You are on page 1of 125

Structural Engineering Testing Hall (SETH)

Civil & Environmental Engineering Department


The Henry Samueli School of Engineering
University of California, Irvine
SETH- Evaluation Report Insteel-ICC-ES05-11

Large-Scale Structural Evaluation of


Insteel 3DTM Expanded Polystyrene
Sandwich Wall Panels Subjected to
Cyclic Shear Tests

Prepared by:
A.S. Mosallam, Ph.D., P.E.
I. M.El-Demirdash
A. Nasr, Ph.D.
A. Elsadek
R. Miraj, Ph.D.

November 2011
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

TABLE OF CONTENTS

PAGE

1. REPORT IDENTIFICATION 4

2. ABSTRACT & EXECUTIVE SUMMARY 6

3. OBJECT STATEMENT 9

4. IDENTIFICATION OF EPS PANEL SYSTEMS 9

4.1 Test Matrix 9

5. DESCRIPTIONS OF SPECIMENS AND APPARATUS 11

5.1 Materials 11

5.2 Walls Test Setup 15

6. DESCRIPTION OF EVALUATION TEST PROGRAM 21

6.1Test Protocol 21

6.2Equipment 23

7. EVALUATION TEST RESULTS 23

7.1 Hand Applied 8’x8’ (H8-1) Wall Specimen (AR=1.0) 23

7.2 Hand-Applied 8’x8’ (H8-2) Wall Specimen (AR=1.0) 28

Page 2 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

7.3 Pneumatically-Applied 8’x8’ (P8-1) Wall Specimen (AR=1.0) 31

7.4 Pneumatically-Applied 8’x8’ (P8-2) Wall Specimen (AR=1.0) 35

7.5 Hand-Applied 8’x6’ (H6-1) Wall Specimen (AR=0.75) 36

7.6 Hand-Applied 8’x6’ (H6NG-2) Wall Specimen (AR=0.75) 39

7.7 Pneumatically-Applied Mortar 8’ X 6’ (P6-1) Wall Specimen (AR=0.75) 43

7.8 Low Strength Hand Applied Mortar 8’ X 6’ (H6L-3) Wall Specimen 46

8. ANALYTICAL PROCEDURES 51

9. CONCLUSIONS AND RECOMMENDATIONS 52

10. APPENDIX (A) 58

11. APPENDIX (B) 64

12. APPENDIX (C) 71

13. APPENDIX (D) 73

14. APPENDIX (E) 75

15. APPENDIX (F) 82

16. APPENDIX (G) 92

17. APPENDIX (H) 106

Page 3 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

1. REPORT IDENTIFICATION

This report was prepared by University of California, Irvine (UCI) Structural Engineering

Testing Hall (SETH) and is a true and accurate record of the structural evaluation of Insteel

Panelmex (Insteel) 3DTM Expanded Polystyrene (EPS) sandwich panels with mortar shells

used as shear walls. All the materials were sampled in accordance to the ICC-ES AC85 and

all Insteel 3D EPS Panel specimens were fabricated at UCI by qualified construction

contractors under the supervision of the Principal Investigator and the SETH staff. Testing

procedures of all specimens followed the specifications set forth by the International Code

Council’s Evaluation Service (ICC-ES) Acceptance Criteria for Concrete Floor, Roof, and

Wall Systems and Concrete Masonry Wall Systems AC (15). The reversed cyclic tests were

performed in accordance with ACI ITG 5.1. It should be noted that Insteel was motivated to

undertake this test program in order to provide evidence that the building system conformed

to and met with the requirements of the 2009 International Building Code (IBC 2009). Data

supporting this goal may be found in the body of the following test report.

Page 4 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

PERSONNEL WORKED ON THE PROJECT:

 Staff
Dr. Rashid Miraj, SETH Manager

 Research Staff
Dr. Selim Pul

Mr. Ibrahim El Demirdash

Mr. Ahmed ElSadek

Mr. Ahmed Nasr

Mr. Naif Ghabban

 Contractors

Mr. Rod Hadrian (Sr.)

Mr. Rod Hadrian (Jr.)

Mr. Rod Murphy

 Principal Investigator
Prof. Ayman S. Mosallam, Ph.D., P.E.

Phone: 714-767-4564

Fax: 949-824-2117

e-mail: mosallam@uci.edu

Page 5 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

2. ABSTRACT& EXECUTIVE SUMMARY

This report provides results of structural evaluation of the Insteel 3D EPS panels used as

shear walls. The objective of this evaluation phase is to gather the necessary verification

information for the formulation of an Insteel Limited ICC-ES Evaluation report to satisfy the

current International Building Code seismic Code requirements (IBC 2009) and to determine

an average value of the Seismic Modification Factor (R) as well as the Safety Factor (SF) of

these wall panels. While the 2009 International Residential Code (IRC 2009) does not

currently reference cementitious skin building systems, the data described in the UCI SETH

Test Report No. 3D-ICC-ES01-11 will serve as a foundation for its inclusion in the revised

Insteel Evaluation Report.

All materials used in fabricating these wall specimens were samples in accordance to the

requirements of ICC-ES Acceptance Criteria for Test Reports AC (85). Fabrication and

mortar applications were performed by certified construction contractors and all the

fabrication steps were witnessed by qualified UCI-SETH laboratory staff. Testing

procedures of all specimens followed the specifications set forth by the International Code

Council’s Evaluation Service (ICC-ES) Acceptance Criteria for Concrete Floor, Roof, and

Wall Systems and Concrete Masonry Wall Systems AC (15). The reversed cyclic tests were

performed in accordance with ACI ITG 5.1.

In this evaluation program, two methods for applying the mortar shell were assessed; namely:

(1) Hand-applied; and (2) Pneumatically-applied. The purpose of using two methods of

mortar applications was to evaluate the difference, if any, in the overall seismic behavior of

Page 6 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

the Insteel 3D EPS panel wall specimens. In addition, large-scale wall specimens with two

aspect (AR) ratios were used, namely; 1 and 0.75. Four of the wall specimens had an aspect

ratio of 1, while the other four wall specimens were fabricated with dimensions portraying an

aspect ratio of 0.75. The purpose of this variation was to evaluate the effect of changing the

geometry of the panels and assess its impact on seismic behavior, ductility and the ultimate

failure modes. Seven of the eight wall specimens tested in this evaluation program were

subjected to both lateral cyclic along and sustained simulated gravity load. One wall

specimen was tested only under lateral cyclic loading, without the presence of a sustained

simulated gravity load. This latter test was carried out in accordance with the

recommendation of ICC-ES Engineers in order to evaluate the effect of applying such loads

on the overall structural performance of Insteel 3D EPS panel walls. Comparisons are made

between different wall specimens and the differences are clearly highlighted.

The results of the evaluation tests showed that all the Insteel 3D EPS panel walls with shear-

dominated aspect ratio of 0.75 behaved in a ductile manner with a Seismic Response

Modification Factor (R-Value) up to 5. Therefore, the use of R=5 as commonly used and

specified in ACI 318 and ASCE-07 is acceptable. The reason is that, as the number of

specimens increases, the R-value approaches the target value. For wall specimens with

higher aspect ratio (e.g. 1.0), a mixed flexure/shear behavior appears resulting in a lower

shear ductility of the walls. This observation is beneficial for the designer, where a reduced

R-value should be used for cases where the walls’ aspect ratios are higher than unity. For

this case, and based on the results of obtained from this evaluation program, a recommended

range of R valuesis3.0 to 3.5.These values were also confirmed by similar test results

conducted at other facilities. In order to upgrade the R-value in such cases (Aspect Ratio

Page 7 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

>0.75), special reinforcement detailing may be required including boundary elements to

enhance the wall ductility. It should be noted that the “direct” method, which is used in

determining the seismic design capacity of walls from experimental data, is believed to be a

better fit for cast-in-place sandwich panels as compared to the indirect method, which is

currently adopted through the use of ITG5 and was specifically developed for precast and

prestressed solid walls that behaves in a very different manner. The loading protocol

described in ITG5 was acceptable for both methods.

With regards to the method of application of the mortar shells, results obtained from the full-

scale fully-reversal loading tests indicated that there was no significant difference between

the overall seismic performances of wall specimens fabricated using hand application and

those using a pneumatic application. On very close examination, the hand applied specimens

fared slightly better than those pneumatically-applied. As such, it may be concluded that a

choice between the two methods may ultimately be driven by project economics and time

constraints.

The evaluation results also indicated that variations in mortar compressive strength had an

apparent effect on the strength of the Insteel 3D EPS panel wall. More significantly,

increases in mortar strength (e.g. 5,000 to 6,000 psi) may have had a greater impact on the

ultimate mode of failure as well as the ductility of the walls. As a result of the study, the

recommended mortar strength is between 2,500 to 3,000 psi.

Page 8 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Finally, it was observed that the removal of the simulated gravity from the combined loading

protocol resulted in both strength and stiffness degradation of the wall specimens when

compared to those tested under combined lateral-cyclic and gravity loading conditions. It

should be noted that the combined loading state is more realistic force model for building

applications, while the cyclic-only loading condition may be suitable to fences, retaining

walls, sea walls and similar applications, where gravity loads are negligible as compared to

cyclic shear forces.

3. OBJECT STATEMENT

Insteel was motivated to undertake this test program in order to provide evidence that the

presented building system conformed to and met with the requirements of the 2009

International Building Code (IBC 2009). In addition, it was hoped that information gathered

would provide the foundation for an Insteel 3D EPS ICC-ES Evaluation report that would

satisfy the current IBC seismic requirements and determine an average value of the Seismic

Modification Factor (R) as well as the Safety Factor (SF) applicable to the panel walls. To

fulfill this objective, tests were performed in accordance to section 4.2.2.6: “Wall Cyclic

Shear Tests ICC-ES AC15” with a loading protocol in accordance to ACI ITG 5.1. ITG 5.1.

