Professional Documents
Culture Documents
10 October 2008
Special Instruction
i02980244 AnalogIn1_RefLow ............................................ 16
AnalogIn1_RefHigh ........................................... 16
Pandaros Digital Governor AnalogIn1_ErrorLow ......................................... 16
AnalogIn1_ErrorHigh ......................................... 16
LoadControlFactor and
LoadControlReference .................................... 17
Industrial Engine Synchronizer Settings ....................................... 17
4006 TRS GAS ( SG6) ADC 2_Type .................................................. 17
4008 TRS GAS ( SG8) AnalogIn2_RefLow ........................................ 17
4012-46A ( S12) AnalogIn2_RefHigh ....................................... 17
AnalogIn2_ErrorLow ...................................... 18
4016-61A ( S16) AnalogIn2_ErrorHigh ..................................... 18
SynchronFactor and SynchronReference ..... 18
Table of Contents Additional Programmable Parameters .............. 18
Engine Configuration ......................................... 18
Introduction ........................................................... 2 SpeedMin1 and SpeedMin2 .......................... 18
System Overview .................................................. 3 SpeedMax1 and SpeedMax2 ........................ 18
Description of System ........................................... 4 Engine Stop ....................................................... 18
Diagram of the Governor System ......................... 5 Switch or Impulse .......................................... 18
Specification of Governor System ........................ 5 Close or Open ............................................... 18
Current consumption of the governor ................ 5 Common Alarm ................................................. 18
EMC Directives ................................................. 5 Adjustment of PID parameters .............................. 18
Setting for the Feedback ....................................... 6 PID Maps .............................................................. 19
Setting the Feedback without the Service Tool ..... 10 Speed Ramps ....................................................... 20
Configuration ........................................................ 10 Fixed Speed Ramp ........................................... 21
Speed ................................................................ 11 Programming example .................................. 21
Droop/Isochronous ............................................ 11 Activation ....................................................... 21
External Input for Speed Control .......................... 11 Sectional Speed Ramp ......................................... 21
Single generator fixed speed ............................ 11 Programming Example ...................................... 23
Single generatorvariable speed ........................ 11 Activation ........................................................... 23
Parallel generator Heinzmann LSU/Sync ............. 11 System Wiring ....................................................... 23
Parallel generator LSU/Sync ............................. 11 External Connections Perkins Supplied Cable for
Changing the configuration of the governor .......... 11 Diesel Engines ................................................ 25
Single generator fixed speed ............................ 12 External Connections and the Connector for the
Single generator variable speed ........................... 13 Control Box for Diesel Engines ....................... 26
Droop ................................................................ 13 External Connections for Diesel Engines .......... 27
Droop ............................................................. 13 Cable Sizes ....................................................... 27
DroopRefLo ................................................... 13 Alternative Connections for Speed Setting
DroopRefHi .................................................... 13 Inputs ............................................................... 27
DroopSpeedRef ............................................. 13 Single or Parallel Generator Variable Speed .. 27
ADC1 Type .................................................... 14 Parallel Generator Heinzmann LSU/Sync ..... 28
AnalogIn1_RefLo ........................................... 14 Parallel Generator other LSU/Sync ............... 28
AnalogIn1_RefHi ........................................... 14 Wiring Diagram for the Digital Control Box in IP
AnalogIn1_ErrorLow ...................................... 14 Enclosure ........................................................ 29
AnalogIn1_ErrorHigh ..................................... 14 Diagram for the Wiring Harness for 4006 and 4008
AnalogIn1_Filter ............................................ 14 Diesel Engines ................................................ 30
Parallel generator Heinzmann LSU/Sync ............. 15 Diagram for the Wiring for 4012 and 4016 Diesel
Parallel generator other LSU/Sync .................... 15 Engines ........................................................... 30
Load Control Settings ........................................... 16 Diagram for the Wiring for 4006 and 4008 Gas
ADC 1_Type ...................................................... 16 Engines ........................................................... 32
1
Finding Faults .................................................... 34 The actuator is connected to the linkage of the fuel
Test 1 ............................................................. 34 injector on diesel engines in order to control the
Test 2 ............................................................. 34 amount of fuel. The actuator is connected to the
Test 3 ............................................................. 34 throttle valve on gas engines in order to control the
Test 4 ............................................................. 34 amount of fuel.
