You are on page 1of 34

KSB Know-how, Volume 2

B OA- Sy s t ro n i c
Contents

Intelligent pump and valve management saves energy . . . . . . . . . . . . . 2


1 Heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 System concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Volume flow rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Circulator pump heads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 Hydraulic balancing of branch circuits . . . . . . . . . . . . . . . . . . 12
8 Differential pressure control elements . . . . . . . . . . . . . . . . . . . 14
9 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10 Practical testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
10.1 Plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
10.2 Circulator selection for BOA-Systronic . . . . . . . . . . . . . . . . . . 19
10.3 Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10.4 External temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10.5 Volume flow rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.6 Differential pressures of the pumps . . . . . . . . . . . . . . . . . . . . . 22
10.7 Electrical pump power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11 Payback period for BOA-Systronic . . . . . . . . . . . . . . . . . . . . . 24
11.1 Control valve investment and energy savings . . . . . . . . . . . . . . 24
11.2 Investment costs for heating circuit with Riotec pump . . . . . . 25
11.3 Investment costs for heating circuit with Rio-Eco pump . . . . . 26
11.4 Total savings comparison Riotec/Rio-Eco . . . . . . . . . . . . . . . . 26
12 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
13 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
List of figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
List of tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

060206_knowhow05_e_IS 1 06.02.2006, 12:49:41 Uhr


Intelligent pump and valve management saves energy

The new BOA - Systronic system solution improves the supply temperature control
of heating circuits. It opens up a previously unused potential for saving electrical
energy used by the circulator pump.

060206_knowhow05_e_IS 2 06.02.2006, 12:49:42 Uhr


Heating circuit
1
1 • Mixing or injection-type
Heating circuit systems produce a constant
volume flow rate through the
Every heating circuit consists of consumer installations1. As a
several control components result, part-load conditions –
such as the circulator pump and which account for more than
the control valve, which are 95% of the operating period –
connected by pipes. The circu- result in the circulator pump
lator pump conveys the heating handling predominantly cold
water from the heat generator return water most of the time.
(boiler) to the consumer instal- • In a mixing or injection-type
lations, and the control valve system, the discharge head of
adjusts the volume flow rate the variable-speed circulator
pumped through the consumer pump remains constant, irre-
installations. Conventional spective of the actual load
heating set-ups can be charac- conditions, i.e. irrespective of
terized as follows: external temperature. Only
external heat gains will result
THE CONTROL COMPO- in energy savings, depending
NENTS IN CONVENTION- on the set pump characteristic
AL HEATING SYSTEMS ARE curve (∆p = constant or ∆p =
NOT COORDINATED variable).
• If several heating circuits of
• The circulator pump and a mixing or injection-type
the control valve fitted in con- system branch off a main feed
ventional, mixing or injec- circuit, they must be balanced
tion-type systems operate in- manually.
dependently, without coord-
ination between the two com-
ponents. There is no system
knowledge about the hydraul-
ic conditions in the heating
circuit, so that some of the
hydraulic energy supplied by
the circulator pump may ac-
tually be destroyed by valves
and differential pressure con-
trol elements elsewhere in the
heating circuit.

1
Constant volume fl ow rate through consumer installations: results from the hydraulic confi guration of the main feed circuit (e.g. 3-way mixing
valve). Whether the system is operating under nominal load or part-load conditions, the circulator pump will always deliver the nominal
volume fl ow rate calculated for the design point. Only when external heat is acting on the consumer installations will the level of this volume
fl ow rate be adjusted by the control function of the thermostats.

060206_knowhow05_e_IS 3 06.02.2006, 12:49:42 Uhr


2 System concept

2
System concept

An analysis of this situation re- The supply temperature is in- main feed manifold is now
sulted in the BOA-Systronic creased by the higher-level con- automatically performed via the
system concept, which has the troller. This results in hydraulic circulator pump, which reduces
clearly defined benefit of reduc- savings regarding both volume commissioning costs for the
ing the running costs of the flow rate ∆Q and discharge heating circuit. When the heat-
heating circuit. head ∆H, whose product is pro- ing circuit of a conventional
portional to the corresponding mixing or injection-type system
SAVINGS POTENTIAL BY electrical power savings for the is commissioned, the tempera-
SYSTEM CONCEPT circulator pump2 . ture difference between supply
and return (temperature differ-
BOA-Systronic coordinates the A positive side effect is that ential) is set for the design point
operation of circulator pump static hydraulic balancing at the using the balancing valve, usu-
and control valve. Depending
on the control signal issued by
the higher-level heating control-
ler the two BOA-CVE Super-
Compact control valves adjust
the resulting volume flow rate
pumped through the consumer
installations. At the same time,
the appropriate discharge head
setpoint is transmitted to the Higher-level heating
controller
variable-speed drive of the cir-
culator pump.

BOA-Systronic transforms the


conventional, constant-flow
mixing or injection-type system
into a variable-flow system, and
adjusts the discharge head of
the circulator pump to the re-
duced volume flow rates via the
system control curve.
The radiator diagram illustrates
the physical fact that – at identi-
cal heat output – the volume
flow rates provided to the con-
sumer installations can be re-
duced if the supply temperature
is increased at the same time. Fig. 01 Hydraulics schematics of BOA-Systronic

t2
2
Electrical power input of circulator pump: P = constant · ∫ Q(t) · H(t)dt.
electr. t1
The constant describes the efficiency of circulator pump and frequency inverter as well as water density and acceleration due to gravity.

060206_knowhow05_e_IS 4 06.02.2006, 12:49:43 Uhr


System concept
2
ally by throttling this valve. ic balancing of branch circuits,
The pressure drop across the they can even be replaced by
valve may amount to several more cost-effective balancing
tenths of bar. With BOA-Sys- valves. Variable volume flow
tronic, this step is dispensed rate control by BOA-Systronic
with. has no influence on the hydraul-
As BOA-Systronic produces ic balancing of the branch cir-
only the discharge head actually cuits, which is performed for
required to overcome system the design point.
resistance, flow noises are pre-
vented, even with external heat
input, and expensive differen-
tial pressure control elements
are not required for balancing
the heating circuits. For hydraul-

KNOWLEDGE ABOUT
PIPING CHARACTERISTIC
OF HEATING CIRCUIT

Fig. 02 Comparison of systems

Conclusion

The savings realised by BOA - Systronic result from knowledge about the hydraulic
conditions in the heating circuit. They are completely independent from differential
pressure control of the circulator pump. With BOA - Systronic , differential pressure
control of the circulator pump is effected as before.

060206_knowhow05_e_IS 5 06.02.2006, 12:49:44 Uhr


3 Components

3
Components

The transformation into a sys- ing on the actual load (external and thus the hydraulic resist-
tem with variable volume flow temperature). ance of the heating circuit. The
presupposes that the partial The control unit is mounted on measuring valve remains fully
volume flows are hydraulically the main control valve at the open both during commission-
decoupled and that information factory. The BOA-Control ing and over the entire operat-
about the flow rates required in IMS 4 valve is used here to ing range and – due to its very
the heating circuit is available. measure the volume flow rate at low ζ-coefficient – acts just like
For this reason, BOA-Systronic the main feed manifold during a piece of pipe. The measuring
comprises three valves. The two commissioning. This measuring computer is not included in the
BOA-CVE SuperCompact con- signal is used to determine the system scope of supply.
trol valves are used for adjust- discharge head of the circulator
ing volume flow through the pump for the design point as
consumer installations depend- well as the system control curve