4. IDENTIFICATION OF INSTEEL 3D EPS PANEL SYSTEMS

In this evaluation program:

Two methods for applying the mortar shells were used in fabricating the wall

specimens, namely; (i) Hand-applied; (i) Pneumatically-applied;

Two wall panels aspect ratios,1.0 and 0.75 were evaluated;

Page 9 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Different mortar compressive strength were evaluated; and

Two loading cases were also evaluated, namely; (i) Combined cyclic/gravity, and (ii)

Cyclic only (with no gravity load applied).

4.1 Test Matrix

A total of eight (8) wall specimens, fabricated from sampled Insteel 3D EPS panels were

tested. Seven wall specimens were subjected to a combined lateral cyclic/gravity loading

condition, while one wall specimen was tested only under lateral cyclic loading only (i.e.

without the presence of sustained gravity loads). Table (1) presents a summary of the test

matrix used in this evaluation program.

Table (1): Insteel 3D EPS Panel Wall Test Matrix

DIMENSIONS
TEST CODE DESCRIPTION TEST DATE
(L X H X T*)

H8-1 Hand-Applied Mortar 8’X8’X 7” 5/26/2010

H8-2 Hand-Applied Mortar 8’X8’X 7” 7/1/2010

P8-1 Pneumatically-Applied Mortar 8’X8’X 7” 8/8/2010

P8-2 Pneumatically-Applied Mortar 8’X8’X 7” 11/10/2010

H6-1 Hand-Applied Mortar 8’X6’X6.5” 1/24/2011

P6-1 Pneumatically-Applied Mortar 8’X6’X6.5” 2/23/2011

H6NG-2 Hand Applied Mortar (No Axial Load) 8’X6’X6.5” 1/25/2011

H6L-3 Hand-Applied Low-Strength Mortar 8’X6’X6.25” 2/19/2011

*T: is the total wall thickness including the EPS foam and the two mortar shell thicknesses (see Figure 1)

Page 10 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

1. EPS foam core for insulation.


2. Wire mesh on outer sides of
the EPS
3. Welded wire truss diagonals
4. Mortar or Concrete Shell.

Figure (1): Typical Details of Insteel 3D EPS Panel™

5. DESCRIPTIONS OF SPECIMENS AND APPARATUS

5.1 Materials

5.1.1 Reinforcement

Reinforcement within the Insteel 3D EPS panel wall specimens was composed of cold rolled

steel wire, which was used to create the three dimensional (3-D) welded-wire space truss that

consisted of opposing wire mesh face sheets and connecting diagonal wires(refer to Figure

1). Wires used in the wire mesh face sheets are positioned at two inch intervals, so that the

mesh opening on every specimen is 2” x 2”. For all specimens, galvanized 11 gauge wire

(conforming to ASTM A-185 and ASTM A-82) was used to create the meshed face sheets and

galvanized 9 gauge wire was used as the diagonal reinforcement that connected the opposing

face sheets into a rigid three dimensional structure.

Page 11 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

According to ACI 318 section 21.9.2.1, the minimum reinforcement ratio, which, in the

current application, corresponds to the ratio of wire area to cementitious skin area, is 0.0025.

Wall systems that exceed this value satisfy reinforcement requirements for seismic design

specified in Section 21.9 of ACI 318 and Section 1908.1 of IBC 2009. Wall specimens used

in the current experimental program were designed with two different mortar shell

thicknesses. One set consisted of cementitious skins that were 1.25 inches thick and the

second consisted of cementitious skills that were 1.50 inches thick. Calculation of the

minimum reinforcement ratio for the tested walls yielded a value of 0.0036, for walls with

1.25 inch thick shells, and a value of 0.0044, for walls with 1.50 inch thick shells. In both

cases, the calculated value exceeded the minimum reinforcement requirement stated above

and, therefore, validated the use of the Insteel™ 3D EPS panel wall system in seismic

applications.

Similarly, Section 7.12 of ACI 318-08 specifies the minimum reinforcement ratio for floors

and slabs to be 0.0018. Design provisions within section 21.11.7 of ACI 318–08 state that

the reinforcement ratio for floors and roofs must not fall below this value. A more detailed

perspective of this issue is discussed within the ICC/ES draft legacy report ER-5618 and

within the Insteel 3D EPS Panel Product Technical Manual, which supports typical design

details related to floors and slabs. It should be noted that the above referenced provisions are

outside of the scope of this test report, i.e. UCI SETH Test Report No. 3D-ICC-ES01-11.

However, as identified in the previous discussion, typical design scenarios for the Insteel 3D

EPS panel yield reinforcement ratios that easily surpass the minimum requirement. In

Page 12 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

summary, while the ICC/ES draft legacy report ER-5618 and the Insteel 3D EPS Panel

Product Technical Manual provide guidance with regard to a typical construction, all

building design requirements should be ultimately checked and approved by a licensed

professional engineer.

5.1.2 EPS Foam Core

The modified Expanded Poly Styrene (EPS) core had a density of 0.9 lb/ft3, which complied

with ASTM Specification C578-07a. All wall specimens tested in the evaluation program

utilized a foam core with a thickness of 4” (four inches). The width and length of a given

core corresponded to the size of the tested panel. A clear spacing or gap of 0.75 inch was

maintained between the wire mesh surface and the exterior surface of the EPS foam core on

both side of the panel. The purpose of the gap was to ensure that the wire mesh was

properly embedded in the mortar shell during the construction of the finished Insteel 3D

EPS panels.

5.1.3 Mortar

All Insteel 3D EPS panel wall specimens employed cementitious skins (i.e. mortar shells) for

their external covering. Compressive strength properties of the cementitious skin were

established in accordance with the protocols of ASTM C109/C109M–11, Standard Test

Method for Compressive Strength of Hydraulic Cement Mortars, and were specified for each

test specimen. Initially, a total of six different mixes were designed and compressive strength

for each mix was tested to determine its corresponding compressive strength after 7 days, 14

Page 13 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

days and 28 days. Two mortar mixes with 28-day compressive strengths of 2,500 psi and

5,500 psi were ultimately selected.

5.1.4 Mortar Application

As mentioned earlier, two methods for applying the mortar to the faces of the Insteel 3D EPS

panels were used and evaluated. These two methods were: (i) manual or hand-applied, and

(ii) pneumatically-applied using compressed air and hopper system as shown in Figures (2)

and (3), respectively. Mortar thickness variedbetween1.5”and1.25” on both sides of the

foam core for most of the specimens. A mortar thickness of 1.125 inch was used on the last

specimen. The consistency of the thickness was accomplished by placing a spacer (two

horizontal bars) between the wire mesh and the dowels as shown in Figure (2). In order to

ensure the consistency of the mortar mix for all specimens, standard cylinders and cubes

were prepared for each mortar batch used in fabricating the individual wall specimens.

Compressive strength test results for each mortar mix applied to a specific specimen are

presented in this report.

5.1.5 Wall/Footing Shear Connectors

To avoid any possible wall specimen lift-up or translation (rigid-body movement) during

testing, Grade 60 rebar dowels were used to connect the shear walls to the footing, as shown

in Figure (4). A high-strength grout was used to fix the dowels into the reinforced concrete

strip footing, as shown in Figure (5). Results and observations from the evaluation tests

confirmed that the dowels performed very satisfactory in marinating the wall specimens in

its horizontal and vertical original position.

Page 14 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (2): Hand-applied Mortar Method

Figure (3): Pneumatically-Applied Mortar (using a Hopper Spray) Method

Page 15 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (4): Dowels Connecting Footing to Insteel 3D EPS Shear Walls

Figure (5): Rebar Firmly Connected to the Foundation via High-Strength Grout

Page 16 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

5.2 Wall Test Setup

5.2.1 Insteel 3D EPS Panel Wall Specimens

As mentioned earlier, the overall test configuration consisted of two wall dimensions with

two different aspect ratios (AR); namely, (i) 8’x8’ walls specimens with AR=1, and (ii) 8’x6’

walls specimens with AR=0.75. These wall specimens consisted of cementitious skins that

encased the opposing wire mesh sheets and bonded to the EPS foam cores. Here, the welded

diagonal wires provided an efficient means of shear transfer between the two sides of the

sandwich panel. After the placement of cementitious mortar, the total thickness of the

various wall specimens ranged between 6.25”and 7.5”. It should be noted that, in all wall

specimens and tests hot-rolled reinforcements were not used; however, standard U-mesh

strips were applied to the specimens to confine the wall boundaries, as noted in Figure (6).

Here, the U-mesh provided uniform confinement to the wall boundaries and aided overall

ductility of the specimens.

5.2.2 Wall RC Strip Footing

Several reinforced concrete (RC) strip foundations, 9’-07” in length by 1’-06” in width by 1’-

06” in thickness, were designed and fabricated for the test program. Once fully cured, RC

foundations were positioned in front of the strong wall and secured to the strong floor with

the assistance of high strength Dywidag steel rods (1 ½” diam.), nuts and washers. Detailed

attention was applied to the installation process to ensure that the center axis of the footing

coincided with the central axis of the servo-hydraulic actuator, which was mounted on the

strong wall. This process was repeated when the wall specimen was centered and secured to

the footing.

Page 17 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (6): Wall Confinement using U-mesh

5.2.3 Wall/Footing Connection

Dowels were used to secure the walls to the footing. Ten Grade 60 hot rolled #3 rebar, all of

the same length, were used with the first wall specimen (H8-1), while sixteen twenty-four

inch long Grade 60 hot-rolled #4 steel rebars were used with the remaining specimens. The

rebars were positioned twenty-four inches apart on both sides of the wall and were embedded

to a depth of six inches within the footing. The dowels were placed between the EPS

exterior faces and inner faces of the wire meshes as shown in Figure (7) and Figure (8).

High-strength epoxy grout was used to bond the dowels into the footing. The rebars were

secured to the welded wire mesh with tie wires to ensure that they remained vertical during

and after the application of mortar.

Page 18 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

In order to ensure proper composite action between the dowels and the wall, foam behind

each exposed portion of the dowels was removed to a minimum depth of 1” to allow greater

bonding interaction between the mortar and the rebars. In addition to resisting uplift and

securing a wall to the foundation, this simple procedure ensured the proper tranfer of shear

forces between the wall and the foundationAll descriptions of the dowels, panel to panel

connections and wall end details are listed in Appendix (H).

