TABLE: Joint Reactions

Total
Load Dead Live
Joint Column Service
Story Column ID Case/ Load Load
Label Grid Load
Combo

kip kip kip

Base 174 A/1,2 C1-(12"X12") DL+LL 5.26747 -1.3089 244.24


-1.89788

Base 138 A/2 C1-(12"X12") DL+LL 8.07387 1.50159 268.32


2.1773

Base 139 A/3 C2-(14"X14") DL+LL 11.0214 1.8993 263.07


2.75399

Base 140 A/4 C1-(12"X12") DL+LL 8.922 1.35658 269.92


1.96704
Base 141 A/5 C1-(12"X12") DL+LL 7.59595 1.42734 272.38
2.06964

Base 142 B/1 C1-(12"X12") DL+LL 10.9918 6.27878 271.33


9.10423

Base 143 B/3 C2-(14"X14") DL+LL 12.4595 8.48811 307.35


12.3078
Base 144 B/5 C1-(12"X12") DL+LL 9.25115 3.43856 246.87
4.98591

Base 145 C/1 C1-(12"X12") DL+LL 8.14675 2.18205 370.97


3.16397

Base 146 C/3 C2-(14"X14") DL+LL 12.382 8.95423 394.98


12.9836
Base 147 C/5 C1-(12"X12") DL+LL 8.66108 3.08268 442.68
4.46988

Base 148 D/1 C1-(12"X12") DL+LL 8.72687 3.09905 464.25


4.49362

Base 149 D/3 C2-(14"X14") DL+LL 12.6388 9.25288 483.27


13.4167
Base 150 D/5 C1-(12"X12") DL+LL 8.64365 2.95392 462.41
4.28319

Base 151 E/1 C1-(12"X12") DL+LL 8.57238 2.85619 427.50


4.14148
Base 152 E/3 C2-(14"X14") DL+LL 12.6994 9.36522 300.90
13.5796
Base 153 E/5 C1-(12"X12") DL+LL 8.59383 2.89419 423.80
4.19657

Base 154 F/1 C1-(12"X12") DL+LL 8.57969 2.86847 459.58


4.15929

Base 155 F/3 C2-(14"X14") DL+LL 12.7304 9.41036 439.12


13.645
Base 156 F/5 C1-(12"X12") DL+LL 8.58162 2.87225 457.01
4.16476

Base 157 G/1 C1-(12"X12") DL+LL 8.57587 2.86224 474.50


4.15024

Base 158 G/3 C2-(14"X14") DL+LL 12.7332 9.41457 447.73


13.6511
Base 159 G/5 C1-(12"X12") DL+LL 8.5802 2.87014 492.42
4.16171

Base 160 H/1 C1-(12"X12") DL+LL 8.58551 2.88079 349.15


4.17714
Base 161 H/3 C2-(14"X14") DL+LL 12.7099 9.38074 305.46
13.6021

Base 162 H/5 C1-(12"X12") DL+LL 8.58861 2.88649 346.34


4.18541

Base 163 I/1 C1-(12"X12") DL+LL 8.62893 2.93159 302.31


4.2508

Base 164 I/3 C2-(14"X14") DL+LL 12.6646 9.29114 346.20


13.4722
Base 165 I/5 C1-(12"X12") DL+LL 8.63058 2.93461 338.68
4.25518

Base 166 J/1 C1-(12"X12") DL+LL 8.62518 3.02674 275.22


4.38877

Base 167 J/3 C2-(14"X14") DL+LL 12.4448 9.04898 325.34


13.121
Base 168 J/5 C1-(12"X12") DL+LL 8.63061 3.03673 244.96
4.40326
Base 175 K/1 C1-(12"X12") DL+LL 9.22446 3.40464
4.93673

Base 177 K/3 C2-(14"X14") DL+LL 12.5488 8.62389


12.5046
Base 176 K/5 C1-(12"X12") DL+LL 9.20361 3.36626
4.88107
Base 169 L/1 C1-(12"X12") DL+LL 7.46061 1.19402
1.73132

Base 173 L/2 C1-(12"X12") DL+LL 8.97128 1.39849


2.0278
Base 170 L/3 C2-(14"X14") DL+LL 10.8956 1.93502
2.80577
Base 172 L/4 C1-(12"X12") DL+LL 8.96224 1.38486 10.35

Base 171 L/5 C1-(12"X12") DL+LL 7.55791 1.36461 8.92


Punching Check Total Canculation

Load on Surcharg
Column Load
Level Column e load &
Grid Combo
(Kip) self wt.

nk Base DL+LL -1.90 1


A/7

nk Base DL+LL 2.18 1


B/7

nk Base DL+LL 2.75 1


C/7

nk Base DL+LL 1.97 1


D/7
nk Base DL+LL 2.07 1
E/7

nk Base DL+LL 9.10 1


G/7

nk Base DL+LL 12.31 1


A/8
nk Base DL+LL 4.99 1
D/8

nk Base DL+LL 3.16 1


H/8

nk Base DL+LL 12.98 1


A/9
nk Base DL+LL 4.47 1
D/9

nk Base DL+LL 4.49 1


H/9

nk Base DL+LL 13.42 1


A/10
nk Base DL+LL 4.28 1
D/10

nk Base DL+LL 4.14 1


H/10
nk Base DL+LL 13.58 1
A/11
nk Base DL+LL 4.20 1
D/11

nk Base DL+LL 4.16 1


H/11

nk Base DL+LL 13.65 1


A/12
nk Base DL+LL 4.16 1
D/12

nk Base DL+LL 4.15 1


H/12

nk Base DL+LL 13.65 1


A/13
nk Base DL+LL 4.16 1
D/13

nk Base DL+LL 4.18 1


H/13
nk Base DL+LL 13.60 1
A/14

nk Base DL+LL 4.19 1


D/14

nk Base DL+LL 4.25 1


H/14

nk Base DL+LL 13.47 1


A/15
nk Base DL+LL 4.26 1
D/15

nk Base DL+LL 4.39 1


H/15

nk Base DL+LL 13.12 1


A/16
nk Base DL+LL 4.40 1
D/16
Base DL+LL 4.94 2
H/16

Base DL+LL 12.50 3


A/17
Base DL+LL 4.88 4
C/17
Base DL+LL 1.73 5
D/17

Base DL+LL 2.03 6


F/17
Base DL+LL 2.81 7
H/17
Base L/4 DL+LL 10.35 8

Base L/5 DL+LL 8.92 9


Distance
Selected Selected Net from Moment,
Total
Size of Size of Area (sq. upward Column Column Column k-ft
Load
footing footing ft) pressure Size (a) Size (b) face, Ft
(Kip)
(a), Ft (b), Ft (ksf)

-1.89788 4 4 16 -0.11862 12 12 1.50 (0.13)

