Question
How do you configure a ring redundancy with FDC 157-0 DP/PA couplers and
active field distributors (AFDs)?
Answer
The instructions and notes listed in this document provide a detailed answer to this
question.
Ring redundancy
2 V1.1, Item ID: 44887866
Table of contents
Table of contents
1 Introduction........................................................................................................ 4
2 Commissioning.................................................................................................. 7
3 STEP 7 Hardware Configuration ...................................................................... 9
3.1 Configuration of the Interface Module IM 153-2................................... 9
3.2 Configuration of the FDC 157-0 DP/PA Coupler................................ 12
3.3 Save and Compile the Hardware Configuration and Load It into
the CPU of the S7 Station .................................................................. 15
4 Diagnostics ...................................................................................................... 16
4.1 Status of the LEDs for Ring Redundancy .......................................... 16
4.2 Status of the LEDs with Fault on the PROFIBUS PA ........................ 17
Ring redundancy
V1.1, Item ID: 44887866 3
1 Introduction
1 Introduction
Ring redundancy
The use a DP/PA coupler pair and active field distributors (AFDs) increases the
availability of the PROFIBUS PA. Ring redundancy is created by configuring a ring
structure with two FDC 157-0 DP/PA couplers and up to eight AFDs.
The active FDC 157-0 DP/PA coupler supplies the PROFIBUS PA. If there is a
short-circuit or wire break on the main line of the PROFIBUS PA, the second
DP/PA FDC 157-0 DP/PA coupler also gets active. The DP/PA couples supply the
separated PROFIBUS PA in both directions to the interrupt. The functions of the
PA field devices are retained.
Repairs can be made during operation.
Hardware configuration
Table 1-1 shows an overview of the hardware configuration for using a DP/PA
coupler pair in redundancy mode.
Table 1-1
Module Order number Quantity
ET 200M, mounting channel 6ES7195-1G... 1
Power supply PS 307 6ES7307-1... 2
Bus module BM PS/IM for ET 200M for a 6ES7195-7HA00-0XA0 1
power supply unit and an IM153-2
IM153-2 6ES7153-2BA82-0XB0 1
Bus module pair BM DP/PA for two FDC 6ES7195-7HG80-0XA0 1
157-0 DP/PA couplers
Field device connection FDC 157-0 6ES7157-0AC83-0XA0 2
DP/PA coupler
Active field distributor (AFD) 6ES7157-0AF81-0XA0 At least 1
Installation of the hardware configuration with active bus modules and modules for the
"Change Module during Operation" and/or "Redundancy" modes
Follow the instructions below to install the hardware configuration with active bus
modules and modules for the "Change Module during Operation" and/or
"Redundancy" modes.
Table 1-2
Ring redundancy
4 V1.1, Item-ID: 44887866
1 Introduction
4. Insert the power supply and interface module IM153-2 in the mounting channel in
the bus module BM PS/IM.
Then insert the two FDC 157-0 DP/PA couplers in the mounting channel in the
bus module pair BM DP/PA.
Use the side guides of the bus modules for this. When you screw the modules
tight, at the same time also fasten the bus module on the mounting channel.
5. Mount the bus module cover on the last bus module, in this case BM DP/PA. If
there is no module slotted in a slot, then also mount the backplane bus cover on
the unoccupied slot.
main line
spur line
Note You can use a maximum of eight AFDs in the ring structure.
You can connect a maximum of four PA field devices to each AFD.
Altogether, the number of PA field devices in one PROFIBUS PA bus segment is
limited to 31 and 1A maximum current, i.e. you can only connect a maximum of
31 PA field devices in a ring structure.
Ring redundancy
V1.1, Item ID: 44887866 5
1 Introduction
Ring redundancy
6 V1.1, Item-ID: 44887866
2 Commissioning
2 Commissioning
IM 153-2
Set the valid PROFIBUS address on the interface module IM 153-2. The
PROFIBUS address set on the interface module must match the PROFIBUS
address entered in the STEP 7 hardware configuration.
Figure 2-1
Set the PROFIBUS address and ring redundancy on the DP/PA coupler
Open the front door of the DP/PA coupler to set the PROFIBUS address and ring
redundancy on the DP/PA coupler. Figure 2-2 shows the DP/PA coupler with the
front door open.
Figure 2-2
Ring redundancy
V1.1, Item ID: 44887866 7
2 Commissioning
Table 2-1
No. Instructions
Set the "PA bus terminator" DIP switch of both DP/PA couplers to the "ON"
1 position to switch on the terminating resistor for the PROFIBUS PA.
On both DP/PA couplers you set the PROFIBUS address with the DIP switches
2 (value range: 3 to 125).
Note:
The PROFIBUS addresses must not be duplicated in one PROFIBUS PA bus
segment.
Set the redundancy mode with the DIP switches on both DP/PA couplers, i.e.
3 set the lowest DIP switch "RING" to the "ON" position to switch on ring
redundancy.
Note:
The presetting of the "RING" DIP switch is the "OFF" position, i.e. coupler
redundancy is switched on in the presetting.
Ring redundancy
8 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration
dra
g&
dro
p
Ring redundancy
V1.1, Item ID: 44887866 9
3 STEP 7 Hardware Configuration
If the "Properties - PROFIBUS interface IM 153-2 OD" dialog does not open
automatically, right-click on the interface module IM 153-2 in the Hardware
Configuration. Open the "Properties" dialog of the interface module IM 153-2 via
the "Object Properties" menu.
In the Properties dialog of the interface module IM 153-2 you switch to the
"General" tab. Click on the "PROFIBUS" button. The "Properties - PROFIBUS
interface IM 153-2 OD" dialog opens.
Figure 3-3
Ring redundancy
10 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration
Ring redundancy
V1.1, Item ID: 44887866 11
3 STEP 7 Hardware Configuration
Ring redundancy
12 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration
If the "Properties - PROFIBUS interface FDC 157-0" dialog does not open
automatically, right-click on the FDC 157-0 in the Hardware Configuration. Open
the "Properties" dialog of the FDC 157-0 via the "Object Properties" menu.
In the Properties dialog of the FDC 157-0 you switch to the "General" tab. Click on
the "PROFIBUS" button. The "Properties - PROFIBUS interface FDC 157-0" dialog
opens.
Figure 3-7
Ring redundancy
V1.1, Item ID: 44887866 13
3 STEP 7 Hardware Configuration
drop
drag &
Ring redundancy
14 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration
Enter the PROFIBUS address of the second FDC 157-0 DP/PA coupler and set the
ring redundancy for the second FDC 157-0 DP/PA coupler.
Ring redundancy
V1.1, Item ID: 44887866 15
4 Diagnostics
4 Diagnostics
The PROFIBUS PA main line is connected to the active field distributor via PA1
and PA2.
The spur lines to the PROFIBUS PA field devices are connected via X1 to X4 on
the active field distributor.
The diagnostics is done via the LEDs of the modules.
main line
PA1 X1 X2 X3 X4 PA2
spur line
Ring redundancy
16 V1.1, Item-ID: 44887866
4 Diagnostics
ON On Green
Ring redundancy
V1.1, Item ID: 44887866 17
4 Diagnostics
Figure 4-2
IM 153-2 FDC 157-0 (left) FDC 157-0 (right)
main line
PA1 X1 X2 X3 X4 PA2
spur line
Ring redundancy
18 V1.1, Item-ID: 44887866
4 Diagnostics
ON On Green
The PROFIBUS PA field devices that are connected to the active field distributor
via spur lines continue to run without disruption.
Ring redundancy
V1.1, Item ID: 44887866 19