SECONDARY LINE AT 225 VOLTS

LOCATION OF 1Փ TRANSFORMER @ POLE


150 ft. span 50˚C, 60 Hz @ 3.0 ft. spacing

POLE LOAD Current Distance Assumed Computed Actual Computed Ra Xa Xd Xt Ratio AC Vac % R.
NO. S Area Area Drop
KVA Amps ft Vdc CM CM Vdc Cond/ml Cond/ml Cond/ml Cond/ml Factor Drop %
NORTH 1-11 190.94 848.622 299.09 541,469.35 480,489.78 4.26 0.2148 0.0678 0.0264 0.498 2.31 2.157 2.198 4.16
SIDE
13-25 188.66 838.49 302.27 540,694.13 180,231.38 4.25 0.2148 0.0678 0.0264 0.498 2.31 2.157 2.198 4.15
SOUTH
SIDE

18
USE: USE 2 SETS OF 3 – 477 000 CM ( ) ACSR wire for Pole 1 to 11
1

18
USE: USE 2 SETS OF 3 – 477 000 CM ( ) ACSR wire for Pole 13 to 25
1