2.177303 4 4 16 0.136081 12 12 1.50 0.15

2.753985 5 5 25 0.110159 14 14 1.92 0.20

1.967038 4 4 16 0.12294 12 12 1.50 0.14

2.069644 4 4 16 0.129353 12 12 1.50 0.15

9.104227 4 4 16 0.569014 12 12 1.50 0.64

12.30776 5 5 25 0.49231 14 14 1.92 0.90

4.985906 4 4 16 0.311619 12 12 1.50 0.35

3.163971 4 4 16 0.197748 12 12 1.50 0.22

12.98363 5 5 25 0.519345 14 14 1.92 0.95

4.469879 4 4 16 0.279367 12 12 1.50 0.31

4.493618 4 4 16 0.280851 12 12 1.50 0.32

13.41667 5 5 25 0.536667 14 14 1.92 0.99

4.283187 4 4 16 0.267699 12 12 1.50 0.30

4.141481 4 4 16 0.258843 12 12 1.50 0.29


13.57956 5 5 25 0.543183 14 14 1.92 1.00

4.196571 4 4 16 0.262286 12 12 1.50 0.30

4.159287 4 4 16 0.259955 12 12 1.50 0.29

13.64503 5 5 25 0.545801 14 14 1.92 1.00

4.164755 4 4 16 0.260297 12 12 1.50 0.29

4.150241 4 4 16 0.25939 12 12 1.50 0.29

13.65113 5 5 25 0.546045 14 14 1.92 1.00

4.161709 4 4 16 0.260107 12 12 1.50 0.29

4.17714 4 4 16 0.261071 12 12 1.50 0.29

13.60207 5 5 25 0.544083 14 14 1.92 1.00

4.185406 4 4 16 0.261588 12 12 1.50 0.29

4.250798 4 4 16 0.265675 12 12 1.50 0.30

13.47216 5 5 25 0.538886 14 14 1.92 0.99

4.255185 4 4 16 0.265949 12 12 1.50 0.30

4.388767 4 4 16 0.274298 12 12 1.50 0.31

13.12102 5 5 25 0.524841 14 14 1.92 0.96

4.403257 4 4 16 0.275204 12 12 1.50 0.31

9.873465 4 4 16 0.617092 12 12 1.50 0.69

37.51392 5 5 25 1.500557 14 14 1.92 2.76


19.52429 4 4 16 1.220268 12 12 1.50 1.37

8.656616 4 4 16 0.541039 12 12 1.50 0.61

12.16682 4 4 16 0.760426 12 12 1.50 0.86

19.64042 5 5 25 0.785617 14 14 1.92 1.44

82.77681 4 4 16 5.173551 12 12 1.50 5.82

80.30273 4 4 16 5.01892 12 12 1.50 5.65


Punching Check

Provided Shear on
d Concrete
Footing critical Allowable Design
required, strength,
inch f'c (psi)
depth, d
b0
section, V
allowable stress Check
(inch) kip

#NUM! 2045 9.5 86 -1.517113 -1.86 90.44 OK

1 2045 9.5 86 1.740472 2.13 90.44 OK

1 2045 12.5 106 2.216767 1.67 90.44 OK

1 2045 9.5 86 1.572393 1.92 90.44 OK

1 2045 9.5 86 1.654413 2.02 90.44 OK

2 2045 9.5 86 7.277652 8.91 90.44 OK

2 2045 12.5 106 9.906891 7.48 90.44 OK

1 2045 9.5 86 3.985587 4.88 90.44 OK

1 2045 9.5 86 2.529186 3.10 90.44 OK

2 2045 12.5 106 10.45092 7.89 90.44 OK

1 2045 9.5 86 3.57309 4.37 90.44 OK

1 2045 9.5 86 3.592067 4.40 90.44 OK

2 2045 12.5 106 10.79949 8.15 90.44 OK

1 2045 9.5 86 3.423854 4.19 90.44 OK

1 2045 9.5 86 3.310579 4.05 90.44 OK


2 2045 12.5 106 10.93061 8.25 90.44 OK

1 2045 9.5 86 3.354616 4.11 90.44 OK

1 2045 9.5 86 3.324812 4.07 90.44 OK

2 2045 12.5 106 10.9833 8.29 90.44 OK

1 2045 9.5 86 3.329183 4.07 90.44 OK

1 2045 9.5 86 3.317581 4.06 90.44 OK

2 2045 12.5 106 10.98821 8.29 90.44 OK

1 2045 9.5 86 3.326748 4.07 90.44 OK

1 2045 9.5 86 3.339083 4.09 90.44 OK

2 2045 12.5 106 10.94873 8.26 90.44 OK

1 2045 9.5 86 3.345691 4.10 90.44 OK

1 2045 9.5 86 3.397963 4.16 90.44 OK

2 2045 12.5 106 10.84415 8.18 90.44 OK

1 2045 9.5 86 3.40147 4.16 90.44 OK

1 2045 9.5 86 3.508252 4.29 90.44 OK

2 2045 12.5 106 10.56151 7.97 90.44 OK

1 2045 9.5 86 3.519834 4.31 90.44 OK

2 2045 9.5 86 7.892558 9.66 90.44 OK

4 2045 12.5 106 30.1961 22.79 90.44 OK


3 2045 9.5 86 15.60715 19.10 90.44 OK

2 2045 9.5 86 6.919845 8.47 90.44 OK

2 2045 9.5 86 9.725799 11.90 90.44 OK

3 2045 12.5 106 15.80918 11.93 90.44 OK

6 2045 9.5 86 66.16935 80.99 90.44 OK

5 2045 9.5 86 64.19164 78.57 90.44 OK


Punching Check

Load on Concrete
Provided
Shear
V
Level Point
Column
Column ID Column strength,
Footing
Perimeter allowable
Grid thickness, shear
(Kip) f'c (psi) , bo (in)
d (inch) (kip)

Base 174 C1-(12"X12") 4.2 3000 9 84 124.22


A/7

Base 138 C1-(12"X12") 12.1 3000 9 84 124.22


B/7

Base 139 C2-(14"X14") 16.3 3000 9 92 136.05


C/7

Base 140 C1-(12"X12") 12.9 3000 9 84 124.22


D/7
Base 141 C1-(12"X12") 11.4 3000 9 84 124.22
E/7

Base 142 C1-(12"X12") 23.2 3000 9 84 124.22


G/7

Base 143 C2-(14"X14") 28.5 3000 9 92 136.05


A/8
Base 144 C1-(12"X12") 16.6 3000 9 84 124.22
D/8

Base 145 C1-(12"X12") 13.3 3000 9 84 124.22


H/8

Base 146 C2-(14"X14") 29.2 3000 9 92 136.05


A/9
Base 147 C1-(12"X12") 15.3 3000 9 84 124.22
D/9

Base 148 C1-(12"X12") 15.4 3000 9 84 124.22


H/9

Base 149 C2-(14"X14") 30.0 3000 9 92 136.05


A/10
Base 150 C1-(12"X12") 15.1 3000 9 84 124.22
D/10

Base 151 C1-(12"X12") 14.9 3000 9 84 124.22


H/10
Base 152 C2-(14"X14") 30.2 3000 9 92 136.05
A/11
Base 153 C1-(12"X12") 14.9 3000 9 84 124.22
D/11

Base 154 C1-(12"X12") 14.9 3000 9 84 124.22


H/11

Base 155 C2-(14"X14") 30.3 3000 9 92 136.05


A/12
Base 156 C1-(12"X12") 14.9 3000 9 84 124.22
D/12

Base 157 C1-(12"X12") 14.9 3000 9 84 124.22


H/12

Base 158 C2-(14"X14") 30.3 3000 9 92 136.05


A/13
Base 159 C1-(12"X12") 14.9 3000 9 84 124.22
D/13

Base 160 C1-(12"X12") 14.9 3000 9 84 124.22


H/13
Base 161 C2-(14"X14") 30.3 3000 9 92 136.05
A/14

Base 162 C1-(12"X12") 14.9 3000 9 84 124.22


D/14

Base 163 C1-(12"X12") 15.0 3000 9 84 124.22


H/14

Base 164 C2-(14"X14") 30.1 3000 9 92 136.05


A/15
Base 165 C1-(12"X12") 15.1 3000 9 84 124.22
D/15

Base 166 C1-(12"X12") 15.2 3000 9 84 124.22


H/15

Base 167 C2-(14"X14") 29.4 3000 9 92 136.05


A/16
Base 168 C1-(12"X12") 15.2 3000 9 84 124.22
D/16
Base 175 C1-(12"X12") 16.5 3000 9 84 124.22
H/16