Fig. 03 BOA-Systronic components

3
BOA- CVE SuperCompact: Automated shut-off and control valve for HVAC applications with smart electric actuator. The valve is produced
in nominal sizes from DN20 to DN150 and nominal pressure class PN6/10/16. Thanks to its compact design, it is the smallest and lightest
valve of this pressure class manufactured in series production today, enabling the space-saving design of air-conditioning and heating centrals.
Due to its low weight, the valve is easy to install and handle. The self-calibration feature of the actuator is another benefi t, which does away
with the adjustment of limit switches.
4
BOA- Control IMS: The valve measures volume fl ow rates independently from valve travel positions and minimum differential pressures.
Unlike on conventional valve models, the measurement accuracy is constant across the entire valve travel. The measuring signal is read and
processed by a measuring computer. Valves of this kind are often insulated, and any identifi cation on their bodies may be diffi cult to read.
After start-up, the computer display therefore fi rst shows the nominal diameter of the connected valve. The operator can then choose via two
keys whether the current fl ow rate is to be indicated [in m 3 /h] or the temperature of the fl uid handled [in C°]. Volume fl ow rates can be checked
within a matter of seconds in this way. BOA- Control IMS, which has a linear characteristic, can also be used as shut-off valve. Thanks to a
travel stop with a protective cap, the valve can be set exactly to its original position once the shut-off process has been completed.
5
ζ-coeffi cient: describes the resistance a valve offers to the fl uid passing through it. The ζ-coeffi cient depends on the valve type and design.

060206_knowhow05_e_IS 6 06.02.2006, 12:49:46 Uhr


Control
4
4
Control

BOA-Systronic is a control sys- supply temperature measured,


tem which is installed down- the higher-level controller gen-
stream of the heating system’s erates the control error signal,
control unit. It does not replace which is the input of the (PI or
the higher-level controller. PID) control algorithm. This
control algorithm generates a
HIGHER-LEVEL CONTROL- signal, which – in conventional
LER IS RETAINED mixing / injection-type systems –
is then transmitted to the control
Supply temperature control valve.
remains the task of the higher- This output control signal from
level controller. Input signals the higher-level controller is the
for this controller are, among input for BOA-Systronic, i.e. it
others, the external tempera- is transmitted to the Systrobox
ture measured and the supply control unit. With the help of
temperature measured in the the system control curves deter-
heating circuit. With the help of mined during commissioning,
the heating curve stored in the Systrobox translates the control
higher-level control unit, the signal into two separate control
setpoint for the supply tempera- signals for the two BOA-CVE
ture of the heating circuit is SuperCompact control valves
generated on the basis of the and into a discharge head set-
external temperature measured. point for the circulator pump.
Based on this setpoint and the

060206_knowhow05_e_IS 7 06.02.2006, 12:49:51 Uhr


5 Volume flow rates

5 type systems. As a result, pre- water, whereas the control valve


Volume flow rates dominantly cold return water in the mixing line adjusts the
is pumped through the heating volume of cold return water to
Thermal output of the heating circuit under part-load be mixed in. The additional op-
circuit is calculated for the conditions. timizing effect of external heat
design point as the product of The volume flow rate through load compensation by the ther-
volume flow rate Q and temper- the heating circuit is only re- mostatic valves remains un-
ature differential ∆T. duced by the regulating func- affected.
tion of the thermostatic valves The radiator diagram illustrates
Pth = 1.163 · Q · ∆T (external heat load compensa- that volume flow rate can be re-
tion). duced while thermal output at
Conventional systems the consumer installations stays
Owing to their hydraulic con- BOA-Systronic the same, if the supply tempera-
figuration, conventional mixing The innovative control concept ture is increased accordingly.
or injection-type systems 6 can of BOA-Systronic regulates Two methods can be used,
provide the consumer installa- thermal output by variation of which can be realized by mak-
tions only with a constant vol- the temperature differential and ing use of a standard function
ume flow rate, irrespective of the volume flow rate, consider- offered by the heating control-
the heating controller’s signal. ably reducing the water volume ler.
The volume flow in the supply to be pumped through the heat-
line is coupled with the volume ing circuit. This is possible Parallel shift of heating
flow of the cold return water because the two BOA-CVE curve
pumped through the mixing SuperCompact control valves The controller’s heating curve is
line (Fig. 04). decouple the volume of heating shifted parallel by a fixed
water coming from the supply amount towards higher supply
Qtotal =Q1supply+Q2mixing line from the volume of cold re- temperatures. The controller
turn water pumped through the adds the fixed amount ∆T to the
So thermal output of the heating mixing line. supply temperature setpoint
circuit can only be regulated via The main control valve installed (parallel shift of the heating
the temperature differential in in the supply or return line regu- curve). Due to the increased
conventional mixing / injection- lates the volume of heating temperature differential, the

100 Q total
Volume flow rate Q [%]

Q 2 mixing
80

Q 1 supply 60
(hot)
Q total

40

20
Q 1 supply
0
0 20 40 60 80 100
Q 2 mixing (cold)
Controller signal [%]

Fig. 04 Volume flow rates of 3-way valve


6
3-way configuration: In a 3-way mixing valve, the fl uids to be mixed enter the valve via two input ports and the sum of their fl ow exits
through a single output port. The ratio between the fl ow rates through both inlet ports is determined by the stem position. The sum of the
throttling cross-sections on both inlet ports is constant over the entire valve travel. The valve therefore provides a constant volume fl ow at its
outlet port, independent of stem position.

060206_knowhow05_e_IS 8 06.02.2006, 12:49:51 Uhr


Volume flow rates
5
nominal volume flow rate is In principle, this new design design point of the circulator
reduced by 25% in all cases, point can also be achieved with pump remain unchanged. In
resulting in a new design point a conventional hydraulic con- this case, the investment costs
for the circulator pump (Fig. 05) figuration. However, BOA- for the circulator pump and the
Systronic offers a number of other valves cannot be reduced.
INCREASED SUPPLY TEM- benefits.
PERATURE BY PARALLEL • The consultant can size the
SHIFT OR SLOPE MODIFI- consumer installations of the
CATION OF HEATING heating circuit as usual
CURVE • The consultant can use the
benefits offered by BOA-
Thanks to the new design Systronic without changing
point, investment costs for the his planning
circulator pump and the valves • The consultant saves
in the heating circuit can be planning work and thus time
reduced considerably. and costs
• Normally, a circulator
pump with a lower output Slope modification of heat-
rating can be selected ing curve
Benefit: Substantially reduced The controller’ s heating curve
investment costs for the circu- is shifted towards higher supply
lator pump temperatures only if the system
• The nominal diameter of is running under part-load con-
the heating circuit can usually ditions. Depending on the value
be chosen one nominal diam- of the control signal, the control-
eter smaller. ler internally adds an amount
Benefit: Reduced investment ∆T to the supply temperature
costs for piping, shut-off setpoint (slope modification of
valves and strainers, including heating curve). The nominal
insulation. volume flow rate and thus the

100
Volume flow rate Q [%]

Q 1 supply 80
(hot) Q total
60

Q total 40
+
20
Q 2 mixing Q 1 supply Q 2 mixing
(cold)
0
0 20 40 60 80 100

Controller signal [%]

