Inverse Definite Minimum Time
Description
21JM70
The relay comprises 2 die-cast frame, which carries all the sub-
assemblies of induction disc, electro-magnetic system,
operating coil, plug bridge and the contact assembly.
Instantaneous ‘high-set and directional elements canbe
provided. The electro-magnetic system comprises primary and
secondary magnets arranged with four air gaps each
contributing to the driving toraue. The primary coil energizes
the primary magnet and a secondary winding which in turn
energizes the secondary magnet. Teppings on the primary coil
permit various fault settings to be made via a plug-bridge, The
plug -bridge automatically selects the highest setting wnen the
setting-plug is withdrawn,
Two normally open contacts are provided of the bridging type,
the operating arm being driven by a cam track atthe nub of the
naduction disc. This gives considerable mechanical advantage
and ensure high contact pressures, even at low operating
current levels, making the contact suitable for direct tripping
Relay operating time is determined by the starting position of
the induction disc, this is set by the time multiplier dial
calibrated from 0.1 to 1.0, there is also “T" mark, before the
(0.1 setting, inthis position the contacts are held closed, locked
ut. Setting are applied ampere
2TJM71
The type 2TJM71 relay is basically similar to the type 2TIM7O,
the exception being the addition of a miniature instantaneous
high-set over current element (type MCAA) which is fitted to the
‘movement frame and has its operating coil connected in series
with the relay primary coil, The element is of the attracted
armature type and primarily designed for use with I.D.M.T.L.
relays. The over current setting is continuously variable by
‘means of the calibrated cam. This element may be ‘locked out”
by advancing the setting adjuster to its extremity, i.e. past the
highest fault setting. The flag indicator shows on operation and,
‘sand reset by a push fitted inthe relay cover.
2TJM72
This relay comprises the |.D.M.T.L. element previously
described and a directional element type ‘ES’. The elements are
vertically mounted on a mild steel backplate with the
directional element in the upper position; the composite relay is
then housed ina 11/2 pote vertical case.
Peace
The directional element operates on the induction watlmeter
principle and consists essentially of an aluminum sector
‘mounted on a vertical spindle and arranged to rotate in the air
ap between the magnetic fields derived from the line current
and voltage transformers. The electro magnetic system with
the three coils which provide loss of voltage compensation ang
hence reliable operation should the line voltage be reduced,
under fault conditions, tovalues as low as 2% of nominal
Under healthy system conditions or under fault conditions
where the current flow is in the normal direction eddy currents
induced in the sector produce a torque, the direction of which
restrains relay operation. Should current reversal occur, then
the direction ofthe torque reverses causing the moving system
to rotate and thus close the contact, the latter being so
connected that they complete the .D.M.T.L. element
operating coil circuit
‘The maximum torque exerted on the movement occurs when
the voltage and current in the coils are in phase. However, 28
the system power factor may be considerably removed from
tunity under fault conditions, depending on both the nature of
the fault and system conditions, the element can be supplied
with a phase-angle introduced by fault conditions. This is
achieved by employing a suitable shading ring, the requisite
value of resistance and tne appropriate connection,
‘Type 2TJM70 Single Pole Relay
Phase-fault Relays: 45degree Lead Power Factor
Characteristic: Relays supplied with the 45 degree lead power
factor characteristic utilize the 90 degree connection, ie,
relays monitoring A-phase current are polarized by B-C
voltage, thus the relay develops maximum torque with 2 45
degree lagging fault current.rth-fault Relays : Earth-fault relays are normally supplied
with 12 % degree lagging power factor characteristic. The
current coil is connected in the residual circuit of the line
current transformers and the voltage coil in the open delta
tiary winding ofthe line voltage transformer, the voltage coil
being suitable for 190V and 63.5V on resistance and solidly
earthed systems respectively.
Directional earth fault relays with a 45 lagging power factor
characteristics are used in highly inductive earthling systems.
The characteristic is achieved in the relay with a RC circuit in
the ES element.
Features
No standing drain on substation battery supplies
Easy totest and maintain
Extremely long service life
Designed to comply with IEC 60255 specifications (where
applicable)
The 2TJM range isas follows:
+ ZTJM 70 Normal inverse IDMTL form 1.3/0 (1.3 sees for
10times Current)
+ 21JM71 IDMTL+ High -set element
+ 21JM72 Directional IDMTL.
Technical Information 2TJM70
Rating
O.5A,1A,2A0rSA
‘System Frequency :
50Hz
Current Settings
ang Range | Steph Taig
0802 028 n
O04 005 z
oa i
25
02.
025) 5
08: =
125 —[ps
Pick-up current: Not greater than 130% of plug-setting
Reset current Not ess than 95% of plug-setting
De
Fig 2 : High-Set element MCAA
Time Settings
Time Multiplier ":0.1 to 1.0.continuously
Adjustable with 0.05 Calibrated Marking
Operating time : See Fig J for time/current characteristics
Short Term Overload (2TJM70 For 1.8 Sec}
me | AM
fea
barn
Zanwe on | S0vsetng-nexet 250A
satoun. | eta” | Sov sete
Got | Sot setie-maxot 250.4
0.581024 | 50.xsetting - max of 250 A
1atowTL | 0.2 t00.8a | 50 xsetting
ol toa4a | 50xsetting
Burden
‘3 VAat current setting
Output Contacts
2 normally open selfreset
Cary continuously. 5A ACor DC
Make & carry
2OAACor DCfor0.5 secs.
