Professional Documents
Culture Documents
Design and
Construction Manual
Structural steel decking system
2
Lysaght W-Dek Design & Construction Manual 2009
Contents
Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 7. Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1. Features and applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7.1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.1 Spanning capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1.2 Composite action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7.2.1 Propping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1.3 Design efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7.2.2 Laying. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1.4 Economical design for fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7.2.3 Interlocking the sheets . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1.5 Quicker trouble free installation . . . . . . . . . . . . . . . . . . . . . . . . 5 7.2.4 Securing the platform . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1.6 Technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 7.2.5 Installing 7
$%+ on steel frames . . . . . . . . . . . . . . . . . . . 32
2. Specification and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 7.2.6 Fastening side lap joints . . . . . . . . . . . . . . . . . . . . . . . . . 33
2.1 ,93!'(4 7
$%+ composite slabs. . . . . . . . . . . . . . . . . . . . . . . 6 7.2.7 Fitting accessories for edge form . . . . . . . . . . . . . . . . . . 33
2.2 ,93!'(4 7
$%+ section properties . . . . . . . . . . . . . . . . . . . . . 6 7.2.8 Sealing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.3 Sheeting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7.2.9 Items embedded in slabs . . . . . . . . . . . . . . . . . . . . . . . . 35
2.4 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7.2.10 Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.5 Reinforcement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7.2.11 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.6 Shear connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7.2.12 Cutting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
2.7 Design methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 7.3 Reinforcement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3. Formwork design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 7.3.1 Transverse reinforcement . . . . . . . . . . . . . . . . . . . . . . . . 36
3.1 Deflection limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7.3.2 Longitudinal reinforcement . . . . . . . . . . . . . . . . . . . . . . . 37
3.2 Formwork design load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7.3.3 Trimmers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.2.1 Design for strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2.2 Design for serviceability . . . . . . . . . . . . . . . . . . . . . . . . . 10 7.4 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.3 Formwork Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 7.4.1 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4. Composite slab design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 7.4.2 Concrete additives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 7.4.3 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 7.4.4 Construction joints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.3 Crack control options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 7.4.5 Placing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.4 Durability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 7.4.6 Curing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.5 Design load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 7.4.7 When to remove props . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.5.1 Strength load combination . . . . . . . . . . . . . . . . . . . . . . . 14 7.5 Finishing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.5.2 Serviceability load combination . . . . . . . . . . . . . . . . . . . 14 7.5.1 Soffit and edge form finishes . . . . . . . . . . . . . . . . . . . . . 39
4.5.3 Superimposed dead load. . . . . . . . . . . . . . . . . . . . . . . . . 14 7.5.2 Plastering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.6 Design for Strength in negative regions . . . . . . . . . . . . . . . . . . . 15 7.5.3 Change in floor loadings . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.6.1 Negative bending Strength . . . . . . . . . . . . . . . . . . . . . . . 15 7.6 Suspended ceilings & services . . . . . . . . . . . . . . . . . . . . . . . . 40
4.6.2 Shear strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 7.6.1 Plasterboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.7 Design for strength in positive regions . . . . . . . . . . . . . . . . . . . . 15 7.6.2 Suspended ceiling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.7.1 Positive bending Strength . . . . . . . . . . . . . . . . . . . . . . . . 15 7.6.3 Suspended services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.7.2 Shear strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 8. Composite beams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5. Design for fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 8.1 Shear stud capacities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 9. References. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.2 Design for insulation and integrity . . . . . . . . . . . . . . . . . . . . . . . 16
5.3 Design for structural adequacy . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3.1 Design loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.4 Reinforcement for fire design . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.5 Location of longitudinal reinforcement
for fire design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6. Design Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.1 Use of design tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.2 Single span design tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.3 Interior span design tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.4 End spans design tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3
Lysaght W-Dek Design & Construction Manual 2009
Background
LYSAGHT W-DEK is a new innovative profiled steel decking which brings
greater economy and design freedom to building with composite concrete
slabs. Our design engineers scoured the globe to find the best “W”-
profiles in the world. After careful examination, our engineers incorporated
the best aspects of each profile into new ,93!'(4 7
$%+. The profile
has been specifically developed for Australian high tensile steels - which
makes ,93!'(4 7
$%+ one of the best performing ‘W’ profiles in the
world.
,93!'(4 7
$%+ is a profiled zinc-coated high tensile steel decking for use
in the construction of composite floor slabs. It has exceptional composite
performance – no additional reinforcement is required in most applications.
It can be used as formwork during construction and as a reinforcement
system in composite slabs.
Our increased understanding of composite slabs, together with testing in
our NATA-accredited laboratory and leading Australian universities, has
paid off with an optimised product, which provides significant cost savings
for projects.
,93!'(4 7
$%+ has exceptional spanning characteristics and spans up to
4.1 metres, reducing the need for supporting structures.
The built-in properties of high tensile steel are maximised in the design
and fabrication of the deck profiles which result in products with high
strength-to-weight ratio. ,93!'(4 7
$%+ is currently the most economical
structural steel decking in Australia for typical applications because it
provides widest cover per weight of steel.
The profiled ribs are 78mm in height, resulting in ,93!'(4 7
$%+ having
excellent concrete displacement characteristics and minimal propping
requirements. This speeds up installation and makes the costs of delivery,
erection and structural framing significantly lower than for other systems.
Scope
This manual provides information on the design of formwork, propping,
composite slabs and design for fire and some information for composite
beams.
This manual is developed to the latest versions of the relevant Australian
Standards and Eurocodes.