Fig. 05 Reduced volume flow rates of BOA-Systronic

060206_knowhow05_e_IS 9 06.02.2006, 12:49:55 Uhr


6 Circulator pump heads

6 Control IMS valve measures the cuit, the pressure losses in the
Circulator pump heads volume flow rate in the heating consumer installations, balanc-
circuit and thus determines the ing valves, differential pressure
Owing to the hydraulic config- required nominal discharge head control elements, strainers as
uration of conventional mixing of the circulator at the design well as thermostatic and shut-
or injection-type systems, the point. The values obtained are off valves.
circulator pump head cannot be then used to determine the The volume flow rate and dis-
matched to the system control system constant of the heating charge head are shown in nor-
curve. The circulator pump can circuit. As a result, the hydraul- malized representation here.
only react to reduced volume ic resistance of the heating The circulator pump of a mix-
flow rates resulting from the circuit is known, and the control ing or injection-type system can
control function of the thermo- unit knows the circulator head only respond to reduced volume
static valves at the consumer in- required for the individual load flow rates (external heat gain)
stallations. Depending on the conditions. with a constant discharge head,
pump curve selected, the dis- thus saving a certain amount of
charge head either remains The H/Q diagram on page 11 energy.
constant (∆p = constant) or is shows an example of the possi-
reduced accordingly (∆p = ble discharge heads of a differ- NEW DESIGN POINT FOR
variable). ential pressure controlled THE PUMP
pump. The diagram shows the
BOA-SYSTRONIC CON- H/Q data of a pump controlled With BOA-Systronic, parallel
TROLS THE PUMP AS A independently of throughflow shift of the heating curve results
FUNCTION OF THE SYSTEM (∆p = constant) and offers a in the new nominal volume
CURVE OF THE HEATING comparison between a conven- flow rate
CIRCUIT tional system and a system
equipped with BOA-Systronic. Q new = 0.75 · Q old
BOA-Systronic, by means of the
two control valves, adjusts the The design point is represented and, by application of the affin-
volume flow rate as a function by the intersection of the system ity law, yields the associated
of external temperature and curve of the heating circuit with discharge head of the circulator
measures the system curve of the characteristic curve of the pump:
the heating circuit during com- circulator pump. (see equation below)
missioning. As a result, the cir-
culator’s discharge head can be Q new 2
75% 2

matched to the volume flow


(
H new = H old ·
Q old ) (
= 100%·
100% ) ·H old
= 0.56 · H old

rate to be pumped. This is done


by means of the system control The system curve describes the The valve authority of the main
curve (Fig. 6). The system resistance the volume flow has control valve must then be add-
control curve is automatically to overcome, and corresponds ed to this value. It describes the
determined by measuring the to the discharge head required pressure drop at the control
volume flow rate during of the circulator pump. It de- valve, in relation to the differ-
commissioning; it is limited by pends on the length and nom- ential pressure to be produced
the minimum discharge head of inal diameter of the supply and by the pump (overall pressure
the circulator pump. The BOA- return lines in the heating cir- drop in the system). With BOA-

10

060206_knowhow05_e_IS 10 06.02.2006, 12:49:56 Uhr


Circulator pump heads
6
Systronic, valve authority is the BOA-Systronic controlled pump curve set, the discharge
constant over the entire operat- circulator pump moves along head either remains constant
ing range. This correlation is the system control curve. As (∆p=constant) or decreases with
reflected in the system control external temperature rises, the decreasing volume flow rate
curve and explains why the sys- operating point moves towards (∆p=variable). All the familiar
tem control curve runs parallel lower volume flow rates and features of the variable-speed
to the system curve, at a slightly lower discharge heads. pump and the thermostatic
higher level (Fig. 6) valves are retained.
ALL FEATURES OF THE
In our example, a new design VARIABLE SPEED PUMP
point is established for the cir- ARE RETAINED
culator pump: the nominal vol-
ume flow rate is reduced by The diagram also illustrates the
25%, and the nominal dis- effect the control function of
charge head of the circulator the thermostatic valves has on
pump is reduced accordingly. various operating points (exter-
As a result, a circulator pump nal heat load). Under the influ-
with a lower performance rat- ence of external heat load, the
ing can be selected. operating point also moves
along the characteristic curve of
Depending on the external tem- the differential pressure con-
perature, the operating point of trolled pump. Depending on the

P el 1 constant Q1 H1 Q1 H1
= =
P el2 constant Q2 H2 Q2 H2

180
Discharge head H [%]

Chara Operating point, conventional Design point, conventional


o f f ixedc t e r i s t i c c u r v e with external heat load without external heat load
160 speed p
ump P el 11 = 84% Pel 1 = 100%

140

120
External
heat effect
Characteristic curve of
100 variable speed pump ∆p = constant
Design point BOA-Systronic
with external heat load
80 External
P el 21 = 35%
heat effect
Characteristic curve of Design point BOA-Systronic
60 variable speed pump ∆p = constant without external heat load
Operating point BOA-Systronic P el 2 = 45%
ic
part-load, with external heat load External st ron
40 P el 31 = 11% heat effect A -Sy
BO Operating point BOA-Systronic
Characteristic curve of part-load, without external heat load
variable speed pump
20 e P el 3 = 16%
urv
System control curve em c
Syst
0
0 10 20 30 40 50 60 70 80 90 100 110 120

Volume flow rate Q [%]

Fig. 06 Circulator pump heads (example)

11

060206_knowhow05_e_IS 11 06.02.2006, 12:49:57 Uhr


7 Hydraulic balancing of branch circuits

7
Hydraulic balancing of
branch circuits

BOA-Systronic operates the


heating circuit with variable
volume flow rates. The question
therefore arises whether the
branch circuits are hydraulically
balanced for these variable
operating points.

The branch circuits are hydraul-


ically balanced for the design
point (nominal load). This en-
sures adequate heat supply to
the consumer installations in the
individual branch circuits. In
the following, the nominal load
case is indexed N, whereas the Fig. 07 Heating circuit with branch circuits
part-load case is indexed T.
At the design point (nominal mains unchanged. The pressure
The following is to show that load), the differential pressure drop at the valve then only de-
variable volume flow control by at the balancing valve of the pends on the volume flow rate
BOA-Systronic has no influence branch circuit drops as follows: (Q).
on branch circuit balancing.
Differential pressure at
The volume flow rates in branch nominal load:
circuits 1, 2 and 3 are adjusted 1 1 QN 2

by means of balancing valves 2 ( )


∆ pN = · ρ · ζ · w 2 = · ρ · ζ ·
2 A
BV1, BV2 and BV3. What is Equation 1
of interest is the ratio of the
pressure drops at the balancing where ρ is the water density, ζ is The opening cross-section (A)
valves at nominal load the valve’s zeta coefficient, w is and the zeta coefficient (ζ) of
the flow velocity of the water, A the valve remain unchanged.
∆ pN2
(e.g. ) and is the flow cross-section at the
∆ pN1 1 1 2
∆ pT2
throttling point, and Q N is the
2
·ρ·ζ·()
A
= constant = c
part load (e.g. ). volume flow rate at design point.
∆ pT1 Equation 2

Hydraulic balancing of the Differential pressure at the bal-


branch circuit is performed for ancing valve therefore only
the design point (nominal load). depends on a factor (c) which
After that, the throttling pos- describes the valve and the vol-
ition of the balancing valve re- ume flow rate (Q):

12

060206_knowhow05_e_IS 12 06.02.2006, 12:49:57 Uhr


Hydraulic balancing of branch circuits
7
Differential pressure at Differential pressure BV1
nominal load:
∆ pT1 = F2 ·∆ p N1
∆ pN = c · Q 2 N

Equation 3 Equation 6

Under part-load conditions, the


differential pressure at the bal- Differential pressure BV2
ancing valve (BV) is reduced as ∆ pT2 = F2 ·∆ p N2
follows:
Equation 7
Differential pressure at
parl load:
∆ pT = c ·(F·Q N ) 2 Differential pressure BV3
Equation 4 ∆ pT3 = F2 ·∆ p N3

where factor F describes the Equation 8


part-load level (0-100)%.
Inserting equation 3 in equation Therefore, the ratios of these
4 yields differential pressures are as
follows:

∆ pT = F2 ·∆ p N
∆ pT2 ∆ pN2
Equation 5 =
∆ pT1 ∆ pN1

resulting in the following differ- Equation 9


ential pressures at nominal and
part-load for branch circuits 1,
2 and 3:

Conclusion

The same law governing differential pressures in


the branch circuits can be established for part load
conditions as for nominal load conditions. It is
therefore ensured that the branch circuits are actually
supplied with the necessary volume flow rate for the
thermal output required.

