Professional Documents
Culture Documents
Know How Broschuere BOA Systronic Data
Know How Broschuere BOA Systronic Data
B OA- Sy s t ro n i c
Contents
The new BOA - Systronic system solution improves the supply temperature control
of heating circuits. It opens up a previously unused potential for saving electrical
energy used by the circulator pump.
1
Constant volume fl ow rate through consumer installations: results from the hydraulic confi guration of the main feed circuit (e.g. 3-way mixing
valve). Whether the system is operating under nominal load or part-load conditions, the circulator pump will always deliver the nominal
volume fl ow rate calculated for the design point. Only when external heat is acting on the consumer installations will the level of this volume
fl ow rate be adjusted by the control function of the thermostats.
2
System concept
An analysis of this situation re- The supply temperature is in- main feed manifold is now
sulted in the BOA-Systronic creased by the higher-level con- automatically performed via the
system concept, which has the troller. This results in hydraulic circulator pump, which reduces
clearly defined benefit of reduc- savings regarding both volume commissioning costs for the
ing the running costs of the flow rate ∆Q and discharge heating circuit. When the heat-
heating circuit. head ∆H, whose product is pro- ing circuit of a conventional
portional to the corresponding mixing or injection-type system
SAVINGS POTENTIAL BY electrical power savings for the is commissioned, the tempera-
SYSTEM CONCEPT circulator pump2 . ture difference between supply
and return (temperature differ-
BOA-Systronic coordinates the A positive side effect is that ential) is set for the design point
operation of circulator pump static hydraulic balancing at the using the balancing valve, usu-
and control valve. Depending
on the control signal issued by
the higher-level heating control-
ler the two BOA-CVE Super-
Compact control valves adjust
the resulting volume flow rate
pumped through the consumer
installations. At the same time,
the appropriate discharge head
setpoint is transmitted to the Higher-level heating
controller
variable-speed drive of the cir-
culator pump.
t2
2
Electrical power input of circulator pump: P = constant · ∫ Q(t) · H(t)dt.
electr. t1
The constant describes the efficiency of circulator pump and frequency inverter as well as water density and acceleration due to gravity.
KNOWLEDGE ABOUT
PIPING CHARACTERISTIC
OF HEATING CIRCUIT
Conclusion
The savings realised by BOA - Systronic result from knowledge about the hydraulic
conditions in the heating circuit. They are completely independent from differential
pressure control of the circulator pump. With BOA - Systronic , differential pressure
control of the circulator pump is effected as before.
3
Components
The transformation into a sys- ing on the actual load (external and thus the hydraulic resist-
tem with variable volume flow temperature). ance of the heating circuit. The
presupposes that the partial The control unit is mounted on measuring valve remains fully
volume flows are hydraulically the main control valve at the open both during commission-
decoupled and that information factory. The BOA-Control ing and over the entire operat-
about the flow rates required in IMS 4 valve is used here to ing range and – due to its very
the heating circuit is available. measure the volume flow rate at low ζ-coefficient – acts just like
For this reason, BOA-Systronic the main feed manifold during a piece of pipe. The measuring
comprises three valves. The two commissioning. This measuring computer is not included in the
BOA-CVE SuperCompact con- signal is used to determine the system scope of supply.
trol valves are used for adjust- discharge head of the circulator
ing volume flow through the pump for the design point as
consumer installations depend- well as the system control curve
3
BOA- CVE SuperCompact: Automated shut-off and control valve for HVAC applications with smart electric actuator. The valve is produced
in nominal sizes from DN20 to DN150 and nominal pressure class PN6/10/16. Thanks to its compact design, it is the smallest and lightest
valve of this pressure class manufactured in series production today, enabling the space-saving design of air-conditioning and heating centrals.
Due to its low weight, the valve is easy to install and handle. The self-calibration feature of the actuator is another benefi t, which does away
with the adjustment of limit switches.
4
BOA- Control IMS: The valve measures volume fl ow rates independently from valve travel positions and minimum differential pressures.