Test 5 ............................................................. 35
Test 6 ............................................................. 35 The control unit is engine mounted within an IP55
The governor lever moves when cranking the enclosure.
engine but the engine will not start (Diesel
Engines only) ................................................... 35
Test 1 ............................................................. 35
Test 2 ............................................................. 35
Test 3 ............................................................. 36
Test 4 ............................................................. 38
Test 5 ............................................................. 38
Governor moves to maximum position when power
supply is switched on. ..................................... 39
Test 1 ............................................................. 39
Test 2 ............................................................. 39
The engine goes to overspeed after starting ..... 39
Test 1 ............................................................. 39
Test 2 ............................................................. 39
Test 3 ............................................................. 40
The governor is not stable ................................. 40
Test 1 ............................................................. 40
Test 2 ............................................................. 40
Test 3 ............................................................. 40
Test 4 ............................................................. 40
Test 5 ............................................................. 41
Test 6 ............................................................. 41
Test 7 ............................................................. 41
Speed droops under load .................................. 41
Test 1 ............................................................. 41
Test 2 ............................................................. 41
Test 3 ............................................................. 42
Test 4 ............................................................. 42
The engine will not pull load .............................. 42
Error Codes ....................................................... 43
Error Memory .................................................... 46
Introduction
The Heinzmann Pandaros digital speed governor
is installed to a Perkins 4000 Series engine.
This Special Instruction gives an overview of the
governor system and details of customer interface
requirements.
• Control unit
• Actuator
• Setpoint adjusters
• Sensors
• Connection cables
2
System Overview
g01216812
Illustration 1
(1) Laptop computer (9) Load sharing (17) Mains parallel
(2) Control unit (10) Voltage matching (18) Island parallel
(3) Run status (11) Reactive load share (19) Group synchronizing
(4) CAN Communication (12) Speed ramp (20) Digital power control
(5) DC - Desk displays (13) Load ramp (21) Governor sensor
(6) Governor errors (14) Soft load transfer (22) Actuator
(7) Stop/Run (15) Isochronous ramp
(8) Synchronizing (16) Power factor set
3
Note: A protection device for the external overspeed
NOTICE must always be used with the internal overspeed.
Adjustments to the control unit may only be made
by an authorised Perkins representative equipped
with the necessary programmer. There are no user
adjustments inside the box.
Description of System
The electronic control unit is the center of the system.
There is a 16 bit microprocessor in the control unit.
The processor operates the program which controls
the system. The program which controls the system
is stored in a FLASH-EPROM section of the memory
. The control unit compares the actual engine speed
that is measured by the magnetic pickup on the
flywheel with the desired speed of the engine. The
control unit helps to drive the actuator and the input
of the fuel to the engine so that the actual engine
speed matches the desired engine speed.
• Engine temperature
• Fueling control against engine temperature
• Connection of additional automatic load sharing
• Synchronizing equipment
A PC program with special interface cable is used for
initial setting of the parameters for the governor and
optimizing the system and for finding faults.
4
Diagram of the Governor System
g01216814
Illustration 2
(1) Switch inputs (5) Failure lamp (9) Pressure sensor
(2) Analog setpoint adjuster (6) Interface RS 232 (10) Temperature sensor
(3) Analog synchronizer (7) 24 V Power supply (11) Actuator that senses position
(4) Analog unit of measure for the load (8) Speed sensor (12) Actuator drive
• The protection of the fuse for the governor is fifteen ISO 11452-2: Frequency band F2, 60 V/m
amp.
Functional status B
5
Functional status B
Functional status B
6
g01216887
Illustration 3
(1) PC (2) Control box
7
g01216892
Illustration 4
8
g01216909
Illustration 5
g01216949
Illustration 7
7. The user will then be asked if the parameter 9. The actuator can now be installed to the engine
values should be stored in the control unit. The and the linkage connected.
user should select the option that states yes.