Conditions of use
This publication contains technical information on the following grades of
,93!'(4 7
$%+:
s ,93!'(4 7
$%+ 0.75 mm thickness
s ,93!'(4 7
$%+ 1.00 mm thickness
Additionally, ,93!'(4 7
$%+ software allows you to get quicker and
more economical solutions with a range of options. Call Steel Direct
on 1800 641 417 to obtain additional copies of the Design Manual and
Software.
Where we recommend use of third party materials, ensure you check
the manufacturer's requirements. Diagrams are used to explain the
requirements of a particular product. Adjacent construction elements of
the building that would normally be required in that particular situation
are not always shown. Accordingly aspects of a diagram not shown should
not be interpreted as meaning these construction or design details are
not required. You should check the relevant Codes associated with the
construction or design.
Warranties
Our products are engineered to perform according to our specifications
only if they are installed according to the recommendations in this manual
and our publications. Naturally, if a published warranty is offered for the
product, the warranty requires specifiers and installers to exercise due
care in how the products are applied and installed and are subject to final
use and proper installation. Owners need to maintain the finished work.
4
Lysaght W-Dek Design & Construction Manual 2009
1. Features and Applications
Contact Steel Direct for advice on the design of concrete frame buildings.
Use on masonry buildings is acceptable if the requirements of Section 7
are satisfied.
5
Lysaght W-Dek Design & Construction Manual 2009
2. Specification and Design
2.1 LYSAGHT W-DEK composite slabs
D yb
Figure 2.1
LYSAGHT W-DEK profile dimension and
reinforcement
78mm
700mm
713.6mm
Figure 2.2
,93!'(4 7
$%+ profile and dimensions
6
Lysaght W-Dek Design & Construction Manual 2009
2.3 Sheeting
,93!'(4 7
$%+ is rolled-formed from hot dipped, zinc-coated, high
tensile steels in base metal thickness (BMT) of 1.0 and 0.75 mm.
1.2 mm BMT is not available in the design tables and software. However,
the solution using ,93!'(4 7
$%+ 1.2 mm BMT is available subject to
enquiry.
The steel conforms to:
s !3 AND
s AND "-4
STEEL GRADE IS '
s "-4 n STEEL GRADE IS '
The coating is Z350 (350 g/m2 minimum coating mass) or Z450 (450 g/m2
minimum coating mass) is available subject to enquiry.
Embossments on the top of flanges and web embossing provide the
mechanical connection between the steel and concrete.
2.4 Concrete
All tables have been developed for the 32 MPa grade of concrete with
normal density of 2400 kg/m3 (wet density). Other concrete grades are
available in the software.
2.5 Reinforcement
s 3TEEL REINFORCEMENT IS NECESSARY TO CONTROL SHRINKAGE AND TEMPERATURE
effects, as flexural negative reinforcement over supports and in
some instances for fire engineering purposes and as bottom tensile
reinforcement. It shall comply with the requirements of AS/NZS
4671:2001.
s &OR NEGATIVE POSITIVE AND FIRE REINFORCEMENT $. OR 9 IS USED IN
the software. D500N is used only in the tables.
s $, OR $. REINFORCEMENT CAN BE USED AS SHRINKAGE MESH
s /UR DESIGN TABLES ASSUME THE USE OF $. MM MAXIMUM DIAMETER
bars for negative and fire reinforcement in addition to 500L shrinkage
mesh.
2.6 Shear Connectors
Extensive testing has been conducted in our NATA-registered lab and
the University of Western Sydney. Shear stud capacities are available
for secondary and primary composite beams. Those capacities can be
achieved using conventional reinforcement in secondary beams and
specific reinforcement developed by One Steel/University of Western
Sydney in primary beams.
For more information refer to Section 8 of this Manual: Composite Beams.
2.7 Design Methods
There are a number of ways you can design concrete slabs using ,93!'(4
7
$%+:
s 5SING THE DESIGN TABLES GIVEN IN THIS MANUAL
s #ALCULATE FROM FIRST PRINCIPLES USING THE RELEVANT !USTRALIAN 3TANDARDS
Eurocodes and data from this manual.
s 2UN OUR ,93!'(4 7
$%+ design software. This is also likely to produce
a more economical design.
s #ONTACT 3TEEL $IRECT ON
However, if in doubt you should get advice from a specialist where
required.
7
Lysaght W-Dek Design & Construction Manual 2009
3. Formwork Design
The ,93!'(4 7
$%+ formwork shall be designed in accordance to AS
3610 - 1995 and AS2327.1.
,93!'(4 7
$%+ capacities and stiffness have been derived from tests
conducted at our NATA-accredited laboratory at BlueScope Lysaght
Technology, Chester Hill, NSW.
Our design tables can be used to detail ,93!'(4 7
$%+ acting as a
structural formwork, provided the following conditions are satisfied:
s 4HE SUPPORT LINES EXTEND ACROSS THE FULL WIDTH OF THE SHEETING AND HAVE A
minimum bearing of 50 mm at the ends of the sheets, 100 mm minimum
bearing length for interior supports.
s 4HE SHEETS CONTINUE WITHIN EACH SLAB SPAN LENGTH WITHOUT ANY OVERLAPS
or intermediate splicing or jointing longitudinally.
s 4HE SHEETS ARE DESIGNED AS SINGLE OR CONTINUOUS SPAN FORMWORK
s 4HE SLAB HAS A UNIFORM CROSS SECTION
s 3EPARATE CONSIDERATION IS GIVEN TO SIDES OF THE SHEETING WHERE EDGES
shall be restrained.
s ,93!'(4 7
$%+ sheeting ends shall be securely fixed at all permanent
and temporary supports to the supporting structure
s 4HE RATIO OF THE LONGER SLAB SPAN TO THE SHORTER SLAB SPAN ,l/Ls) of any
two adjacent spans does not exceed 1.2 (i.e. Ll/Ls 1.2).
s 4HE SUPPORTS ARE EFFECTIVELY RIGID SUCH THAT THEIR VERTICAL DEFLECTIONS
during the construction phase can be ignored in design.
