Applicable for outgoing motor

1. ACID GAS INCINERATOR - AIR BLOWER

Data sheet motor :


cos phi : 0.88 Total Qty : 9 Pcs (3sets of panel)
Id (starting current - locked rotor) : 600 %
starts/hour :3
starting time : 39s
service factor :1
motor efficiency : 95.7 %

Motor Typical rating 510kW

Motor Data

Power (P): 510000 W


Nominal Current (In): 53 A
Starting Current (Istart): 318 A (Istart = 6 x In)
Starting Time (t): 39 sec.
Maximum number of start/hour (n): 3 at warm (Equal to derating factor d = 1.8)

Current Selection
I = d x Istart
= 1.8 x 318
= 572.4 A

Time selection n = 125% for >25s


T = nxt
= 1.25 x 39
= 48.75 s

Selected fuse-SIBA as shown in below figure is 200A

49s

572A
Applicable for outgoing motor
1. MEMBRANE PERMEATE INCINERATOR - AIR BLOWER

Data sheet motor :


cos phi : 0.86 Total Qty : 6 Pcs (2sets of panel)
Id (starting current - locked rotor) : 600 %
starts/hour :3
starting time : 36s
service factor :1
motor efficiency : 95.5 %

Motor Typical rating 450kW

Motor Data

Power (P): 450000 W


Nominal Current (In): 47.9 A
Starting Current (Istart): 287 A (Istart = 6 x In)
Starting Time (t): 36 sec.
Maximum number of start/hour (n): 3 at warm (Equal to derating factor d = 1.8)

Current Selection
I = d x Istart
= 1.8 x 287
= 516.6 A

Time selection n = 125% for >25s


T = nxt
= 1.25 x 36
= 45 s

Selected fuse-SIBA as shown in below figure is 160A

45s

517A