Base 177 C2-(14"X14") 28.9 3000 9 92 136.05


A/17
Base 176 C1-(12"X12") 16.4 3000 9 84 124.22
C/17
Base 169 C1-(12"X12") 10.9 3000 9 84 124.22
D/17

Base 173 C1-(12"X12") 13.0 3000 9 84 124.22


F/17
Base 170 C2-(14"X14") 16.2 3000 9 92 136.05
H/17
Base 172 C1-(12"X12") 13.0 3000 9 84 124.22
A/7

Base 171 C1-(12"X12") 11.3 3000 9 84 124.22


B/7
Footing Area Check

Bearing
Load on
Design Column Capacity
Level Node Column ID Column
Check Grid (KSF)
(Kip)
(F.S.-2.5)

Ok Base 174 A/2 F1-(4'X4') -1.898 1.80

Ok Base 138 A/3 F2-(5'x5') 2.177 1.80

Ok Base 139 A/4 F1-(4'X4') 2.754 1.80

Ok Base 140 A/5 F1-(4'X4') 1.967 1.80

Ok Base 141 B/1 F1-(4'X4') 2.070 1.80

Ok Base 142 B/3 F2-(5'x5') 9.104 1.80

Ok Base 143 B/5 F1-(4'X4') 12.308 1.80

Ok Base 144 C/1 F1-(4'X4') 4.986 1.80

Ok Base 145 C/3 F2-(5'x5') 3.164 1.80

Ok Base 146 C/5 F1-(4'X4') 12.984 1.80

Ok Base 147 D/1 F1-(4'X4') 4.470 1.80

Ok Base 148 D/3 F2-(5'x5') 4.494 1.80

Ok Base 149 D/5 F1-(4'X4') 13.417 1.80

Ok Base 150 E/1 F1-(4'X4') 4.283 1.80

Ok Base 151 E/3 F2-(5'x5') 4.141 1.80


Ok Base 152 E/5 F1-(4'X4') 13.580 1.80

Ok Base 153 F/1 F1-(4'X4') 4.197 1.80

Ok Base 154 F/3 F2-(5'x5') 4.159 1.80

Ok Base 155 F/5 F1-(4'X4') 13.645 1.80

Ok Base 156 G/1 F1-(4'X4') 4.165 1.80

Ok Base 157 G/3 F2-(5'x5') 4.150 1.80

Ok Base 158 G/5 F1-(4'X4') 13.651 1.80

Ok Base 159 H/1 F1-(4'X4') 4.162 1.80

Ok Base 160 H/3 F2-(5'x5') 4.177 1.80

Ok Base 161 H/5 F1-(4'X4') 13.602 1.80

Ok Base 162 I/1 F1-(4'X4') 4.185 1.80

Ok Base 163 I/3 F2-(5'x5') 4.251 1.80

Ok Base 164 I/5 F1-(4'X4') 13.472 1.80

Ok Base 165 J/1 F1-(4'X4') 4.255 1.80

Ok Base 166 J/3 F2-(5'x5') 4.389 1.80

Ok Base 167 J/5 F1-(4'X4') 13.121 1.80

Ok Base 168 L/1 F1-(4'X4') 4.403 1.80

Ok Base 175 L/3 F2-(5'x5') 4.937 1.80

Ok Base 177 L/5 F1-(4'X4') 12.505 1.80


Ok Base 176 L/4 F1-(4'X4') 4.881 1.80

Ok Base 169 L/2 F1-(4'X4') 1.731 1.80

Ok Base 173 A/1 F1-(4'X4') 2.028 1.80

Ok Base 170 J/1 F1-(4'X4') 2.806 1.80

Ok Base 172 J/5 F1-(4'X4') 10.347 1.80

Ok Base 171 J/3 F2-(5'x5') 8.923 1.80


Pile Capacity Check

Provided
Required Column
Area Remarks Level Point Column ID
Area (SFT) Grid
(SFT)

-1.1 16.00 Ok Base 174 A/1,2 C1-(12"X12")

1.2 25.00 Ok Base 138 A/2 C1-(12"X12")

1.5 16.00 Ok Base 139 A/3 C2-(14"X14")

1.1 16.00 Ok Base 140 A/4 C1-(12"X12")

1.1 16.00 Ok Base 141 A/5 C1-(12"X12")

5.1 25.00 Ok Base 142 B/1 C1-(12"X12")

6.8 16.00 Ok Base 143 B/3 C2-(14"X14")

2.8 16.00 Ok Base 144 B/5 C1-(12"X12")

1.8 25.00 Ok Base 145 C/1 C1-(12"X12")

7.2 16.00 Ok Base 146 C/3 C2-(14"X14")

2.5 16.00 Ok Base 147 C/5 C1-(12"X12")

2.5 25.00 Ok Base 148 D/1 C1-(12"X12")

7.5 16.00 Ok Base 149 D/3 C2-(14"X14")

2.4 16.00 Ok Base 150 D/5 C1-(12"X12")

2.3 25.00 Ok Base 151 E/1 C1-(12"X12")


7.5 16.00 Ok Base 152 E/3 C2-(14"X14")

2.3 16.00 Ok Base 153 E/5 C1-(12"X12")

2.3 25.00 Ok Base 154 F/1 C1-(12"X12")

7.6 16.00 Ok Base 155 F/3 C2-(14"X14")

2.3 16.00 Ok Base 156 F/5 C1-(12"X12")

2.3 25.00 Ok Base 157 G/1 C1-(12"X12")

7.6 16.00 Ok Base 158 G/3 C2-(14"X14")

2.3 16.00 Ok Base 159 G/5 C1-(12"X12")

2.3 25.00 Ok Base 160 H/1 C1-(12"X12")

7.6 16.00 Ok Base 161 H/3 C2-(14"X14")

2.3 16.00 Ok Base 162 H/5 C1-(12"X12")

2.4 25.00 Ok Base 163 I/1 C1-(12"X12")

7.5 16.00 Ok Base 164 I/3 C2-(14"X14")

2.4 16.00 Ok Base 165 I/5 C1-(12"X12")

2.4 25.00 Ok Base 166 J/1 C1-(12"X12")

7.3 16.00 Ok Base 167 J/3 C2-(14"X14")

2.4 16.00 Ok Base 168 J/5 C1-(12"X12")

2.7 25.00 Ok 175

6.9 16.00 Ok 177


2.7 16.00 Ok 176

1.0 16.00 Ok 169

1.1 16.00 Ok 173

1.6 16.00 Ok 170

5.7 16.00 Ok 172

5.0 25.00 Ok 171


Top Deflection
TABLE: Joint Displacements

Per Pile
Load on
Capacity Nos of Total Pile
Column Remarks Story Label
(FS 2.5) Piles Capacity
(Kip)
(Kip)