9
Setting the Feedback without the
Service Tool
When the actuator is replaced and the Service Tool
is not available, the setting for the feedback can be
calibrated. Follow steps 3.c to 6.
g01216965
Illustration 8
1. Remove the lid of the IP55 box for the governor. Note: To properly perform automatic calibration, the
Remove the lid of the Pandaros box. actuator must operate smoothly and the actuator
must be able to easily move from 0% to 100% (left
2. Connect the cable from the control box to the stop and right stop). It is therefore necessary for the
actuator and apply 24 volts to the governor. actuator to be disconnected from the engine linkage.
This procedure is not necessary with the combined
3. Locate the push button (1) for the setting for the actuator and the valve for the throttle that is installed
feedback. Refer to illustration 8. to gas engines.
4. Ensure that the actuator output shaft has been 6. Remove the 24 V supply. Replace the covers and
disconnected from the engine linkage. The install the actuator to the engine.
actuator should be free to move from 0% to 100%.
10
Speed Note: Any other changes to the configuration
require the use of the Service Tool and the special
• 1500 rev/min communication cable. Refer to the Service Tool
manual for information on other configurable
• 1800 rev/min parameters.
Single generator fixed speed The various parameter settings for the engine modes
are detailed below.
The default configuration is Single Generator Fixed
Speed. The single generator has no provision for Note: After the parameters are changed, it is
parallel operation or speed control. The speed will be necessary to store the parameters in governor. Then
fixed at 1500 rev/min or 1800 rev/min. power down the governor. Power up the governor
again before the changes take effect.
Single generatorvariable speed
Refer to illustration 9 in order to view the configuration
This mode allows the Load Sharer input to be used screen for the service tool.
with an external 5K potentiometer for manual speed
setting control. In this configuration, an external
speed setting control must be connected in order to
enable the engine to run. There are options for either
the synchronizer or the droop operation.
11
g01217756
Illustration 9
Single generator fixed speed For single speed 1800 rev/min operation, the
parameter number SpeedFix2 is used to set the
Select the button for Single generator fixed speed engine speed.
on the Generator Mode. The engine will operate in
isochronous mode at a fixed speed of 1500 rev/min For 1500/1800 rev/min operation, the parameter
or 1800 rev/min. The engine will be switchable SpeedFix1 is used to set 1500 rev/min and the
between these speeds. parameter SpeedFix2 is used to set 1800 rev/min.
Note: For some engines, the selection of 1800 rpm If the box LockedSwitchOn is selected, the engine
running can only be done by the factory. will be single speed. The speed is selected by the
SpeedFix1Locked or SpeedFix2Locked buttons.
NOTICE
Engines supplied as 1500 rev/min units must not be If the box LockedSwitchOn is not selected the engine
switched to 1800 rev/min units without approval from is switchable speed from an external switch. When
the factory. Hardware changes may be required for the engine speed of 1500 or 1800 is selected,
the engine to run at 1800 rev/min. Failure to heed various parameters such as overspeed settings are
this notice can lead to premature failures, product automatically adjusted in order to suit the selected
damage, personal injury or death. speed of the engine. The current overspeed setting
is displayed on the screen. The setting cannot be
changed.
For single speed 1500 rev/min operation, the
parameter SpeedFix1 is used to set the engine
speed.
12
Single generator variable speed
Droop
For manual parallel operation, droop mode is required
with an engine speed that is capable of being varied
for synchronizing and the sharing of the load. This
mode is selected by setting the Generator Mode to
Parallel generator variable speed with droop.
Droop
DroopRefLo
DroopRefHi
DroopSpeedRef
13
g01217988
Illustration 10
The parameter enables the selection of the correct AnalogIn1_Refhi will set the highest value for the
type of analog input. The settings are shown below. analog input as an input that is valid. For an external
speed control for the potentiometer, this should be
• 0 to 5 volt input set to 5.
Note: After selecting a different type of analog input, AnalogIn1_ErrorHigh sets the high input level when
the governor must reset for the change in order to an error will occur.
take effect.
AnalogIn1_Filter
The other available adjustments are detailed below.
AnalogIn1_Filter sets the filter level. It is not normally
AnalogIn1_RefLo necessary to change this value.
The AnalogIn1_RefLo will set the lowest value for The remainder of the settings on the screen
the analog input as an input which is valid. For an determine the value in the event of an error on the
external speed control for the potentiometer, this speed input. Store the last valid value or use a
should be set to 0. substitute value.
