Scania DEC2 control system


Tuning and calibration
Dealer version

Part. No.
1 588 594 ©
Scania CV AB, Sweden, 1999-01:1
Important information

• Changes must not be made to the DEC2 control unit or sensors and wiring. Doing so
may effect the control unit’s safety system and cause damage to the operator, the
engine or driven equipment.
• The sensors for the DEC2 control system are dedicated for use in DEC2 only.
• Check that the cables for the battery and alternator/s are properly connected before
starting the engine as otherwise the DEC2 control unit might be damaged.
• Before disconnecting the cable to the control unit, all power to the unit should first
be switched off. If not, the DEC2 control unit may be damaged.
• Disconnect the DEC2 control unit when boost charging the battery to avoid damag-
ing the control unit.
• Never splice a damaged cable. Change the entire cable, otherwise the safety and
operation of the system could be impaired.
• Disconnect the battery if arc welding in order to avoid damage to the DEC2 control
unit.

Contents
Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Tuning: All speed or single speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Change of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Explanation of the other parameters shown on the Tuning screen . . .6
Explanation of the Function keys . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Governor Configuration: All speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Change of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Governor Configuration: Single speed . . . . . . . . . . . . . . . . . . . . . . . . . .9
Change of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Governor Calibration: All speed and single speed . . . . . . . . . . . . . . . .10
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Calibration procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Saving the calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Calibration has failed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Final check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Possible fault messages that can occur during calibration . . . . . . . .15

2 ©
Scania CV AB, Sweden, 1999-01:1 03:02-03
Start-up procedure
Note The PC should only be connected to the control unit using a special cable marked
DEC at one end and PC at the other, after the cover over the COMM/DIAG PORT has
been removed. The program can only be started if the PC is connected to a powered
control unit. However, the program menu below can be reached without powering
the control unit.

- Log in and open the file manager. GOVERNOR DIAGNOSTIC SYSTEM V4.0
- Open the program directory DEALER. - DEALER Version
ALL SPEED Application
- Open the appropriate program:
- 1002DXX1)A.EXE for all speed engines or
- 1002DXXS.EXE for single speed engines
GOVERNOR DIAGNOSTIC SYSTEM V4.0
- 1002DXXC.EXE for all speed engines DEALER version
(OEM only) SINGLE SPEED Application
- When the program starts, it first states version
and type of application: all speed or single or
speed.
- Press any key to continue. GOVERNOR DIAGNOSTIC SYSTEM V4.0
DEALER version
1) ALL SPEED with J1939 Communication Application
XX is a version number of the program that is
changed at program changes e.g. 61.

03:02-03 ©
Scania CV AB, Sweden, 1999-01:1 3
- In the Main Menu there are three alternatives:
Tuning, Configuration and Calibration. Governor
<T> Tuning
- Press the T, K or C key for wanted alternative. <K> Configuration
<C> Calibration

Tuning: All speed or single speed

Cntl Gain 6 CNT


Cntl Stability 4 CNT Act Gain 5 CNT
Cntl Deadtime 2 CNT Act Stability 8 CNT

4 ©
Scania CV AB, Sweden, 1999-01:1 03:02-03
General • Cntl Deadtime which gives a quick change of
the fuel supply at a quick change of the
When the chosen menu appears, the following speed.
applies when changing values: • Act Gain and Act Stability show the setting
- The Tab key moves the user forward between of the solenoid on the injection pump and
the modifiable parameter fields. See picture. affects its sensitivity to the output signal from
the control unit.
- When the cursor hits a new field, this is high-
lighted. Approximate values for these five parameters are:
Single speed All speed
- With Shift+Tab the cursor is moved backwards
between the modifiable parameter fields. Cntl Gain 15 6
- When pressing the space bar, the user is Cntl Stability 15 3
prompted for a new value.
Cntl Deadtime 1 1
- Enter the new chosen value.
Act Gain 7 4
- Confirm by pressing Enter.
Act Stability 15 10*)
- Save by pressing F2. See page 7.
*) Never choose a value less than 10.
- A higher value gives a faster governing.
Change of parameters
- A lower value gives a slower governing.
In the menu for Tuning the following parameters
can be changed. Note Make changes in small steps (nor-
For the governor there are three alternatives that mally 1 or 2), if change is necessary.
control the governing of the engine:
• Cntl Gain governs the magnitude of the fuel
supply change at a deviation in speed.
• Cntl Stability adjusts the quantity of fuel to
the engine until the speed error is eliminated.