-1.9 190.94 2.0 381.88 Ok 83.75 Chillakotha 12

2.2 190.94 2.0 381.88 Ok 94.26 Chillakotha 13

2.8 190.94 2.0 381.88 Ok 108.875 Chillakotha 15

2.0 190.94 2.0 381.88 Ok Chillakotha 18

2.1 190.94 2.0 381.88 Ok Chillakotha 19

9.1 190.94 2.0 381.88 Ok Chillakotha 20

12.3 190.94 2.0 381.88 Ok Chillakotha 21

5.0 190.94 2.0 381.88 Ok Chillakotha 23

3.2 190.94 3.0 572.82 Ok Chillakotha 26

13.0 190.94 3.0 572.82 Ok Chillakotha 27

4.5 190.94 3.0 572.82 Ok Chillakotha 80

4.5 190.94 3.0 572.82 Ok Chillakotha 81

13.4 190.94 3.0 572.82 Ok Chillakotha 12

4.3 190.94 3.0 572.82 Ok Chillakotha 13

4.1 190.94 3.0 572.82 Ok Chillakotha 15


13.6 190.94 2.0 381.88 Ok Chillakotha 18

4.2 190.94 3.0 572.82 Ok Chillakotha 19

4.2 190.94 3.0 572.82 Ok Chillakotha 20

13.6 190.94 3.0 572.82 Ok Chillakotha 21

4.2 190.94 3.0 572.82 Ok Chillakotha 23

4.2 190.94 3.0 572.82 Ok Chillakotha 26

13.7 190.94 3.0 572.82 Ok Chillakotha 27

4.2 190.94 3.0 572.82 Ok Chillakotha 80

4.2 190.94 2.0 381.88 Ok Chillakotha 81

13.6 190.94 2.0 381.88 Ok

4.2 190.94 2.0 381.88 Ok

4.3 190.94 2.0 381.88 Ok

13.5 190.94 2.0 381.88 Ok

4.3 190.94 2.0 381.88 Ok

4.4 190.94 2.0 381.88 Ok

13.1 190.94 2.0 381.88 Ok

4.4 190.94 2.0 381.88 Ok


Column PMM Ratio
TABLE: Concrete Column Summary - ACI 318-11

Load Case/ Umax H/360


Remarks Story Label
Combo

in in

Wx 0.734 2.803 Ok 1F C2

Wx 0.734 2.803 Ok 1F C2

Wx 0.733 2.803 Ok 1F C2

Wx 0.711 2.803 Ok 1F C3

Wx 0.707 2.803 Ok 1F C3

Wx 0.701 2.803 Ok 1F C3

Wx 0.701 2.803 Ok 1F C4

Wx 0.700 2.803 Ok 1F C4

Wx 0.679 2.803 Ok 1F C4

Wx 0.676 2.803 Ok 1F C5

Wx 0.700 2.803 Ok 1F C5

Wx 0.733 2.803 Ok 1F C5

Wy 1.351 2.803 Ok 1F C6

Wy 1.357 2.803 Ok 1F C6

Wy 1.370 2.803 Ok 1F C6
Wy 1.352 2.803 Ok 1F C7

Wy 1.355684 2.803 Ok 1F C7

Wy 1.350511 2.803 Ok 1F C7

Wy 1.357151 2.803 Ok 1F C8

Wy 1.370361 2.803 Ok 1F C8

Wy 1.352585 2.803 Ok 1F C8

Wy 1.364529 2.803 Ok 1F C9

Wy 1.364051 2.803 Ok 1F C9

Wy 1.364076 2.803 Ok 1F C9

1F C10

1F C10

1F C10

1F C11

1F C11

1F C11

1F C12

1F C12

1F C12

1F C13
1F C13

1F C13

1F C14

1F C14

1F C14

1F C15

1F C15

1F C16

1F C16

1F C16

1F C17

1F C17

1F C17

1F C20

1F C20

1F C20

1F C21

1F C21

1F C21

1F C22
1F C22

1F C22

1F C23

1F C23

1F C23

1F C28

1F C28

1F C28

1F C29

1F C29

1F C29

1F C30

1F C30

1F C30

1F C31

1F C31

1F C31

1F C1

1F C1

1F C1
1F C34

1F C34

1F C34

1F C35

1F C35

1F C35

1F C36

1F C36

1F C36

1F C39

1F C39

1F C39

1F C40

1F C40

1F C40

1F C43

1F C43

1F C43
1F C44

1F C44

1F C44

1F C47
1F C47
1F C47
1F C48
1F C48
1F C48
1F C41
1F C41
1F C41
1F C42
1F C42
1F C42
1F C45
1F C45
1F C45
1F C46
1F C46
1F C46
1F C37
1F C37
1F C37
1F C37
1F C37
1F C38
1F C38
1F C38
ummary - ACI 318-11 Torsional Irregularity Check

PMM Load
Design Section PMM Combo Remarks
Ratio Case

BNBC16:
C1-18x18-GF 0.612 1.05DL+1.275LL- Ok
1.4EQx
Ex

C1-18x18-GF 0.362 BNBC2: 1.4DL+1.7LL Ok

BNBC5:
C1-18x18-GF 0.439 1.05DL+1.275LL+1.2 Ok
75Wy
Ex
BNBC15:
C3-18x22-GF 0.63 1.05DL+1.275LL+1.4 Ok
EQx

C3-18x22-GF 0.357 BNBC2: 1.4DL+1.7LL Ok

BNBC5: Ey
C3-18x22-GF 0.414 1.05DL+1.275LL+1.2 Ok
75Wy
BNBC16:
C3-18x22-GF 0.633 1.05DL+1.275LL- Ok
1.4EQx Ey
C3-18x22-GF 0.357 BNBC2: 1.4DL+1.7LL Ok

BNBC5:
C3-18x22-GF 0.384 1.05DL+1.275LL+1.2 Ok
75Wy
Wx
BNBC15:
C3-18x22-GF 0.633 1.05DL+1.275LL+1.4 Ok
EQx

C3-18x22-GF 0.363 BNBC2: 1.4DL+1.7LL Ok

BNBC15: Wx
C3-18x22-GF 0.39 1.05DL+1.275LL+1.4 Ok
EQx
BNBC16:
C3-18x22-GF 0.633 1.05DL+1.275LL- Ok
1.4EQx Wy
C3-18x22-GF 0.37 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C3-18x22-GF 0.382 1.05DL+1.275LL+1.4 Ok
EQx
Wy
Wy
BNBC16:
C3-18x22-GF 0.633 1.05DL+1.275LL- Ok
1.4EQx

C3-18x22-GF 0.368 BNBC2: 1.4DL+1.7LL Ok

BNBC16:
C3-18x22-GF 0.38 1.05DL+1.275LL- Ok
1.4EQx
BNBC16:
C3-18x22-GF 0.651 1.05DL+1.275LL- Ok
1.4EQx

C3-18x22-GF 0.393 BNBC2: 1.4DL+1.7LL Ok

BNBC16:
C3-18x22-GF 0.4 1.05DL+1.275LL- Ok
1.4EQx
BNBC15:
C1-18x18-GF 0.623 1.05DL+1.275LL+1.4 Ok
EQx

C1-18x18-GF 0.366 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C1-18x18-GF 0.416 1.05DL+1.275LL+1.4 Ok
EQx
BNBC14: 0.9DL-
C2-20x25-GF 0.738 Ok
1.3Wy
BNBC17:
C2-20x25-GF 0.41 1.05DL+1.275LL+1.4 Ok
EQy
BNBC5:
C2-20x25-GF 0.551 1.05DL+1.275LL+1.2 Ok
75Wy
BNBC16:
C2-20x25-GF 0.664 1.05DL+1.275LL- Ok
1.4EQx