14
Parallel generator Heinzmann
LSU/Sync
When the Generator Mode - Parallel generator option
is selected, the screen will change. The screen will
allow the selection of Heinzmann LMG/Syg or Other
options.
g01217991
Illustration 11
If Heinzmann LMG/Syg is selected, the Load Control The Load Control tab allows the setting of the input
and the inputs for the synchronizer are automatically parameters of the Analogue 1. The Synchronizer
set to the correct values and no other adjustments tab allows the setting of the input parameters of the
are required. Analogue 2.
Parallel generator other LSU/Sync Note: The range of the external speed control may
be limited by parameters SpeedMin and SpeedMax.
There are many possible variations of load sharing The parameters can be changed.
and requirements for the input of the synchronizer
unit. Some options may only require one input The remainder of the settings on this screen
whereas other options may require two inputs. The determine the value in the event of an error on the
section details the available inputs and the possible speed input. Store the last valid value or use a
settings for the inputs. substitute value.
For this mode, the Generator Mode must be set to For use with the digital load sharing or synchronizing
Parallel Operation and the LSU/Sync mode set to units, refer to the factory.
Other. The Load Control and the Synchroniser tabs
will allow the two analog inputs to be set for the
variable speed option.
15
Load Control Settings
g01217994
Illustration 12
AnalogIn1_RefHigh
AnalogIn1_RefHigh will set the largest value that
analog input 1 will accept as a valid input.
16
LoadControlFactor and
LoadControlReference
If analogue input 1 is used, the two parameters set
the range of the external speed control and the
reference % for nominal speed. If 1500 rev/min is the
nominal running speed and speed variation of +/- 5%
speed variation is required, set LoadControlFactor at
10% and LoadControlReference at 50%.
Synchronizer Settings
g01220859
Illustration 13
The parameter enables the correct selection of input AnalogIn2_RefLow will set the smallest value that
that is required by analog input 2. The settings are analog input 2 will accept as a valid input.
listed below.
AnalogIn2_RefHigh
• 0 to 5 volt input
AnalogIn2_RefHigh sets the highest value the analog
• 0 to 10 volt input input will accept as a valid input.
• 4 to 20 mA input
17
AnalogIn2_ErrorLow Common Alarm
AnalogIn2_ErrorLow sets the lowest value at Connect a 24 volt lamp to the output in order to
which the analog 2 input signal will give an indicate a fault with the governor.
error. If AnalogueIn2_RefLo was set at 0.5 volt,
AnalogIn2_ErrorLo could be set at 0.3 volt. This Adjustment of PID parameters
enables detection of an open circuit or faulty input
signal.
The engine is supplied with the governor PID
(Proportional, Integral and Derivative) gain
AnalogIn2_ErrorHigh
parameters. The PID will give a stable operation with
the majority of engine and alternator combinations.
AnalogIn2_ErrorHigh sets the highest value at When instability occurs with a particular combination
which the analog 2 input signal will give an
of engines and alternators, it will be necessary to
error. If AnalogueIn2_RefHi is set at 4.5 volt,
change the governor PID.
AnalogIn2_ErrorHi could be set at 4.7 volt. This
enables detection of a faulty input signal.
The PID parameters are available on the Adjustment
– Speed Governor tab. Refer to illustration 14.
SynchronFactor and SynchronReference
Engine Configuration
SpeedMin1 and SpeedMin2
Engine Stop
Switch or Impulse
Close or Open
18
g01220944
Illustration 14
To set the parameters, the engine is started. The Set the parameter values. Interrupt the engine speed
engine can be operated to the working point. The for a short period of time by operating the engine stop
adjustment can be made at this point. Usually, this switch. Observe the transient response. Continue
working point will be at rated speed and off-load. to modify the PID parameters until the transient
To optimize the PID parameters, use the following response is satisfactory.
procedure.
PID Maps
• Increase the P-factor Gain until the engine tends
to become unstable. Decrease the P-factor until The PID values which give optimum performance
the speed oscillations disappear or the speed
are different for the various load values. Gains may
oscillations are reduced to a moderate level.
be greater with increasing load. The governor gains
are plotted. Plot gain versus load. The maps are
• Increase the I-factor Stability until the engine created during the process of engine development.
operation alters to speed oscillations that have
The service tool can change the maps.
longer waves.
