Ring Redundancy
FDC 157-0 DP/PA Couplers and Active Field Distributors
(AFDs)

FAQ  October 2010

Service & Support


Answers for industry.
Question

This entry is from the Service&Support portal of Siemens AG, Sector Industry,
Industry Automation and Drive Technologies. The general terms of use
(http://www.siemens.com/terms_of_use) apply.

Clicking the link below directly displays the download page of this document.
http://support.automation.siemens.com/WW/view/en/44887866

Question
How do you configure a ring redundancy with FDC 157-0 DP/PA couplers and
active field distributors (AFDs)?

Answer
The instructions and notes listed in this document provide a detailed answer to this
question.

Ring redundancy
2 V1.1, Item ID: 44887866
Table of contents

Table of contents
1 Introduction........................................................................................................ 4
2 Commissioning.................................................................................................. 7
3 STEP 7 Hardware Configuration ...................................................................... 9
3.1 Configuration of the Interface Module IM 153-2................................... 9
3.2 Configuration of the FDC 157-0 DP/PA Coupler................................ 12
3.3 Save and Compile the Hardware Configuration and Load It into
the CPU of the S7 Station .................................................................. 15
4 Diagnostics ...................................................................................................... 16
4.1 Status of the LEDs for Ring Redundancy .......................................... 16
4.2 Status of the LEDs with Fault on the PROFIBUS PA ........................ 17

Ring redundancy
V1.1, Item ID: 44887866 3
1 Introduction

1 Introduction
Ring redundancy
The use a DP/PA coupler pair and active field distributors (AFDs) increases the
availability of the PROFIBUS PA. Ring redundancy is created by configuring a ring
structure with two FDC 157-0 DP/PA couplers and up to eight AFDs.
The active FDC 157-0 DP/PA coupler supplies the PROFIBUS PA. If there is a
short-circuit or wire break on the main line of the PROFIBUS PA, the second
DP/PA FDC 157-0 DP/PA coupler also gets active. The DP/PA couples supply the
separated PROFIBUS PA in both directions to the interrupt. The functions of the
PA field devices are retained.
Repairs can be made during operation.

Hardware configuration
Table 1-1 shows an overview of the hardware configuration for using a DP/PA
coupler pair in redundancy mode.
Table 1-1
Module Order number Quantity
ET 200M, mounting channel 6ES7195-1G... 1
Power supply PS 307 6ES7307-1... 2
Bus module BM PS/IM for ET 200M for a 6ES7195-7HA00-0XA0 1
power supply unit and an IM153-2
IM153-2 6ES7153-2BA82-0XB0 1
Bus module pair BM DP/PA for two FDC 6ES7195-7HG80-0XA0 1
157-0 DP/PA couplers
Field device connection FDC 157-0 6ES7157-0AC83-0XA0 2
DP/PA coupler
Active field distributor (AFD) 6ES7157-0AF81-0XA0 At least 1

Installation of the hardware configuration with active bus modules and modules for the
"Change Module during Operation" and/or "Redundancy" modes
Follow the instructions below to install the hardware configuration with active bus
modules and modules for the "Change Module during Operation" and/or
"Redundancy" modes.
Table 1-2

1. Mount the ET 200M mounting channel in its place.


2. Insert the bottom edge of the bus module BM PS/IM in the mounting channel and
press it into the mounting channel and push it to the left until it locks in.
3. Insert the bus module pair BM DP/PA in the mounting channel and press it into
the mounting channel. Push them up to the left bus module BM PS/IM so that the
module connection makes contact.

Ring redundancy
4 V1.1, Item-ID: 44887866
1 Introduction

4. Insert the power supply and interface module IM153-2 in the mounting channel in
the bus module BM PS/IM.
Then insert the two FDC 157-0 DP/PA couplers in the mounting channel in the
bus module pair BM DP/PA.
Use the side guides of the bus modules for this. When you screw the modules
tight, at the same time also fasten the bus module on the mounting channel.
5. Mount the bus module cover on the last bus module, in this case BM DP/PA. If
there is no module slotted in a slot, then also mount the backplane bus cover on
the unoccupied slot.