Figure (7): Six #4 Hot-Rolled Steel Dowels (in each face of the wall)
Connecting the Insteel 3D EPS Panel Wall to the Foundation

Page 19 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (8): Wall/Footing Details

5.2.4 Reinforced Concrete Floor Slab Portion (at top of wall)

A reinforced concrete bearing slab was fabricated onsite (at the UCI-SETH IAS Accredited

Facility), on top of the wall, with dimensions consistent with the design of an actual floor

slab and a length equivalent to the wall specimen. The purpose of the reinforced area was to

facilitate the uniform transfer of the lateral cyclic loads to the wall as well as provide

adequate bearing to transfer the gravity-simulating sustained vertical load. The bearing slab
Page 20 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

was fabricated by integrating a "horizontally positioned" 24-inch Insteel 3D EPS panel

section with the unfinished wall specimen. Specifically, the foam core was completely

removed from the 24” wide panel, as well as top 4” of the unfinished wall specimen. Next,

the two components were tied together and filled with mortar. The total thickness of the slab

was 7”. In this manner, the floor-wall junction, shown in Figure (9), served to transfer shear

and flexural stresses through the specimen. The final dimensions of the solid portions of the

wall and slabs were dependent on the wall height, floor spans, loads, and other factors. The

length of the floor slab was identical to the length of the wall, 8 feet, and, as stated above,

had a width of 24”. The reinforcement of the slab was in the form of the wire mesh, the same

used for the wall specimens. Figure (10) shows the typical wall setup that was used in all

evaluation tests.

24”

4”7”

Figure (9): Wall-Floor Junction Details

Page 21 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Sustained Vertical Load (Simulating Gravity Loads)


Cyclic Loading

Figure (10): Typical Full-reversal Wall Test Setup

6 DESCRIPTION OF EVALUATION TEST PROGRAM

6.1 Test Protocol

Eight specimens were evaluated in the current test program. As mentioned earlier, ACI ITG 5.1

displacement control loading protocol was used in all tests (refer to Figure 11). The primary

purpose of the tests was to provide evidence that the building system conformed to and met with

the requirements of the 2009 International Building Code (IBC 2009). At the same time, the test

Page 22 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

program sought to evaluate the ultimate strength, ductility and modes of failure of the wall

specimens. Further, the program sought to assess the efficacy of the two methods of mortar

application. In all tests, wall specimens were exposed to full-reversal lateral cyclic loading.

Similarly, all, but one specimen, were also subjected to a gravity simulated sustained vertical

load (refer to Figure 10).

Figure (11): Cyclic Displacement Loading Protocol used in all tests (Based on ACI ITG 5.1.)

6.2 Equipment

The equipment used to undertake the test program consisted of hydraulic pumps to generate

force, servo-hydraulic actuators and jacks to impart loads, test frames to transfer loads, tie-rods

Page 23 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

to constrain motion, sensors and transducer to capture behavior, and data acquisition systems to

record behavior. Additional supplemental equipment was also present and used as needed.

6.2.1 Hydraulic Actuators:

The full reverse cyclic racking shear load was applied, via a steel transfer beam, by a Quincy-

Ortman servo hydraulic actuator with a maximum stroke of ±17” and a maximum load of

105 kips. The Quincy-Ortman actuator, shown in Figure (10), incorporated a 100-kip load

cell and 40 inch displacement transducer. Both devices were calibrated and supported

traceable certificates. Vertical sustained load was achieved with the aid of four Enerpac R-

605 hydraulic jacks, hoses, a hydraulic pump, a custom designed steel load frame and a

calibrated pressure transducer, with a NIST traceable calibration certificate..

6.2.2 Load Cell

The load cell used in all tests was a Northrop 100-kip calibrated load cell with a NIST

traceable certificate from United Calibrations of Huntington Beach, California.

6.2.3 String Potentiometers

Lateral displacements of wall specimens were measured using the hydraulic actuator’s ’built-

in displacement transducer and several external, individually calibrated, String

Potentiometers (String Pot). All deflection and strain data were collected using a

computerized National Instruments, data acquisition system. Stress/Strain (and

Load/Deflection (P/ curves were developed for each specimen. Crack initiation, crack

progression, and ultimate failure were identified, recorded and then analyzed.

Page 24 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

6.2.4 Electronic Strain Gages

All wall specimens were instrumented with electronic foil resistance strain gages bonded at

critical locations on each face of the wall specimen and on the internal reinforcements.

6.2.5 Data Acquisition

Data acquisition was accomplished with the aid of an MTS Flex Test Controller and a

National Instruments PXI-1042Q data acquisition chassis. In addition to software control of

the servo-hydraulic actuator, the MTS Flex Test Controller recorded actuator motion and

load based on feedback from the calibrated sensors that were integrated into the servo-

hydraulic test system. The NI system captured data from load cells, displacement

transducers, strain gages and environmental monitors to provide the full perspective of the

behavior of the test specimens under the defined loading protocol.

6.2.6 Environmental Monitors

During the tests, both temperature and relative humidity were monitored and recorded by

devices with NIST traceable calibration certificates. The average temperature and relative

humidity during the test were 72oF and 60%.

7 EVALUATION TEST RESULTS

Evaluation of the wall specimens was undertaken in the Structural Engineering Test Hall of the

Department of Civil Engineering at the University of California, Irvine. Tests were administered

by SETH personnel and supervised by the lab Director, Dr. Ayman Mosallam. Eight specimens

were tested. The results of those tests are described in the following paragraphs.

Page 25 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

7.1 Hand Applied 8’x8’ (H8-1) Wall Specimen (AR=1.0)

The first specimen to be tested was given the designation H8-1, which corresponded with the

method of manual hand-applied mortar application and the height of the member. The

dimensions of this wall test specimen were 8’ x 8’ x 7” (Length by Width by Thickness) and the

associated aspect ratio had a value of 1. The thickness of the expanded polystyrene (EPS) foam

ore used with this specimen was 4” and 1.5 inches of mortar were applied to both sides of the

original panel. As described earlier, full-reversal cyclic loading was applied to the upper edge of

the wall specimen with the assistance of a servo-hydraulic as demonstrated in Figure (10). In

addition, a gravity-simulating vertical load was applied to the capitol of the specimen with the

assistance of a rigid steel fixture. Prior to, and during the course of the test, a sustained 24 kips

axial load simulated the gravity load was applied via calibrated hydraulic jacks and the

aforementioned steel fixture. The average 28-day compressive strength of the hand applied

mortar at the day of the test was 2,500 psi. Table (2) shows the compressive strength of the

mortar shell for wall specimens H8-1 and H8-2. For specimen H8-1, hot-rolled 18”, # 3 steel

dowels were placed on opposite sides of the wall panel at 24” on-center (oc). The first six inches

of each dowel was embedded in the footing while the remaining twelve inches was integrated

with the wire mesh reinforcement of the wall panel. As it will be described in the following

section, this wall/footing reinforcement detail was found to be deficient and was deemed

responsible for a premature localized failure at the wall footing interface or junction, which

resulted in early termination of the test before the ultimate capacity of the wall could be

achieved. This deficiency was corrected in all subsequent tests described in this report. It should

be noted that no special detailing was used at the wall boundaries except for the use of standard

Insteel 3D EPS panel 11 gauge cold-rolled U-wire mesh.

Page 26 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

With regard to testing, it was observed that a number of horizontal cracks began to appear at the

lower edges of the wall, as the lateral cyclic load increased, which indicated the development of

flexural stress. Gradually, inclined shear cracks started to appear on the two faces of the wall

(refer to Figure 12). The bulk of cracks were due to the presence of both flexure (horizontal)

and shear (inclined) stress. As mentioned earlier, the failure of the specimen was initiated at the

wall-foundation interface due to yielding of the steel dowels, which suggested that insufficient

reinforcement was afforded to the junction in comparison to the shear capacity of the wall

specimen (refer to Figures 13 and 14). The local premature failure of the wall/footing joint

prevented the wall specimen from supporting its ultimate load capacity. However, the result

highlighted the need to upgrade the shear transfer reinforcement and proper detailing at wall–

footing interface, in order to complete the desired test program.

The maximum load at the moment of local failure, occurred at 39 kips during the pull cycle of

the loading protocol. This value was 56% of the expected capacity of the wall specimen and

confirmed the premature nature of the overall failure. Information gathered from the test

indicated that the behavior of the wall specimen was flexure-dominated, even though some shear

cracks were observed at relatively higher load levels. All data related to the test was confirmed,

analyzed, stored and properly backed-up. Data resulting from the process was used to generate

the load-lateral displacement hysteresis, depicted in Figure (15), and the unique failure envelope

for this wall specimen, presented in Figure (16).