Figure 3.1
,93!'(4 7
$%+ formwork
8
Lysaght W-Dek Design & Construction Manual 2009
3.1 Deflection Limits
AS-3610—1995 Formwork for concrete, defines five classes of surface
finish (numbered 1 to 5) covering a broad range of applications and
AS2327.1.
We recommend a deflection limit of span/240 for the design of composite
slabs in which good general alignment is required, so that the soffit
appears straight when viewed as a whole. We consider span/240 to be
suitable for a Class-3 and 4 surface finish and, in many situations, Class
2. Where alignment affects the thickness of applied finishes (for example
vermiculite), you may consider a smaller limit of span/270 to be more
suitable.
We consider span/130 to be a reasonable maximum deflection limit
appropriate for profile steel sheeting in situations where visual quality is
not significant (Class 5).
3.2 Formwork Design Loads
,93!'(4 7
$%+ must be designed as formwork for two stages of
construction according to AS 3610-1995 and AS2327.1.
Stage I
Prior to the placement of the concrete:
s DURING HANDLING AND ERECTION OF THE FORMWORK AND
s O NCE THE FORMWORK IS ERECTED BUT PRIOR TO THE PLACEMENT OF THE
concrete,
When a live load due to stacked materials can be adequately controlled
on the site at less than 4 kPa, the reduced design live load must be clearly
indicated on the formwork documentation. (1kPa in tables from Section 3.3)
Stage II
During placement of the concrete up until the concrete has set (until fcm
reaches 15-MPa and concrete is able to act flexurally to support additional
loads such as stacked materials).
NOTE: No loads from stacked materials are allowed until the concrete has
set.
s $IFFERENT PATTERN LOADING SHALL BE CONSIDERED INCLUDING WHEN ONE
formwork span only is loaded - with live loads, loads due to stacked
materials and wet concrete. The ,93!'(4 7
$%+ has sufficient
capacity for a concentrated point load of 2.0 kN for all spans and
BMT. It is not necessary to perform formwork capacity checks for
concentrated loads.
9
Lysaght W-Dek Design & Construction Manual 2009
3.2.1 Design For Strength
Design bending capacities
The positive bending moment should be calculated using partial plastic
theory. Negative moments over supports should not exceed the values
given in Table 3.1.
If the negative bending moment over the support obtained from linear
elastic analysis exceeds the design negative bending capacity - negative
moments shall be redistributed into positive area such as negative moment
does not exceed value given in the tables.
Table 3.2
Values of coefficient kd for calculation of $
(The maximum vertical deflection always occurs in the
end span for these conditions.)
10
Lysaght W-Dek Design & Construction Manual 2009
3.3 Formwork tables
1 prop
Slab thickness, mm 130 135 140 145 150 160 175 200
Single span 5200 5200 5400 5600 5600 6000 5950 5650
Two spans 5200 5200 5400 5600 5600 6000 5950 5650
Three or more spans 5200 5200 5400 5600 5600 6000 5950 5650
NOTES: 1. Continuous maximum spans are limited as given in composite slab tables for interior spans and total 6000mm limit.
2. Maximum formwork spans are based on Ll/240 deflection limit and ratio of two adjacent spans equal 1:1.
3. Use ,93!'(4 7
$%+ software to get longer spans with Ll/130 deflection limit and wider supports.
4. 1kPa Live Load due to stacked materials is used.
11
Lysaght W-Dek Design & Construction Manual 2009
4. Composite Slab Design
4.1 General
This chapter discusses the parameters upon which our design tables and
software are based. Solutions to your design problems may be obtained by
direct reference to either our ,93!'(4 7
$%+ design software, or our design
tables in this Manual.
Design data about composite performance of slabs with ,93!'(4 7
$%+
have been obtained from full scale slab tests conducted at the University of
Newcastle.
4.2 Application
Our design tables and software can be used to design composite slabs
with ,93!'(4 7
$%+ provided the following conditions are satisfied:
s 4 HE SPECIFIED CONCRETE STRENGTH GRADE ƒ´c is in the range 25 MPa to 40
MPa (as specified in AS-3600—2001). The concrete density Rc may be
for normal weight concrete, taken as Rc 2400kg/m3.
s 4 HE CONCRETE MANUFACTURE AND MATERIALS SATISFY THE REQUIREMENTS OF
AS 3600—2001, Section 19.
s 4 HE LINES OF SUPPORT EXTEND ACROSS THE FULL WIDTH OF THE SHEETING AND
have a minimum bearing of 50 mm at the ends of the sheets, and 100
mm at intermediate supports over which sheeting is continuous.
s 4 HE RATIO OF THE LONGER SLAB SPAN L1) to the shorter slab span ( Ls ) of
any two adjacent spans does not exceed 1.2, that is L1/Ls b 1.2.
s 4HE SLAB HAS A UNIFORM CROSS
SECTION
s 4 HE DESIGN LOADS FOR SERVICEABILITY AND STRENGTH DESIGN SHALL BE
uniformly-distributed and static in nature.
s 4 HE BENDING MOMENTS AT THE SUPPORTS ARE ONLY CAUSED BY THE ACTION OF
vertical loads applied to the slab.
s 4HE EXPOSURE CLASSIFICATION IS ! ! " OR "
s /
NLY ,93!'(4 7
$%+ profiles can be used in conjunction with this
manual. High values of Tu,Rd responsible for composite performance can
only be achieved due to advanced features of ,93!'(4 7
$%+.