Configuration of the ring structure


Figure 1-1 shows the ring structure configuration
To operate ring redundancy you configure a ring structure with two DP/PA couplers
and at least one active field distributor (AFD). Connect the PA field devices to the
AFD via spur lines.
The maximum length of a spur line depends on the number of spur lines on the
main line (see Table 1-3).
Figure 1-1
IM FDC FDC
153-2 157-0 157-0

Active Field Distributor AFD


PROFIBUS DP PROFIBUS PA

main line

Active Field Distributor AFD Active Field Distributor AFD

spur line

Note You can use a maximum of eight AFDs in the ring structure.
You can connect a maximum of four PA field devices to each AFD.
Altogether, the number of PA field devices in one PROFIBUS PA bus segment is
limited to 31 and 1A maximum current, i.e. you can only connect a maximum of
31 PA field devices in a ring structure.

Ring redundancy
V1.1, Item ID: 44887866 5
1 Introduction

Functions of the active field distributor (AFD)


The AFD provides the functions below:
• Connection of field devices for PROFIBUS PA
• Automatic bus termination
• Isolation of defective PROFIBUS PA bus segments
• Connection of isolated PROFIBUS PA bus segments after troubleshooting
• Extension of a PROFIBUS PA bus segment during operation

Spur line length


The maximum permissible spur line lengths are shown in the table below.
Table 1-3
Number of spur lines Maximum length of one spur line
1 to 12 120m
13 to 14 90m
16 to 18 60m
19 to 24 30m

Ring redundancy
6 V1.1, Item-ID: 44887866
2 Commissioning

2 Commissioning
IM 153-2
Set the valid PROFIBUS address on the interface module IM 153-2. The
PROFIBUS address set on the interface module must match the PROFIBUS
address entered in the STEP 7 hardware configuration.
Figure 2-1

Set the PROFIBUS address and ring redundancy on the DP/PA coupler
Open the front door of the DP/PA coupler to set the PROFIBUS address and ring
redundancy on the DP/PA coupler. Figure 2-2 shows the DP/PA coupler with the
front door open.
Figure 2-2

Switch on the terminating resistor for PROFIBUS PA

Setting the PROFIBUS address

Setting the redundancy mode

Follow the instructions below to commission the DP/PA coupler.

Ring redundancy
V1.1, Item ID: 44887866 7
2 Commissioning

Table 2-1
No. Instructions
Set the "PA bus terminator" DIP switch of both DP/PA couplers to the "ON"
1 position to switch on the terminating resistor for the PROFIBUS PA.

On both DP/PA couplers you set the PROFIBUS address with the DIP switches
2 (value range: 3 to 125).
Note:
The PROFIBUS addresses must not be duplicated in one PROFIBUS PA bus
segment.
Set the redundancy mode with the DIP switches on both DP/PA couplers, i.e.
3 set the lowest DIP switch "RING" to the "ON" position to switch on ring
redundancy.
Note:
The presetting of the "RING" DIP switch is the "OFF" position, i.e. coupler
redundancy is switched on in the presetting.

Ring redundancy
8 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration

3 STEP 7 Hardware Configuration


In the SIMATIC Manager you open the STEP 7 project that contains the
configuration for your S7 station.
Open the hardware configuration of the S7 station. An S7-300 station is used in
this example.

3.1 Configuration of the Interface Module IM 153-2


Inserting IM 153-2 in the Hardware Configuration
In the Hardware Catalog, under "PROFIBUS  DP/PA Link", select the interface
module IM 153-2 OD and drag-and-drop it into the DP master system of the CPU.
Figure 3-1

dra
g&
dro
p

Ring redundancy
V1.1, Item ID: 44887866 9
3 STEP 7 Hardware Configuration

Enter the PROFIBUS address of the interface module IM 153-2


The "Properties - PROFIBUS interface IM 153-2 OD" dialog opens. Enter the
PROFIBUS address that you have set with the DIP switches on the module and
close the dialog with "OK".
Figure 3-2

If the "Properties - PROFIBUS interface IM 153-2 OD" dialog does not open
automatically, right-click on the interface module IM 153-2 in the Hardware
Configuration. Open the "Properties" dialog of the interface module IM 153-2 via
the "Object Properties" menu.
In the Properties dialog of the interface module IM 153-2 you switch to the
"General" tab. Click on the "PROFIBUS" button. The "Properties - PROFIBUS
interface IM 153-2 OD" dialog opens.
Figure 3-3