Unlike on conventional valve models, the measurement accuracy is constant across the entire valve travel. The measuring signal is read and
processed by a measuring computer. Valves of this kind are often insulated, and any identifi cation on their bodies may be diffi cult to read.
After start-up, the computer display therefore fi rst shows the nominal diameter of the connected valve. The operator can then choose via two
keys whether the current fl ow rate is to be indicated [in m 3 /h] or the temperature of the fl uid handled [in C°]. Volume fl ow rates can be checked
within a matter of seconds in this way. BOA- Control IMS, which has a linear characteristic, can also be used as shut-off valve. Thanks to a
travel stop with a protective cap, the valve can be set exactly to its original position once the shut-off process has been completed.
5
ζ-coeffi cient: describes the resistance a valve offers to the fl uid passing through it. The ζ-coeffi cient depends on the valve type and design.
100 Q total
Volume flow rate Q [%]
Q 2 mixing
80
Q 1 supply 60
(hot)
Q total
40
20
Q 1 supply
0
0 20 40 60 80 100
Q 2 mixing (cold)
Controller signal [%]
100
Volume flow rate Q [%]
Q 1 supply 80
(hot) Q total
60
Q total 40
+
20
Q 2 mixing Q 1 supply Q 2 mixing
(cold)
0
0 20 40 60 80 100
6 Control IMS valve measures the cuit, the pressure losses in the
Circulator pump heads volume flow rate in the heating consumer installations, balanc-
circuit and thus determines the ing valves, differential pressure
Owing to the hydraulic config- required nominal discharge head control elements, strainers as
uration of conventional mixing of the circulator at the design well as thermostatic and shut-
or injection-type systems, the point. The values obtained are off valves.
circulator pump head cannot be then used to determine the The volume flow rate and dis-
matched to the system control system constant of the heating charge head are shown in nor-
curve. The circulator pump can circuit. As a result, the hydraul- malized representation here.
only react to reduced volume ic resistance of the heating The circulator pump of a mix-
flow rates resulting from the circuit is known, and the control ing or injection-type system can
control function of the thermo- unit knows the circulator head only respond to reduced volume
static valves at the consumer in- required for the individual load flow rates (external heat gain)
stallations. Depending on the conditions. with a constant discharge head,
pump curve selected, the dis- thus saving a certain amount of
charge head either remains The H/Q diagram on page 11 energy.
constant (∆p = constant) or is shows an example of the possi-
reduced accordingly (∆p = ble discharge heads of a differ- NEW DESIGN POINT FOR
variable). ential pressure controlled THE PUMP
pump. The diagram shows the
BOA-SYSTRONIC CON- H/Q data of a pump controlled With BOA-Systronic, parallel
TROLS THE PUMP AS A independently of throughflow shift of the heating curve results
FUNCTION OF THE SYSTEM (∆p = constant) and offers a in the new nominal volume
CURVE OF THE HEATING comparison between a conven- flow rate
CIRCUIT tional system and a system
equipped with BOA-Systronic. Q new = 0.75 · Q old
BOA-Systronic, by means of the
two control valves, adjusts the The design point is represented and, by application of the affin-
volume flow rate as a function by the intersection of the system ity law, yields the associated
of external temperature and curve of the heating circuit with discharge head of the circulator
measures the system curve of the characteristic curve of the pump:
the heating circuit during com- circulator pump. (see equation below)
missioning. As a result, the cir-
culator’s discharge head can be Q new 2
75% 2
10
P el 1 constant Q1 H1 Q1 H1
= =
P el2 constant Q2 H2 Q2 H2
180
Discharge head H [%]
140
120
External
heat effect
Characteristic curve of
100 variable speed pump ∆p = constant
Design point BOA-Systronic
with external heat load
80 External
P el 21 = 35%
heat effect
Characteristic curve of Design point BOA-Systronic
60 variable speed pump ∆p = constant without external heat load
Operating point BOA-Systronic P el 2 = 45%
ic
part-load, with external heat load External st ron
40 P el 31 = 11% heat effect A -Sy
BO Operating point BOA-Systronic
Characteristic curve of part-load, without external heat load
variable speed pump
20 e P el 3 = 16%
urv
System control curve em c
Syst
0
0 10 20 30 40 50 60 70 80 90 100 110 120
11
7
Hydraulic balancing of
branch circuits
12
Equation 3 Equation 6
∆ pT = F2 ·∆ p N
∆ pT2 ∆ pN2
Equation 5 =
∆ pT1 ∆ pN1
Conclusion
13
Conclusion
BOA -Systronic provides the circulator pump with the discharge head required for
the actual load conditions. No excess discharge heads are produced under part load
conditions, nor flow noises at the consumers. Expensive differential pressure control
elements for balancing the heating circuits can be dispensed with. For hydraulic balancing
of branch circuits, they can even be replaced by lower priced balancing valves.