13

060206_knowhow05_e_IS 13 06.02.2006, 12:49:59 Uhr


8 Differential pressure control elements

8 circulator pump is immediately higher excess discharge head at


Differential pressure reduced by the differential pres- the thermostatic valve (∆p 2 ), as
control elements sure control valve in many cases! does the fixed speed pump
By way of example, the H/Q (∆p1).
If external heat is acting on a diagram in fig. 08 compares the
room – sunlight, for instance – influence of external heat gain
the thermostatic valves will re- on the operating behaviour of a
duce the volume flows passing fixed speed circulator pump, a
through the radiators in this differential pressure controlled
room. If volume flow rates are circulator pump of a mixing or
reduced, the circulator pump of injection-type system, and a
a conventional heating system differential pressure controlled
will either be operated with a pump controlled by BOA-Sys-
constant or variable discharge tronic. The diagram shows that
head, depending on the set the BOA-Systronic controlled
pump curve. The reduced vol- pump generates only little ex-
ume flow rate will result in a cess differential pressure, which
reduced pressure drop in the drops at the thermostatic valve.
piping. The excess differential
pressure produced by the circu- NO DIFFERENTIAL
lator pump can only drop at the PRESSURE CONTROL
thermostatic valve, which caus- ELEMENTS REQUIRED
es considerable flow noise or
whistling. Differential pressure This differential pressure results
control elements are often used from the hydraulic resistance of
to prevent this. Their function the heating circuit and the dis-
limits the increase in differen- charge head of the circulator
tial pressure across the thermo- pump controlled by BOA-
static valve, thus preventing Systronic. The differential
flow noise. In conventional sys- pressure controlled pump of a
tems, therefore, part of the dis- mixing or injection-type system,
charge head provided by the by contrast, produces a much

Conclusion

BOA -Systronic provides the circulator pump with the discharge head required for
the actual load conditions. No excess discharge heads are produced under part load
conditions, nor flow noises at the consumers. Expensive differential pressure control
elements for balancing the heating circuits can be dispensed with. For hydraulic balancing
of branch circuits, they can even be replaced by lower priced balancing valves.

14

060206_knowhow05_e_IS 14 06.02.2006, 12:49:59 Uhr


Commissioning
9
9 BOA-Systronic automatically de- this procedure has been com-
Commissioning termines the circulator’s discharge pleted, the system knows the
head required for the design circulator’s discharge head for
If parallel shift of the heating point. To do so, the circulator the design point and the system
curve is planned, BOA-Systronic pump is started up with its constant of the heating circuit,
will always reduce the volume minimum discharge head. A and thus its system curve.
flow rate for the design point by corresponding volume flow rate Therefore, the correlation be-
25 %, based on the volume flow is produced in the heating cir- tween discharge head and vol-
rate the system designer has cal- cuit, which is measured by the ume flow rate for the heating
culated for a conventional mixing BOA-Control IMS valve at the circuit is known.
or injection-type system. main feed manifold. The
BOA-Systronic has to be config- BOATRONIC M- 420 measur- BOA-SYSTRONIC AUTO-
ured prior to commissioning. ing computer converts this MATICALLY DETERMINES
This is done by entering the value measured value into an analog THE OPTIMUM PUMP HEAD
of the volume flow rate deter- (4-20)mA current signal and
mined for a conventional mixing transmits it to the Systrobox With the data stored for the
or injection-type system into the control unit, where it is com- volume flow rate at part load
commissioning software, together pared against the value for the conditions, BOA-Systronic then
with the nominal system diam- (new) nominal volume flow generates the system control
eter of BOA-Systronic (param- rate. The circulator’s discharge curve as well as the two valve
eterization). The nominal diam- head is increased step by step, control curves.
eter of the BOA-Control IMS until the difference between set-
measurement valve corresponds point and measured value falls
to this nominal system diameter. below a certain limit. When

180
Discharge head H [%]

Operating point, conventional, Operating point, conventional,


160 fixed speed pump variable speed pump
with external heat load with external heat load
H1
140
External Design point, conventional
heat effect without external heat load
120

100 H2
External
∆p1 heat effect
Operating point Operating point
80 BOA-Systronic BOA-Systronic rve
cu
tem
variable speed pump variable speed pump
∆p2 s
60
with external heat load without external heat load Sy
c
oni
External
y str
40 heat effect A-S
BO
H3 ∆p
3
Hydraulic
20
resistance
of heating circuit
0
0 10 20 30 40 Q part-load 60 70 Q NS 80 90 QN 110 120

Volume flow rate Q [%]

Fig. 08 Excess circulator pump heads (example)


Q Design point of heating circuit with 3-way valve ∆p1 Differential pressure at thermostatic valve (fi xed speed pump)
N
Q Design point of heating circuit with BOA-Systronic ∆p2 Differential pressure at thermostatic valve
N Sys
Q Part load condition (example) (variable speed pump ∆p=const.)
T
∆p3 Differential pressure at thermostatic valve (BOA-Systronic)
15

060206_knowhow05_e_IS 15 06.02.2006, 12:49:59 Uhr


10 Practical testing

10
Practical testing

10.1 Plant

BOA-Systronic has been in use


in the office building of DeTe-
Immobilien in Heidelberg, Ger-
many, since 2001. The heating
water is produced in a two-
boiler system with a thermal
output of approx. 2 MW. Each
boiler is equipped with a
2-stage burner. The main feed
manifold is connected directly Fig. 09 Two-boiler system
to the boilers (without hydraul-
ic separator) and feeds 4 heat- sections, any disturbances in CONTROLLER TRANSMITS
ing circuits plus several other room temperature (external CONTROL SIGNAL TO BOA-
hot water circuits. Four heating heat gain) are re-adjusted by SYSTRONIC
controllers control supply tem- means of the radiators’ thermo-
perature in the four building static valves. Both circulator The main control valve is
sections. The controllers are pumps are differential pressure supplied in nominal system
fitted in a separate control controlled (∆p = constant). diameter DN50 (Fig. 15). Fitted
cabinet in the plant room. Table 01 demonstrates the with an EA-C40 actuator, it is
benefits of BOA-Systronic by installed in the supply line of the
FOUR HEATING CIRCUITS comparing the performance heating circuit. The designation
HEAT THE BUILDING data of the two heating circuits. EA-C40 means that this actua-
tor has an actuation force of
BOA-Systronic supplies heat to
the West wing of the building.
The East wing is equipped with
a conventional mixing system.
Both building sections require
the same heat output. The
“Stat. Heizung West” heating
controller transmits its control
signal (for the control valve) to
the control unit of BOA-Sys-
tronic, where it is converted
into the load-dependent dis-
charge head setpoint for the cir-
culator pump and two separate
control signals for the two con-
trol valves. In both building Fig. 10 Return manifold

16

060206_knowhow05_e_IS 16 06.02.2006, 12:50:00 Uhr


Practical testing
10
4,000 N. The photo shows the al-position feedback (2-10)VDC.
terminal box for cable connec- When combined with BOA-Sys-
tion and the black handwheel tronic, it is configured with a
for emergency operation in the linear valve characteristic and
event of a power failure. The fed by an analog (2-10) VDC
smart actuator makes it pos- voltage signal.
sible to select either a linear or
an equal-percentage valve EA-C40 FOR NOMINAL
characteristic. Configuration is SYSTEM DIAMETERS FROM
performed exclusively by means DN 65
of the parameterization soft-
ware. The mixing valve is always se-
lected two nominal diameters
smaller than the nominal sys-
tem diameter and replaces the
swing check valve in the mixing
Fig. 11 Control cabinet line (Fig. 16).