Ring redundancy
10 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration

Define the master system for the interface module IM 153-2


The "Define Master System" dialog opens automatically. Select the "Interface
module for PROFIBUS-PA" option and close the dialog with "OK".
Figure 3-4

Ring redundancy
V1.1, Item ID: 44887866 11
3 STEP 7 Hardware Configuration

3.2 Configuration of the FDC 157-0 DP/PA Coupler


Insert the FDC 157-0 DP/PA coupler in the Hardware Configuration
In the Hardware Catalog, under "PROFIBUS  DP/PA Link", select the FDC157-0
and drag-and-drop it into the PROFIBUS PA master system of the interface module
IM 153-2.
Figure 3-5

drag & drop

Enter the PROFIBUS address of the FDC 157-0 DP/PA coupler


The "Properties - PROFIBUS interface IM 157-0 OD" dialog opens. Enter the
PROFIBUS address that you have set with the DIP switches on the module and
close the dialog with "OK".
Figure 3-6

Ring redundancy
12 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration

If the "Properties - PROFIBUS interface FDC 157-0" dialog does not open
automatically, right-click on the FDC 157-0 in the Hardware Configuration. Open
the "Properties" dialog of the FDC 157-0 via the "Object Properties" menu.
In the Properties dialog of the FDC 157-0 you switch to the "General" tab. Click on
the "PROFIBUS" button. The "Properties - PROFIBUS interface FDC 157-0" dialog
opens.
Figure 3-7

Ring redundancy
V1.1, Item ID: 44887866 13
3 STEP 7 Hardware Configuration

Set ring redundancy for the FDC 157-0


In the Hardware Configuration, right-click on the FDC 157-0 and open the
Properties dialog of the FDC 157-0 via the "Object Properties" menu.
In the Properties dialog of the FDC 157-0 you switch to the "Parameter
Assignment" tab.
Under "Station parameters  Device-specific parameters" you set the value "Ring
redundancy" for the "Redundancy mode" parameter. You set the value "DPV1" for
the "DP Interrupt Mode" parameter.
Close the Properties dialog of the FDC 157-0 with "OK".
Figure 3-8

Insert two FDC 157-0 DP/PA couplers in the Hardware Configuration


In the Hardware Catalog, under "PROFIBUS  DP/PA Link", select the FDC157-0
and drag-and-drop a second FDC 157-0 into the PROFIBUS PA master system of
the interface module IM 153-2.
Figure 3-9

drop
drag &

Ring redundancy
14 V1.1, Item-ID: 44887866
3 STEP 7 Hardware Configuration

Enter the PROFIBUS address of the second FDC 157-0 DP/PA coupler and set the
ring redundancy for the second FDC 157-0 DP/PA coupler.

3.3 Save and Compile the Hardware Configuration and


Load It into the CPU of the S7 Station
In the Hardware Configuration you click on the "Save and Compile" button to save
and compile the configuration.
Then click on the "Load" button to load the configuration into the CPU of the S7
station.
Figure 3-10

Speichern und übersetzen laden

Ring redundancy
V1.1, Item ID: 44887866 15
4 Diagnostics

4 Diagnostics
The PROFIBUS PA main line is connected to the active field distributor via PA1
and PA2.
The spur lines to the PROFIBUS PA field devices are connected via X1 to X4 on
the active field distributor.
The diagnostics is done via the LEDs of the modules.

4.1 Status of the LEDs for Ring Redundancy


Figure 4-1 shows the connection of an active field distributor to a DP/PA coupler
pair and the status of the LEDs on the modules when:
• the power supply is switched on
• the CPU of the S7 station is in the "RUN" operating mode
• the interface module IM 153-2 and the FDC 157-0 DP/PA coupler are ready for
operation
• there are no faults on the PROFIBUS PA
Figure 4-1
IM 153-2 FDC 157-0 (left) FDC 157-0 (right)

main line

Active Field Distributor AFD main line

PA1 X1 X2 X3 X4 PA2

spur line

Ring redundancy
16 V1.1, Item-ID: 44887866
4 Diagnostics

Status of the LEDs on the interface module IM 153-2


If there are no faults on the PROFIBUS PA and the interface module IM 153-2 is
ready for operation, then the LEDs on the interface module IM 153-2 have the
following status.
Table 4-1
LED Status Color Description
SF Off - The "ON" LED lights green, i.e. the power is
supplied to the interface module IM 153-2.
BF1 Off -
The interface module IM 153-2 is exchanging data
BF2 Off - with the DP master and the lower-level slaves.
ACT Off -
ON On Green