Refer to Table 4.1 for longitudinal shear resistance values.
s -
ATERIAL AND CONSTRUCTION REQUIREMENTS FOR CONVENTIONAL REINFORCING
steel must be in accordance with AS 3600—2001, Clause 19.2, and
the design yield stress, ( ƒsy ), must be taken from AS 3600—2001,
Table 6.2.1, for the appropriate type and grade of reinforcement, and
manufacturers’ data.
s -
ATERIAL AND CONSTRUCTION REQUIREMENTS FOR CONCRETE MUST BE IN
accordance with AS 3600—2001, Clause 19.1.
s ,93!'(4 7
$%+ must not be spliced, lapped or joined longitudinally in
any way.
s 4 HE PERMANENT SUPPORT LINES MUST EXTEND ACROSS THE FULL WIDTH
of the slab.
s 3
IMILAR TO THE REQUIREMENT IN AS 2327.1, Clause 4.2.3, composite
action must be assumed to exist between the steel sheeting and the
concrete once the concrete in the slab has attained a compressive
strength of 15 MPa, that is ƒ´cj r15 MPa. Prior to the development of
composite action during construction, potential damage to the shear
CONNECTION MUST BE AVOIDED AND NO LOADS FROM STACKED MATERIALS ARE
allowed.
s 4HE FIRST INTERIOR SPAN MUST HAVE THE SAME THICKNESS AS THE END SPAN
s $ETAILING OF CONVENTIONAL TENSILE REINFORCEMENT OVER NEGATIVE MOMENT
regions shall be arranged in accordance with the Figures 4.1 and 4.2.
Refer to AS3600-2001, clause 9.1.3 for more information on detailing of
tensile reinforcement in one way slab.
12
Lysaght W-Dek Design & Construction Manual 2009
4.3 Crack Control options
Tables and software are developed to the latest recommendations of
AS3600-2001, Clause 9.4.1 regarding flexural crack control. Our design
tables for continuous spans assume full crack control. The software allows
full and relaxed crack control.
s -AXIMUM BAR DIAMETER AND MAXIMUM BAR SPACING DEPEND ON THE STRESS
fs in the reinforcement and the design crack width – a smaller bar
diameter may result in less reinforcement being necessary.
s &OR DETAILED ANALYSIS OF CRACK CONTROL FOR COMPOSITE SLAB REFER TO
AS3600-2001, Clause 9.4.
minimum 100mm
Negative
reinforcement
0.3Ln 0.3Ln
Wall
Wall
Cover
Concrete slab
Minimum 70mm
Wall
Wall
0.3Ln LYSAGHT W-DEK
Minimum 50mm
Ln Ln
L (span) L (span)
Restraint at Continuous over Little or no
end support interior support restraint at
by mass of wall end support
Figure 4.1
Pattern 1 for conventional reinforcement
0.3Ln 0.3Ln
Wall
Wall
Cover
Concrete slab
0.3Ln
LYSAGHT W-DEK
Wall
Wall
1/3 of negative
reinforcement
Ln Ln
L (span) L (span)
Restraint at Continuous over Little or no
end support interior support restraint at
end support
by mass of wall
Figure 4.2
Pattern 2 for conventional reinforcement when imposed load exceeds twice the dead load
13
Lysaght W-Dek Design & Construction Manual 2009
4.4 Durability
The exposure classification relevant to the design of ,93!'(4 7
$%+
slabs are A1, A2, B1 and B2 as defined in AS 3600—2001, Clause 4.3.
The minimum concrete cover (c) to reinforcing steel, measured from the
slab top face, must comply with AS-3600—2001, Table 4.10.3.2.
As per AS3600-2001
1.25 Gc Gsh Gsup 1.5Q
and for bending (composite) and shear capacity in positive (with top outer
fibre of concrete in compression) areas. (as per prEN 1994-1-1)
1.35 Gc Gsh Gsup 1.5Q
where Gc SELF WEIGHT OF CONCRETE Gsh = SELF WEIGHT OF SHEETING
Gsup = superimposed dead load (partitions, floor tiles, etc.) Q = live load
14
Lysaght W-Dek Design & Construction Manual 2009
4.6 Design for Strength in Negative Regions
4.6.1 Negative Bending Strength
For the bending strength design in negative moment regions, the presence
of the sheeting in the slab is ignored and the slab shall be designed
allowing for 50% void area between ribs. For this purpose, use the
provisions of AS3600-2001, Section 9.
The minimum bending strength requirement of AS 3600-2001, Clause 9.1
must be satisfied.
4.6.2 Shear Strength
Negative moment regions must be designed for shear strength, to satisfy
AS 3600-2001, Section 9. The negative moment region of composite slab
shall be calculated allowing for voids between ribs which are 50% of cross
sectional area within decking profile.
4.7 Design for Strength in Positive Regions
4.7.1 Positive Bending Strength
Positive-moment regions are designed for bending strength such that at
every cross-section the design positive moment capacity is not less than
the design positive bending moment capacity.
Table 4.1
LYSAGHT W-DEK Positive bending capacity shall be calculated as per prEN1994-1-1 Clause
Longitudinal shear resistance 9.7.2. Partial shear connection theory shall be employed using values of
BMT u,Rd (kPa) Tu,Rd in Table 4.1.
0.75 115 4.7.2 Shear Strength
1.0 185
The positive shear capacity can be calculated as per Eurocode 2
Clause 4.3.2.3
15
Lysaght W-Dek Design & Construction Manual 2009
5. Design for Fire
5.1 General
The ,93!'(4 7
$%+ composite slabs shall be designed for fire conditions
in accordance to AS 3600-2001. The entire soffit of slab is assumed to
be exposed to fire over both positive and negative moments regions.