There are two sets of PID maps. One map is for
• Increase the D-factor Derivative until the speed speed. The speed is determined by the parameter
oscillations disappear. If the oscillations cannot SpeedFix1. The other map is for speed that is
be eliminated by the D-factor, the I-factor must be
determined by the parameter SpeedFix2.
reduced.
19
To adjust the maps, on the Adjustment – Speed
governor screen, click the PID Map open button.
Then select the edit button on the map screen. For
engines that are a fixed speed, only the first column
is used. If necessary, change the gain entry against
the actuator position (Y axis) when the instability
of the gain occurs. The values are percentages.
For example, 100 represents 100%. This does not
change the basic PID values.
g01220950
Illustration 15
20
The ramp functions are activated by selecting the
SpeedRampOn box on the Configuration – Engine
tab.
Programming example
Table 1
Parameter Value Unit
SpeedRampUp 25 rpmps
Activation
• SpeedRampOn is selected.
• FixedRamp is selected.
21
g01221147
Illustration 16
Note: The points that will result in the ramping rate • SpeedRamp1 - SpeedRampDown.
changing are determined by the parameters that are
listed below. Ramp rate for ramping downward in section 1
22
The unit of the parameters is given by an increase
in speed or a decrease of speed per second. The
ramps are enabled by selecting the SpeedRampOn
box. Selection of the sectional speed ramp is made
by selecting the Sectional Ramp button.
Programming Example
The upward ramping rate between the minimum
speed and 800 rpm is 100 rpmps. The reduction
of speed is operated in a short period of time. The
speed range of upward ramping rate lies between
800 rpm and 1200 rpm is 50 rpmps. The downward
ramping rate is 40 rpmps. Between 1200 rpm and the
maximum speed the upward rates and the downward
rates are 20 rpmps.
Table 2
Parameter Value Unit
SpeedRamp1 - SpeedRampUp 100 rpmps
Activation
• SpeedRampOn is selected.
• Sectional Ramp is selected.
System Wiring
The cables (4) between the system components are
provided and installed by Perkins. A system diagram
is shown in illustration 17.
23
g01237886
Illustration 17
Typical example
(1) Control Box (3) Actuator
(2) Boost Pressure Sensor (if equipped) (5) Magnetic Pickup
24
External Connections Perkins Supplied
Cable for Diesel Engines
g01237943
Illustration 18
25
• CAN+ and CAN-
CAN bus connections for digital load
sharing/synchronizing (if equipped)
g01237963
Illustration 19
26
External Connections for Diesel Engines
g01237972
Illustration 20
(1) 15A fuse (3) Alarm lamp (5) CAN bus connections
(2) Run/Stop Switch (if equipped) (4) 1500/1800 switch (6) External analog controls
27
g01508540 g01507993
Illustration 21 Illustration 23
(1) 5k ten turn speed trim potentiometer (3) AT-01 Thesius with jumper set to digital
Parallel Generator Heinzmann LSU/Sync For the equivalent connections on the analog theseus
unit, refer to the Heinzmann manual.
Connect A3, B3 and E3 wires. Refer to illustration 22.
Parallel Generator other LSU/Sync
g01507990
Illustration 22
g01238308
(1) Synchronizer SYG02 Illustration 24
(2) Load measuring unit LMG 10-01 (1) The external speed setting can be a voltage or a current.
