Section 4
Protection functions
‘1wRS756@87 B
4158 Monitored data
Table 102 JAMPTOC Mentored data
Ta Tipe ‘Vans (Range) [Un Dessision
START BOOLEAN | o-False slat
fst
START_DUR Foatse | 000..10000 | % Ratio of sar tine
operate time
JANPTOC num stats
‘stesvbocked
off
415.9 Technical data
Table 108: JAMPTOC Tectia data
Characters Vale
Operation accuracy Depencing onthe frequency of te curent
measured nH
11.5% ofthe set value 01 10.002 x
Reset tine <40me
Reset aio Typical 0.98
Retardation tine <35me
paral ime accuracy in deine ime mode | #109 of the sa value or 120 me
4.16 Loss of load protection LOFLPTUC
41.64 Identification
Funellon dessin Ec TEs0 | iECwsTT_ ANS EEE GAT
Heerifaton | tenteatlon | devise number
Loss af lad protection vorteruc | ste a
4162 Function block
Figure 36: Function block symbol
18 615 sorhs
Technical Manual‘sMRS750887 8
Section 4
Protection functions
416.3
41.6.4
618 sores
Technical Manual
Functionality
The loss of load protection LOFLPTUC is used to detect a sudden load loss which
is considered as a fault condition.
LOFLPTUC starts when the current is less than the set limit. It operates with the
definite time (DT) characteristics, which means that the function operates after a
predefined operate time and resets when the fault current disappears.
The function contains a blocking functionality. It is possible to block function
outputs, the definite timer or the function itself, if desired,
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Ot
‘The operation of loss of load protection can be described by using a module
diagram, All the modules in the diagram are explained in the next sections,
TA satan “Teas ‘START
ce elector
to
(ase—}
Figure 37: Functional module diagram
Level detector 1
This module compares the phase currents (RMS value) to the set Start value high
setting, Ifall the phase current values are less than the set Start value high value,
the loss of load condition is detected and an enable signal is sent to the timer. This
signal is disabled after one or several phase currents have exceeded the set Start
value high value of the element.
Level detector 2
‘This is a low-current detection module, which monitors the de-energized condition
of the motor. It compares the phase currents (RMS value) to the set Start value low
setting. If any of the phase current values is less than the set Start value low, a
signal is sent to block the operation of the timer.
Timer
Once activated, the timer activates the STAR? output. The time characteristic is
according to DT. When the operation timer has reached the value set by Operate
19Section 4
Protection functions
‘1wRS756@87 B
41.6.5
416.6
120
delay time, the OPERATE output is activated. If the fault disappears before the
module operates, the reset timer is activated. If the reset timer reaches the value set
by Reset delay time, the operate timer resets and the START output is deactivated
The timer calculates the start duration value START_DUR which indicates the
percentual ratio of the start situation and the set operate time. The value is available
through the Monitored data view.
‘The BLOCK signal blocks the operation of the function and resets the timer.
Application
When a motor runs with a load connected, it draws a current equal to a value
between the no-load value and the rated current of the motor. The minimum load
current can be determined by studying the characteristics of the connected load,
‘When the current drawn by the motor is less than the minimum load current drawn,
it can be inferred that the motor is either disconnected from the load or the
coupling mechanism is faulty. If the motor is allowed to run in this condition, it
may aggravate the fault in the coupling mechanism or harm the personnel handling
the machine. Therefore, the motor has to be disconnected from the power supply as
soon as the above condition is detected,
LOFLPTUC detects the condition by monitoring the current values and helps
disconnect the motor from the power supply instantaneously or after a delay
according to the requirement.
When the motor is at standstill, the current will be zero and it is not recommended
to activate the trip during this time, The minimum current drawn by the motor
when it is connected to the power supply is the no load current, that is, the higher
start value current, Ifthe current drawn is below the lower start value current, the
motor is disconnected from the power supply. LOFLPTUC detects this condition
and interprets that the motor is de-energized and disables the function to prevent
unnecessary trip events,
Signals
Table 104: LOFLPTUC input signals
Tam The Dota | Deseeton
LA signal | 0 _| Phase A carent
rr signal [0 | Phase B carent
Le SIGNAL [0 | Phase Ccurent
BLock BOOLEAN | O-Fale | Blok allbnary oun by esating tere
Table 105 LOPLPTUC Out signals
Nan The Dosen
OPERATE BOOLEAN Operate
START BOOLEAN Stat
615 sorts
“Technical Manual‘sMRS750887 8
Section 4
Protection functions
4.1.6.7 Settings
Table 108: LOFLPTUC Group setings
Parameter Vales (Range) [Unt [Step [atau Deserta
Stat value ow 00%..0:50 xn [901_[ 0.10 Current seing/ Star value ow
‘Stat value high 00%..1.00 xn [901 | 080 Current seting/Star value high
‘Operate dlayime | 400..000000 [ms | 10 | 2000 Operate delay time
Table 107: LOFLPTUC Non group sotings
Parameior ‘Vales (Range) [Unk [Step [afaur Deserta
Operation Operation OM17 On
Reset delay tine 0.60000 mm/h 2 Reset delay me
41.6.8 Monitored data
Table 108: —_LOFLPTUC Montored data
Nana Tes Vans (Range) [Unt Desctsten
START_DUR roars | 0.00..10000 | % Ratoof start tine
operate tine
TorLPTUG Enum 5 Status
2
S
*
5
41.6.9 Technical data
Table 108: ——_LOFLPTUC Technical dat
Characters Vata
Operaton accuracy Depending onthe frequency fhe curent
measured y2¢2
3H ofthe st val or 20.002 xl,
Start tne Typical 300 m=
Reset tine =40me
Reset alo Typical 098
Retardation tine <35m8
‘Operate time accuracy nde Uime mode 0% ofthe set value or 220 ms
815 sets 12
Technical Manual