Temperature distribution through a cross section of a composite slab
subject to fire is affected by the geometry of sheeting profile.
Reduction factors are applied to allow for the adverse effect of elevated
temperatures on the mechanical properties of concrete and steel. Values of
these reduction factors shall be derived from the relationships given in
AS 3600-2001, Clause 5.9.
Our tables may be used to detail ,93!'(4 7
$%+ composite slabs when
the soffit is exposed to fire provided the following conditions are satisfied:
s 4HE COMPOSITE SLAB ACTS AS A ONE
WAY ELEMENT SPANNING IN THE DIRECTION
of the sheeting ribs for both room temperature and fire conditions.
s 4HE COMPOSITE SLAB HAS BEEN INITIALLY DESIGNED AND DETAILED FOR ROOM
temperature conditions in accordance to this manual.
s 4HE FIRE DESIGN LOAD IS ESSENTIALLY UNIFORMLY DISTRIBUTED AND STATIC IN
nature.
s !DEQUATE DETAILING OF SLAB JOINTING EDGES SLAB HOLES AND CAVITIES FOR
penetrating, embedded or encased services) to provide the appropriate
fire resistance period. Alternatively the local provision of suitable
protection (such as fire spray material) will be necessary.
s &IRE REINFORCEMENT AS PER &IGURE AND &IGURE
s 4HE FIRE PERIODS ARE OR MIN
s Xb= 140mm as per Figure 5.1 and 5.2 designates zone where fire and
negative reinforcement shall be placed.
16
Lysaght W-Dek Design & Construction Manual 2009
5.4 Reinforcement for Fire Design
The arrangement of reinforcement for fire design is shown in Figure 5.1.
Fire reinforcement may be necessary, in addition to mesh and negative
reinforcement required by our tables for composite slab design.
s $ , REINFORCEMENT SHOULD BE IGNORED AS FIRE REINFORCEMENT LOCATED AT
the plastic hinges.
s 4HE LOCATION OF REINFORCEMENT !st,f- for Fire detail 1 is in a single top layer
at a depth of dct below the slab top face (refer to figure 5.1). This detail
is applicable to continuous slabs only
s 4HE LOCATION OF REINFORCEMENT !st,f+ for Fire detail 2 is in a single bottom
layer at a distance of yb above the slab soffit (refer to Figure 5.1). This
detail is applicable to both continuous and simple spans.
s 4HE CROSS
SECTIONAL AREA OF THE ADDITIONAL REINFORCEMENT FOR FIRE DESIGN
is designated Ast,f+ in our tables (D500 N with bar diameter = 12 mm or
less).
s 4HE NEGATIVE REINFORCEMENT !st-) and the additional fire reinforcement
(Ast,f+ or Ast,f- as applicable), must be located as shown in Figure 5.1 &
5.2.
s 4ABLES HAVE BEEN DEVELOPED FOR &IRE $ETAIL n OUR SOFTWARE PROVIDES
both options.
Concrete xb xb
dct
D
Mesh
LYSAGHT W-DEK (longitudinal - wires not shown)
Ast– Ast.f–
Concrete
LYSAGHT W-DEK
0.3 Ln
Ln
L
Fire detail 1
–
Ast, transverse Ast Ast.f+ Ast
+
Concrete xb xb
D
yb
Mesh
LYSAGHT W-DEK (longitudinal - wires not shown)
Ast- Ast.f+
Concrete
LYSAGHT W-DEK
0.3 Ln
Ln
L
Figure 5.1
Details of reinforcement for fire design Fire detail 2
17
Lysaght W-Dek Design & Construction Manual 2009
5.5 Location of Longitudinal Reinforcement for Fire
Design
The longitudinal bars which make up Ast.f +, Ast.f - or A-st should be located
within the zone shown in Figure 5.2.
xb = 140mm
yb = varies depending on the diameter of the supporting bar
xb xb
yb
Ast.f+
LYSAGHT W-DEK
Permissible zone for
longitudinal fire reinforcement Ast.f+, Ast.f- and A-st
Fig. 5.2
Permissible zone for location of longitudinal fire reinforcement for Fire
Detail 1 & 2.
18
Lysaght W-Dek Design & Construction Manual 2009
6. Design Tables
6.1 Use of Design Tables
KEY - Single Spans The design parameters specific for each table are given on the top of tables:
s 3PANS SINGLE CONTINUOUS END OR INTERIOR
Fire reinforcement required for fire
resistance of 90 minutes (mm2/m) s 3PANS CENTRE TO CENTRE
s 4HICKNESS OF THE SLAB
50 570 s ,IVE LOAD
The rest of parameters are common for all tables and listed below:
Bottom reinforcement required for fire
resistance of 60 minutes (mm2/m) s -ORE THAN FOUR SPANS FOR CONTINUOUS SPANS
s #ONCRETE GRADE F1c = 32MPa.
s 4YPE OF CONSTRUCTION STEEL
FRAME CONSTRUCTION
s $ENSITY OF WET CONCRETE KGM3.
KEY - Continuous Spans
Top tensile (negative) s ,93!'(4 W
$%+ used as a structural deck with thickness 0.75 or
reinforcements over 1.0mm BMT
supports (mm2/m)
Fire reinforcement required s -INIMUM MM WIDTH OF PERMANENT SUPPORTS
for fire resistance of 90
minutes (mm2/m) s ! EXPOSURE CLASSIFICATION
1440
50 570 s #OMPOSITE SLAB DEFLECTION LIMITS , FOR TOTAL LOADS AND , FOR
incremental deflection.