Page 27 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Table (2): Compressive Strength Values of Mortar for Specimens H8-1& H8-2
Compression Specimens Force (lbs.) Strength (psi) Average (psi)

14,855 2,102

12,235 1,731
3” X 6” Cylinders 1,930.75
15,060 2,130

12,444 1,760

10,240 2,560

9,040 2,260
2” X 2” Cubes 2,421.25
10,320 2,580

9,140 2,285

Figure (12): Crack Initiation and Monitoring of Wall SpecimenH8-1

Page 28 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (13): Failure of Wall-Foundation Connection due to Insufficient


Shear Transfer Reinforcements of Wall Specimen H8-1

Figure (14): A Close-Up Photograph Showing the Localized Bond Failure


of Embedded Dowels of Wall Specimen H8-1

Page 29 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (15): Cyclic Load-Displacement of H8-1

Figure (16): P-Envelope of Wall Specimen H8-1

Page 30 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

7.2 Hand-Applied 8’x8’ (H8-2) Wall Specimen (AR=1.0)

The second specimen to be tested was H8-2. It was eight feet wide, eight feet tall, and seven

inches wide. It had an aspect ratio of 1.0 and was fabricated with a hand applied mortar, which

resulted in a 1.5 inch thick cementitious skin on both sides of the finished wall specimen. The

specimen was identical in shape and form to H8-1. However, based on the premature failure of

the first specimen, the wall/footing junction was redesigned to preclude premature failure. In this

case, the size of the hot-rolled steel dowels was increased from # 3 to # 4, while the position of

the dowels in relation to the wall and the footing remained the same. Specifically, the dowels

were placed symmetrically on both sides of the panel, once again at 24 inches on center,. The

total dowel length was increased from 18” to 24” with same embedment depth of 6” as for the

first wall specimen (H8-1), shown earlier. As with the first wall, high-strength epoxy grout was

used to secure the positions of the dowels. In addition, the same 28-day, 2,500 psi compressive

strength mortar mix, which was used with specimen H8-1, was applied by hand to specimen H8-

2. The actual test setup for specimen H8-2 is presented in Figure (17.

As loading commenced in accordance with the previously defined load protocol, flexural cracks

appeared. As the load increased, mixed flexure/shear cracks were observed, which indicated that

the wall was behaving in a mixed mode manner, with ultimate failure likely to be triggered by

high flexural stresses. As compared to the first specimen with deficient wall/footing details,

specimen H8-2 proved to be more ductile. The ultimate shear load was 68 kips and failure

occurred during the final push cycle. Once again, all data related to the test was confirmed,

analyzed, stored and properly backed-up. Although the behavior of the specimen was captured

and plotted in real-time, additional analysis and data evaluation was undertaken after testing. The

confirmed data set was used to generate the load-lateral displacement hysteresis, depicted in

Page 31 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (18). At the conclusion of testing, the specimen was riddled with cracks. Significant

horizontal flexure separation is presented in Figure (19). Similarly, the complete load-

displacement envelope is depicted in Figure (20).

Figure (17): Setup of Wall Specimen H8-2

Page 32 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (18):Load-Displacement Hysteresis of Wall Specimen H8-2

Figure (19): Location of Flexural Horizontal Crack Where the Ultimate failure was
Initiated for Wall Specimen H8-2

Page 33 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (20): Load-Displacement Envelope for Wall Specimen H8-2

7.3 Pneumatically-Applied 8’x8’ (P8-1) Wall Specimen (AR=1.0)

The third specimen to be tested was given the designation P8-1. As the name indicated, this

specimen’s cementitious skin was applied with pneumatic hardware. In all other areas, the third

specimen was identical to H8-2, the second specimen, in terms of aspect ratio test setup, joint

detailing, and loading protocol. It should be noted that the pneumatically applied mortar had an

average compressive strength of 3,074 psi at the time of testing, as listed in Table (3). In addition

to evaluating the efficacy of the panel system, the test program also sought to identify and

Page 34 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

possibly quantify differences in performance of the panel walls when fabricated with either

manually applied or pneumatically applied cementitious skins. .

Table (3):Compressive Strength Results of Mortar for P8-1

Specimen Size Test Date (Days) Force (lbs) Strength (psi)


2” X 2” 14 12,040 3,010
2” X 2” 14 12,535 3,133
2” X 2” 14 12,315 3,079
Average 12,230 3,074

The results of testing suggested that specimen P8-1 behaved similarly to specimen H8-2.

However, it should be noted that P8-1 sustained more shear cracks than were observed in H8-2.

This difference was attributed to the slight variation in the mortar compressive strength between

the two specimens. The number and size of cracks increased and propagated along the length of

the wall, as the cyclic loads and displacements increased, as noted in Figure (21). Just prior to

experiencing the ultimate load, mid-height horizontal cracks from both edges of the wall met

creating a surface crack across the thickness of the wall as shown in Figure (22). This through-

the-thickness crack was observed at the wall sides and was the cause of the ultimate failure of the

specimen, as shown in Figure (23). Further, it was concluded that the mode failure was a result

of a combined shear/flexure action. Accordingly, the data collected was confirmed, stored and

properly duplicated and was used to create the load-displacement hysteresis and envelope of this

wall specimen, respectively. An envelope of the load-displacement curve is presented in Figure

(26). As shown in these figures, the ultimate load of this wall specimen was 59 kips and failure

occurred during the final push loading cycle.

Page 35 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (21): Initiation and Progression of Cracks

Figure (22): Development of Through-the-Thickness Crack Just Before Ultimate Load

Page 36 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (23): Ultimate Failure of Wall Specimen P8-2

Figure (24): Load-Displacement Hysteresis of Wall Specimen P8-1

Page 37 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (25): P- Envelope of Wall Specimen P8-1

7.4 Pneumatically-Applied 8’x8’ (P8-2) Wall Specimen (AR=1.0)

P2-2 was the fourth specimen to be tested. It was eight feet tall, eight feet wide and, logically,

had an aspect ratio equal to one, which was identical to all previous test articles. The wall

specimen was fabricated with a panel that had a four inch thick foam core. The cementitious

skin was applied pneumatically on both sides of the panel to a thickness of about 1.5 inches. As

such the total wall thickness, i.e. the total specimen thickness, was 7 inches, which again was

consistent with the other specimens. However, unlike previous tests, the average 28-day

compressive strength of the pneumatically applied mortar mix was determined from testing to be

to be 5,500 psi, as shown in Table (4). This value is almost double the compressive strength of

other wall specimens described earlier. The test setup and loading protocol were identical to all

Page 38 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

previous tests. The junction detailing and reinforcement at the wall-footing interface was

consistent with efforts associated with the last three tests.

Table (4): Compressive Strength Results of Mortar for P8-2

Specimen Size Force Strength (psi)


(lbs)
2” X 2” 22760 5,690
2” X 2” 21940 5,485
2” X 2” 21440 5,360
Average 22,047 5,512

The behavior of the specimen during testing was similar, initially, to wall specimen P8-1.

However, more shear cracks appeared at an early stage of loading when compared with other

tests. This was an expected consequence of the higher mortar compressive strength. The

ultimate failure load of this wall was about 40% higher than the corresponding ultimate failure

load of the previous specimen, P8-1 (83 kips vs. 59 kips). The ultimate load was reached during

the final pull cycle of loading and is captured in Figures (26) and (27), which present the load-

displacement hysteresis and failure envelop for this wall specimen. It should be noted that

specimen P8-2 exhibited a slight improvement in ductility as compared to wall specimen P8-1.

7.5 Hand-Applied 8’x6’ (H6-1) Wall Specimen (AR=0.75)

The fifth specimen to be tested was given the designation H6-1. The prior tests had provided a

sense of the behavior of the specimens with an aspect ratio of 1.0. Based on those results and

observations, ,a second set of tests were conducted to evaluate the effect of changing the aspect

Page 39 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

ratio on the overall structural behavior of shear wall made of Insteel 3D EPS panel sandwich

system. Specimen H6-1, the first test of a short, squat, wall, had a length of 8’, a height of 6’

and a thickness of 6.5”. The cementitious skin was applied by hand during fabrication and the

28-day average compressive strength of the mortar was determined to be 3,000 psi, as indicated

in Table (5), which presents a summary of the experimental values of the 28-day compressive

strength of the mortar mix used in fabricating this wall specimen.

Figure (26):Load-Displacement Hysteresis of Wall Specimen P8-2

Page 40 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (27):Load-Displacement Envelope for Wall Specimen P8-2

The majority of the cracks developed in specimen H6-1 were diagonal shear cracks and the

ultimate failure was shear-dominated. The ultimate failure shear capacity of this wall was 75

kips. Specimen H8-2 had an aspect ratio equal to one, hand applied cementitious skin and a

mortar compressive strength of around 3,000 psi. When compared to specimenH8-2, the ultimate

load for specimen H6-1 was approximately 27% higher, i.e. 75 kips vs. 59 kips. Data collected

for this test was confirmed, secured, duplicated, analyzed and presented in Figures (28) and (29)

as the load-displacement hysteresis and the failure envelope for this wall, respectively.

Table (5):Compressive Strength Results of Mortar for H6-1


Specimen Size Test Date (Days) Force (lbs) Strength (psi)
2” X 2” 17 12,455 3,114
2” X 2” 17 12,970 3,243
2” X 2” 17 12,220 3,055
Average 12,548 3,137

Page 41 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (28): Cyclic Load-Displacement of H6-1

Figure (29): P- Envelope of Wall Specimen for H6-1

Page 42 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

7.6 Hand-Applied 8’x6’ (H6NG-2) Wall Specimen (AR=0.75)

In this test, a wall specimen identical to wall specimen (H6-1) was constructed. The only

difference between this specimen and wall specimen (H6-1) was the removal of the gravity-

simulated axial vertical wall that was used for all other tests evaluated in this program. This was

done upon the recommendation of ICC-ES engineer to assess the effect of this load on the

overall behavior, including strength and ductility of these types of walls. This application

mimicked a state of stress for applications where gravity loads were minimal. The aspect ratio

of this wall specimen remained 0.75 and the mortar was applied by hand in a manner consistent

with specimen H6-1. The desired targeted compressive strength for the specimen was 3,000 psi.

However, the average 28-day compressive strength of the actual mortar mix used in fabricating

H6NG-2 failed to achieve the desired mark and, instead, obtained a compressive strength of just

over 2300 psi, which is summarized in Table (6).

As expected, specimen H6NG-1 experienced greater lateral displacements (higher drift ratio),

compared to specimen H6-1, due to the absence of gravity load, which provided stability akin to

a prestressing force on the wall. Further, the behavior of H6NG-1 was apparently more ductile

than H6-1, for the same reason. Throughout the loading process, diagonal shear cracks appeared

and propagated in a typical X-pattern, as shown in Figure (30). The ultimate failure mode was

dominated by shear stresses (refer to Figure 31). The ultimate shear strength, failure load, of

H6NG-1 was 67 kips. This value was about 90% of the ultimate strength of the wall specimen

H6-1, which was tested in the presence of a sustained axial vertical load. It was believed that

the absence of the vertical load in addition to the slightly lower compressive strength were the

Page 43 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

reason behind this degradation of the wall specimen. Data collected for specimen H6NG-1 was

confirmed, secured, duplicated, analyzed and presented in Figures (32) and (33) as the load-

displacement hysteresis and the failure envelope for this wall, respectively.

