Professional Documents
Culture Documents
Dr. G. Gurusamy
Dean EEE department
Bannari Amman Instituteof Technology
Sathyamangalam
ABSTRACT :
Increasing application of electronics to all kinds of appliances makes possible real
time communication and continuous operation. This improves facilities performance
levels throu gh effective data & energy management. But electronic d evices are non linear
loads and introduce disturbance in the facility they are fed b y. Therefore facilities &
sensible equipment are becoming more dep endent on both quality & continuity of electric
power supply. In this paper an attempt is made to compare power qu ality aspects of DG
set with utility supply. Harmonics at the out of DG set & single phase UPS (load fed from
DG) wer e measured using Fluke 434 Analyzer. Harmonic effects are more pronounced
when operated on DG b ecause of its high internal impedance.
1. INTRODUCTION
Proper design and imp lementation of emergency power supply systems is
essential for improving reliability and quality of power supply for critical loads.
Auxiliary power sources are independent from the utility grid. They mainly supply
backup energy in the case of planned outages and when the mains fail. Stand by power
systems are reserve of power supply and they ensure continuity of operation in the event
of long normal power outage namely power failure or maintenance procedures or
continued low power quality of supply. [1] Their continuity of operation ranges from few
seconds to days.
118
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
119
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
120
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
common neutral carries zero sequence triplen harmonics that are additive in the neutral
along with positive & negative sequence components from unbalance.[3] We some times
experience that single phase UPS unable to work in heavily loaded DG set due to
distortion in current waveform but works well with utility supply. Sensitivity adjustments
have to be done in the UPS to enable it to work with DG supply. Another alternative is to
reduce the load thereby reducing the current distortion.
3.1 Comparison of % THD current harmonics when loaded lightly and
heavily
“Figure 3” shows the peak values of rms voltage/current when moderately loaded.
There is a neutral current of 4 amps flows whose peak value is 8.7 amps. “Figure 4 “%
THD of Third harmonic current is 290.6 % which is the highest harmonic content.
Figure 4 Third harmonic content in the neutral of DG output under moderately loaded
conditions
121
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
“Figure 5” shows the peak values of rms voltage/current when lightly loaded.
There is a neutral curr ent of 1.8 amps flows whose peak value is 3.5 amps. “Figure 6” %
THD of Third harmonic current is 45.2 % which is the highest harmonic content.
Figure 6 Third harmonic content in the neutral of DG output under reduced load
In the case of DG set the frequency seldom remains constant but varies as load
varies. We always see UPS initiate alarms or may not function properly when operated
on DG set.
“Figure 7” shows that the current waveforms are nearly sinusoidal as the DG set
is having less number of non linear loads connected to it .
”Figure 8 “is more distorted on account of more number of non linear loads.
122
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
Figure 7 DG output current waveforms with less number of non linear lo ads
Figure 8 DG output current waveforms with max number of non linear loads(mainly
UPS, Air conditioners, Tube lights &fans)
“Figure 9” shows the output waveform of a stand b y UPS which was working on
its battery unit when the unit was shifted to work on DG owing to a power failure of
utility supply.
123
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
124
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
5 CONCLUSIONS
It was found that fifth harmonic content of current in the three lines were
excessively high at the DG set output which can b e reduced by using short pitched angle
of nearly 150 degrees. Single phase UPS which were working smoothly on utility supply,
were not functioning properly on DG set. Neutral current third harmon ic content was
125
International Jo urnal of Electrical Engineering and Technology (IJEET),
ISSN 0976 – 6545(Print), ISSN 0 976 – 6553(Online) Volume 1, Number 1, May - June (2010), © IAEME
excessively high. Harmonic distortion at the generator output affected other sensitive
loads too.
6. REFERENCES
1 Hand book of Power Quality by Angelo Baggini, University of Bergamo, Italy
2. Alternating current generators – section 7 Standard hand book for Electrical Engineers.
th
McGraw Hill, 11 Ed1978, ISBN007020974X
3. Selected topics in Power quality By Dr.Ashok. S Department of Electrical Engineering
NIT Calicut.
126