Fire reinforcement required for fire resistance
of 60 minutes (mm2/m)
s )NDOOR CONDITIONS FOR CREEP AND SHRINKAGE
s 2ATIO OF LONGER ADJACENT SPAN TO SHORTER DOES NOT EXCEED
s #RACK CONTROL REQUIRED
Notes:
1. Areas without cells mean that a design solution is s -AXIMUM MM DIAMETER REINFORCING BARS
not possible.
2. Single spans do not require top tensile reinforcement, s K0A OF SUPERIMPOSED DEAD LOAD
relevant cells are not shown. s 2EINFORCEMENT $. FOR NEGATIVE AND FIRE REINFORCEMENT
3. All spans are centre to centre.
4. A dash (-) means no fire reinforcement s ,OCATION OF NEGATIVE REINFORCEMENT AS SHOWN ON &IG
is necessary.
5. N/A means a design solution with this particular fire s ,OCATION OF FIRE REINFORCEMENT AS SHOWN ON &IG AND &IRE DETAIL
rating is not possible.
s 3HRINKAGE MESH AS IN THE 4ABLE FOR MINOR DEGREE OF CRACK CONTROL
6. Top tensile/negative reinforcement is additional to
shrinkage mesh area s &ORMWORK WITH AT LEAST ONE SUPPORT ASSUMED FULLY SUPPORTED CONDITIONS
Table 6.1 Shrinkage mesh used with tables. s MM SUPPORT WIDTH
s .EGATIVE AND FIRE REINFORCEMENT SHOWN IN TABLES IS IN ADDITION TO SHRINKAGE
Depth Mesh
130 SL62 mesh specified in Table 6.1. If negative fire reinforcement is required,
135 SL62 at least one bar per ,93!'(4 7
$%+ rib should be placed. Smaller bar
140 SL62 diameter may result in less negative and fire reinforcement.
145 SL62
150 SL62
160 SL72
175 SL72
200 SL82
19
Lysaght W-Dek Design & Construction Manual 2009
6.2 Single Spans
20
Lysaght W-Dek Design & Construction Manual 2009
Single Spans 150 mm slab
Span Characteristic Imposed Load Qk (kPa)
(mm) 1.5 2 2.5 3 4 5.0 7.5 10
2400 100 110 100 120 110 120 120 130 130 140 140 160 170 190 210 220
2600 120 140 130 150 140 150 150 160 160 180 180 190 210 230 250 270
2800 150 170 160 180 170 190 180 190 200 210 210 230 260 280 310 320
3000 180 200 190 210 200 220 210 230 240 250 260 270 310 330
3200 220 230 230 250 240 260 250 270 280 290 300 320
3400 250 270 270 280 280 300 290 310 320 340
3600 290 310 310 330 320 340 340 360
3800 340 350 350 370
4000
4200
21
Lysaght W-Dek Design & Construction Manual 2009
6.3 Interior Spans
22
Lysaght W-Dek Design & Construction Manual 2009
Interior Spans 140 mm slab
Span Characteristic Imposed Load Qk (kPa)
(mm) 1.5 2 2.5 3 4 5.0 7.5 10
90 90 90 90 90 90 120 180
2200
- N/A - N/A - N/A - N/A - N/A - N/A - N/A - N/A
90 90 90 90 90 90 160 230
2400
- N/A - N/A - N/A - N/A - N/A - N/A - N/A - N/A
90 90 90 90 100 130 210 300
2600
- N/A - N/A - N/A - N/A - N/A - N/A - N/A - N/A
90 90 90 90 130 170 270 370
2800
- N/A - N/A - N/A - N/A - N/A - N/A - N/A - N/A
90 90 90 120 170 220 320 440
3000
- N/A - N/A - N/A - N/A - N/A - N/A - N/A 10 N/A
90 110 120 150 220 260 390
3200
20 N/A 10 N/A - N/A - N/A - N/A - N/A 10 N/A
110 130 140 190 250 310 460
3400
10 N/A - N/A - N/A - N/A - N/A 10 N/A 20 N/A
140 150 220 230 290 360
3600
- N/A - N/A - N/A 10 N/A 10 N/A 20 N/A
160 220 220 270 340 420
3800
- N/A 10 N/A 10 N/A 10 N/A 20 N/A 20 N/A
220 220 230 310 390 480
4000
10 N/A 10 N/A 20 N/A 20 N/A 30 N/A 30 N/A
220 240 260 360 450
4200
20 N/A 20 N/A 20 N/A 30 N/A 30 N/A
250 270 300 400 510
4400
20 N/A 30 N/A 30 N/A 40 N/A 40 N/A
280 300 340 460
4600
30 N/A 40 N/A 40 N/A 40 N/A
310 340 380 510
4800
40 N/A 50 N/A 50 N/A 50 N/A
340 380 430
5000
50 N/A 50 N/A 60 N/A
380 420
5200
60 N/A 60 N/A
410
5400
70 N/A
5600
23
Lysaght W-Dek Design & Construction Manual 2009
Interior Spans 150 mm slab
Span Characteristic Imposed Load Qk (kPa)
(mm) 1.5 2 2.5 3 4 5.0 7.5 10
110 110 110 110 110 110 150 220
2400
- - - - - - - - - - - - - - - -
110 110 110 110 110 120 200 280
2600
- - - - - - - - - - - - - - - -
110 110 110 110 120 160 250 340
2800
- - - - - - - - - - - - - - - 10
110 110 110 120 160 200 300 410
3000
- - - - - - - - - - - - - 10 - 10
110 120 130 150 190 240 360 480
3200
- - - - - - - - - - - 10 - 10 10 20
120 140 150 180 240 290 420
3400
- - - - - - - 10 - 10 - 10 10 20
150 160 180 240 280 340 490
3600
- 10 - 10 - 10 - 10 - 20 10 20 20 N/A
170 190 240 250 320 390
3800
- 10 - 10 - 20 - 20 10 20 10 30
200 240 240 290 370 450
4000
- 20 10 30 10 20 10 20 20 30 20 30
240 240 270 340 420 510
4200
10 20 10 30 10 30 20 30 20 40 30 N/A