Parameter East wing West wing Unit


(3-way configuration) (BOA-Systronic)
Thermal output 300.00 300.00 kW
Temperature differential 20.00 27.00 K
Volume flow rate (max.) 13.00 9.75 m³/h
Discharge head (max.) 8.00 4.50 m
Circulator pump Riotec 65 -100 Riotec 50 -100
Differential pressure control ∆ p = constant ∆ p = constant
Nom. diameter of main heating circuit DN65 DN50
Parallel shift of heating curve No +3.5 K

Table 01: Performance data of


main feed circuits

2 ACTUATOR TYPES FOR


DIFFERENT NOMINAL
SYSTEM DIAMETERS

The actuator can either be


supplied with 24 VAC/DC or
230 VAC/DC. As standard, it is
capable of processing 230/24
VAC 3-point control signals as
well as analog (0/4-20) mA cur-
rent or (0/2-10) VDC voltage Fig. 12 Heating controllers for Fig. 13 Main feed manifold,
signals and features active actu- West and East wings West and East wings

17

060206_knowhow05_e_IS 17 06.02.2006, 12:50:09 Uhr


10 Practical testing

In the event of a power failure, dressed by an analog voltage


the valve can be actuated by signal (2-10) VDC.
means of an Allen key.
The Systrobox is the “heart” of
EA-B12 FOR NOMINAL BOA-Systronic. The control
SYSTEM DIAMETERS UP TO unit stores the two valve control
DN50 curves for the main control
valve and the mixing valve, as
For applications other than well as the system control curve
BOA-Systronic, this actuator for the pump.
also offers the option of setting
a linear or equal-percentage SYSTROBOX IS THE
valve curve. “HEART” OF BOA-
A five-core cable supplies the SYSTRONIC. IT RECEIVES
actuator with supply and con- AND TRANSMITS ALL
trol voltage. As the terminals SIGNALS.
Fig. 14 Main feed circuit with are located inside the actuator,
BOA-Systronic the cover must be removed prior The control unit is powered by
to installation. Operating on a 24 VAC. It contains the inter-
It adjusts the volume flow rate 24 VAC/DC voltage supply, face for powering the BOA-
in the mixing line in accordance the actuator requires an ana- TRONIC measuring computer
with the valve control curve log (0/2-10)V control signal and for receiving and process-
stored in the Systrobox. In this and provides (2-10)VDC active ing its measuring signal. As in-
case, it is of nominal size DN32 actual-position feedback. When terface with the (higher-level)
and therefore equipped with ac- combined with BOA-Systronic, controller, it receives the con-
tuator type EA-B12, which has it is configured with a linear troller’s control signal and
an actuating force of 1,200 N. valve characteristic and ad- transmits the three control sig-

Fig. 15 Main control valve Fig. 16 Mixing valve BOA-Systronic


BOA-Systronic

18

060206_knowhow05_e_IS 18 06.02.2006, 12:50:14 Uhr


Practical testing
10
nals simultaneously to the 10.2
pump and the control valves. Circulator selection 8
k heating circuit = = 0.0473
132
for BOA -Systronic
The control valves receive a Equation 11
separate analog (2-10)VDC The following analysis shows
control signal each, whereas the that the Riotec 50-100 circula- The example is based on a tem-
integrated FTT10 transceiver tor pump selected, which is perature differential of ∆T =
sends the currently required controlled by BOA-Systronic, is 20K, and the heating curve of
discharge head as digital signal oversized. The system curve of the higher-level controller was
to the pump via LON bus. A the heating circuit is calculated shifted by 3.5K (parallel shift),
second pair of integrated LON as the quotient of the pump resulting in a new design point:
terminals serves to transmit the head (H) and the square of the the nominal volume flow rate is
LON output variables of BOA- volume flow rate (Q): reduced by 25%.
Systronic as well as any other (Equation 12: see below)
nodes of the LON bus to a H
k heating circuit =
higher-level building manage- Q2 For selecting the circulator
ment system. Equation 10 pump operated with BOA-Sys-
tronic, the required discharge
Systrobox comes pre-assembled The volume flow rate for the de- head is calculated for the design
to the main control valve as sign point of the conventionally point, including equations 2
standard. However, it can also equipped main feed circuit is and 3.
3
be mounted on the mixing Qnom = 13m /h. At this volume (Equation 13: see below)
valve, as in the present case, or flow rate, the Riotec 65-100
in the control cabinet. pump can provide a maximum This new design point [Q/H] =
head of approx. H=8m (see [9.75m 3 /h / 4.5m] can be han-
pump catalogue). For this max- dled by a Riotec 50-60 pump.
imum case, the following sys- For the present example, invest-
tem constant is calculated for ment costs for the circulator
the heating circuit: pump are reduced as follows:

Q N, Systronic = 0.75 · Q N,conv = 0.75 · 13m 3 /h = 9.75m 3 /h

Equation 12

H N,Systronic = k heating circuit · Q2 N,Systronic = 0.0473 · 9.75m 2 = 4.5m

Equation 13

Pump Catalogue price 2005 [€] Difference [€]


Riotec 65 – 100 1,825.11
Riotec 50 – 60 1,223.20 602.91
Fig. 17 Control unit of BOA-
Systronic (Systrobox Table 02: Reduced investment costs for circulator pump

19

060206_knowhow05_e_IS 19 06.02.2006, 12:50:23 Uhr


10 Practical testing

10.3
Measurements
Heating circuit East Heating circuit West
(3-way mixing configuration) (BOA-Systronic)
To verify the function of the
External temperature External temperature
BOA-Systronic system, the
Volume flow rate at main feed manifold Volume flow rate at main feed manifold
following quantities were
Differential pump pressure Differential pump pressure
measured, among others. (Table 03)
Electrical power input Electrical power input

Measurements were taken on Tab. 03: Measured quantities


545 days in the period from
2000 to 2002. The measured measuring period 2000 to temperature of the heating
values were recorded at two- 2002. The diagram shows an system is [(-12°C) – (+16°C)] =
minute intervals, resulting in average external temperature of 28°C. The temperature differ-
711 values per day (24 hours), approx. 10°C in the period ence between the design point
from which the day mean monitored. Depending on the and the average temperature is
values were calculated for each location, the heating circuits are [(-12°C) – (+10°C)] = 22°C.
measured quantity. selected for an external temper- The ratio between both values
ature of approx. –12°C to –15°C. is 22/28 = 0.79. This means
Regulations stipulate that the that in the monitored period
10.4 building must be heated until both heating circuits on average
External temperature the external temperature only require about 21% of the
reaches approx. 16°C. The tem- thermal output they were se-
The external temperatures perature difference between the lected for. This theory should
measured were plotted for the design point and the switch-off be confirmed by a comparison

External temperature – Heidelberg test installation – Average temp. 10°C (approx)


35
External temperature [°C]

30

25

20

15

10

-5

-10
1. Nov 00

1. Dec 00

31. Dec 00

30. Jan 01

1. Mar 01

31. Mar 01

30. Apr 01

30. May 01

29. Jun 01

29. Jul 01

28. Aug 01

27. Sep 01

27. Oct 01

26. Nov 01

26. Dec 01

25. Jan 02

24. Feb 02

26. Mar 02

25. Apr 02

25. May 02

24. Jun 02

24. Jul 02

23. Aug 02

22. Sep 02

22. Oct 02

Years
External temperature

Fig. 18 External temperatures measured at the test installation in 2000 – 2002

20

060206_knowhow05_e_IS 20 06.02.2006, 12:50:25 Uhr


Practical testing
10
of the volume flow rates meas- required volume flow rate Qnom heating circuit by BOA-Systronic
ured, the differential pump for the design point is calculat- during the utilization period is
pressures and the pump power ed as follows: considerably smaller than the vol-
consumption of both systems.
Pth 300
Qnom = = m 3 /h = 13m 3 /h.
10.5 1.163 · ∆ T 1.163 · 20
Volume flow rates Equation 14