C2-20x25-GF 0.421 BNBC2: 1.4DL+1.7LL Ok

BNBC16:
C2-20x25-GF 0.429 1.05DL+1.275LL- Ok
1.4EQx
BNBC16:
C2-20x25-GF 0.681 1.05DL+1.275LL- Ok
1.4EQx

C2-20x25-GF 0.47 BNBC2: 1.4DL+1.7LL Ok

C2-20x25-GF 0.464 BNBC2: 1.4DL+1.7LL Ok

BNBC16:
C2-20x25-GF 0.681 1.05DL+1.275LL- Ok
1.4EQx
C2-20x25-GF 0.481 BNBC2: 1.4DL+1.7LL Ok

C2-20x25-GF 0.475 BNBC2: 1.4DL+1.7LL Ok

BNBC16:
C2-20x25-GF 0.685 1.05DL+1.275LL- Ok
1.4EQx

C2-20x25-GF 0.497 BNBC2: 1.4DL+1.7LL Ok

C2-20x25-GF 0.491 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C2-20x25-GF 0.68 1.05DL+1.275LL+1.4 Ok
EQx

C2-20x25-GF 0.48 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C2-20x25-GF 0.66 1.05DL+1.275LL+1.4 Ok
EQx

C2-20x25-GF 0.424 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C2-20x25-GF 0.427 1.05DL+1.275LL+1.4 Ok
EQx
BNBC26: 0.9DL-
C2-20x25-GF 0.696 Ok
1.43EQy
BNBC17:
C2-20x25-GF 0.358 1.05DL+1.275LL+1.4 Ok
EQy
BNBC5:
C2-20x25-GF 0.454 1.05DL+1.275LL+1.2 Ok
75Wy
BNBC16:
C2-20x25-GF 0.679 1.05DL+1.275LL- Ok
1.4EQx

C2-20x25-GF 0.466 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C2-20x25-GF 0.475 1.05DL+1.275LL+1.4 Ok
EQx
BNBC15:
C2-20x25-GF 0.686 1.05DL+1.275LL+1.4 Ok
EQx

C2-20x25-GF 0.484 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C2-20x25-GF 0.494 1.05DL+1.275LL+1.4 Ok
EQx
BNBC16:
C2-20x25-GF 0.693 1.05DL+1.275LL- Ok
1.4EQx
C2-20x25-GF 0.503 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C2-20x25-GF 0.497 1.05DL+1.275LL+1.4 Ok
EQx
BNBC16:
C2-20x25-GF 0.677 1.05DL+1.275LL- Ok
1.4EQx

C2-20x25-GF 0.481 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C2-20x25-GF 0.476 1.05DL+1.275LL+1.4 Ok
EQx
BNBC24: 0.9DL-
C3-18x22-GF 0.876 Ok
1.43EQx
BNBC15:
C3-18x22-GF 0.495 1.05DL+1.275LL+1.4 Ok
EQx
BNBC24: 0.9DL-
C3-18x22-GF 0.639 Ok
1.43EQx
BNBC15:
C3-18x22-GF 0.668 1.05DL+1.275LL+1.4 Ok
EQx

C3-18x22-GF 0.464 BNBC2: 1.4DL+1.7LL Ok

BNBC15:
C3-18x22-GF 0.501 1.05DL+1.275LL+1.4 Ok
EQx
BNBC16:
C3-18x22-GF 0.667 1.05DL+1.275LL- Ok
1.4EQx

C3-18x22-GF 0.442 BNBC2: 1.4DL+1.7LL Ok

BNBC16:
C3-18x22-GF 0.478 1.05DL+1.275LL- Ok
1.4EQx
BNBC23:
C3-18x22-GF 0.941 Ok
0.9DL+1.43EQx
BNBC16:
C3-18x22-GF 0.456 1.05DL+1.275LL- Ok
1.4EQx
BNBC23:
C3-18x22-GF 0.71 Ok
0.9DL+1.43EQx
BNBC16:
C2-20x25-GF 0.706 1.05DL+1.275LL- Ok
1.4EQx
BNBC16:
C2-20x25-GF 0.544 1.05DL+1.275LL- Ok
1.4EQx

C2-20x25-GF 0.508 BNBC2: 1.4DL+1.7LL Ok


C2-20x25-GF 0.502 BNBC2: 1.4DL+1.7LL Ok

C2-20x25-GF 0.503 BNBC2: 1.4DL+1.7LL Ok

C2-20x25-GF 0.497 BNBC2: 1.4DL+1.7LL Ok

BNBC6:
C2-20x25-GF 0.673 1.05DL+1.275LL- Ok
1.275Wy
BNBC15:
C2-20x25-GF 0.498 1.05DL+1.275LL+1.4 Ok
EQx
BNBC15:
C2-20x25-GF 0.376 1.05DL+1.275LL+1.4 Ok
EQx
BNBC18:
C2-20x25-GF 0.404 1.05DL+1.275LL- Ok
1.4EQy
BNBC18:
C2-20x25-GF 0.359 1.05DL+1.275LL- Ok
1.4EQy
BNBC6:
C2-20x25-GF 0.449 1.05DL+1.275LL- Ok
1.275Wy
BNBC15:
C1-18x18-GF 0.726 1.05DL+1.275LL+1.4 Ok
EQx
BNBC15:
C1-18x18-GF 0.531 1.05DL+1.275LL+1.4 Ok
EQx
BNBC15:
C1-18x18-GF 0.39 1.05DL+1.275LL+1.4 Ok
EQx
BNBC18:
C1-18x18-GF 0.532 1.05DL+1.275LL- Ok
1.4EQy
BNBC15:
C1-18x18-GF 0.404 1.05DL+1.275LL+1.4 Ok
EQx
BNBC15:
C1-18x18-GF 0.591 1.05DL+1.275LL+1.4 Ok
EQx
BNBC15:
C2-20x25-GF 0.702 1.05DL+1.275LL+1.4 Ok
EQx
BNBC5:
C2-20x25-GF 0.534 1.05DL+1.275LL+1.2 Ok
75Wy

C2-20x25-GF 0.484 BNBC2: 1.4DL+1.7LL Ok


C2-20x25-GF 0.478 BNBC2: 1.4DL+1.7LL Ok

C2-20x25-GF 0.477 BNBC2: 1.4DL+1.7LL Ok

BNBC5:
C2-20x25-GF 0.522 1.05DL+1.275LL+1.2 Ok
75Wy
C3-18x22-GF 0.88 BNBC23: 0.9DL+1.43EQx Ok
C3-18x22-GF 0.623
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C3-18x22-GF 0.511
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C3-18x22-GF 0.497
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C3-18x22-GF 0.514
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C3-18x22-GF 0.662
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C1-18x18-GF 0.764
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C1-18x18-GF 0.578
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C1-18x18-GF 0.454 BNBC2: 1.4DL+1.7LL Ok
C1-18x18-GF 0.447 BNBC2: 1.4DL+1.7LL Ok
C1-18x18-GF 0.458
BNBC16: 1.05DL+1.275LL-1.4EQx
Ok
C1-18x18-GF 0.598
BNBC6: 1.05DL+1.275LL-1.275Wy
Ok
C2-20x25-GF 0.774
BNBC6: 1.05DL+1.275LL-1.275Wy
Ok
C2-20x25-GF 0.582
BNBC6: 1.05DL+1.275LL-1.275Wy
Ok
C2-20x25-GF 0.45
BNBC18: 1.05DL+1.275LL-1.4EQy
Ok
C2-20x25-GF 0.436 BNBC2: 1.4DL+1.7LL Ok
C2-20x25-GF 0.435
BNBC18: 1.05DL+1.275LL-1.4EQy
Ok
C2-20x25-GF 0.543
BNBC6: 1.05DL+1.275LL-1.275Wy
Ok
C3-18x22-GF 0.874 BNBC24: 0.9DL-1.43EQx Ok
C3-18x22-GF 0.584
BNBC15: 1.05DL+1.275LL+1.4EQx
Ok
C3-18x22-GF 0.455
BNBC15: 1.05DL+1.275LL+1.4EQx
Ok
C3-18x22-GF 0.451
BNBC15: 1.05DL+1.275LL+1.4EQx
Ok
C3-18x22-GF 0.451
BNBC15: 1.05DL+1.275LL+1.4EQx
Ok
C3-18x22-GF 0.464
BNBC15: 1.05DL+1.275LL+1.4EQx
Ok
C3-18x22-GF 0.557
BNBC15: 1.05DL+1.275LL+1.4EQx
Ok
C3-18x22-GF 0.876
BNBC15: 1.05DL+1.275LL+1.4EQx
Ok
Torsional Irregularity Check

