% Biased Differential Protection

of Transformer

Sensitivity: LNT Construction Internal Use


Different vector groups of transformer

Sensitivity: LNT Construction Internal Use


Star - Delta

Sensitivity: LNT Construction Internal Use


Star – Delta (Diff. Protection)

Sensitivity: LNT Construction Internal Use


Delta – Star (1:1)

Sensitivity: LNT Construction Internal Use


Delta – Star (Diff. Protection)

Sensitivity: LNT Construction Internal Use


Delta – Star (Diff. Protection)

Sensitivity: LNT Construction Internal Use


Delta – Star (Diff. Protection)

Sensitivity: LNT Construction Internal Use


External fault on “c”

Sensitivity: LNT Construction Internal Use


Internal fault on “c”

Sensitivity: LNT Construction Internal Use


Sensitivity: LNT Construction Internal Use
Sensitivity: LNT Construction Internal Use
Assuming slope of 40%,
Spill current required to operate the relay
= 0.4 (I1+I2)/2
= 0.4 *(3.936+3.938) /2
= 1.57 A

Sensitivity: LNT Construction Internal Use