03:02-03 ©
Scania CV AB, Sweden, 1999-01:1 5
Explanation of the other parameters shown on the Tuning screen

Speed Droop = Calculated speed reduction Boost Press = Absolute charge air pressure
depending on current speed droop. after the turbo charger
Velocity = Actual speed Atemp LOP = Shows the limit value (warning
level) for charge air temp. when operation
Starting Fuel = Max control rack travel during turns into limited power level (POWER- ).
start (cranking cycle).
Etemp LOP = Shows the limit value (warning
Actual Fuel = Current control rack travel level) for coolant temperature when operation
Operating Mode = Shows actual operating turns into the limited power level (POWER- ).
mode Eng. Shutdn = Shows limit value (shutdown
Air Temp = Air temperature in inlet manifold level) for coolant temperature when engine is
stopped by the control unit (if chosen by DIP
Engine Temp = Coolant temperature in switch 4 on the control unit).
engine
OS Limit = Shows at which overspeed value
Load = Shows actual load at current speed. the engine will be stopped.
Speed Request = Requested speed signal OS Time Limit = Shows the time delay
from throttle position sensor. between overspeed and engine shutdown.
Torque Limit = Shows max control rack travel Speed Accel = Shows the acceleration time
in the torque limiter map at current speed . for the control rack to reach the programmed
max travel.
Boost Fuel = Shows max control rack travel
in the smoke limiter map at current speed and Speed Decel = Same as speed acceleration
boost pressure. but now from max travel down to min travel.
Oil Pressure = Oil pressure in engine The actual ramp time will be somewhat
shorter than the entered value for Speed
Atmospheric P = Displays the atmospheric
Accel and Speed Decel .
pressure before the cranking cycle. This
value is updated before each startup.

6 ©
Scania CV AB, Sweden, 1999-01:1 03:02-03
Explanation of the Function keys

F1 - Refresh = All recorded parameter values F3 - File = This key prompts the user for a file
in the control unit are refreshed and name in order to store the parameters that
displayed on the screen can be modified in a separate file. This file
can be printed and saved for reference or
F2 - Save = All of the modifiable values, that trouble shooting
are displayed on the screen, are saved and
stored in the permanent (non-volatile) control F5 - Cont = The screen is updated approx.
unit memory. every second when depressed. The function
is interrupted if F5 is pressed again.
Each value is now retrieved at every reset
until it is changed again. If a parameter value F6 - Log = Shows the fault log menu
is not saved in this way after a change, the
last saved value will be shown at reset. ESC = This option will return the user to the
previous screen

03:02-03 ©
Scania CV AB, Sweden, 1999-01:1 7
Governor Configuration: All speed

Min Spd Req 700 RPM


Droop Map 1 4.69 %
Droop Map 1 10.16 %

General In order to switch between Droop 1 and Droop 2,


the position of DIP-switch 8 underneath the round
When the chosen menu appears, the following black cap on the control panel must be changed.
applies when changing values: Position OFF means Droop 1.
- The Tab key moves the user forward between
the modifiable parameter fields. See picture. Explanation of the other parameters
- When the cursor hits a new field, this is high- shown on the Configuration screen:
lighted. Teeth = number of teeth on the flywheel ring
- With Shift+Tab the cursor is moved backwards gear
between the modifiable parameter fields. Max Spd Req = In the Unloaded mode, the
- When pressing the space bar, the user is given value is high idle speed (DIP switch 7 in
prompted for a new value. position ON)