Max Avg dmax/davg


Story
Point/ Story Story Max
Level Dift Check
Lebel Drift Drift value =
1.2

d dmax davg

57 1.821

Roof 1.821 1.708 1.066 Ok

55 1.595

98 1.821
Roof 1.821 1.698 1.072 Ok

61 1.575

98 1.301
Roof 1.419 1.36 1.043 Ok
57 1.419

61 1.301
Roof 1.419 1.36 1.043 Ok
55 1.419

57 0.77
Roof 0.77 0.719 1.071 Ok
55 0.668

98 0.77
Roof 0.77 0.715 1.077 Ok
61 0.66

98 1.333
Roof 1.383 1.358 1.018 Ok
57 1.383

61 1.334
Roof 1.384 1.359 1.018 Ok
Roof 1.384 1.359 1.018 Ok
55 1.384
Load on Concrete Provided Required Shear on
Column Footing Footing critical Allowable
Level Point
Grid
Column strength,
(Kip) f'c (psi) thickness, thickness, section, Vallowable stress
d (inch) d (inch) kip

Base 1 B/1 223.346 2000 19 12 190.7165 73.81 89.44


Base 2 B/2 472.983 2000 14 21 434.2763 235.00 89.44
Base 3 B/3 305.511 2000 19 28 260.8777 100.96 89.44
Base 4 C/1 402.448 2000 14 28 373.2743 208.30 89.44
Base 5 C/2 541.246 2000 14 24 479.9157 252.06 89.44
Base 6 C/3 438.898 2000 14 26 407.082 227.17 89.44
Base 8 D/2 498.164 2000 14 22 441.7154 231.99 89.44
Base 9 D/3 393.25 2000 14 22 364.743 345.54 89.44
Base 10 E/1 379.267 2000 14 20 351.7737 196.30 89.44
Base 13 F/1 412.02 2000 14 24 382.1524 213.25 89.44
Base 14 F/2 508.479 2000 14 26 450.8616 236.80 89.44
Base 15 F/3 417.323 2000 14 22 387.071 216.00 89.44
Base 16 G/1 469.444 2000 14 20 435.4137 242.98 89.44
Base 17 G/2 455.367 2000 14 26 403.7679 212.06 89.44
Base 18 G/3 473.951 2000 14 34 439.594 245.31 89.44
Base 19 H/1 277.897 2000 19 32 237.2979 91.83 89.44
Base 20 H/2 456.769 2000 14 32 419.3892 397.31 89.44
Base 21 H/3 274.954 2000 19 32 234.7849 90.86 89.44
Base 25 A/1 109.839 2000 14 24 92.26476 68.65 89.44
Base 26 A/2 209.237 2000 14 28 175.7591 130.77 89.44
Base 27 A/3 114.467 2000 14 24 96.15228 71.54 89.44
Base 29 C/4 27.753 2000 14 28 25.74117 14.36 89.44
Base 30 I/4 30.473 2000 14 32 28.26399 15.77 89.44
Design
Check

OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
Not OK
OK
Not OK
OK
OK
OK
TABLE: Joint Reactions

Total
Load Dead Live
Joint Column FF PW Service
Story Column ID Case/ Load Load
Label Grid Load
Combo

kip kip kip kip kip


Base 1 1/A C4-18" dia DL+LL 22.271 1.897 10.41 3.174 37.756
Base 2 1/B C4-18" dia DL+LL 40.217 6.66 18.21 10.791 75.88
Base 3 1/C C4-18" dia DL+LL 42.71 7.309 17.80 11.78 79.6
Base 4 1/D C4-18" dia DL+LL 41.943 7.099 16.31 11.438 76.79
Base 5 1/E C4-18" dia DL+LL 42.303 7.18 15.75 11.548 76.778
Base 6 1/F C4-18" dia DL+LL 31.53 4.691 15.02 7.706 58.943
Base 7 2/A C2-15X18 DL+LL 96.406 15.972 51.16 26.532 190.072
Base 8 3/A C2-15X18 DL+LL 151.316 29.641 92.15 45.937 319.039
Base 9 4/A C2-15X18 DL+LL 135.507 27.518 94.96 40.674 298.663
Base 10 5/A C2-15X18 DL+LL 132.32 23.174 64.34 37.777 257.615
Base 11 6/A C2-15X18 DL+LL 129.043 21.219 81.59 32.238 264.091
Base 12 2/F C2-15X18 DL+LL 132.602 28.087 64.68 47.143 272.507
Base 13 3/F C2-15X18 DL+LL 206.242 48.426 67.84 80.702 403.206
Base 14 4/F C2-15X18 DL+LL 203.11 47.641 68.88 79.379 399.007
Base 15 5/F C2-15X18 DL+LL 201.993 47.291 61.46 78.815 389.5628
Base 16 7/F C2-15X18 DL+LL 156.846 34.447 82.16 57.568 331.0249
Base 17 2/B C2-18X15 DL+LL 154.935 34.311 62.59 57.338 309.175
Base 18 2/C C2-18X15 DL+LL 170.086 38.826 47.60 65.085 321.598
Base 19 2/D C2-18X15 DL+LL 168.577 38.351 43.61 64.311 314.853
Base 20 2/E C2-18X15 DL+LL 169.063 38.386 43.53 64.209 315.183
Base 21 6/B C2-18X15 DL+LL 167.797 35.184 63.47 56.829 323.278
Base 22 7/C C2-18X15 DL+LL 200.08 46.518 65.84 77.22 389.6539
Base 23 7/D C2-18X15 DL+LL 200.75 47.064 64.52 78.368 390.6977
Base 24 7/E C2-18X15 DL+LL 200.716 46.906 63.20 77.919 388.7391
Base 25 8/A C1-15x12 DL+LL 79.849 11.62 65.14 16.335 172.943
Base 26 8/B C1A-18x12 DL+LL 107.55 19.17 79.08 29.177 234.98
Base 27 3/B C3-15x20 DL+LL 269.001 63.159 89.59 102.435 524.184
Base 28 4/B C3-15x20 DL+LL 289.737 68.262 83.83 109.17 550.994
Base 29 5/B C3-15x20 DL+LL 212.17 50.864 14.44 84.039 361.517
Base 30 3/C C3-15x20 DL+LL 268.267 68.644 9.51 114.28 460.699
Base 31 4/C C3-15x20 DL+LL 262.633 67.2 3.14 111.565 444.541
Base 32 5/C C3-15x20 DL+LL 258.78 66.149 -2.63 110.286 432.588
Base 33 3/D C3-15x20 DL+LL 265.757 68.277 -2.72 113.86 445.17
Base 34 4/D C3-15x20 DL+LL 260.742 67.125 -0.86 111.837 438.841
Base 35 5/D C3-15x20 DL+LL 261.02 66.913 -2.01 111.62 437.5467
Base 36 3/E C3-15x20 DL+LL 266.657 68.17 4.35 113.74 452.921
Base 37 4/E C3-15x20 DL+LL 262.97 67.421 5.70 112.354 448.442
Base 38 5/E C3-15x20 DL+LL 261.464 66.686 -1.99 111.275 437.4301
Pile Capacity Check