The conventional, mixing-type This value is confirmed by the ume flow rate the conventional,
system must provide a thermal measurements (Fig. 19). Irrespect- mixing-type system provides to its
output Pth = 300 kW at the de- ive of its degree of opening, the heating circuit. Fig. 19 shows that
sign point. Based on a tempera- three-way control valve of the the measured nominal volume
ture differential ∆T = 20K, the conventional, mixing-type system flow rates supplied by the conven-
always supplies the nominal vol- tional, mixing-type system do not
ume flow rate to the heating circuit quite reach the theoretical, calcu-
(constant-flow system). BOA- lated values. This is due to the
Systronic, by contrast, adjusts the control function of the thermostat-
resulting volume flow rate in the ic valves under the influence of
main feed circuit depending on the external heat input to the heating
opening degree of the two control circuit. The equation
valves and thus depending on the t2
control signal issued by the heat- water volume flow = ∫ Q(t) dt
ing controller. As expected, the t1
volume flow rate supplied to the is used to calculate the amounts

Volume flow rates – Heidelberg test installation – Savings by BOA-Systronic approx. 65%

16
Volme flow rate [m3/h]

14

12

10

0
1. Nov 00

1. Dec 00

31. Dec 00

30. Jan 01

1. Mar 01

31. Mar 01

30. Apr 01

30. May 01

29. Jun 01

29. Jul 01

28. Aug 01

27. Sep 01

27. Oct 01

26. Nov 01

26. Dec 01

25. Jan 02

24. Feb 02

26. Mar 02

25. Apr 02

25. May 02

24. Jun 02

24. Jul 02

23. Aug 02

22. Sep 02

22. Oct 02

Years

3-way configuration BOA-Systronic

Fig. 19 Volume flow rates measured at the main feed manifold in 2000 – 2002

21

060206_knowhow05_e_IS 21 06.02.2006, 12:50:25 Uhr


10 Practical testing

of water (volume flow rates) At identical thermal output,


pumped through the two heat- BOA-Systronic was shown to
ing circuits, respectively. The pump only 40 % of the water
mean values of the volume flow volume through the heating cir-
rates measured in the two heat- cuit, compared to the conven-
ing circuits are calculated. tionally equipped heating circuit.

Measured Quantity Volume flow rate (Q) Ratio


Heating circuit 3-way configuration BOA-Systronic Q Systronic /Q 3 - way configuration
3 3
Unit [m /h] [m /h]
Mean value 11.2 3.2 0.29

Table 4: Analysis of volume flow rates in 2000-2002

10.6 With BOA-Systronic, the pump


Differential pressures is operated on average at only
of the pumps about 66% of the nominal
discharge head at design point.

Measured Quantity Differential pressure (H) Ratio


Heating circuit 3-way configuration BOA-Systronic H Systronic /H 3 - way configuration
Unit [m] [m]
Mean value 4.4 2.9 0.66

Table 5: Analysis of differential pump pressures in 2000 -2002

Pump differential pressures – Heidelberg test installation – Savings by BOA-Systronic approx. 37%

800
Pump differential pressures [mbar]

700

600

500

400

300

200

100

0
1. Nov 00

1. Dec 00

31. Dec 00

30. Jan 01

1. Mar 01

31. Mar 01

30. Apr 01

30. May 01

29. Jun 01

29. Jul 01

28. Aug 01

27. Sep 01

27. Oct 01

26. Nov 01

26. Dec 01

25. Jan 02

24. Feb 02

26. Mar 02

25. Apr 02

25. May 02

24. Jun 02

24. Jul 02

23. Aug 02

22. Sep 02

22. Oct 02

22
Years

3-way configuration BOA-Systronic

Fig. 20 Differential pressures of the circulators measured in 2000 – 2002

22

060206_knowhow05_e_IS 22 06.02.2006, 12:50:26 Uhr


Practical testing
10
10.7
Pump input
power

The pump input power, and heads, the pump draws much
thus its power consumption, is less power from the electricity
proportional to the product of grid. BOA-Systronic was shown
the discharge head and volume to save approx. 70% in
flow rate. As BOA-Systronic electrical energy.
operates the pump at reduced
volume flow rates and discharge

Measured quantity Pump input power (P) Ratio


Heating circuit 3-way configuration BOA-Systronic PSystronic /P3 - way configuration
Unit [W] [W]
Mean value 561 184 0.33

Table 6: Savings in pump power consumption

Pump input power – Heidelberg test installation – Savings by BOA-Systronic approx. 70%

900
Pump input power [W]

800

700

600

500

400

300

200

100

0
1. Nov 00

1. Dec 00

31. Dec 00

30. Jan 01

1. Mar 01

31. Mar 01

30. Apr 01

30. May 01

29. Jun 01

29. Jul 01

28. Aug 01

27. Sep 01

27. Oct 01

26. Nov 01

26. Dec 01

25. Jan 02

24. Feb 02

26. Mar 02

25. Apr 02

25. May 02

24. Jun 02

24. Jul 02

23. Aug 02

22. Sep 02

22. Oct 02

Years

3-way configuration BOA-Systronic

Fig. 21 Pump power input in 2000 – 2002

Conclusion
In our example, both heating circuits on average require only 21% of the thermal
output at design point. By comparison, BOA - Systronic consumes only about 30 % of
the electricity required by the conventional set- up ( here : 3 - way mixing system) .

23

060206_knowhow05_e_IS 23 06.02.2006, 12:50:27 Uhr


11 Payback period for BOA - Systronic

11 valves and the pump as well configuration, the differences


Payback period as automatic hydraulic bal- depending on the nominal sys-
for BOA -Systronic ancing at the main feed mani- tem diameter of the main feed
fold. circuit (table 07).
11.1
Control valve invest- Items (1) to (5) can also be In the present example, a main
ment and energy planned and achieved in a con- feed circuit with a thermal out-
savings ventional system by increasing put of 300 kW was equipped
the temperature differential at with BOA-Systronic of nominal
With BOA-Systronic, the nom- design point. Items (6) and (7), system diameter DN50, where-
inal diameter of the heating cir- however, can only be realized as a nominal diameter of DN65
cuit components can be smaller with BOA-Systronic. was selected for the convention-
than usual. This is due to the al set-up of identical thermal
combined effect of increased To compare the prices of the output (table 08).
temperature differential (differ- two systems, the average price
ence between supply and return for a conventional, mixing-type A simulation (version 1.21) was
temperature) and reduced vol- system of nominal diameter used to estimate the energy
ume flow rates at design point, DN65 was determined on the costs incurred for the glandless
so that basis of the catalogue prices Riotec 50-100 pump during the
1. the main feed pipe is one given by 5 competitors. The heating period (table 10). Com-
nominal diameter smaller mixing-type configuration com- pared to the average price of a
2. the shut-off valves in the prises the following compo- mixing-type system, the invest-
main feed circuit are one nents: ment costs for BOA-Systronic
nominal diameter smaller • 3-way control valve would be approx. € 402 higher
3. the strainers in the main • swing check valve in the mix- in this case. If this extra price is
feed circuit are one nominal ing line deducted from the electricity
diameter smaller • balancing valve savings realized per heating
4. a smaller circulator pump The gross price of BOA-Sys- period, investment in BOA-
can be chosen tronic, by contrast, is somewhat Systronic will pay back after
5. the measurement and con- higher than the average price of roughly one year.
trol valves are one nominal a conventional mixing-type
diameter smaller
6. differential pressure control- Nominal Average extra price compared to
system diameter 3-way mixing configuration in [%]
lers for balancing the heat-
ing circuits are not required DN25 to DN50 11 %