14
180
Discharge head H [%]
100 H2
External
∆p1 heat effect
Operating point Operating point
80 BOA-Systronic BOA-Systronic rve
cu
tem
variable speed pump variable speed pump
∆p2 s
60
with external heat load without external heat load Sy
c
oni
External
y str
40 heat effect A-S
BO
H3 ∆p
3
Hydraulic
20
resistance
of heating circuit
0
0 10 20 30 40 Q part-load 60 70 Q NS 80 90 QN 110 120
10
Practical testing
10.1 Plant
16
17
18
Equation 12
Equation 13
19
10.3
Measurements
Heating circuit East Heating circuit West
(3-way mixing configuration) (BOA-Systronic)
To verify the function of the
External temperature External temperature
BOA-Systronic system, the
Volume flow rate at main feed manifold Volume flow rate at main feed manifold
following quantities were
Differential pump pressure Differential pump pressure
measured, among others. (Table 03)
Electrical power input Electrical power input
30
25
20
15
10
-5
-10
1. Nov 00
1. Dec 00
31. Dec 00
30. Jan 01
1. Mar 01
31. Mar 01
30. Apr 01
30. May 01
29. Jun 01
29. Jul 01
28. Aug 01
27. Sep 01
27. Oct 01
26. Nov 01
26. Dec 01
25. Jan 02
24. Feb 02
26. Mar 02
25. Apr 02
25. May 02
24. Jun 02
24. Jul 02
23. Aug 02
22. Sep 02
22. Oct 02
Years
External temperature
20
The conventional, mixing-type This value is confirmed by the ume flow rate the conventional,
system must provide a thermal measurements (Fig. 19). Irrespect- mixing-type system provides to its
output Pth = 300 kW at the de- ive of its degree of opening, the heating circuit. Fig. 19 shows that
sign point. Based on a tempera- three-way control valve of the the measured nominal volume
ture differential ∆T = 20K, the conventional, mixing-type system flow rates supplied by the conven-
always supplies the nominal vol- tional, mixing-type system do not
ume flow rate to the heating circuit quite reach the theoretical, calcu-
(constant-flow system). BOA- lated values. This is due to the
Systronic, by contrast, adjusts the control function of the thermostat-
resulting volume flow rate in the ic valves under the influence of
main feed circuit depending on the external heat input to the heating
opening degree of the two control circuit. The equation
valves and thus depending on the t2
control signal issued by the heat- water volume flow = ∫ Q(t) dt
ing controller. As expected, the t1
volume flow rate supplied to the is used to calculate the amounts
Volume flow rates – Heidelberg test installation – Savings by BOA-Systronic approx. 65%
16
Volme flow rate [m3/h]
14
12
10
0
1. Nov 00
1. Dec 00
31. Dec 00
30. Jan 01
1. Mar 01
31. Mar 01
30. Apr 01
30. May 01
29. Jun 01
29. Jul 01
28. Aug 01
27. Sep 01
27. Oct 01
26. Nov 01
26. Dec 01
25. Jan 02
24. Feb 02
26. Mar 02
25. Apr 02
25. May 02
24. Jun 02
24. Jul 02
23. Aug 02
22. Sep 02
22. Oct 02
Years
Fig. 19 Volume flow rates measured at the main feed manifold in 2000 – 2002
21
Pump differential pressures – Heidelberg test installation – Savings by BOA-Systronic approx. 37%
800
Pump differential pressures [mbar]
700
600
500
400
300
200
100
0
1. Nov 00
1. Dec 00
31. Dec 00
30. Jan 01
1. Mar 01
31. Mar 01
30. Apr 01
30. May 01
29. Jun 01
29. Jul 01
28. Aug 01
27. Sep 01
27. Oct 01
26. Nov 01
26. Dec 01
25. Jan 02
24. Feb 02
26. Mar 02
25. Apr 02
25. May 02
24. Jun 02
24. Jul 02
23. Aug 02
22. Sep 02
22. Oct 02
22
Years
22
The pump input power, and heads, the pump draws much
thus its power consumption, is less power from the electricity
proportional to the product of grid. BOA-Systronic was shown
the discharge head and volume to save approx. 70% in
flow rate. As BOA-Systronic electrical energy.