28
Wiring Diagram for the Digital Control
Box in IP Enclosure
g01238312
Illustration 25
(1) CAN H (3) Temperature Sensor (5) Boost Sensor 4 - 20mA
(2) CAN L (4) Boost Sensor 0.5 - 4.5V
29
Diagram for the Wiring Harness for 4006
and 4008 Diesel Engines
g01248438
Illustration 26
(1) Control Box (5) Connector for the OEM (J3) Connector for the control box
(2) Boost Pressure Sensor (J1) Connector for the control box for the (J4) Actuator connector
(3) Actuator magnetic pickup (J5) Boost pressure sensor connector
(4) Magnetic Pickup (J2) Connector for the magnetic pickup
30
g01248511
Illustration 27
31
(1) Relay RL2 (5) Control box (9) Connector for the OEM
(2) Relay RL1 (6) Actuator (10) Stop solenoid
(3) 3 pin Deutsch connector (7) Boost pressure sensor
(4) Start relay (8) Magnetic pickup
32
g01248508
Illustration 28
Typical example of the wiring diagram for a 4008 gas engine
33
(1) Hall effect pickup (5) HT leads (9) Connector for the OEM
(2) Magnets on the camshaft gear (6) Control box for the governor
(3) Ignition unit (7) Actuator or throttle valve
(4) Ignition coils (8) Magnetic speed pickup
Note: The faults relate to problems with the governor If the result is OK, proceed to Test 3.
system. The faults are not mechanical problems with
the engine. If the result is not OK, the governor is supplied with
24 volts from the wiring for the OEM onto the 14 pin
Test 1 plug at the left of the control box. Check for any blown
fuses in the supply line and for damaged wiring or
The lever of the governor will not move to the run broken wiring.
position when the engine is cranked.
Check for reversed battery polarity. A diode is
Ensure that the Shutdown switch is working. Ensure installed inside the control unit in order to protect
that the switch is in the Run position. against wrong polarity. No voltage will be measured
if the battery polarity is incorrect.
1. Remove the lid of the control box by removing
the 4 screws. If necessary, repair the components or replace the
components.
2. Turn off the 24 volt supply. Select the function for
ohms on the multimeter. Connect the multimeter to Replace the lid of the control box.
terminals 11 and 21 of the Pandaros DC 6 module.
STOP
3. Operate the run/stop switch. The run/stop switch
is part of the panel for the OEM so details will vary. Test 3
Note: The control box can be programmed for the Check the signal from magnetic pickup.
Run/Stop switch to be open or closed for operation.
The default setting is closed for operation. 1. Disconnect the 2 pin plug from the pickup at the
control box.
Result
2. Connect a multimeter on the AC voltage range to
The result is OK when the resistance that is measured the cable from the pickup.
is less than 1 ohm with the switch closed. There
should be a high resistance with an open switch. 3. Crank the engine. Check the pickup voltage at the
speed of the engine cranking. The voltage should
Proceed to Test 2. be 1.5V AC at the A2/B2 plug.
34
If the resistance is OK, it is possible that metal If the result is not OK, there may be a problem
particles have collected on the magnetic pickup. with the linkage. Correct the fault and retest the
The reduced output or the gap between the pickup equipment. If the resistance of the actuator is
and the teeth of the timing ring may be greater incorrect, the actuator is faulty. Replace the actuator
than 0.5 to 0.8 mm. Remove the magnetic pickup. and retest the new actuator.
Clean the magnetic pickup or replace the magnetic
pickup. Refer to Operation and Maintenance Manual, STOP
“Engine Speed/Timing Sensor - Clean/Inspect”.
The governor lever moves when cranking
If the result is not OK, there is a wiring fault or the
magnetic pickup is faulty. If necessary, repair the
the engine but the engine will not start
magnetic pickup or replace the magnetic pickup. (Diesel Engines only)
STOP Test 1
STOP STOP
35
Test 3
36
g01259965
Illustration 29
(1) RL2 (3) 3 pin Deutsch connector (5) The solenoid for the fuel stop is
(2) RL1 (4) Start relay energized in order to operate.
To start the engine, a 24 volt supply is initially put If the result is not OK, ensure that the 24 volt supply
onto pin B of connector J4. This will immediately is on. Use a multimeter on the DC voltage range
energize relay RL2. Both solenoids will be energized. across the coil of relay RL2. The reading should read
The first solenoid moves into position. The internal at least 24 volts.
contact supplies a battery negative onto the coil of
relay RL1 which energizes. This supplies a voltage to
the start relay contact. The second solenoid moves
into position. The contact of the second solenoid
supplies a battery negative onto the coil of the start
relay. The start button is pressed. This supplies a
positive battery voltage through pin C of J4 onto the
other side of the start relay which then puts power to
the solenoid coil of the starting motor (SMC).
