— SERVICING OF POINTERS AND MANUAL CONTROL UNIT —
Series 130 Controllers and Control Stations
(Por servicing of automatic control sections of pneumatic
‘controllers, see Instruction MI 17-458 and MI 17-459.)
Jo Remove Pointers
4. Withdvew instrument part way
( from panel. Raise top cover.
SS \, 2. Renove knov(s) by sliding
‘3 3 “nob Formerd off shaft.
3, Remove 2 smsll screws.
CAURION: Do not lose
AMULET
4, Remove scale, lens, and housing.
5. Loogen the 2 serews, holding
pointer am to pointer move~
ent. Renove pointer out
through front of instrument. Projection on
Lens faces up
Access Opening at Right
Side of Enptrucent
Moasuzonent Set Polat
Pointer Index
(ith Model 130, local set 6. After potnter 19 reinstalled, position
point index is én opposite lens ih recess in front of tastrunent.
é Side. Remove left side Then hook bottom of housing onto bottom
5 panel for access to screws front of instrmont, and owing top of
( on pointer aovenent. } housing over tap of instrunent.
Reinstall the 2 serews on top and knob(s)
on bottom, Insert scate behind Lens.
‘7. Rajust tension on pointer (see Page 2).Mr 17-468
Page 2
To Aust Pointer Tension
Unless potnter tension (pressure agsinst vertical surface at front
of instrument) 4s correct, pointer may Jag in response to changes In
signs (too much tension) or tend to vibrate (too iivtLe tension).
NOT: When instrument hes two pointers
Ageess Opening et Right Tension on Tight side, pointers must not
Bide of Instrument Adjustments, touch when they pass each other.
‘Tension sdjustmont
‘fe correct when
Quter ourface of net point
Thdex just touches side
plate.
mor surface of noscure-
Measurement Bet Point, lent pointer Just touches
Pointer Index edge of plate behind atai,
Outer sumface of Local set
point Index (Model 1307
only} Just touenes tide
plate.
With Model 1307, local eet point
30: int
index tension adjustment 1g) on
opposite side. Konove loft sia
yanel for access to adjustment. )Mr 27-468
= SERVICING MANUAL CONTROL UNIT —
Schematic Arrangement,
TRansreR
Seva
spo ae
OW REAR OF SHEL.
0 auromanic
‘SontROL UNIT
venr—_|
TRANSFER SWITCH
(in aN petign) —————|
The cutput, whether from the automa-
tie or manual Control unit, is indicated
cn the dial of the manual anit.
When the transfer switch is in AUTO,
the flapper positicn and relay diaphrage
presgure continually track the output of
the automatic contre) uit. Thus when
‘the Granafer switch 1s moved to MAN, the
output gonsrated by the manual unit’ will
match the last output in AUTO,
Relay
Air Supply
‘Transfer Signal
output to Valve
Page 3
equine
RELAY tee
OUTPUT oat,
1 we
Manual,
ADJUSTMENT
THUNEWHEEL
NOEZLE.
There 1s a linkage (not shown) con=
necting the transfer awiteh and the
manual adjustment thumbwheel. When the
tronsfer switch is tn MAN, thie linkage
moves the Unumbyiieel to céntact the
flapper ami. Since tuming the thunb-
wheel causes the clearance between the
Flapper and nozzle to change, the output
(in Man) can be varied by adjusting the
thunbwneel.
output Dial
‘vransfer
Switchur 172468
Pago
Preliminary Cal tbretion Steps
CAUTION: When reinstalling manual control unit 1n panel, make sure that transfer ewltch
te in AUTO position to prevent process bump.
It is recomended that a calibration fixture (Part cOLIBS, obtainable from The Foxboro
Company) be used. If this fixture is not used, connections must be made ct rear of manual
control unit.
1. Move transfer switch to AUTO. Remove
manual control unit from pang.
to renoye unit, rurat witnaraw controler
SBout"B"° Bo eh) then “white pashing. ti GT—e|
SRIE' (to {Ereund eaten} Tite"up and waite cat
0-20 pst {0-1h0 xPa) test gauge or manometer ia
ual control unit, as shown. i:
UNE? WETE CALIBRATING FETUS UNI WELMOUT CALIERATING FLETURE
Use 1/4" oD Polyfie tub=
ing to make connections.
2
aaa ‘Install unit Air ‘Plug center
In Fixture. Supply comiection,
Comections
are 1/4 NPE
Calibration check
L. Set up calibrating equipment
pero as ahown in section above.
Move tusnefor switen to MAN.
Adjust outrut with
Shimbuheel. 30 hat
Pending on ange are
Sand 15 pot (or 20 and
lod" ka). "tote reaaings
on pointer at both pressures
Soabinge enowid se 6 and 100%
3. Adjust thumbuhee2 so that
pointer is ab midsesie.
AL Adjust nero screw so that
cubpat on geuge Le 9 pet
If either reading is In error by more or 60 KPa.
than #2, calibration ts required.
See calibration procedure on Page 5.1, Set up calibration equipment
as shown on Page |. Move
transfer switch to HAN,
2, Remove plastic cover (and
attached transfer ewiten in
MAN position) by removing
the 1 screws holding down.
cover. Hote that front and
rear Seren are not tne same.
MI 17-468
Eage 5
Calibrablon Procedure
Controi unit sith
Gover renoved
Zero Adjustment
Span Adjustwent,
Output Adjustment
‘Thumowneal,
(When replacing cover, make
Sure that switch Le 1A MAN
position so thet cover WiLL
Hit on unit.)
3. Adjust thumbwheel co that output on gauge is 3 psi or 20 kPa.
A, Loosen 2 span adjustment Locking screwe, and move plate
50 that pointer is at Og. Rettghten sefens.
5. Adjust thumbwheel so tha output on gauge ts 15 pel or 109 kPa.
Pointer should read 100%. If roading 15 more than 42% off,
adjust span so that errors at OB and 100% are equal.
6, Repeat calibration check on Page 4, If necessary, repeat calibration
procedure until readings oF pointer are satisfactory, Note that with
Cover off, zero adjustment 1s thumbwheel ao left side of unit,
Adjustment of Stops
1. Set up calibretion equipment ae show on Fage
Move transfer switch to MAN.
2, Remove plastic cover (see Step 2 avove).
3. Adjust output thumbwheel so that
polnter 1s adjacent to triangle
at iert of "oF graduation on
seals,
4. SLightay loosen the 2
lowelinit adjustmont 5. Carefully position am
Lockscrews. assonbly so that output
on gauge just fazis to
zero, Tighten serewa,
High and Low
6. Adjust output thumvwnesl so thet
pointer ig adjacent to triangle at
right of "100" graduation on seals.
Output Adjustment,
‘Thumowbeet 7, Loosen locknut and carerully adjust
serew so that output Just goes to full
Supply pressure, Tighten Losknut.ur 17-468
Page 6
To Service Relay
To Clean Restrictor
1, Remove relay (see section abeve)},
2, Carefully Lift out restrictor
using nesdle-nose pliers,
To remove relay, venove the
2 large serews and corefully
pry relay off of minual con=
Erol unit,
A gasket is supplied with
each replacement relay, For
sarvicing detalla see instruc
fon ME 11-193.
|e
‘S
Clean by inserting @ 0.005"
dla. wire (or Foxtore ¢lean=
ing wire, Part 2527) through
orifice.
10/73