You are on page 1of 4

Incus Ultrasonic Gas Leak Detector Product Data Sheet

FGD_PDS_Incus_Ultrasonic_Gas_Leak_Detector November 2014

Incus Ultrasonic Gas Leak Detector


Wide Area Coverage for Pressurized Gas Leaks
The Incus is an advanced gas leak detector that
uses four sensitive acoustic sensors to monitor
wide areas for the ultrasound generate from
pressurized gas releases.

Ideally suited for monitoring ventilated outdoor applications,


the Incus has been engineered to withstand extreme
conditions. Detection is unaffected by inclement weather, wind,
leak direction, or gas dilution, with fast speed of response.
„„ Instantaneous response to all gas leaks (LEL or ppm)
„„ Operates in extreme temperatures
„„ Automated electronic self-test offers failsafe operation
„„ Widest area of coverage through four independent sensors Incus
„„ 4–20 mA analog or stepped, “multi-drop” RS485 digital
interface, and HART® communication protocol
„„ Certified worldwide for hazardous locations Sensor Design - They Just Keep Working
„„ Innovative mapping tool helps optimize coverage for a Each sensor is completely free of moving parts and will not
target risk age, drift, and never need replacing under normal operating
„„ Programmable time delays screen intermittent unwanted conditions. Maintenance free protection
alarm sources with proven reliability.

Four Multi-Directional Sensor Heads Continuous Self-test Ensures


Quad sensing heads provide the widest overall detection range
available on the market. The sensing heads are independent Instrument Health
with the detector output being based on the highest ultrasound Electronic self-test checks the detector every 320 ms by
measured by any one head. If one or more sensing heads fails sending an amplitude signal through the sensing circuitry.
complete coverage is not lost. The sensor suffers no loss of detection while in test mode in
contrast to those based on diaphragm microphones.

Field-proven Ultrasonic Sensor Principle


Incus responds to the ultrasound produced by pressurized Built for Extreme Conditions
gas releases, a technology proven with hundreds of detectors The Incus is designed to operate at -40 °C to +85 °C and may
installed worldwide. be supplied for monitoring areas of regard at -55 °C. Corrosion
resistant stainless steel housing is standard, units are ingress
rated to IP66/67 or NEMA Type 4X.
Sealed Ceramic Sensor Housing
Piezo-electric sensor heads are encased in a ceramic housing
and sealed against temperature, moisture, corrosive
atmospheres, and industrial contaminants.
IGNITION Wide Area
Explosive Fire

IGNITION
IGNITION Deep Pool
Fuel Fire

Incus Ultrasonic Gas Leak Detector DETECT DISTINGUISH


November 2014
DEFEND
Ultrasonic Gas Fixed Combustible Fixed Toxic Optical
Leak Detection Gas Detection Gas Detection Flame Detection
RESPONSE LEVEL 1 RESPONSE LEVEL 2 RESPONSE LEVEL 2 RESPONSE LEVEL 3

Ultrasonic Detection Overview


Ultrasonic (acoustic) gas leak detection technology functions Figure 2
through the constant monitoring of wide areas by advanced
Audible Sound 0 KHz to 20 KHz - Turbines, motors, and Incus Detection Range
acoustic sensors specially tuned to process ultrasound emitted compressors generate within this frequency range Ultrasonic Sound 25 KHz to 100 KHz

from pressurized gas leaks. Ultrasonic gas leak detectors


do not have to wait until a hazardous gas concentration has Human Hearing Range Beyond Human Hearing Range
accumulated or the gas cloud made physical contact with a
sensor. In addition, the response is instantaneous for all gas
Figure 3
types (Figure 1).
Pressurized Gas Release Response Levels — Detect • Distinguish • Defend

Simply put, the ultrasonic gas leak detector only triggers an Pressurized
Gas Leak
Explosive Clound
Formation
Toxic Cloud
Formation
Liquid
Accumulation
EXPLOSION
EVENT
alarm when inaudible, ultrasound is detected (between 25 and
100 kHz), which is only produced with the release of highly IGNITION High Pressure
Jet Fire

pressurized gas (Figure 2). This makes for reliable and efficient Wide Area
IGNITION
Explosive Fire
detection, since ultrasonic gas leak detectors are immune to
IGNITION
IGNITION Deep Pool
poisoning, it never requires field calibration, and all intermittent Fuel Fire

sources of background ultrasound noises may be ignored by


time delay settings.
DETECT DISTINGUISH DEFEND
Ultrasonic Gas Fixed Combustible Fixed Toxic Optical
Leak Detection Gas Detection Gas Detection Flame Detection
RESPONSE LEVEL 1 RESPONSE LEVEL 2 RESPONSE LEVEL 2 RESPONSE LEVEL 3

Figure 1

Audible Sound 0 KHz to 20 KHz - Turbines, motors, and Incus Detection Range
compressors generate within this frequency range Ultrasonic Sound 25 KHz to 100 KHz

Human Hearing Range Beyond Human Hearing Range

The Incus detects gas leaks at the speed of sound while providing wide area coverage. It is unaffected
by inclement weather, wind, leak direction, and gas dilution or stratification. When used with
Emerson’s point gas and optical flame detectors, a complete and comprehensive safety system is
ensured (Figure 3).