operates the pump at reduced
volume flow rates and discharge
Pump input power – Heidelberg test installation – Savings by BOA-Systronic approx. 70%
900
Pump input power [W]
800
700
600
500
400
300
200
100
0
1. Nov 00
1. Dec 00
31. Dec 00
30. Jan 01
1. Mar 01
31. Mar 01
30. Apr 01
30. May 01
29. Jun 01
29. Jul 01
28. Aug 01
27. Sep 01
27. Oct 01
26. Nov 01
26. Dec 01
25. Jan 02
24. Feb 02
26. Mar 02
25. Apr 02
25. May 02
24. Jun 02
24. Jul 02
23. Aug 02
22. Sep 02
22. Oct 02
Years
Conclusion
In our example, both heating circuits on average require only 21% of the thermal
output at design point. By comparison, BOA - Systronic consumes only about 30 % of
the electricity required by the conventional set- up ( here : 3 - way mixing system) .
23
initialization of the control Tab. 07: Average extra prices for BOA-Systronic
Tab. 08: Extra price for BOA-Systronic with Riotec pump (example: DN50)
24
Table 09: Extra price for BOA-Systronic with Rio-Eco pump (example: DN 50)
11.2 If the extra price for BOA- present hourly rates (2005), this
Investment costs for Systronic is deducted from the results in an additional € 45
heating circuit with reduced investment costs saved.
Riotec pump (€ 1,059–€ 402), the investment
costs for the main feed circuit Investment in BOA-Systronic
By utilizing all saving potentials will be reduced to € 657 in this would, therefore, pay back im-
offered by BOA-Systronic, the case. In addition, automated mediately, and the investment
investment costs of the present commissioning further reduces and commissioning costs for
heating circuit can be reduced the commissioning costs per the heating circuit would be re-
by € 1,059. heating circuit by one hour. At duced substantially.
Tab. 11: Reduced investment costs for heating circuit with Riotec pump, example (prices 2005)
25
Table 12: Reduced investment costs for heating circuit with Rio-Eco pump, example (prices 2005)
11.4
Total savings compari -
son Riotec / Rio - Eco
26
Savings [€]
Period
Year 01 -1,059 402 -45 -417 -1,119 -34 -1,503 -933 372 -45 - 456 -1,062 -32 -1,094 0,11 6,800
Year 02 -455 -1,608 -48 -1,656 - 498 -1,592 - 48 -1,640 0.12 6,800
Year 03 -455 -2,111 -63 -2,174 - 498 -2,138 - 64 -2,202 0.12 6,800
Year 04 -493 -2,667 -80 -2,747 -539 -2,741 - 82 -2,283 0.13 6,800
Year 05 -493 -3,240 -97 -3,337 -539 -3,362 -101 -3,463 0.13 6,800
Year 06 -531 -3,868 -116 -3,984 -581 - 4,044 -121 - 4,165 0.14 6,800
Year 07 -531 -4,515 -135 -4,651 -581 - 4,746 -142 - 4,889 0.14 6,800
Year 08 -569 -5,220 -157 -5,376 - 622 -5,511 -165 -5,676 0.15 6,800
Year 09 -569 -5,945 -178 -6,124 - 622 - 6,298 -189 - 6,487 0.15 6,800
Year 10 -607 -6,731 -202 -6,933 - 664 -7,151 -215 -7,365 0.16 6,800
Year 11 -607 -7,540 -226 -7,766 - 664 - 8,029 -241 - 8,270 0.16 6,800
Year 12 -645 -8,411 -252 -8,663 -705 - 8,975 -269 -9,244 0.17 6,800
Year 13 -645 -9,308 -279 -9,588 -705 -9,949 -298 -10,248 0.17 6,800
Year 14 -682 -10,270 -308 -10,578 -747 -10,995 -330 -11,325 0.18 6,800
Year 15 -682 -11,260 -338 -11,597 -747 -12,072 -362 -12,434 0.18 6,800
Year 16 -720 -12,317 -370 -12,687 -788 -13,222 -397 -13,619 0.19 6,800
Year 17 -720 -13,407 -402 -13,809 -788 -14,407 - 432 -14,839 0.19 6,800
