiX580 Infrared Camera + Tele lens
▪ Fluke BT-521 Battery Tester
▪ Fluke 1625-II + Split core
▪ Fluke Normal 6004+
▪ UAT 620 Underground Cable Locator
▪ Fluke 125B scope meter
▪ TIC 300 High Voltage Detector
▪ Fluke Normal 6004+

76

76

38
2/22/2021

THANK YOU!
p

Email Fluke South East Asia:


FSEA.info@fluke.com

For related product information, go to:


https://www.fluke.com/en-sg

77

77

39

You might also like