- Enter the new chosen value In the Loaded mode, the given value is the
full load speed (DIP switch 7 in position OFF).
- Confirm by pressing Enter.
Surge time = shows the time period during
- Save by pressing F2. See page 7. which the engine can be run at a higher
power level (torque map 2) (OEM only)
Change of parameters Recovery time = shows the time period dur-
ing which the engine must run acc. to torque
In the menu for Governor Configuration the fol- map 1 before the higher power level (torque
lowing parameters can be changed: map 2) can be used again. (OEM only)
- Low idle (Min Spd Req). Actual low idle is
governed by the speed droop. Note It is not standard with two different
torque maps. As standard Map1=
- Speed droop (Droop 1 and Droop 2)
Map2
Values between 0-20 % are accepted for the
speed droop. Normally only map 2 is used for
governing of speed droop.

8 ©
Scania CV AB, Sweden, 1999-01:1 03:02-03
Governor Configuration: Single speed

Max Spd Req 1800 RPM


Idle Speed 700 RPM Min Spd Req 1500 RPM
Droop Map 1 4.69 %
Droop Map 2 10.16 %

Change of parameters This applies if droop has been chosen with switch
S16. For further information on switching
In the single speed version, two operation speeds between isochronous and droop operation, see
can be adjusted. installation instruction.
- The two speeds most common for gensets, There is a possibility to externally switch between
1500 or 1800 rpm can be preprogrammed. Min the low idle (Idle Speed) and operation speed
and max speed are programmed at the same (high idle) with an extra switch S24, Run/Idle,
level when delivered from Scania. connected to the control unit.
- If both 1500 and 1800 rpm are requested, this When the Run/Idle input on the control unit is
has to be specified separately when ordering switched to Battery-, the engine runs in idle and
the engine. when it is switched to Battery+, the engine will
run in the operation speed wanted.
If there is a need for switching the speeds,
DIP switch No. 6 underneath the round black cap
on the control unit must be changed.
- Normally the speed is 1800 rpm with the
switch in the ON position and 1500 rpm in the
OFF position.
- Values between 0-20% are accepted for the
speed droop. When the engine is delivered
from Scania, map 2 is used for the setting of
speed droop.

03:02-03 ©
Scania CV AB, Sweden, 1999-01:1 9
Governor Calibration: All speed and single speed

General
The menu for calibration of the governor gives the
possibility to calibrate and match the injection
pump against the control unit.
2 1
This calibration should be performed when any of
these components have been exchanged.
- Remove the round black cap over the DIP
switches in the control unit.
- Remove the red CAUTION label on the control
unit, carefully not to damage the label, to ABC
expose the calibration hole. After the calibra-
tion, the label should be put back to cover the
hole.
7
1

- Remove the cover over the COMM/DIAG 3


PORT and connect the computer cable with
12
12

DEC end to this port.


- Connect a multimeter with + (plus) to the mea-
suring pin (1) in the control unit and with
– (minus) to the brown cable marked TPSR
(A7=pin 7 in row A) in the main connector.

Note It is important to use a calibrated


multimeter in order to get accurate
voltage readings.

10 ©
Scania CV AB, Sweden, 1999-01:1 03:02-03
20.3

The calibration procedure involves the adjustment Calibration procedure


of two voltage levels:
- at control rack travel = 0 mm and - Turn on the power to the control unit.