Year 18 -758 -14,567 -437 -15,004 - 830 -15,669 - 470 -16,139 0.20 6,800
Year 19 -758 -15,762 -473 -16,235 - 830 -16,969 -509 -17,478 0.20 6,800
Year 20 -758 -16,993 -510 -17,503 - 830 -18,308 -549 -18,857 0.20 6,800
27
-1000
-2000
-3000
-4000
-5000
-6000
-7000
-8000
Savings [€]
-9000
-10.000
-11.000
-12.000
-13.000
-14.000
-15.000
-16.000
-17.000
-18.000
-19.000
-20.000
-21.000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Years [a]
Riotec pump: Savings plus interest (parallel shift) Rio-Eco pump: Savings plus interest (parallel shift)
Riotec pump: Savings plus interest (slope modification) Rio-Eco pump: Savings plus interest (slope modification)
Fig. 22 Savings realized by Riotec and Rio-Eco pumps with slope modifi cation and parallel shift (example)
28
29
13 pressure control valves for bal- tions are prevented, and flow
Conclusion ancing the heating circuits are noises at the consumer points
not required. They can be re- are avoided.
BOA-Systronic reduces operat- placed by balancing valves, BOA-Systronic is gentle on the
ing costs. which are less expensive. Even environment.
in heating circuits already
An analysis of load profiles in equipped with a LON-compat- Electricity is something you
heating systems revealed that ible variable speed pump, in- cannot produce and store for
heating circuits operate under vestment in BOA-Systronic will later use, but it must be avail-
part-load conditions for more pay back in less than two years. able at the exact moment when
than 95% of their operating it is needed. Burning fossil fuels
time. From this finding, it is BOA-Systronic reduces the produces CO2 emissions of
safe to conclude that in conven- commissioning costs for the roughly 0.53 kg per 1 kWh of
tional mixing or injection-type heating circuit. electrical energy produced.
systems cold return water is be- Thanks to the drastic reduction
ing circulated through the heat- The circulator pump and the in power consumption, BOA-
ing circuit most of the time. control valves are initialized Systronic therefore makes a
BOA-Systronic, by contrast, automatically. Static balancing positive contribution to envir-
provides only the volume flow at the main feed manifold is onmental protection.
actually required and can thus performed automatically by the
save an average of 70% electri- pump. The hydraulic operation
city costs for the circulator pump of the heating circuit is opti-
over the heating period, which mized. The system immediately
– depending on the thermal detects any air in the piping and
output of the heating circuit – thus prevents unnecessary com-
may amount to several hun- missioning work. Altogether,
dreds of Euros in electricity the costs for heating circuit
savings per year. commissioning are reduced.
30
List of tables
31
At your request, we will be pleased to send you all “KSB know-how” brochures previously published as
well as any volumes to be published in the future. All we need is your address and confirmation below.
Company:
Attn.:
Street address:
Post or ZIP code / City / Country:
KSB Aktiengesellschaft
Johann-Klein-Straße 9
67227 Frankenthal
www.ksb.com
© KSB Aktiengesellschaft
Your local KSB representative:
11/06
kubbli
0508.023-10