Result
37
g01260004
Illustration 30
Wiring for the relay
(1) Coil terminals (2) Contact terminals (3) J4 Deutsch DT3 connector
Result Result
If the result is OK, proceed to test 4. If the result is OK, the relay RL2 is OK. Proceed to
Test 5.
If the result is not OK, there is a problem with
the supply to relay RL2. Trace the wiring fault If the result is not OK, the relay has failed. Replace
back through connector J4 to the control panel. If the relay and check that the solenoids are now
necessary, repair the component or replace the energized.
component.
STOP
STOP
Test 5
Test 4
Check the solenoid 1.
Check the voltage on the relay contact..
1. Remove the rubber covers from the end of both
Turn on the 24 volt supply. Select the DC voltage solenoids.
range on the multimeter. Use a multimeter to check
the voltage between each contact terminals. The 2. Locate the solenoid which has wire numbers 14
contact terminals are the large connections on the and 15. Wires 14 and 15 are connected to the
top of the relay. The wire numbers are 10 and 14. main terminals.
Test the voltage between the contacts and the battery
negative. Both the terminals should be 24 volts to
the battery negative.
38
3. Turn on the 24 volt supply. Select the DC voltage The internal power driver in the control box may
range on the multimeter. Use a multimeter to have failed. Replace the control box and retest the
check the voltage on the positive terminal and the equipment.
negative terminal of the solenoid. The numbers
for the wires of the terminal are 14 and 15. The STOP
voltage should read 24 volts.
The engine goes to overspeed after
4. The solenoid should be energized. The solenoid
should be pulled in.
starting
STOP
Test 1
Governor moves to maximum position Check the condition of the magnetic pickup.
when power supply is switched on.
It is possible that metal particles have collected on
Note: Do not attempt to start the engine. the magnetic pickup. This reduces the output or the
gap between the pickup and the teeth for the engine
The actuator should not move until the governor flywheel may be greater than 0.5 to 0.8 mm. Remove
receives a signal from the magnetic pickup in order the pickup. Clean the pickup or replace the pickup.
to indicate that the engine is rotating. In this fault Reinstall the magnetic pickup. Refer to Operation
condition, the engine is likely to go into overspeed. and Maintenance Manual, “Engine Speed/Timing
Sensor - Clean/Inspect”.
Test 1
If the result is not OK, there is a wiring fault or the
Inspect the wiring harness. magnetic pickup is faulty. If necessary, repair the
components or replace the components.
1. Carefully examine all wiring between the control
box and the actuator. Examine the cable to the Test 2
pickup. Check the continuity of the screen on the
magnetic pickup cable since failure of the screen Check the parameters of the governor.
can allow electrical interference to enter the cable.
Electrical interference can result in a false speed 1. The test can only be carried out if the Pandaros
signal. Packager service tool is available. Remove the
lid from the control box. Connect the cable that
Result is supplied with the service tool to the 9 pin
connector on the DC 6 control module.
If the result is OK proceed to test 2.
2. Connect the other end of the cable to the serial
If the result is not OK, repair the wiring harness. If port of the PC. Operate the Pandaros Packager.
necessary, replace the wiring harness and retest the Ensure that the security dongle is connected to
wiring harness. the PC.
39
b. The default gain on the adjustment screen is Test 2
12%.
Check the resistance at the control unit.
c. The default stability on the adjustment screen
is 50%. Select the function for ohms on the multimeter. Use
the multimeter to check the resistance at the control
d. The default derivative on the adjustment screen unit A2/B2 plug. The resistance is approximately 52
is 15%. ohm.
Test 3 Test 3
The governor is not stable 4. Run the engine. Run the engine at the load
conditions that cause the engine speed to become
Test 1 unstable.
1. Disconnect the 2 pin plug from the pickup at the If the result is OK, there is a problem with the external
control box. speed control and the engine is following variations in
the input voltage. Investigate the fault. If necessary,
2. Connect a multimeter on the AC voltage range to repair the component or replace the component.
the cable from the pickup.