Table (6):Compressive Strength Results of Mortar for Wall Specimen H6NG-2

Specimen Size Test Date (Days) Force (lbs) Strength (psi)

2” X 2” 12 9,470 2,368

2” X 2” 12 9,415 2,354

2” X 2” 12 8,565 2,141

2” X 2” 12 9,110 2,278

2” X 2” 12 9,340 2,335

2” X 2” 12 9,835 2,459

Average 9,289 2,322

Page 44 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (30): Crack Propagation for Wall SpecimenH6NG-2

Page 45 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (31): Final Failure of Wall SpecimenH6NG-2

Figure (32): Load-Displacement Hysteresis of Wall Specimen H6NG-2

Page 46 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (33): P- Envelope of Wall SpecimenH6NG-2

7.7 Pneumatically-Applied Mortar 8’ X 6’ (P6-1) Wall Specimen (AR=0.75)

The seventh specimen to be tested, P6-1, was identical in design, shape and geometry to

specimen H6-1, except that the cementitious skin was applied pneumatically The 28-day

compressive strength of the mortar mixed used with P6-1 had an average compressive strength of

2,254 psi as shown in Table (7). During testing, P6-1 exhibited the same behavior patterns as

the two previous walls that were tested with an aspect ratio equal to 0.75. Accordingly, shear

cracks formed, in typical X-patterns on both sides of the wall up to the point of failure. A

typical dispersion of the shear cracks is presented in Figure (34). Just prior to ultimate load, a

large horizontal crack opened and propagated along the length of the wall just below the capitol,

as shown Figure (35). As with H6-1 and H6NG-1, the ultimate mode of failure for P6-1 was

due to shear. The ultimate load was 67.7 kips, which was slightly lower than the corresponding

Page 47 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

strength of specimen H6-1, which, again, was fabricated with hand-applied mortar. It was

assumed that the variation of the strength between H6-1 and P6-1 was attributable to the

difference in compressive strength of the mortar used to fabricate each specimen. The load-

displacement hysteresis and failure envelope were plotted for this wall specimen and are

presented in Figures (36) and (37), respectively.

Table (7):Mortar Compressive Strength Results


for Wall Specimen P6-1

Specimen Size Test Date (Days) Force (lbs) Strength (psi)


2” X 2” 7 9,920 2,480
2” X 2” 7 9,200 2,300
2” X 2” 7 8,635 2,159
2” X 2” 7 9,310 2,328
2” X 2” 7 8,970 2,243
2” X 2” 7 8,050 2,013
Average 9,014 2,254

Page 48 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (34): Crack Propagation for Wall Specimen P6-1

Figure (35): Final Failure Mode of Wall Specimen P6-1

Page 49 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (36): Load-Displacement Hysteresis of Wall Specimen P6-1

Figure (37): P- Envelope of Wall SpecimenP6-1

Page 50 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

7.8 Low-Strength Hand-Applied Mortar 8’ X 6’ (H6L-3) Wall Specimen (AR=0.75)

The eighth specimen to be tested was H6L-3. As identified by its designation, mortar was placed

on this specimen by hand to the required depth. The specimen was eight feet long and six feet

wide. It had an aspect ratio of 0.75, which was consistent with the three previous specimens.

However, unlike those members, both the thickness of the mortar shell, the 28-day compressive

strength of the mortar mix and reinforcement detailing were altered for this specimen.

Specifically, H6L-3 employed a mortar mix with a 28-day compressive strength of

approximately 1,500 psi. A summary of the 28-day compressive strength for the mortar used

with this specimen is presented in Table (8). Further, the cementitious skin on either side of the

H6L-3 was manually applied to a depth of 1.125” on the original panel. This process resulted in

a total wall thickness of 6.25”, which was 10% less than the average thickness of other

specimens evaluated in this program. Finally, unlike previous specimens, the fabrication of H6L-

3 included the introduction of lightly-reinforced boundary elements at the ends, i.e. edges, of the

walls. This was accomplished in three steps. First, a, 4” deep and 24” tall, section of EPS foam

was removed from both sides of the unfinished panel, from the wall-footing interface to a height

24” above the interface, to expose the #4 wall end dowels. Second, the exposed #4 wall end

dowels are encased in the U-mesh end reinforcements to create a bounded cavity. Third, both

cavities are filled with mortar to produce solid boundary elements at the foot of wall. The

justification for this modification was (i) to demonstrate the utilization of boundary elements as a

simple means to enhance the ductility of the wall, and (ii) to demonstrate a simple process to

avoid localized failure of the thin, low-strength mortar-shell due to high-compressive stress

concentration at the wall toes. It was hoped that the combined design modification replicated

Page 51 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

the worst case construction scenario that involved the application of low-quality mortar with too

thin, i.e. below design specification, cementitious skin. Specimen H6L-3 with the two boundary

elements is shown in Figure (38). Once again, the identical test setup and cyclic/axial loading

protocol used in previous experiments was adopted for this specimen (refer to Figure 39).

During testing, specimen H6L-3 exhibited a shear dominated behavior up failure, in which

diagonal shear cracks initiated and propagated along the two faces of the Insteel 3D EPS panel

wall, as shown in Figure (40). Ultimate failure for H6L-3, captured in Figure (41) occurred at

79.7 kips and was slightly higher than the strength exhibited by wall specimen H6-1, even

though the applied mortar mix had a lower compressive strength. This result confirmed the

efficiency of the boundary elements in providing the additional system strength and enhanced

ductility required to overcome deficiencies associated with poor mortar compressive strength and

inadequate mortar cover. The results of H6L-3 were comparable to results for specimens with

higher compressive strength mortar and adequate mortar shell thickness. Data collected for

specimen H6L-3 was confirmed, secured, duplicated, analyzed and presented in Figures (42) and

(43) as the load-displacement hysteresis and the failure envelope for this wall, respectively.

Table (8): Mortar Compressive Strength Results for Wall Specimen H6L-3
Specimen Size Test Date (Days) Force (lbs) Strength (psi)
2” X 2” 4 6,120 1,530
2” X 2” 4 5,320 1,330
2” X 2” 4 7,330 1,833
2” X 2” 4 5,760 1,440
2” X 2” 4 5,955 1,489
Average 6,097 1,525

Page 52 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Solid Boundary
Elements (no foam)

Figure (38): Boundary Elements of Wall Specimen H6L-3

Page 53 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (39): Setup of Wall SpecimenH6L-3 prior to Testing

Figure (40): Crack Propagation for Specimen H6L-3

Page 54 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (41): Failure of Specimen H6L-3

Figure (42): Load-Displacement Hysteresis of Wall Specimen H6L-3

Page 55 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (43): P- Envelope of Wall SpecimenH6L-3

8 ANALYTICAL PROCEDURES

The following section describes the analytical procedure used to predict the strength and ductility

characteristics of the Insteel 3D EPS panel walls evaluated in this program. The results of this

analysis identified several important design parameters and influencing factors. According to

ICC-ES AC15 (2010), two major values are required for the evaluation and estimation of a wall

system. These values are the safety factor, SF, and the seismic response modification factor or R-

value. The process to determine these values is described in the following paragraphs.

With regard to the SF and R-value, all procedures followed ACI 318 outlines for designing

reinforced concrete structures. Hand calculations were used to calculate the shear strength of

Page 56 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

each wall specimen. Flexural results were obtained with the assistance of the computer software,

Response 2000, which is known to accurately calculate the strength and ductility of wall

specimens in response to shear, moment, and axial loads. Response 2000 was particularly

helpful because of its ability to address the complex reinforcement requirements of the wall

specimens associated with this study. Details of the analytical results are listed in Appendix

(A) through (G) at the end of this report.

9. CONCLUSIONS AND RECOMMENDATIONS

Based on the results obtained from the evaluation tests described in this report, the

following conclusions are drawn:

The results of the evaluation tests showed that all the walls with shear-dominated

aspect ratios behaved in a ductile manner with Seismic Response Modification Factor

(R-Values) up to 4.8. The use of R=5 as commonly used and specified in ACI 318 and

ASCE-07 is acceptable. It is believed the limited sample pool size skewed the results to

a lower value. It is the belief of the authors that a larger sample pool size, i.e. an

increase in the number of specimens, would have resulted in higher values for R that

would have approached the targeted goal. It should be noted that the “direct” method,

which is used in determining the seismic design capacity of walls from experimental

data, is more applicable to cast-in-place sandwich panels than the indirect method,

which is currently adopted through the use of ITG5 documents that were developed

specifically for precast and prestressed solid walls that behave in different manner. It

should be added that proposed loading protocol described in ITG5 was acceptable for

the duration of the test program,

Page 57 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

It was observed that as the aspect ratio increases, a mixed flexure/shear behavior

appears, which results in a lower shear ductility for the walls. This conclusion should

be beneficial for the designer, where a reduced R-value would be used for cases where

the walls’ aspect ratios are higher than unity. Thus in the case of increased aspect

ratio, the recommended R value is 3 to 3.5.,

By reducing the height of the wall specimen while maintaining the specimen’s length, it

was possible to shift the failure dominance from flexure to shear, as well as, increase

the R factor. The increase in R factor suggests a corresponding increase in wall energy

dissipation capability, which would allow for allow for higher seismic capacity,

With regards to the method of application of the mortar shells, results obtained from

the full-scale fully-reversal loading tests indicated that there was not any significant

difference between the overall seismic performance of wall specimens fabricated using

hand application and those fabricated using a pneumatic approach (see Figures 43

through 45). In fact, the limited results indicated that the manually fabricated

specimens yielded a slightly better performance than those that were fabricated with

pneumatic equipment. So the choice between the two methods will mainly be a factor

of the project costs and time constraints.

The overall test results indicated that mortar compressive strength was not the primary

factor controlling the strength of the Insteel 3D EPS panel walls. However, an

increase in the mortar compressive strength (e.g. 5,000 to 6,000 psi) may have an effect

on controlling the ultimate behavior and the mode of failure of the walls.

