Job Information
Job01
TIG
General Data
Evaporator Information
Evaporator application Standard cooling Evaporator configuration 1 pass evaporator
Evap fouling factor 0,0176 m2-deg K/kW Flow switch Factory installed 35 cm/s
Leaving fluid evap 7,00 C Saturated evap temp - ckt 1 7,2 C
Entering fluid evap 14,96 C Saturated evap temp - ckt 2 3,7 C
Flow evap 130,00 m3/hr Min flow evap 83,35 m3/hr
Fluid pressure drop evap 21,1 kPa Fluid pressure drop min flow 8,70 kPa
Evaporator fluid type Water Evap fluid freeze point 0,00 C
Evap fluid concentration --
Condenser Information
Electrical Information
Incoming unit power line connection Dual point unit power Short circuit current rating Default amp rating
Unit voltage 380.V/60.Hz/3 phase Power line connection type Terminal block
Total power 362,3 kW Dual point power MCA - ckt 1 556 A
Compressor power 335,7 kW Dual point power MCA - ckt 2 324 A
Compressor 1A - RLA/AFD input 199,00 A Dual point power MOP - ckt 1 800 A
Compressor 1B - RLA 245,00 A Dual point power MOP - ckt 2 500 A
Compressor 2A - RLA/AFD input 240,00 A
Physical Information
Job Information
Job01
TIG
Acoustical Performance
Unit sound package Standard noise
A-weighted sound power 105 dBA A-weighted sound pressure * 77 dBA
A-weighted 75% sound power 101 dBA A-weighted 75% sound pressure 73 dBA
A-weighted 50% sound power 98 dBA A-weighted 50% sound pressure 71 dBA
A-weighted 25% sound power 93 dBA A-weighted 25% sound pressure 66 dBA
Note: * At 30 feet in free field.
This unit complies with the efficiency requirements of all versions of ASHRAE Standard 90.1 and
CANS/CSA C743.
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program,
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units
may be found in the AHRI Directory at www.ahridirectory.org.
This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 and CANS/CSA C743
version 2007 (which are based on AHRI standard rating conditions) and, therefore, also meets the LEED "Minimum
Energy Performance" prerequisite in the Energy and Atmosphere section.
The LEED Green Building Rating System™, developed by the U.S. Green Building Council, provides independent, third-party verification that a
building project meets green building and performance measures.