7. commissioning costs are re- DN65 to DN80 4%

duced thanks to automatic DN100 to DN150 13 %

initialization of the control Tab. 07: Average extra prices for BOA-Systronic

Heating circuit Unit Value Difference


Average gross price of 3-way mixing configuration, DN65 (prices of 2005) € 1,673
Gross price of BOA-Systronic, DN50 (prices of 2005) € 1,858
Gross price of LON module for Riotec pump, pre -initialized € 217 +402

Tab. 08: Extra price for BOA-Systronic with Riotec pump (example: DN50)

24

060206_knowhow05_e_IS 24 06.02.2006, 12:50:27 Uhr


Payback period for BOA - Systronic
11
Heating circuit Unit Value Difference
Average gross price of 3-way mixing configuration, DN65 (prices of 2005) € 1,673
Gross price of BOA-Systronic, DN50 (prices of 2005) € 1,858
Gross price of LON -module forRio - Eco pump, non-initialized € 187 +372

Table 09: Extra price for BOA-Systronic with Rio-Eco pump (example: DN 50)

Cost factor Unit Value Difference


Average price of electricity € /kWh 0.11
Average operating hours per heating period h 6,800
Average efficiency η of Riotec circulator pump % 35
Average pump power consumption/heating period; conv., mixing-type system DN65 kWh 5,000
Average pump power consumption/heating period; BOA-Systronic DN50 kWh 1,200 -3,800
Average price of electricity/heating period; conv., mixing-type system DN65 € 548
Average price of electricity/heating period; BOA-Systronic DN50 € 131 - 417

Table 10: Energy costs in fi rst year (example: DN 50)

11.2 If the extra price for BOA- present hourly rates (2005), this
Investment costs for Systronic is deducted from the results in an additional € 45
heating circuit with reduced investment costs saved.
Riotec pump (€ 1,059–€ 402), the investment
costs for the main feed circuit Investment in BOA-Systronic
By utilizing all saving potentials will be reduced to € 657 in this would, therefore, pay back im-
offered by BOA-Systronic, the case. In addition, automated mediately, and the investment
investment costs of the present commissioning further reduces and commissioning costs for
heating circuit can be reduced the commissioning costs per the heating circuit would be re-
by € 1,059. heating circuit by one hour. At duced substantially.

Cost factor Unit Difference


(1) Smaller nominal diameter of main feed pipe € -75
(2) 3 shut- off valves of smaller DN in main feed circuit € -123
(3) 1 strainer (standard mesh) of smaller DN in main feed circuit € -29
(4) 1 Riotec 50 - 60 circulator pump instead of Riotec 65 -100 € - 602
(5) Measurement and control valves one DN smaller (BOA-Systronic) € see above
(6) No differential pressure controller required (1 no. per heating circuit, 1.5 -inch) € -230
Sum total of factors (1) to (6) € -1,059

Tab. 11: Reduced investment costs for heating circuit with Riotec pump, example (prices 2005)

25

060206_knowhow05_e_IS 25 06.02.2006, 12:50:28 Uhr


11 Payback period for BOA - Systronic

11.3 If the extra price for BOA-Sys- Investment in BOA-Systronic


Investment costs for tronic is deducted from the re- would, therefore, pay back im-
heating circuit with duced investment costs (€ 933– mediately, and the investment
Rio - Eco pump € 372), the investment costs for and commissioning costs for
the main feed circuit are re- the heating circuit would be
By utilizing all saving potentials duced to € 561 in this case. In reduced substantially.
offered by BOA-Systronic, the addition, automated commis-
investment costs of the present sioning reduces the commis-
heating circuit can be reduced sioning costs per heating circuit
by € 933. by one hour. At present hourly
(Table 12) rates (2005), this saves an addi-
tional € 45.

Cost factor Unit Difference


(1) Smaller nominal diameter of main feed pipe € -75
(2) 3 shut- off valves of smaller DN in main feed circuit € -123
(3) 1 strainer (standard mesh) of smaller DN in main feed circuit € -29
(4) 1 Rio - Eco 40 - 80 circulator pump instead of Riotec 65 -100 € - 476
(5) Measurement and control valves one DN smaller (BOA-Systronic) € see above
(6) No differential pressure controller required (1 no. per heating circuit, 1.5 -inch) € -230
Sum total of factors (1) to (6) € -933

Table 12: Reduced investment costs for heating circuit with Rio-Eco pump, example (prices 2005)

11.4
Total savings compari -
son Riotec / Rio - Eco

In the present example, the


Rio-Eco pump could be expect-
ed to pay back after approxi-
mately three years, compared to
the Riotec pump.

26

060206_knowhow05_e_IS 26 06.02.2006, 12:50:28 Uhr


Payback period for BOA - Systronic
11
Riotec (η =35%) Rio - Eco (η =50%)

Reduced investment costs for heating circuit (1) – (6) [€]

Reduced investment costs for heating circuit (1) – (6) [€]


Reduced commissioning costs for heating circuit [€]

Reduced commissioning costs for heating circuit [€]


Extra price for BOA-Systronic [€]

Extra price for BOA-Systronic [€]


Interest on savings (3% ) [€]

Interest on savings (3% ) [€]


Reduced operating costs [€]

Reduced operating costs [€]

Price of electricity [€ / kWh]

Pump operating hours [h]


Savings plus interest [€]

Savings plus interest [€]


Savings [€]

Savings [€]
Period

Year 01 -1,059 402 -45 -417 -1,119 -34 -1,503 -933 372 -45 - 456 -1,062 -32 -1,094 0,11 6,800

Year 02 -455 -1,608 -48 -1,656 - 498 -1,592 - 48 -1,640 0.12 6,800

Year 03 -455 -2,111 -63 -2,174 - 498 -2,138 - 64 -2,202 0.12 6,800

Year 04 -493 -2,667 -80 -2,747 -539 -2,741 - 82 -2,283 0.13 6,800

Year 05 -493 -3,240 -97 -3,337 -539 -3,362 -101 -3,463 0.13 6,800

Year 06 -531 -3,868 -116 -3,984 -581 - 4,044 -121 - 4,165 0.14 6,800

Year 07 -531 -4,515 -135 -4,651 -581 - 4,746 -142 - 4,889 0.14 6,800

Year 08 -569 -5,220 -157 -5,376 - 622 -5,511 -165 -5,676 0.15 6,800

Year 09 -569 -5,945 -178 -6,124 - 622 - 6,298 -189 - 6,487 0.15 6,800

Year 10 -607 -6,731 -202 -6,933 - 664 -7,151 -215 -7,365 0.16 6,800

Year 11 -607 -7,540 -226 -7,766 - 664 - 8,029 -241 - 8,270 0.16 6,800

Year 12 -645 -8,411 -252 -8,663 -705 - 8,975 -269 -9,244 0.17 6,800

Year 13 -645 -9,308 -279 -9,588 -705 -9,949 -298 -10,248 0.17 6,800

Year 14 -682 -10,270 -308 -10,578 -747 -10,995 -330 -11,325 0.18 6,800

Year 15 -682 -11,260 -338 -11,597 -747 -12,072 -362 -12,434 0.18 6,800

Year 16 -720 -12,317 -370 -12,687 -788 -13,222 -397 -13,619 0.19 6,800

Year 17 -720 -13,407 -402 -13,809 -788 -14,407 - 432 -14,839 0.19 6,800

Year 18 -758 -14,567 -437 -15,004 - 830 -15,669 - 470 -16,139 0.20 6,800

Year 19 -758 -15,762 -473 -16,235 - 830 -16,969 -509 -17,478 0.20 6,800

Year 20 -758 -16,993 -510 -17,503 - 830 -18,308 -549 -18,857 0.20 6,800

Table 13: Outline of costs expected in 20 years of useful life

27

060206_knowhow05_e_IS 27 06.02.2006, 12:50:29 Uhr


11 Payback period for BOA - Systronic

-1000

-2000

-3000

-4000

-5000

-6000

-7000

-8000
Savings [€]