250 270 300 380 480
4400
20 30 20 30 20 30 20 40 30 40
280 310 330 430 530
4600
20 40 30 40 30 40 30 50 40 N/A
310 340 370 480
4800
30 40 30 50 40 50 40 50
340 370 410 530
5000
40 50 40 50 40 60 50 N/A
380 410 450
5200
40 60 50 60 50 70
410 450 500
5400
50 70 60 70 60 N/A
450
5600
60 70
5800
6000
24
Lysaght W-Dek Design & Construction Manual 2009
Interior Spans 175 mm slab
Span Characteristic Imposed Load Qk (kPa)
(mm) 1.5 2 2.5 3 4 5.0 7.5 10
300 300 300 300 300 300 300 300
2800
- - - - - - - - - - - - - - - -
300 300 300 300 300 300 300 450
3000 - - - - - - - - - - - - - - - -
300 300 300 300 300 300 450 450
3200
- - - - - - - - - - - - - - - -
300 300 300 300 300 300 450 450
3400
- - - - - - - - - - - - - - - -
300 300 300 300 300 450 450 530
3600
- - - - - - - - - - - - - - - 10
300 300 300 300 450 450 460 610
3800 - - - - - - - - - - - - - 10 - N/A
300 300 300 300 450 450 520
4000
- - - - - - - - - - - 10 - 10
300 300 450 450 450 450 590
4200 - - - - - - - - - 10 - 10 10 20
300 450 450 450 450 470
4400
- - - 10 - 10 - 10 - 10 - 20
450 450 450 450 450 530
4600
- 10 - 10 - 10 - 20 - 20 10 30
450 450 450 450 490 590
4800 - 10 - 20 - 20 10 20 10 30 20 30
450 450 450 450 550 650
5000
- 20 10 20 10 30 10 30 20 30 20 N/A
450 450 450 460 610
5200
10 30 10 30 20 30 20 40 30 N/A
450 450 470 500 670
5400
20 30 20 40 20 40 30 40 30 N/A
450 470 510 540
5600 20 40 30 40 30 50 30 50
480 510 550 580
5800 30 50 30 50 40 50 40 60
520 550 590
6000
40 50 40 60 50 60
25
Lysaght W-Dek Design & Construction Manual 2009
6.4 End Spans
4600
4600
26
Lysaght W-Dek Design & Construction Manual 2009
End Spans 140 mm slab
Span Characteristic Imposed Load Qk (kPa)
(mm) 1.5 2 2.5 3 4 5.0 7.5 10
90 90 90 90 90 90 140 220
2200
10 N/A 10 N/A 10 N/A 10 N/A 20 N/A 30 N/A 40 N/A 50 N/A
90 90 90 90 90 110 190 260
2400
20 N/A 20 N/A 30 N/A 30 N/A 50 N/A 40 N/A 60 N/A 80 N/A
90 90 90 90 120 150 240 330
2600
40 N/A 50 N/A 50 N/A 60 N/A 50 N/A 60 N/A 80 N/A 100 N/A
90 90 100 120 150 220 300 400
2800
70 N/A 70 N/A 70 N/A 70 N/A 70 N/A 80 N/A 100 N/A 130 N/A
100 120 130 150 220 240 360 490
3000
80 N/A 80 N/A 80 N/A 80 N/A 90 N/A 100 N/A 130 N/A 150 N/A
130 140 160 220 240 290 430
3200
90 N/A 100 N/A 90 N/A 100 N/A 110 N/A 120 N/A 150 N/A
150 220 220 220 280 350 510
3400
110 N/A 100 N/A 110 N/A 120 N/A 130 N/A 150 N/A 180 N/A
220 220 220 270 340 410
3600
110 N/A 120 N/A 130 N/A 140 N/A 150 N/A 170 N/A
220 230 260 310 390 470
3800
140 N/A 140 N/A 150 N/A 160 N/A 180 N/A 200 N/A
240 270 300 360 450
4000
160 N/A 170 N/A 180 N/A 190 N/A 210 N/A
280 300 340 410
4200
180 N/A 190 N/A 200 N/A 220 N/A
310 400 400
4400
210 N/A 220 N/A 230 N/A
400
4600
230 N/A
4800
4800
5000
27
Lysaght W-Dek Design & Construction Manual 2009
End Spans 150 mm slab
Characteristic Imposed Load Qk (kPa)
Span
(mm) 1.5 2 2.5 3 4 5.0 7.5 10
110 110 110 110 110 110 170 240
2400 10 20 10 30 10 30 20 30 20 40 30 40 40 60 60 70
110 110 110 110 120 140 240 310
2600 20 30 20 40 30 40 30 50 40 50 40 60 60 70 80 90
110 110 110 120 150 180 280 370
2800 30 50 40 60 50 60 50 60 50 70 60 70 80 90 100 110
110 130 140 150 190 240 340 450
3000 60 70 60 70 50 70 60 70 70 80 80 90 100 110 120 140
140 150 170 180 240 270 400
3200 60 80 70 80 70 80 80 90 90 100 100 110 120 140
160 180 200 240 270 330 470
3400 80 100 80 100 90 100 90 110 100 120 120 130 150 160
190 240 240 250 320 380 550
3600 90 110 100 110 110 120 110 130 120 140 140 150 170 N/A
240 240 260 300 370 440
3800 110 120 120 130 120 140 130 150 150 160 160 180
250 270 300 340 420 500
4000 130 140 140 150 150 160 150 170 170 190 190 N/A
280 310 330 390 480
4200 150 160 160 170 170 180 180 190 200 210
320 340 370 440
4400 170 190 180 200 190 210 200 220
350 440 440
4600 190 210 200 220 220 230
440
4800 220 230
5000
5200
5200
28
Lysaght W-Dek Design & Construction Manual 2009
End Spans 175 mm slab
Span Characteristic Imposed Load Qk (kPa)
(mm) 1.5 2 2.5 3 4 5.0 7.5 10
300 300 300 300 300 300 300 450
2800
- 20 - 20 10 20 10 30 10 30 20 40 30 50 50 60
300 300 300 300 300 300 450 450
3000
10 30 20 30 20 30 20 40 30 40 30 50 50 70 60 80
300 300 300 300 300 300 450 450
3200
20 40 30 40 30 50 30 50 40 60 50 60 70 80 80 100
300 300 300 300 300 450 450
3400