2 www.EmersonProcess.com/Safety
November 2014 Incus Ultrasonic Gas Leak Detector

Specifications
Table 1 - Incus Ultrasonic Gas Leak Detector

General Specifications Incus


Detection Frequency Range 25 kHz to 100 kHz
Dynamic Range 40–120 dB (standard); 58 to 104 dB or 40–200 dB
Area Coverage 2 to 40 meter (7 to 130 feet) radius (leak pressure, size and background level dependent)
Response Time Instantaneous (< 1 s - speed of sound)
Programmable Alarm Delay Configurable alarm delay via one second increments
Operating Temperatures -40 °C to +85 °C (-40 °F to +185 °F), option -55 °C (-67 °F), NOT c FM us approved
Operating Humidity Range 0 to 100 % RH, non-condensing
Self Test Continuous electronic check of sensor integrity
Ingress Protection Rated IP66/67 & NEMA Type 4X to withstand harsh environments
Enclosure Material AISI 316 Stainless Steel
Mounting Bracket AISI 316 Stainless Steel (included)
Weight (with bracket) 18 kg (40 lbs)
Conduit Entry ½'' or ¾'' NPT Available as Single Entry (all listings) or M20/M25 Single Entry and all Dual Entry (all listings EXCEPT FM)
Analog [0 mA: Zero/Low Power,
Two Form C Relay Contacts
Output Signals 0.5 mA to 4.0 mA: Detector faults, RS-485 Digital Interface HART® Protocol
[Error/Fault, Alarm, Maintenance]
4–20 mA]
ATEX Ex d ib IIB+H2T4 Gb (Tamb -40 °C to +85 °C); (Tamb -55 °C to +85 °C) option
IECEx ITS 10.0004X
GOST K
KOSHA: 14-KB4BO-0294X
EMC: EN 50270 2006, EN 61000-6-3 2007, EN 61000-6-2 2005
Approvals/Classifications
ABS: 13-LD1021861
DNV: A-13745
SIL 2 suitable
c FM us CL1 Division 1, GP B, C, D T4
CL1 Zone I, AEx/Ex d ib IIB+H2 T4
Input Voltage 24 Vdc (15 to 30 Vdc)
Power Consumption 250 mA - standard operation
Warranty 18 months after shipment or 12 months after installation, whichever comes first

ORDERING INFORMATION
Accessories

- GDU-01-TT
Test Transmitter: Handheld
Rechargeable Ultrasonic Sound
Emitter

- GDU-01-MT
Mapping Tool: Handheld Rechargeable
Ultrasonic Sound Receiver

- GDU-PTV
Performance Target Verification Kit

www.EmersonProcess.com/Safety 3
Incus Ultrasonic Gas Leak Detector Product Data Sheet
FGD_PDS_Incus_Ultrasonic_Gas_Leak_Detector November 2014

Emerson Process Management


Ultrasonic Gas Leak Detection
and Gas & Smoke Aspirated Sampling Systems
Unit 18, Somerford Business Park, Wilverley Road,
Christchurch, Dorset, BH23 3RU, UK
T +1 855-724-2638 (855 RAI-AND-U)
T + 44 (0) 1202 400630
F + 44 (0) 1202 496796
©2014 Emerson Process Management. All rights reserved.
www.emersonprocess.com/safety
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks
Emerson Process Management are the property of their respective owners.
Flame & Gas Detection
2721 Hopewell Place NE The contents of this publication are presented for information purposes only, and while effort
Calgary, Alberta, Canada T1Y 7J7 has been made to ensure their accuracy, they are not to be construed as warranties or
T +1 855-724-2638 (855 RAI-AND-U)
T + 1 (403) 219 0688 guarantees, express or implied, regarding the products or services described herein or their
T +1 866 347 3427 use or applicability. All sales are governed by our terms and conditions, which are available on
F +1 (403) 219 0694 request. We reserve the right to modify or improve the designs or specifications of our products
www.emersonprocess.com/safety at any time without notice.