Status of the LEDs on the FDC 157-0 DP/PA coupler (left)


First of all the FDC 157-0 (left) is the actively supplying DP/PA coupler and
receives the PROFIBUS PA messages. This is displayed by the LEDs on the FDC
157-0 (left).
Table 4-2
LED Status Color Description
SF Off - The "ON" LED lights green, i.e. the power is
supplied to the FDC 157-0. The FDC 157-0 is
BF Off -
ready for operation.
DP On Yellow PROFIBUS PA messages are being received.
PA Flashes Yellow The FDC 157-0 is the actively supplying DP/PA
ACT On Yellow coupler.

ON On Green

Status of the LEDs on the FDC 157-0 DP/PA coupler (right)


The FDC 157-0 (right) is ready for operation. This is displayed by the LEDs on the
FDC 157-0 (right).
Table 4-3
LED Status Color Description
SF Off - The "ON" LED lights green, i.e. the power is
BF Off - supplied to the FDC 157-0. The FDC 157-0 is
ready for operation.
DP On Yellow The FDC 157-0 is the passive DP/PA coupler.
PA Off -
ACT Off -
ON On Green

4.2 Status of the LEDs with Fault on the PROFIBUS PA


Figure 4-2 shows the connection of an active field distributor to a DP/PA coupler
pair and the status of the LEDs on the modules when there is a fault on the
PROFIBUS PA.
In this example there is a fault on the main line between FDC 157-0 (left) and the
active field distributor.

Ring redundancy
V1.1, Item ID: 44887866 17
4 Diagnostics

Figure 4-2
IM 153-2 FDC 157-0 (left) FDC 157-0 (right)

main line

Active Field Distributor AFD main line

PA1 X1 X2 X3 X4 PA2

spur line

Status of the LEDs on the interface module IM 153-2


If there are no faults on the PROFIBUS PA then the LEDs on the interface module
IM 153-2 that is ready for operation have the following status.
Table 4-4
LED Status Color Description
SF On Red The "ON" LED lights green, i.e. the power is
supplied to the interface module IM 153-2.
BF1 Off -
All the slaves are exchanging data. At least one
BF2 Off - slave has reported a fault.
ACT Off -
ON On Green

Status of the LEDs on the FDC 157-0 DP/PA coupler (left)


Since in this example the main line between FDC 157-0 (left) and the active field
distributor has a fault, the FDC 157-0 (left) can no longer receive the PROFIBUS
PA messages. The fault is displayed by the LEDs on the FDC 157-0 (left).
Table 4-5
LED Status Color Description
SF On Red The "ON" LED lights green, i.e. the power is
supplied to the FDC 157-0. The FDC 157-0 is
BF Off -
ready for operation.
DP On Yellow The FDC 157-0 has a diagnostics message.
PA Off -
ACT Off -
ON On Green

Ring redundancy
18 V1.1, Item-ID: 44887866
4 Diagnostics

Status of the LEDs on the FDC 157-0 DP/PA coupler (right)


First of all the FDC 157-0 (right) becomes the actively supplying DP/PA coupler
and receives the PROFIBUS PA messages. This is displayed by the LEDs on the
FDC 157-0 (right).
LED Status Color Description
SF Off - The "ON" LED lights green, i.e. the power is
supplied to the FDC 157-0. The FDC 157-0 is
BF Off -
ready for operation.
DP On Yellow PROFIBUS PA messages are being received.
PA Flashes Yellow The FDC 157-0 is the actively supplying DP/PA
ACT On Yellow coupler.

ON On Green
The PROFIBUS PA field devices that are connected to the active field distributor
via spur lines continue to run without disruption.

Ring redundancy
V1.1, Item ID: 44887866 19