40 50 40 60 40 60 50 60 60 70 60 80 80 100
300 300 300 300 450 450 450
3600
50 60 50 70 60 70 60 80 70 90 80 100 100 120
300 300 450 450 450 450 510
3800
60 80 70 80 70 90 80 90 90 100 100 110 120 140
300 450 450 450 450 450
4000
80 90 80 100 90 100 90 110 100 120 120 130
450 450 450 450 450 470
4200
90 110 100 120 100 120 110 130 120 140 140 150
450 450 450 450 450 530
4400
110 130 120 130 120 140 130 150 140 160 160 170
450 450 450 450 510 600
4600
130 140 130 150 140 160 150 170 160 180 180 N/A
450 450 450 470 570
4800
140 160 150 170 160 180 170 190 190 200
450 450 490 510
5000
160 180 170 190 180 200 190 210
490 490
5200
180 200 190 210
500
5400
200 220
5600
6000
29
Lysaght W-Dek Design & Construction Manual 2009
7. Construction
7.1 Safety
,93!'(4 7
$%+ is available in long lengths, so large areas can be quickly
and easily covered to form a safe working platform during construction.
One level of formwork gives immediate protection from the weather,
and safety to people working on the floor below. The minimal propping
requirements provide a relatively open area to the floor below.
It is common sense to work safely, protecting yourself and work mates
FROM ACCIDENTS ON THE SITE 3AFETY INCLUDES THE PRACTICES YOU USE AS WELL
as personal protection of eyes and skin from sunburn, and hearing from
noise. For personal safety, and to protect the surface finish of ,93!'(4
7
$%+, wear clean dry gloves. Don’t slide sheets over rough surfaces or
over each other. Always carry tools, don’t drag them.
Occupational health and safety laws enforce safe working conditions in
most locations. Local laws may require you to have fall protection which
includes safety mesh, personal harnesses and perimeter guard rails where
they are appropriate. We recommend that you adhere strictly to all laws
that apply to your State.
,93!'(4 7
$%+ is capable of withstanding temporary construction loads
including the mass of workmen, equipment and materials as specified in
Section 3.0 of this manual. However, it is good construction practice to
ensure protection from concentrated loads, such as barrows, by use of
some means such as planks and/or boards.
7.2 Installation
,93!'(4 7
$%+ is delivered in strapped bundles. If not required for
immediate use stack sheets or bundles neatly and clear of the ground, on
a slight slope to allow drainage of water. If left in the open, protect with
waterproof covers.
Cover
Cover
Concrete slab
p
LYSAGHT W-DEK
Props where Props where
Bearing of LYSAGHT W-DEK required required
(Not less than 50 mm
at end of sheets) Bearing of LYSAGHT W-DEK
(Not less than 100 mm
where sheeting is
continuous)
Slab span Slab span
Figure 7.1 (Interior span) End span)
Typical layout
30
Lysaght W-Dek Design & Construction Manual 2009
7.2.1 Propping
It is a common practice to specify unpropped ,93!'(4 7
$%+ formwork,
however, depending on the span of a ,93!'(4 7
$%+ slab, temporary
propping may be needed between the slab supports to prevent excessive
deflections or collapse of the formwork.
,93!'(4 7
$%+ formwork is normally placed directly on prepared
propping. Props must stay in place during the laying of ,93!'(4 7
$%+
formwork, the placement of the concrete, and until the concrete has
reached the strength of 15 MPa.
Propping generally consists of substantial timber or steel bearers
supported by vertical props. The bearers must be continuous across the full
width of LYSAGHT W-DEK formwork.
Propping must be adequate to support construction loads and the mass of
wet concrete. Maximum propped and unpropped spans are given in
Section 3.3.
7.2.2 Laying
,93!'(4 7
$%+ must be laid with the sheeting ribs aligned in the
direction of the designed spans. Other details include the following:
s 4 HE SLAB SUPPORTS MUST BE PREPARED FOR BEARING AS REQUIRED
s , AY ,93!'(4 7
$%+ sheets continuously over each slab span
without any intermediate splicing or jointing.
s , AY ,93!'(4 7
$%+ sheets end to end. Centralise the joint at the
slab supports. Where jointing material is required the sheets may be
butted against the jointing material.
s 3 UPPORT ,93!'(4 7
$%+ sheets across their full width at the slab
support lines and at the propping support lines.
s &