- at control rack travel = 20.3 mm. - Open the appropriate program:

This is done with two trim pots located at posi- - 1002DXX1)A.EXE for all speed engines
tions 2 and 3 in the control unit picture on - 1002DXXS.EXE for single speed engines
page 10.
- 1002DXXC.EXE for all speed engines
Both trim pots are adjusted in the same way,
(OEM only)
meaning that when you turn them clockwise, the
voltage reading will increase and vice versa. 1)
XX is a version number of the program that is
However, the resulting effect is different. changed at program changes e.g. 61

- trim pot 2 moves the entire measuring range - Choose Calibration from the main menu by
i.e. both values are increased or decreased. pressing key C.
- trim pot 3 increases or decreases the measuring - Put DIP switch 3 in the OFF position. See pic-
range between the two values. ture below.
- Then press A for Actuator Calibration

DIP switch 3

03:02-03 ©
Scania CV AB, Sweden, 1999-01:1 11
In the first screen picture (page 11), the control - The value should be 4.54 (4.50 - 4.58) VDC.
unit will ask for a value for max. control rack
travel. - Adjustment to reach these values is done with
calibration screws 2 and 3.
- First read off the voltage value on the multime-
ter with control rack travel = 0. The voltage - Repeat the procedure and check that the correct
should be 0.454 (0.450-0.458) VDC. values have been obtained.
- Then write the value 20.3 and press Enter. Note It can happen that the control unit
See picture on page 11. switches to Shutdown during the
- The control unit now moves the control rack calibration. By turning off power to
twice to max and then back to zero. At the the control unit momentarily, the
same time Sending fuel rack travel .... is shown function is reset to normal and the
on screen. calibration procedure can be
resumed.
- Read off the highest voltage value when the
control rack reaches max travel (twice).

12 ©
Scania CV AB, Sweden, 1999-01:1 03:02-03
Saving the calibration

When the calibration procedure has been com- - Check that a green text flickers in the lower left
pleted and accepted, the message Calibration has hand corner, which confirms that the save
passed appears. function is working.
Save the calibration in accordance with the fol- - Put DIP switch 3 in the control unit in the ON
lowing: position (standard position).
- Press the space bar so that the text Enter choice - Press ESC twice and confirm with Y to Exit.
appears.
- Save Calibration by pressing F2.

03:02-03 ©
Scania CV AB, Sweden, 1999-01:1 13
Calibration has failed Final check
- If the calibration values are outside the Turn off the power to the control unit and then
approved range, the message Calibration has power the unit again.
failed will appear.
- Open the Calibration window and check the
- In this case the Calibration procedure has to be values for Act F/B Offset and Act F/B Range.
repeated from the start.
- Act F/B Offset should be within
81-102 CNT (RV=0).
Note It can happen that the calibration
fails although the voltage values are - Act F/B Range should be within
correct. In this case it is also neces- 921-942 CNT (RV=20.3).
sary to repeat the calibration proce-
dure. - Press F3 if you want to store the data in a sepa-
rately named PC file.
- Exit the program as before and turn off power.
- Disconnect the computer cable and restore the
control unit to normal.

14 ©
Scania CV AB, Sweden, 1999-01:1 03:02-03
Possible fault messages that can occur during calibration

• If calibration fails although both high and • If the following text appears on the screen:
low voltage values are correct and the CNT Press any key to continue (blue text) and
values are within the tolerence range, Sending fuel rack travel.......0 (green text):
proceed as follows: - Press the space bar.
- Exit the DEC2 calibration program.
• If the following text appears on the screen:
- Turn off the main switch for powering the Press any key to continue (blue text) and Cal-
control unit. ibration has failed (green text):
- Put back DIP switch 3 in the ON position. - Press the space bar.
- Resume the Calibration procedure from the • If the following text appears on the screen:
start on page 11. Would you like to (R)etry, (D)isable, or
(Q)uit (blue text) and Comm Error while
• If Shutdown occurs and the LED lights up on reading byte/word, data (e.g.) CCEF,
the control unit, momentarily turn off power status = 10 (green text)
to the control unit and then resume the cali-
- Press the Q key and restart the Calibration
bration procedure.
procedure from the start on page 11.
• If the following text appears on the screen:
Press any key to continue (blue text) and
Error communication failure, Status: (e.g.)
E000 (red text):
- Press the space bar.

03:02-03 ©
Scania CV AB, Sweden, 1999-01:1 15