The test results confirmed that ensuring the proper slab-to-wall (capitol-to-wall)

connection as well as wall-to-foundation connection was critical to both achieving and

Page 58 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

determining the wall’s ultimate strength capacity. This was also a deciding factor in

location of the ultimate failure of the walls,

When wall-to-foundation connections were properly designed and installed, the 8’ X 8’

wall specimens failed due to a combination of flexure and shear, whereas the 8’ X 6’

wall specimens failed predominantly due to shear. So reducing the wall height by 2

feet, i.e. reducing the aspect ratio while maintaining the length, was greatly beneficial

in achieving the desired mode of failure.

When comparing the overall behavior of the 8’ X 6’ walls, with and without the

application of gravity-simulated load (wall specimen H6NG-2), one may conclude that

the absence of gravity load (as for the case of fences) resulted in a larger drift.

However, the wall’s shear strength capacity was lower than that of an identical wall

tested under combined gravity and lateral loading.

The higher height-to-length aspect ratio of the 8’ X 8’walls specimens, resulted in a

higher drift ratio when compared to the 0.75 aspect ratio of the 8’ X 6’ walls (Squat

walls).

Page 59 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (43): Effect of Method of Application on Ultimate Load Capacity


(Wall HB2 vs. P8-1)

Figure (44): Effect of Method of Application on Maximum Drift Ratio


(Wall HB2 vs. P8-1)
Page 60 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (45): Effect of Method of Application on R-value


(Wall HB2 vs. P8-1)

Figure (46): Effect of Compressive Strength fc' on Ultimate Load Capacity


(Walls P8-1 of 3,000 psi vs. P8-2 of 5,500 psi)

Page 61 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (47):Effect of Compressive Strength fc' on Maximum Drift Ratio


(Walls P8-1 of 3,000 psi vs. P8-2 of 5,500 psi)

Figure (48): Compressive Strength fc'' Effect on R-value (Walls P8-1 and P8-2)

Page 62 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX (A)
Analytical Prediction of Shear and Flexural
Strength of Different Wall Specimens

Page 63 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

As mentioned earlier, the prediction of the shear strength of each wall was performed using hand

calculations as detailed in this Appendix. Only final analytical results for flexural strength are

presented since the flexural analysis was performed using RESPONSE 2000 computer software.

A.1 SHEAR WALLS CAPACITY CALCULATIONS

√ Eq. (1)

Eq. (2)

( )Eq. (3)

A.1.1 Hand-Applied 8’x8’ (H8-1), (H8-2) Wall Specimens

( )

( )

Each wire area = 0.012 in2 spaced at 2” (each wythe)

Thus,

A.1.2 Pneumatically-Applied 8’x8’ (P8-1) Wall Specimen

( )

Page 64 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

( )

Each wire area = 0.012 in2 spaced at 2”

Thus,

A.1.3 Pneumatically-Applied 8’x8’ (P8-2) Wall Specimen

( )

( )

Each wire area = 0.012 in2 spaced at 2” (each wythe)

Thus,

A.1.4 Hand-Applied 8’x6’ (H6-1) Wall Specimen

( )

Page 65 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

( )

Each wire area = 0.012 in2 spaced at 2” (each wythe)

Thus, .

A.1.5 Hand-Applied 8’x6’ (H6NG-2) Wall Specimen

( )

( )

Each wire area = 0.012 in2 spaced at 2” (each wythe)

Thus,

A.1.6 Pneumatically-Applied 8’ X 6’ (P6-1) Wall Specimen

( )

Page 66 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

( )

Each wire area = 0.012 in2 spaced at 2” (each wythe)

Thus,

A.1.7 Hand Applied 8’ X 6’ (H6L-3) Wall Specimen

( )

( )

Each wire area = 0.012 in2 spaced at 2” (each wythe)

Thus,

Table (A-1) demonstrates the difference between the analysis values obtained and the results

obtained from the actual test for flexure dominated wall specimens. The length to height aspect

ratio is the primary difference that separates what type of failure dominated the wall specimens.

Page 67 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

The smaller the height to length ratio the more the shift of failure dominance is towards shear.

The reason for the variation between the analysis values and the test results for the First wall or

H8-1 is that the anchorage was realized to have been weak. Therefore, the test results gave a

much lower values than expected. Table (A-2) demonstrates the difference between the analysis

values obtained and the results obtained from the actual test for shear dominated wall specimens.

Table (A-1): Comparison between Analysis Values and Test


Results for Flexure Dominated Walls
H8-1 H8-2 P8-1 P8-2
Load(kips) Load (kips) Load (kips) Load (kips)

Analysis Values
78.5 78.5 80.7 89.7
(Shear)
Analysis Values
48 48 49 55
(Flexure)
Test Results 39 68 59 83

Table (A-2): Comparison between Analysis Values and Test


Results for Shear Dominated Walls
H6-1 H6NG-2 P6-1 H6L-3

Shear (kips) Shear (kips) Shear (kips) Shear (kips)

Analysis Values 58 55.7 55.6 53.1

Test Results 75 67 67.7 79.7

Page 68 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX(B)
CALCULATIONS OF SEISMIC RESPONSE

MODIFICATION FACTOR

(R-FACTOR)(R)

CALCULATIONS

Page 69 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

B.1 DETERMINATION OF APPROXIMATE SEISMIC RESPONSE

MODIFICATION FACTOR (R)

Seismic codes consider a reduction in design loads, taking advantage of the fact that the

structures possess significant reserve strength (over-strength) and capacity to dissipate energy

(ductility). The over-strength and the ductility are incorporated in structural design through a

force reduction or a response modification factor. This factor represents ratio of maximum

seismic force on a structure during specified ground motion if it was to remain elastic to the

design seismic force. Thus, actual seismic forces are reduced by the factor ``R'' to obtain

design forces.

The response modification factors were first proposed in ATC3-06, in ATC-19 and ATC-34

was calculated as the product of three factors: Over-Strength factor ( ), Ductility factor

( ), and Redundancy factor (RR).

The following approximate method was used in order to calculate the Seismic Response

Modification Factor (for simplicity RR was assumed to be 1 since the determination of that

factor requires very complex procedures to evaluate it that were not carried out in the

evaluation). The parameters used to calculate the Over-Strength factor ( ) and Ductility

factor ( ) are defined in Figure (B-1).

Page 70 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (B-1): Parameters to calculate the Over-Strength Factor (𝑅𝑠 ) and Ductility factor (𝑅𝜇 )

B.1.1 Hand-Applied 8’x8’ (H8-1) Wall Specimen

Page 71 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

B.1.2 Hand-Applied 8’x8’ (H8-2) Wall Specimen

B.1.3 Pneumatically -Applied 8’x8’ (P8-1) Wall Specimen

B.1.4 Pneumatically Applied 8’x8’ (P8-2) Wall Specimen

Page 72 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

B.1.5 Hand Applied 8’x6’ (H6-1) Wall Specimen

B.1.6 Hand Applied 8’x6’ (H6NG-1) Wall Specimen

B.1.7 Pneumatically Applied 8’ X 6’ (P6-1) Wall Specimen

Page 73 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

B.1.8 Hand Applied 8’ X 6’ (H6L-3) Wall Specimen

Table (B-1) presents a summary of the R-values calculated for the four Insteel 3D EPS panel

walls with AR=1.0 (flexural-dominated behavior). The average value of the response

modification factor from the flexure-dominated walls as seen in Table (B-1), with a

maximum value of 3.5. For this reason, and based on the results of the limited number of walls

in this evaluation, it is recommended that for AR=1, an R-value can be taken as 3.0. However,

the R-value may be increased provided that boundary elements with ductile details are

introduced.

Table (B-1): Seismic Response Modification Factor (R) for Flexure-Dominated Walls

H8-1 H8-2 P8-1 P8-2

R Value 2.73 2.5 2.67 3.5

Table (B-2) presents a summary of the R-values calculated for the four Insteel 3D EPS panel

walls with AR=0.75 (shear-dominated behavior). The average response modification factor

based on the results for these four walls tests is with a maximum value of 5.0. Since

Page 74 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

accurate prediction of the R-values requires a very large range of tests that is not practical for the

evaluation purposes, the use of R=5 that is commonly used in practice for special concrete is

acceptable for Insteel 3D EPS panel walls based on this evaluation.

Table (B-2): Seismic Response Modification Factor (R) for Shear Dominated Walls

H6-1 H6NG-2 P6-1 H6L-3

R Value 4.3 4.8 3.34 5.0

Page 75 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX(C)
Coefficient of Variation of
Average Maximum Strength for
Shear Dominated Walls

Page 76 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

The Coefficient of Variation of Average Maximum Strength was calculated using AC15

(2010)Acceptance Criteria for Concrete Floor, Roof, And Wall Systems and Concrete Masonry

Wall Systems. It was calculated for the shear dominated wall tests that had an aspect ratio of

0.75. The test values and analysis values can be seen in Table (C-1).

Table (C-1): Comparison between Analysis Values and Test Results for Shear Dominated Walls
H6-1 H6NG-2 P6-1 H6L-3 AVERAGE

Shear Load Shear Load Shear Load Shear Load Shear (kips)

(kips) (kips) (kips) (kips)

Analysis 58 55.7 55.6 53.1 55.6

(RD)

Experiment 75 67 67.7 79.7 72.4

(R)

The value of ( ) ( )

where:

R: Average Maximum Strength RD: Design Value of Strength

(C-8)

(C-9c)

Using Table (A.1) of Appendix (A) of the ICC-ES AC15 (2010) the corresponding Safety Factor

(SF) of 2.1 is obtained.

Page 77 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX(D)

CALCULATIONS OF INTERFACE
SHEAR TRANSFER AND WIRE
SHEAR WEB DESIGN

Page 78 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Interface Shear ( )

( ) Where = Zero as there is no prestressing involved

Modulus of Rupture = √ = 367 psi

= 289

( )( )( )

Design of Shear Connector

( )

( )

( )
( )

( )

Since , Therefore the Connectors can withstand the Shear Stresses Imposed.

Page 79 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX(E)

COMPARISONS WITH OTHER


PUBLISHED 3D PANEL WALLS
TEST RESULTS

Page 80 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

For traceability purpose and in order to compare the results obtained from this evaluation

program with other independent tests that were conducted in other facilities on similar 3D

panel wall systems. As expected, some variations exist, however, the assessment focused

on the general behavior. The published work utilized an aspect ratio of unity (AR=1.0)

with some other variation described in the following sections.