Total
Onle pile
Service Number
Joint Column Capacity Footing Dimension
Story Column ID Load of pile
Label Grid (kip)
(kip)

DL+LL Ra n T (ft)
Base 1 1/A C4-18" dia 37.756 1 1 1
Base 2 1/B C4-18" dia 75.88 1 1 1
Base 3 1/C C4-18" dia 79.6 1 1 1
Base 4 1/D C4-18" dia 76.79 1 1 1
Base 5 1/E C4-18" dia 76.778 1 1 1
Base 6 1/F C4-18" dia 58.943 1 1 1
Base 7 2/A C2-15X18 190.072 1 1 1
Base 8 3/A C2-15X18 319.039 1 1 1
Base 9 4/A C2-15X18 298.663 1 1 1
Base 10 5/A C2-15X18 257.615 1 1 1
Base 11 6/A C2-15X18 264.091 1 1 1
Base 12 2/F C2-15X18 272.507 1 1 1
Base 13 3/F C2-15X18 403.206 1 1 1
Base 14 4/F C2-15X18 399.007 1 1 1
Base 15 5/F C2-15X18 389.5628 1 1 1
Base 16 7/F C2-15X18 331.0249 1 1 1
Base 17 2/B C2-18X15 309.175 1 1 1
Base 18 2/C C2-18X15 321.598 1 1 1
Base 19 2/D C2-18X15 314.853 1 1 1
Base 20 2/E C2-18X15 315.183 1 1 1
Base 21 6/B C2-18X15 323.278 1 1 1
Base 22 7/C C2-18X15 389.6539 1 1 1
Base 23 7/D C2-18X15 390.6977 1 1 1
Base 24 7/E C2-18X15 388.7391 1 1 1
Base 25 8/A C1-15x12 172.943 1 1 1
Base 26 8/B C1A-18x12 234.98 1 1 1
Base 27 3/B C3-15x20 524.184 1 1 1
Base 28 4/B C3-15x20 550.994 1 1 1
Base 29 5/B C3-15x20 361.517 1 1 1
Base 30 3/C C3-15x20 460.699 1 1 1
Base 31 4/C C3-15x20 444.541 1 1 1
Base 32 5/C C3-15x20 432.588 1 1 1
Base 33 3/D C3-15x20 445.17 1 1 1
Base 34 4/D C3-15x20 438.841 1 1 1
Base 35 5/D C3-15x20 437.5467 1 1 1
Base 36 3/E C3-15x20 452.921 1 1 1
Base 37 4/E C3-15x20 448.442 1 1 1
Base 38 5/E C3-15x20 437.4301 1 1 1
Footing
Footing weight, Effective
depth Total Pile
Back fill & pile Design
Footing Dimension from capacity
Surcharge per capacity Check
existing (kip)
pile (kip) (kip)
GL
B (ft) L (ft) D (ft) Wf Re=Ra-Wf n*Re kip
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
Provided Provided
Concrete
Column Column Footing Design Footing Design
Level strength,
Grid ID thickness, Check thickness, Check
f'c (psi)
Base 33/T PC1-18X2 2843 d (inch)18 Ok d (inch)18 Ok
Base 34/T PC1-18X2 2843 18 Ok 18 Ok
Base 32/S PC1-18X2 2843 18 Ok 18 Ok
Base 31/R PC1-18X2 2843 18 Ok 18 Ok
Base 30/R PC1-18X2 2843 18 Ok 18 Ok
Base 29/R PC1-18X2 2843 18 Ok 18 Ok
Base 28/Q PC1-18X2 2843 18 Ok 18 Ok
Base 25/P PC1-18X2 2843 18 Ok 18 Ok
Base 26/O PC1-18X2 2843 18 Ok 18 Ok
Base 27/O PC1-18X2 2843 18 Ok 18 Ok
Base 28/O PC1-18X2 2843 18 Ok 18 Ok
Base 29/O PC1-18X2 2843 18 Ok 18 Ok
Base 30/O PC1-18X2 2843 18 Ok 18 Ok
Base 32/O PC1-18X2 2843 18 Ok 18 Ok
Base 34/O PC1-18X2 2843 18 Ok 18 Ok
Base 35/O PC1-18X2 2843 18 Ok 18 Ok
Base 5/N PC1-18X2 2843 18 Ok 18 Ok
Base 7/N PC1-18X2 2843 18 Ok 18 Ok
Base 11/N PC1-18X2 2843 18 Ok 18 Ok
Base 14/N PC1-18X2 2843 18 Ok 18 Ok
Base 17/N PC1-18X2 2843 18 Ok 18 Ok
Base 18/N PC1-18X2 2843 18 Ok 18 Ok
Base 19/N PC1-18X2 2843 18 Ok 18 Ok
Base 20/N PC1-18X2 2843 18 Ok 18 Ok
Base 21/N PC1-18X2 2843 18 Ok 18 Ok
Base 23/N PC1-18X2 2843 18 Ok 18 Ok
Base 24/N PC1-18X2 2843 18 Ok 18 Ok
Base 3/M PC1-18X2 2843 18 Ok 18 Ok
Base 21/L PC1-18X2 2843 18 Ok 18 Ok
Base 25/L PC1-18X2 2843 18 Ok 18 Ok
Base 26/L PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 27/L PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 28/L PC1-18X2 2843 18 Not Ok 22 Ok 27.5
Base 29/L PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 30/L PC1-18X2 2843 18 Not Ok 19 Ok 23.75
Base 32/L PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 34/L PC2-18X1 2843 18 Ok 18 Ok
Base 35/L PC2-18X1 2843 18 Ok 18 Ok
Base 2/K PC1-18X2 2843 18 Ok 18 Ok
Base 5/K PC1-18X2 2843 18 Ok 18 Ok
Base 7/K PC1-18X2 2843 18 Ok 18 Ok
Base 11/K PC1-18X2 2843 18 Not Ok 24 Ok 30
Base 14/K PC1-18X2 2843 18 Not Ok 24 Ok 30
Base 17/K PC1-18X2 2843 18 Ok 18 Ok
Base 18/K PC1-18X2 2843 18 Ok 18 Ok
Base 19/K PC1-18X2 2843 18 Not Ok 23 Ok 28.75
Base 20/K PC1-18X2 2843 18 Not Ok 25 Ok 31.25
Base 21/K PC1-18X2 2843 18 Not Ok 19 Ok 23.75
Base 23/K PC1-18X2 2843 18 Not Ok 22 Ok 27.5
Base 24/K PC1-18X2 2843 18 Ok 18 Ok
Base 25/J PC1-18X2 2843 18 Ok 18 Ok
Base 26/J PC1-18X2 2843 18 Ok 18 Ok
Base 27/J PC1-18X2 2843 18 Ok 18 Ok
Base 28/J PC1-18X2 2843 18 Ok 18 Ok
Base 29/J PC1-18X2 2843 18 Ok 18 Ok
Base 30/J PC1-18X2 2843 18 Ok 18 Ok
Base 32/J PC1-18X2 2843 18 Ok 18 Ok
Base 34/J PC1-18X2 2843 18 Ok 18 Ok
Base 35/J PC1-18X2 2843 18 Ok 18 Ok
Base 1/I PC1-18X2 2843 18 Ok 18 Ok
Base 5/I PC1-18X2 2843 18 Ok 18 Ok
Base 7/I PC1-18X2 2843 18 Ok 18 Ok
Base 11/I PC1-18X2 2843 18 Not Ok 23 Ok 28.75
Base 14/I PC1-18X2 2843 18 Not Ok 23 Ok 28.75
Base 17/I PC1-18X2 2843 18 Ok 18 Ok
Base 18/I PC1-18X2 2843 18 Ok 18 Ok