-9000

-10.000

-11.000

-12.000

-13.000

-14.000

-15.000

-16.000

-17.000

-18.000

-19.000

-20.000

-21.000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Years [a]

Riotec pump: Savings plus interest (parallel shift) Rio-Eco pump: Savings plus interest (parallel shift)
Riotec pump: Savings plus interest (slope modification) Rio-Eco pump: Savings plus interest (slope modification)

Fig. 22 Savings realized by Riotec and Rio-Eco pumps with slope modifi cation and parallel shift (example)

Period [a] Reduced costs Unit Riotec Rio - Eco Difference


Investment and commissioning € -702 - 606 96
Pump operation € -2,313 -2,530 -217
5 Interest on savings (3 %) € -322 -327 -4
Total € -3,337 -3,463 -125
Annual savings € - 667 - 693 -25
Investment and commissioning € -702 - 606 96
Pump operation € -5,120 -5,600 - 480
10 Interest on savings (3 %) € -1,111 -1,159 - 49
Total € - 6,933 -7,365 - 433
Annual savings € - 693 -737 - 43
Investment and commissioning € -702 - 606 -96
Pump operation € - 8,381 -9,168 -787
15 Interest on savings (3 %) € -2,514 -2,660 -146
Total € -11,597 -12,434 - 837
Annual savings € -773 - 829 -56
Investment and commissioning € -702 - 606 -96
Pump operation € -12,095 -13,234 -1,139
20 Interest on savings (3 %) € - 4,706 -5,017 -311
Total € -17,503 -18,857 -1,354
Annual savings € - 875 -943 - 68

Tab. 14: Total savings

28

060206_knowhow05_e_IS 28 06.02.2006, 12:50:29 Uhr


References
12
12
References

Since being released for sale in


2003, BOA-Systronic has been
in operation in many heating
systems in public and industrial
buildings throughout Germany.

The photo below shows three


heating circuits equipped with
BOA-Systronic systems of
nominal diameter DN32.

Fig. 23 Heating circuits with BOA-Systronic DN32

29

060206_knowhow05_e_IS 29 06.02.2006, 12:50:30 Uhr


13 Conclusion

13 pressure control valves for bal- tions are prevented, and flow
Conclusion ancing the heating circuits are noises at the consumer points
not required. They can be re- are avoided.
BOA-Systronic reduces operat- placed by balancing valves, BOA-Systronic is gentle on the
ing costs. which are less expensive. Even environment.
in heating circuits already
An analysis of load profiles in equipped with a LON-compat- Electricity is something you
heating systems revealed that ible variable speed pump, in- cannot produce and store for
heating circuits operate under vestment in BOA-Systronic will later use, but it must be avail-
part-load conditions for more pay back in less than two years. able at the exact moment when
than 95% of their operating it is needed. Burning fossil fuels
time. From this finding, it is BOA-Systronic reduces the produces CO2 emissions of
safe to conclude that in conven- commissioning costs for the roughly 0.53 kg per 1 kWh of
tional mixing or injection-type heating circuit. electrical energy produced.
systems cold return water is be- Thanks to the drastic reduction
ing circulated through the heat- The circulator pump and the in power consumption, BOA-
ing circuit most of the time. control valves are initialized Systronic therefore makes a
BOA-Systronic, by contrast, automatically. Static balancing positive contribution to envir-
provides only the volume flow at the main feed manifold is onmental protection.
actually required and can thus performed automatically by the
save an average of 70% electri- pump. The hydraulic operation
city costs for the circulator pump of the heating circuit is opti-
over the heating period, which mized. The system immediately
– depending on the thermal detects any air in the piping and
output of the heating circuit – thus prevents unnecessary com-
may amount to several hun- missioning work. Altogether,
dreds of Euros in electricity the costs for heating circuit
savings per year. commissioning are reduced.

BOA-Systronic reduces the in- BOA-Systronic offers increased


vestment costs for the heating comfort of use.
circuit.
The hydraulic operation of the
In new or replacement installa- heating circuit is optimized
tions, the investment costs for thanks to substantially reduced
the main feed circuit can be re- discharge heads and volume
duced without modifying the flow rates. Excessive discharge
original planning. Differential heads under part-load condi-

30

060206_knowhow05_e_IS 30 06.02.2006, 12:50:32 Uhr


List of figures

Fig. 1 Hydraulics schematics of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4


Fig. 2 Comparison of systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Fig. 3 BOA-Systronic components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fig. 4 Volume flow rates of 3-way valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fig. 5 Reduced volume flow rates of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fig. 6 Circulator pump heads (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fig. 7 Heating circuit with branch circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Fig. 8 Excess circulator pump heads (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fig. 9 Two-boiler system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fig. 10 Return manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fig. 11 Control cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fig. 12 Heating controllers for West and East wings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fig. 13 Main feed manifold, West and East wings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fig. 14 Main feed circuit with BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fig. 15 Main control valve of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fig. 16 Mixing valve of BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Fig. 17 Control unit of BOA-Systronic (Systrobox) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Fig. 18 External temperatures measured at the test installation in 2000 – 2002 . . . . . . . . . . . . . . . 20
Fig. 19 Volume flow rates measured at the main feed manifold in 2000 – 2002 . . . . . . . . . . . . . . . 21
Fig. 20 Differential pressure of the circulators, measured in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . 22
Fig. 21 Pump power input in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fig. 22 Savings realized by Riotec and Rio-Eco pumps with slope modification and parallel shift . . 29
Fig. 23 Heating circuits with BOA-Systronic DN32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

List of tables

Table 1 Performance data of main feed circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17


Table 2 Reduced investment costs for circulator pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 3 Measured quantities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 4 Analysis of volume flow rates in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 5 Analysis of differential pump pressures in 2000 – 2002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 6 Savings in pump power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 7 Average extra prices for BOA-Systronic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 8 Extra price for BOA-Systronic with Riotec pump (example: DN50) . . . . . . . . . . . . . . . . . . 24
Table 9 Extra price for BOA-Systronic with Rio-Eco pump (example: DN 50) . . . . . . . . . . . . . . . . 25
Table 10 Energy costs in first year (example: DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 11 Reduced investment costs for heating circuit with Riotec pump, example (prices 2005) . . . 25
Table 12 Reduced investment costs for heating circuit with Rio-Eco pump, example (prices 2005) . . 26
Table 13 Outline of costs expected in 20 years of useful life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 14 Total savings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

31

060206_knowhow05_e_IS 31 06.02.2006, 12:50:32 Uhr


Fax order form “KSB know-how” series

At your request, we will be pleased to send you all “KSB know-how” brochures previously published as
well as any volumes to be published in the future. All we need is your address and confirmation below.

Company address or stamp:

Company:
Attn.:
Street address:
Post or ZIP code / City / Country:

Please send me the following technical brochures: (tick where applicable)

KSB Know-how KSB Know-how KSB Know-how


Volume 01 Volume 02
Selecting
Centrifugal Pumps Water Hammer Boa-Systronic

... copy and fax this form to:

Fax: +49 (62 33) 86 34 39

KSB Aktiengesellschaft
Johann-Klein-Straße 9
67227 Frankenthal

Tel.: +49 (62 33) 86 21 18


Fax: +49 (62 33) 86 34 39

www.ksb.com

060206_knowhow05_e_IS 32 06.02.2006, 12:50:48 Uhr


Reproduction in whole or in part without express permission of KSB is prohibited.
We look forward to hearing from you.

© KSB Aktiengesellschaft
Your local KSB representative:
11/06
kubbli
0508.023-10

KSB Aktiengesellschaft • Bahnhofplatz 1


91257 Pegnitz (Germany) • www.ksb.com

You might also like