E.1 COMPARISONS BETWEEN UCI &PERU WALL TEST RESULTS

The first set of tests that was used in the comparison was performed on three 3D sandwich

panels in Peru. The dimensions and test setup of these wall panels were similar to those

evaluated at UCI with an aspect ratio of close to unity (AR1.0). The dimensions of the wall

panels were 8’ X 8’[2,470 mm (Length) X 2,600 mm (Height)]with a total thickness of 5.2”

(130 mm). The walls were subjected to both cyclic lateral shear and gravity loading.

However, the loading protocol was different than the one reported herein that follows the

ITG5 procedures. No information was given on the concrete mix nor the exact details of the

wall/footing joint. Two major differences existed between the UCI Insteel 3D EPS panel

walls and the Peru walls: (i) The panel wire gage for Peru was 14-gage while 11-gage wire

was used for Insteel 3D EPS panels, and (ii) The total thickness of the Peru walls was 5.2”

while the UCI Insteel 3D EPS panel walls had an average thickness of 7”. As one can

predict, these two variations are very critical in determining strength capacity of such walls.

A sample of load-displacement envelopes for Peru walls program is shown in Figure (E-1).

Strength results for both Peru and UCI wall tests are summarized in Tables (E-1) and (E-2).

As expected, the average capacity of the Peru walls were about 40% lower than those

reported herein due to the variables described earlier.

Page 81 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (E-1): A Sample of Load-Displacement Envelopes for Peru Walls Program

Table (E-1): Ultimate Load Capacity of Walls Tested at UCI (AR=1.0)


H8-1* H8-2 P8-1 P8-2 Average

UCI Tests 39 kips* 68 kips 59 kips 83 kips 70.0

*Excluded due to premature failure

Table (E-2): Ultimate Load Capacity of Walls Tested in Peru (AR=1.0)


Wall 1 Wall 2 Wall 3 Average

Peru Tests 39.7 kips 44.2 kips 40 kips 41.3

E.1.1 Comparison of Seismic Response Modification Factor (R) for Peru Wall Tests

The Seismic Response Modification Factor (R-value) for the walls tested in Peru were calculated

using the same procedures used for UCI walls.

Page 82 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

E .1.1.1First Wall Specimen:

E.1.1.2Second Wall Specimen:

E.1.1.3Third Wall Specimen:

Page 83 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

As expected and due to the smaller wire gage and wall thickness, the average response

modification factor from the three wall specimens tested in Peru (aspect ratio of 1.0) is 3.2 as

shown in Table (E-3). This value is very similar to those obtained from UCI wall tests with

AR=1.0.

Table (E-3): Seismic Response Modification Factor for Peru Wall Tests

Wall 1 Wall 2 Wall 3 Average

R Value 4 3 2.5 3.2

The maximum drifts obtained for the tests performed at UCI are shown in Tables (E-4) and (E-5)

presents the maximum drift values obtained for Peru tests form tests conducted at UCI,

respectively. As shown in these tables, the average maximum drift angel obtained from UCI

tests was 0.0072 whereas the average maximum drift of the tests performed in Peru was 0.0071

which very similar.

Table (E-4): Maximum Drift of Walls Tested at UCI (SETH)

H8-1 H8-2 P8-1 P8-2


UCI Tests 0.00729 0.00469 0.00885 0.0083

Table (E-5): Maximum Drift of Walls Tested in Peru


Wall 1 Wall 2 Wall 3
Peru Tests 0.0071 0.0079 0.0063

Page 84 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Table (E-6): Maximum Drift of Walls Tested at UCI (SETH)

H8-1 H8-2 P8-1 P8-2

UCI Tests 0.00729 0.00469 0.0083 0.00885

Table (E-7): Maximum Drift of Walls Tested in Peru

Wall 1 Wall 2 Wall 3

Peru Tests 0.0071 0.0079 0.0063

E.2 COMPARISONS BETWEEN UCI and MEXICO WALL TESTS

The second similar wall tests were conducted on EPS sandwich panel walls at the University of

Guadalajara in Mexico. In this program, two walls with aspect ratio of 1.0 were tested under

cyclic lateral loading and gravity sustained load. The dimensions of the walls were 8 ft X 8ft

with a thickness of 7 inches. However, lower compressive strength was used. The average

ultimate capacity of the walls tested in Mexico was 50. 2 kips which is about 30% lower than the

ultimate capacity of the Insteel 3D EPS panel walls tested at UCI (see Tables E-7 and E-8).

Page 85 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Table (E-12): Maximum Shear Load Capacity of Walls Tested in Mexico

Wall 1 Wall 2

Mexico Tests 47 kips 53.8 kips

Table (E-13): Maximum Shear Load Capacity of Insteel 3D EPS Panel Walls Tested at UCI

H8-1* H8-2 P8-1 P8-2

UCI Tests 39 kips* 68 kips 59 kips 83 kips

*Excluded from the calculations due to premature failure

E.2.1 Comparison of Seismic Response Modification Factor (R) for EPS Sandwich Panels

Tested at the University of Guadalajara and Insteel 3D EPS Panel Walls Tested at UCI

The average response modification factor from the wall specimens conducted in Mexico with

flexure dominated aspect ratio of 1.0 is which again very similar to both UCI and

Peru walls with AR=1.0

Page 86 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX (F)

COMPARISONS WITH OTHER

WALL SYSTEMS (different materials)

Page 87 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

F.1 COMPARISONS BETWEEN INSTEEL 3D EPS SANDWICH PANELS

USED AS SHEAR WALLS and MASONRY WALL TESTS

The Insteel 3D EPS sandwich panel walls tested at UCI SETH were compared to two

previously tested masonry wall specimens that were tested under similar loading conditions

(see Figure F-1).The aspect ratio of these masonry walls was 1.0.

The load-displacement hysteresis for the two wall specimens (specimens WU1 and WU2)are

presented in Figures (F-2) and (F-3), respectively.

Figure (F-1): Concrete Masonry Walls Test Earlier at UCI

Page 88 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (F-2): Cyclic Load-Displacement of Specimen WU1

Figure (F-3): Cyclic Load-Displacement of Specimen WU2

Page 89 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

F.1.1 COMPARISON BETWEEN THE SEISMIC RESPONSE MODIFICATION

FACTOR (R) FOR LIGHTLY REINFORCED MASONRYWALL AND INSTEEL 3D

EPS SANDWICH PANEL WALLS

For comparison reason, R-values obtained from this evaluation program for the Insteel 3D EPS

panels were compared to lightly reinforced masonry walls with aspect ratio of 1 that was

evaluated earlier at UCI facility under different evaluation program. The following are the

calculations for determining the R-values for the masonry walls which are identical to those used

for calculation the R-values for Insteel 3D EPS panel walls.

F.1.1.1 WU1 Wall Specimen:

F.1.1.2 WU2 Wall Specimen:

Page 90 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Table (F-1): Seismic Response Modification Factor for Masonry Wall Tests

WU1 WU2

R Value 2.28 2

The average response modification factor from the 2 wall tests performed on masonry wall

specimens conducted with flexure dominated aspect ratio of (1) is shown in Table (20)

The flexure dominated average R-Value with the same aspect ratio tested in the SETH lab at UCI

was 2.85. This indicates that the R-values calculated in UCI SETH gave a higher average

Response Modification Factor R-Value. The higher R-Value indicates that the Insteel 3D EPS

sandwich panels tested with the same aspect ratio as the masonry walls have an ability to

withstand higher seismic loads.

Page 91 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

F.2 COMPARISONS BETWEEN UCI INSTEEL 3D EPS PANEL WALLS

and CUREe WOOD FRAME PROJECT WALLS

In the CUREe program, several cyclic wall tests performed on different wood frame wall

details with different sheathing materials. The typical wall detail is shown in Figure (E-5). 3

of these wall tests were selected as valid tests to be compared with those performed at UCI

SETH. All 3 walls had the same dimensions (8ft X 8ft) with an aspect ratio of 1.0. The

wall tests were classified according to the loading protocol used while performing the cyclic

lateral loading tests. The three loading protocols used were CUREe-Caltech Standard, as

well as the ISO and SPD loading protocols. The hysteresis of the Standard Protocol used in

shown in Figure (E-6), while those for Protocols ISO and SPD are shown in Figures (E-7)

and (E-8) respectively.

Page 92 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (F-5): Typical Wooden Project Frame Details

Page 93 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (F-6): Cyclic Load-Displacement of Specimen loaded using Caltech Standard Protocol

Figure (F-7): Cyclic Load-Displacement of Specimen loaded using ISO Protocol

Page 94 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (F-8): Cyclic Load-Displacement of Specimen loaded using SPD Protocol

F.2.1 Comparison of Seismic Response Modification Factor (R) for Insteel 3D EPS

Sandwich Panel Walls tested at UCI and Wood frame Project Wall Tests

The following are similar procedures for calculating the Seismic Response Modification Factor

(R-Value) for the Wood frame Project walls.

F.2.1.1 CUREe-Caltech Standard Wall Specimen:

Page 95 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

F.2.1.2 ISO Protocol Wall Specimen:

F.2.1.3 SPD Protocol Wall Specimen:

Table (F-2) presents a summary of the calculated R-values for the three wooden frame walls. As

shown in this table, The average R-value for the wood frame walls with the same aspect ratio

was 3.84 which about 30% higher than the Insteel 3D EPS panel walls with AR-1.0 where

Rave=2.8.

Table (F-2): Seismic Response Modification Factor for Wooden Frame Wall Tests

Wall 1 Wall 2 Wall 3

R Value 4 3.55 3.96

Page 96 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX(G)

Drift Angle Comparisons

Page 97 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

G.1 Drift Ratio for Insteel 3D EPS Panel Walls &ASCE7-05 Drift Ratio
Limits

In this section, the drift angels corresponds to the design load for each wall (using SF=2.1) were

compared with the ASCE7 limitations.