If the result is not OK, return the engine configuration
3. Crank the engine. Check the pickup voltage at to the previous setting and reset the governor.
the speed of the crank of the engine at the A2/B2
plug. The voltage is approximately 1.5V AC. Test 4
If the result is OK, the output from the pickup is at 1. By using Pandaros Packager service tool, check
least 1.5 volts when the engine is cranking. Proceed the parameters.
to test 3.
a. The default gain on the adjustment screen is
If the result is not OK, proceed to test 2. 12%.
40
b. The default stability on the adjustment screen If the result is not OK, proceed to test 7.
is 50%.
Test 7
c. The default derivative on the adjustment screen
is 15%. Play or friction in linkage (Diesel Engines only).
2. If the governor gain parameters are much lower Examine the linkage between the actuator and
than the default values, enter the default values injectors for any stiffness or excess play. If necessary,
and retest the equipment. repair the linkage or replace the linkage.
Result STOP
41
Test 3
Result
Test 4
STOP
Result
STOP
STOP
42
g01260016
Illustration 31
Error Codes
The control box continuously monitors the system. If
a fault is detected, the control box registers the fault.
The control box will turn on the lamp for the alarm (if
equipped). If the fault is serious the control box will
stop the engine.
Table 3
43
(Table 3, contd)
3053 ErrActuatorDiff 0 The difference between the set
value of the actuator and the
actual value of the actuator is too
big.
3056 ErrFeedbackRef 0 Error on reference value of the
feedback of the actuator
3059 ErrFeedbackAdjust 0 Error during auto calibration of
actuator
3076 ErrParamStore 0 Error on storing parameters
3077 ErrProgramTest 0 Error on programming checksum
3078 ErrRAMTest 0 Error during RAM test
3080 ErrDisplay 0 Not used
3081 Err5V_Ref 0 Error on 5 volt reference
3085 ErrVoltage 0 Error on voltage supply
3090 ErrData 0 Error on data block
3092 ErrConfiguration 0 Configuration error
3093 ErrStack 0 Error of internal management of
the parameter
3094 ErrIntern 0 Internal software fault
3101 SErrPickUp 0 Sentinel for an error on the speed
sensor
3104 SErrOverSpeed 0 Sentinel for Engine overspeed
3107 SErrLoadInput 0 Sentinel for Load sharer input
error.
3108 SErrSyncInput 0 Sentinel for an error with the
input of the synchronizer
3109 SErrBoostPressure 0 Sentinel for an error with the
boost pressure sensor
3112 SErrCoolantTemp 0 Not used
3132 SErrCoolantTempWarn 0 Not used
3150 SErrFeedback 1 Sentinel for the error for the
actuator feedback signal
3153 SErrActuatorDiff 0 Sentinel for the difference
between the set value of the
actuator and the actual value of
the actuator is too big.
3156 SErrFeedbackRef 0 Sentinel for the error on reference
value of feedback for the actuator
3159 SErrFeedbackAdjust 0 Sentinel for Error during auto
calibration of actuator
3176 SErrParamStore 0 Sentinel for the error on storing
parameters
3177 SErrProgramTest 0 Sentinel for the error on
programming checksum
3178 SErrRAMTest 0 Error during RAM test
3180 SErrDisplay 0 Not used
3181 SErr5V_Ref 0 Sentinel for the error on 5 volt
reference
(continued)
44
(Table 3, contd)
3185 SErrVoltage 0 Sentinel for the error on voltage
supply
3190 SErrData 0 Sentinel for the error on the data
block
3192 SErrConfiguration 0 Sentinel for the error on the
configuration
3193 SErrStack 0 Sentinel for the error of the
management of the internal
parameters
3194 SErrIntern 0 Sentinel for the internal software
fault
3195 SExceptionNumber 0 Sentinel for the exception number
3196 SExceptionAddrLow 0000Hex Sentinel for the software fault
3197 SExceptionAddrHigh 0000Hex Sentinel for the software fault
3198 SExceptionFlag 0000Hex Sentinel for the software fault
g01238737
Illustration 32
45
g01260308
Illustration 33
Error Memory
Although the current errors can be cleared, a history
of errors is stored in the Error Memory. The history of
errors can be displayed. The history of errors cannot
be cleared.
46
g01238433
Illustration 34
47
©2008 Perkins Engines Company Limited Printed in U.K.
All Rights Reserved