{Limit UR = 5omsand 300)
Indication
Hand-Reset flag
2TJM71
‘As type 2TIM7O with the following additions referring to the
high-set element:
urrent Setting
Rating 1A, Rating 2h Rating 5h
OA-1.6A 2-8A
2- 8A 10-408
16h Bah 20-80A
40-160A
50-200A
Operating Time
‘At2timesseting 20ms
ACS times setting Tams
Burden
1.2VAoverthesettingrange
Contacts
‘arangement 2make, seltreset
Rating 410A continuously, 30A for 3
secondsIndication
Hand Reset flag
2TJM72
| type 2TJM70 with the following additions refering to the
directional elements.
Rating Vn
Overcurrent, + 110V nominal
Earthfault + 63,5V or 10¥ nominal
Current Settings
(Expressed asa percentage of [OMTL nominalcurrent)
Overcurrent 15% at MTA (Maxum torque
anele)
arth Fault 715% at MTA
Phase - Angle Settings
Phase Fault 45° leading
Earth-fault + 12:1/2" lagging, 45° lagging
Operating Time
100 msof rated curent setting with 100% volts applied
Burden
Curent Windings 0.5 vAatseting
Voltage Windings + 12 VAtrated voltage (110%)
Characteristics and Vector Diagrams
Vector diagrams (using A phase) Fig6
Current / phase angle diagram Figs
Impedance/ Current characteristics (1Arelay) + Fig9
Impedance/ Current characteristics (SArelay) : Fig 10
Cases
2TIM70&71 —- Single pole - 2/3¥, 1V;
Three pole-2V, 2VH, 3H
2TuM72 - TAY
in 8
Ordering Information
(a) TYPES 2TJM70
1. We
2. Rating
3. Settingrange
4. Case size
(b) TYPE 2TJM71
Same as for 2TJM70 plushigh-set element setting range.
(c) TYPES 2TJM72
Same as or 2TJM70 plus phase angle setting.
Fig 4 : Directional Element : Electro -magnetic systemVOLTAGE APPLIED TO
APHASE RELAY ANGLE OF REVERSE
‘CURRENT FOR
MAXIMUM TORQUE INOPERATIVE
v, ZONE
OPERATING
ZONE
ve ve
‘APHASE CURRENT
|LREVERSED 1h om 4, REVERSED —.'
VECTOR DIAGRAM OF VOLTAGE
AND CURRENT IN A PHASE RELAY (90° CONNECTION)
Fig 6 Vector diagrams : Type 2TJM72 Directional Element
TIME, seconds
83
8
os
02
on
1 2. 8 4 sé 78810 20 30
(CURRENT, muttiplas of plug setting
Fig 7 : Time / Current CharacteristicsT T
VOLTAGE COL,
ENERGISED
AT 110 VOLTS
T
AMPERES.
2 Z
Z PERATING ZONE 2
a 8
Ww 3. w
= =
z =
5 z
& §
g s
Zz z
CURRENT LAG «——+——+ CURRENT LEAD
100. 80 60 40 20 oO 20 40 60 100
Impeanee, ons,
300
400
Pa
2
6
0
a
2
PHASE - ANGLE (DEGREES)
Fig 8 : Current / Phase Angle Diagram
|
7
[-—™
Ps
re
[™— pt
P|
ft oT™ ry
—
Operating Current multiple of seting
1A relay. 0.1 00.44 setting range
nce / Current Charact
1 2 9 4 6 67ee10
1A rel;
HzBoa
e eT
a
ch = fea!
—8s4)
Ta
oN 2 3 4 5 678910 20
berating Curent nutipe ot sening
5A relay, 110 4Aseting range
ig 10 : Impedance / Current Characteristics, 5A relay 5OHz
Qualification
‘The policy of Easun Reyrole is one of continuous improvement and development The company therefore reserves the right
‘0 supply equipment which may ditfer slightly from that described and illustrated in this publication
i
:
Q
5
i
g
:
i
‘CORPORATE OFFICE MANUFACTURING UNIT 182 MANUFACTURING UNIT 1&2 BANGALORE OFFICE i
1398, "Rasarak lima 498, Sipe Intl Complex (1723 ete, Sanehae Raed #380,"Rasshua Humans
Oger Hob, Barnegat oad Hosur 635 126, da, Bangatre 960 076, da, equ Hobl, Sarrepnata Rnd
Bangle 5600076 inci Tek 451 4364 4016000002 ‘sal eo goiooaaaéa Serge 260075 India E
‘s91 806717 7000/7001 Fax 91 4348 276307 Fa 09180 26580642 Teresi gr roo toon
Fa ¥91 806717 7002 frail Dewoaeasireyae. net Faye 091806717 7002 aj
BE
z
Sales Offices é
Mumbai i
Tek: $91 22 22022270122858415 7
Fax: +91 22 22825703 5
Delhi Kolkata z
Bangalore Tel +91 11 25747321/25747322 Tek: +91 33 22848320 i
Tel: +81 80 26685496/51311405 Fax, »91 1125747320 Fax: 491 33 22868326
Fax: 491 22 26685446 Email: delhi@easunreyall.net Email kolkalaGeasunreyoll.ret i
Email: blroffice@easunreyrolle.net :
Chennai g
Bhopal Tel +91 44 24346425/24347608 Secunderabad i
Telefax: 491 755 2684221 Fax +81 44.24306435, Tol: +91 40 27817847 2
Email bhopal@easunreyall.net Emaik chenna @easunreyole net Emil hycerabae@easunreyalnet 3