You are on page 1of 1
(G6KV SUBSTATION MECHANICAL AND ELECTRICAL REQUIREMENTS 35 Cranes and Hoists -\ Electric operated travelling crane shall be provided to respective switchrooms: as follows: Capacity Hoisting Transverse and Geearance height | Switelvoom| of erane Speed Long Travel Speed {tom finshed (Tonne) | Fast ‘Siow Fast Slow Aorlevel to underside of ie) | evi) | (i i) Ceti | tose) | (iy | triode tn 5 5) 1520 3 6 3.5.2 Lifting hoists shall be provided where equipment are located at upper storeys of a multi-storey substation building. The building can be so designed that only one hoist is required for various equipment. In such a case, lifting hoist of the greatest capacity and clearance height required shall be used. 3.5.3 The following table shows the type and capacity of lifting hoists required for respective switchgear / transformer equipment: Hoisting Goss ‘Clearance Speed Travel bight from Type ot Equipment | Capacty Spoed finished Hor ot Host levelto (tonne [Fast | Slow | Fast | Slow | underside of boiet hook (oii | eniny | (vin) a (m 54 SIG 10 v5 | 20 5 6 ‘KV 1G (for upgracing of 6 eo | 115 | 20 5 4 seston) 22K, 68KV SIG 5 eo | 5 | 2 5 as VATE 10 eo | m5 | 2 5 4 Relay room equipment 3 ew | ms | 2 5 30 3.5.4 The minimum clearance height of crane & hoist shall be at least 1000mm {rom the finished floor level to the underside of crane / hoist hook when the wire is fully extended. 3.5.5 The remote control "pendent” of crane & hoist shall also include the "EMERGENCY STOP" and "RESET" buttons. The control “pendent” shall hang-down to about one metre above floor level. Suitable wall-mounted holder for the control "pendent" shall also be provided. Eaton 62 0

You might also like