G.1.1 Wall Specimen H8-1

The load-drift angle hysteresis for specimen H8-1 curve is shown in Figure (G-1).The maximum

drift ratio corresponding to the maximum shear capacity of wall H8-1 was 0.0064 and can be

seen in Figure (G-2). The drift ratio is lower than the maximum allowable drift ratio as shown in

Table 12.12 1 in ASCE7-05. The table demonstrates that the maximum allowable drift ratio for

the case of a residential building (Occupancy category Ι or ΙΙ) and categorized as (Other

Structures) is 0.02 which is higher than the drift ratio corresponding to the maximum shear

capacity and hence also higher than the drift ratio corresponding to the allowable design load.

Therefore the wall is below the ASCE7-05 drift ratio limits.

Page 98 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-1): The load-drift angle hysteresis for Specimen H8-1

Figure (G-2): Load-Drift Envelope for Specimen H8-1

Page 99 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

G.1.2 Wall Specimen H8-2

The load-drift angle hysteresis for specimen H8-2 curve is shown in Figure (G-3). The maximum

drift ratio corresponding to the maximum shear capacity of wall H8-2 was 0.0048 and can be

seen in Figure (G-4). The figure also demonstrates the allowable design load for the wall in

accordance with AC-15 and the corresponding drift ratio of 0.0016. The drift ratio is lower than

the maximum allowable drift ratio as shown in Table 12.12 1 in ASCE7-05. The table

demonstrates that the maximum allowable drift ratio for the case of a residential building

(Occupancy category Ι or ΙΙ) and categorized as (other Structures) is 0.02 which is higher than

the drift ratio corresponding to the maximum shear capacity and hence also higher than the drift

ratio corresponding to the allowable design load. Therefore the wall is below the ASCE7-05 drift

ratio limits.

Figure (G-3): The load-drift angle hysteresis for Specimen H8-2

Page 100 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-4): Load-Drift Curve for Specimen H8-2

G.1.3 Wall Specimen P8-1

The load-drift angle hysteresis for specimen P8-1 curve is shown in Figure (G-5). The maximum

drift ratio corresponding to the maximum shear capacity of wall P8-1 was 0.008 and can be seen

in Figure (G-6). The figure also demonstrates the allowable design load for the wall in

accordance with AC-15 and the corresponding drift ratio of 0.0022. The drift ratio is lower than

the maximum allowable drift ratio as shown in Table 12.12 1 in ASCE7-05. The table

demonstrates that the maximum allowable drift ratio for the case of a residential building

(Occupancy category Ι or ΙΙ) and categorized as (Other Structures) is 0.02 which is higher than

the drift ratio corresponding to the maximum shear capacity and hence also higher than the drift

ratio corresponding to the allowable design load. Therefore the wall is below the ASCE7-05 drift

ratio limits.

Page 101 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-5): The load-drift angle hysteresis for Specimen P8-1

Figure (G-6): Load-Drift Curve for Specimen P8-1

Page 102 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

G.1.4 Wall Specimen P8-2

The load- drift angle hysteresis for specimen P8-2 curve is shown in Figure (G-7). The maximum

drift ratio corresponding to the maximum shear capacity of wall P8-2 was 0.008 and can be seen

in Figure (G-8). The figure also demonstrates the allowable design load for the wall in

accordance with AC-15 and the corresponding drift ratio of 0.0027. The drift ratio is lower than

the maximum allowable drift ratio as shown in Table 12.12 1 in ASCE7-05. The table

demonstrates that the maximum allowable drift ratio for the case of a residential building

(Occupancy category Ι or ΙΙ) and categorized as (Other Structures) is 0.02 which is higher than

the drift ratio corresponding to the maximum shear capacity and hence also higher than the drift

ratio corresponding to the allowable design load. Therefore the wall is below the ASCE7-05 drift

ratio limits.

Figure (G-7): The load-drift angle hysteresis for Specimen P8-2

Page 103 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-8): Load-Drift Curve for Specimen P8-2


G.1.5 Wall Specimen H6-1

The load- drift angle hysteresis for specimen H6-1curve is shown in Figure (G-9). The maximum

drift ratio corresponding to the maximum shear capacity of wall H6-1 was 0.0071 and can be

seen in Figure (G-10). The figure also demonstrates the allowable design load for the wall in

accordance with AC-15 which was (35.7 kips) and the corresponding drift ratio of 0.0021. The

drift ratio is lower than the maximum allowable drift ratio as shown in Table 12.12 1 in ASCE7-

05. The table demonstrates that the maximum allowable drift ratio for the case of a residential

building (Occupancy category Ι or ΙΙ) and categorized as (Other Structures) is 0.02 which is

higher than the drift ratio corresponding to the maximum shear capacity and hence also higher

than the drift ratio corresponding to the allowable design load. Therefore the wall is below the

ASCE7-05 drift ratio limits.

Page 104 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-9): The load- drift angle hysteresis for Specimen H6-1

Page 105 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-10): Load-Drift Curve for Specimen H6-1

G.1.6 Wall Specimen H6NG-2

The load- drift angle hysteresis for specimen H6NG-2 curve is shown in Figure (G-11). The

maximum drift ratio corresponding to the maximum shear capacity of wall H6NG-2 was 0.0098

and can be seen in Figure (G-12). The figure also demonstrates the allowable design load for the

wall in accordance with AC-15 which was (31.9 kips) and the corresponding drift ratio of

0.0023. The drift ratio is lower than the maximum allowable drift ratio as shown in Table 12.12

1 in ASCE7-05. The table demonstrates that the maximum allowable drift ratio for the case of a

residential building (Occupancy category Ι or ΙΙ) and categorized as (Other Structures) is 0.02

which is higher than the drift ratio corresponding to the maximum shear capacity and hence also

higher than the drift ratio corresponding to the allowable design load. Therefore the wall is below

the ASCE7-05 drift ratio limits.

Figure (G-11): The load- drift angle hysteresis for Specimen H6NG-2
Page 106 of 125
Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-12): Load-Drift Curve for Specimen H6NG-2

G.1.7 Wall Specimen P6-1

The load- drift angle hysteresis for specimen P6-1 is shown in Figure (G-13). The maximum drift

ratio corresponding to the maximum shear capacity of wall P6-1 was 0.0061 and can be seen in

Figure (G-14). The figure also demonstrates the allowable design load for the wall in accordance

with AC-15 (2010) which was 32.2 kips and the corresponding drift ratio of 0.0021. The drift

ratio is lower than the maximum allowable drift ratio as shown in Table (12.12) 1 in ASCE7-05.

The table demonstrates that the maximum allowable drift ratio for the case of a residential

building (Occupancy category Ι or ΙΙ) and categorized as (Other Structures) is 0.02 which is

higher than the drift ratio corresponding to the maximum shear capacity and hence also higher

than the drift ratio corresponding to the allowable design load. Therefore the wall is below the

ASCE7-05 drift ratio limits.

Page 107 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-13): The load- drift angle hysteresis for Specimen P6-1

Page 108 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-14): Load-Drift Curve for Specimen P6-1

G.1.8 Wall Specimen H6L-3

The load- drift angle hysteresis for specimen H6L-3 is shown in Figure (G-15). The maximum

drift ratio corresponding to the maximum shear capacity of wall H6L-3 was 0.0052 and can be

seen in Figure (G-16). The figure also demonstrates the allowable design load for the wall in

accordance with AC-15 which was (38 kips) and the corresponding drift ratio of 0.0018. The

drift ratio is lower than the maximum allowable drift ratio as shown in Table 12.12 1 in ASCE7-

05. The table demonstrates that the maximum allowable drift ratio for the case of a residential

building (Occupancy category Ι or ΙΙ) and categorized as (Other Structures) is 0.02 which is

higher than the drift ratio corresponding to the maximum shear capacity and hence also higher

than the drift ratio corresponding to the allowable design load. Therefore the wall is below the

ASCE7-05 drift ratio limits.

Page 109 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-15): The load- drift angle hysteresis for Specimen H6L-3

Figure (G-16): Load-Drift Curve for Specimen H6L-3

Page 110 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Table (G-1): ASCE7-05 Table for Maximum Allowable Drift Ratios

The for the 8ft high walls are shown in Figure (G-17). The 6ft high wall specimen Load-Drift
angle envelopes are shown in Figure (G-18). Figure (G-19) show the Load-Drift angle envelopes
for all wall specimens.

Figure (G-17): Envelopes for 8ft High Walls Aspect Ratio 1

Page 111 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (G-18): Envelopes for 6ft High Walls Aspect Ratio 0.75

Figure (G-19): Envelopes of Load-Displacement for all Wall Specimens

Page 112 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX(H)
Insteel 3D Panel Wall Details

Page 113 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (H-1): Wall Elevation

Page 114 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Figure (H-2): Wall Cross Sections Details

Page 115 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Detail A

Mortar shell

Wire mesh

#4 Dowels embedded 6 " into


the footing and 18 " in the
morter shell (Foam Core is
burned around the dowels to
insure that dowels are fully

18"
embedded) HILTI Concrete footing
Anchoring
Epoxy

6"

18"

36"

Figure (H-3): Typical Wall Anchors Details

Page 116 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Detail B

2" of the foam core


removed at each
each wall end and
filled with mortar

18"
16" 3"
2"

Figure (H-4): Typical Wall End Anchors Details

Page 117 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Detail C

12" wide wire mesh strip at


the connection of two panels

12"

Foam core

Wire mesh Mortar shell

Figure (H-5): Panel to Panel Connection Detail

Detail D

Mortar shell
6"

Foam core

Wire mesh
6" x 6" 90 degree angle
wire mesh

Figure (H-6): Typical Wall End Details

Page 118 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

APPENDIX(I)
Samples of Steel Wires & Rebars
Stress-Strain Curves

Page 119 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Page 120 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Page 121 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Page 122 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Page 123 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Page 124 of 125


Report No. SETH-preliminary report 3D-ICC-ES01-11June 2011
Large-Scale Structural Evaluation of Insteel 3DTM EPS Wall Panels Subjected to Cyclic Shear Tests

Page 125 of 125

You might also like