FAQ February 19, 2008

W h at ’ s t h e d i f f e r e n c e b e t w e e n
“ E x p l o s i o n P r o o f ” & “ I n t r i n s i c a l ly S a f e ”
Electrical equipment sometimes must be installed in areas Intrinsically Safe
where combustible vapors and gases are used or may
be present. These are commonly referred to as “hazard- An “intrinsically safe” classification and design means
ous locations”, and are defined by the National Electrical that an electronic circuit and it’s wiring will not cause any
Code (NEC) in the US, or the Canadian Electrical Code sparking or arcing and cannot store sufficient energy to
(CEC) in Canada. When equipment must be installed in ignite a flammable gas or vapor, and cannot produce a
hazardous locations, there are strict requirements for the surface temperature high enough to cause ignition. Such
construction of the installation, including materials and a design is not explosion proof, nor does it need to be.
design requirements. To prevent inadvertent ignition of For permanent installations, such an installation may
flammable gases and vapors by electrical equipment, the include “intrinsically safe barriers” that are located outside
two most common methods of protection are “Explosion the hazardous location, and limit the amount of energy
Proof” and “Intrinsically Safe”. We will discuss these available to the device located in the hazardous area.
methods as they relate to gas detection equipment. The North American classifications for hazardous locations
as related to flammable gases and vapors:
Explosion Proof
Class I: Gases and vapors
Generally speaking, “explosion proof” is the more com-
monly used method for detector/sensor assemblies for Division 1: Gases or vapors are usually present and/or
fixed gas detection systems, where higher voltages and may be present at any time in sufficient concentrations for
power requirements may be encountered, and the instal- an explosion hazard.
lation is permanent. Intrinsically safe method can also be Division 2: Gases or vapors are not normally present and
used for permanent installations where the detector/sen- are present only in the event of a leak in some kind of
sors are relatively low power devices. Almost all portable containment vessel or piping, again in potentially hazard-
instruments use the “intrinsically safe” method. ous concentrations.
An “explosion proof “ classifi- Groups A, B, C, D: Groups of atmospheres categorized
cation for a sensor/transmitter by the volatility and/or ignition temperatures. “A” is the
means that the housing has most hazardous and “D” is the least hazardous group for
been engineered and con- gases and vapors.
structed to contain a flash or explosion. Such housings
Group A: Atmospheres containing acetylene.
are usually made of cast aluminum or stainless steel and
are of sufficient mass and strength to safely contain an Group B: Atmospheres containing hydrogen or gases or
explosion should flammable gases or vapors penetrate vapors of equivalent hazard.
the housing and the internal electronics or wiring cause an Group C: Atmospheres containing ethyl-ether vapors,
ignition. The design must prevent any surface tempera- ethylene, or cyclo-propane.
tures that could exceed the ignition temperature of the Group D: Atmospheres containing gasoline, hexane,
gases or vapors covered by its Group rating (see below). naptha, benzene, butane, propane, alcohol,
If the sensing element is a high-temperature device (e.g. acetone, benzol, lacquer solvent vapors, or
Catalytic bead or “pellistor”), it may be protected by a natural gas (methane).
flame arrestor to prevent the propagation of high tempera-
ture gases to the ambient atmosphere.

RKI Instruments, Inc., 33248 Central Ave., Union City, CA 94587


Phone (800) 754-5165 or (510) 441-5656
www.rkiinstruments.com