Base 19/I PC1-18X2 2843 18 Not Ok 22 Ok 27.5
Base 20/I PC1-18X2 2843 18 Not Ok 23 Ok 28.75
Base 21/I PC1-18X2 2843 18 Not Ok 23 Ok 28.75
Base 23/I PC1-18X2 2843 18 Not Ok 23 Ok 28.75
Base 24/I PC1-18X2 2843 18 Ok 18 Ok
Base 1/H PC1-18X2 2843 18 Ok 18 Ok
Base 5/H PC1-18X2 2843 18 Ok 18 Ok
Base 7/H PC1-18X2 2843 18 Ok 18 Ok
Base 11/H PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 14/H PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 17/H PC1-18X2 2843 18 Ok 18 Ok
Base 18/H PC1-18X2 2843 18 Ok 18 Ok
Base 19/H PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 20/H PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 21/H PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 23/H PC1-18X2 2843 18 Not Ok 22 Ok 27.5
Base 24/H PC1-18X2 2843 18 Ok 18 Ok
Base 1/G PC1-18X2 2843 18 Ok 18 Ok
Base 5/G PC1-18X2 2843 18 Ok 18 Ok
Base 7/G PC1-18X2 2843 18 Ok 18 Ok
Base 11/G PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 14/G PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 17/G PC1-18X2 2843 18 Ok 18 Ok
Base 18/G PC1-18X2 2843 18 Ok 18 Ok
Base 19/G PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 20/G PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 21/G PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 23/G PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 24/G PC1-18X2 2843 18 Ok 18 Ok
Base 1/F PC1-18X2 2843 18 Ok 18 Ok
Base 5/F PC1-18X2 2843 18 Ok 18 Ok
Base 7/F PC1-18X2 2843 18 Ok 18 Ok
Base 11/F PC1-18X2 2843 18 Not Ok 22 Ok 27.5
Base 14/F PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 17/F PC1-18X2 2843 18 Ok 18 Ok
Base 18/F PC1-18X2 2843 18 Ok 18 Ok
Base 19/F PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 20/F PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 21/F PC1-18X2 2843 18 Not Ok 21 Ok 26.25
Base 23/F PC1-18X2 2843 18 Not Ok 26 Ok 32.5
Base 24/F PC1-18X2 2843 18 Ok 18 Ok
Base 1/E PC1-18X2 2843 18 Ok 18 Ok
Base 5/E PC2-18X1 2843 18 Ok 18 Ok
Base 7/E PC2-18X1 2843 18 Ok 18 Ok
Base 11/E PC1-18X2 2843 18 Ok 18 Ok
Base 14/E PC1-18X2 2843 18 Ok 18 Ok
Base 17/E PC1-18X2 2843 18 Ok 18 Ok
Base 18/E PC1-18X2 2843 18 Ok 18 Ok
Base 19/E PC1-18X2 2843 18 Not Ok 23 Ok 28.75
Base 20/E PC1-18X2 2843 18 Not Ok 25 Ok 31.25
Base 21/E PC1-18X2 2843 18 Not Ok 20 Ok 25
Base 23/E PC1-18X2 2843 18 Ok 18 Ok
Base 24/E PC1-18X2 2843 18 Ok 18 Ok
Base 1/D PC2-18x18 2843 18 Ok 18 Ok
Base 4/D PC2-18x18 2843 18 Ok 18 Ok
Base 6/D PC2-18x18 2843 18 Ok 18 Ok
Base 9/D PC2-18x18 2843 18 Ok 18 Ok
Base 10/D PC2-18x18 2843 18 Ok 18 Ok
Base 12/D PC2-18x18 2843 18 Ok 18 Ok
Base 13/D PC3-13X1 2843 18 Ok 18 Ok
Base 15/D PC3-13X1 2843 18 Ok 18 Ok
Base 13/C PC3-13X1 2843 18 Ok 18 Ok
Base 15/C PC3-13X1 2843 18 Ok 18 Ok
Base 12/B PC2-18x18 2843 18 Ok 18 Ok
Base 12/A PC2-18x18 2843 18 Ok 18 Ok
Base 10/A PC2-18x18 2843 18 Ok 18 Ok
Base 9/A PC2-18x18 2843 18 Ok 18 Ok
Base 6/A PC2-18x18 2843 18 Ok 18 Ok
Base 4/A PC2-18x18 2843 18 Ok 18 Ok
Base 1/A PC2-18x18 2843 18 Ok 18 Ok
2 11 1DL+1LL 0 3.216 0.103 0 0 0
3 11 1DL+1LL 0.004 3.737 0.002 0 0 0
4 11 1DL+1LL 0 3.742 0.064 0 0 0
5 11 1DL+1LL 0.005 1.777 -0.338 0 0 0
6 11 1DL+1LL 0.008 6.665 3.32 0 0 0
32.5 7 11 1DL+1LL 0 13.243 0.013 0 0 0
8 11 1DL+1LL 0 6.662 -3.292 0 0 0
9 11 1DL+1LL -0.003 6.641 3.296 0 0 0
10 11 1DL+1LL 0 13.179 0 0 0 0
11 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
12 11 1DL+1LL -0.002 6.639 3.296 0 0 0
13 11 1DL+1LL 0 13.179 0 0 0 0
14 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
15 11 1DL+1LL -0.002 6.639 3.296 0 0 0
16 11 1DL+1LL 0 13.179 0 0 0 0
17 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
18 11 1DL+1LL -0.002 6.639 3.296 0 0 0
19 11 1DL+1LL 0 13.179 0 0 0 0
20 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
21 11 1DL+1LL -0.002 6.639 3.296 0 0 0
22 11 1DL+1LL 0 13.179 0 0 0 0
23 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
24 11 1DL+1LL -0.002 6.639 3.296 0 0 0
25 11 1DL+1LL 0 13.179 0 0 0 0
26 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
27 11 1DL+1LL -0.002 6.639 3.296 0 0 0
28 11 1DL+1LL 0 13.179 0 0 0 0
29 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
30 11 1DL+1LL -0.001 6.671 3.311 0 0 0
31 11 1DL+1LL 0 13.244 0.002 0 0 0
32 11 1DL+1LL 0.001 6.668 -3.305 0 0 0
33 11 1DL+1LL -0.006 1.798 0.36 0 0 0
34 11 1DL+1LL -0.004 3.648 -0.001 0 0 0
35 11 1DL+1LL -0.005 1.8 -0.364 0 0 0
77 11 1DL+1LL 0 3.746 0.035 0 0 0
86 11 1DL+1LL 0 3.747 -0.039 0 0 0
89 11 1DL+1LL 0.01 1.227 0.128 0 0 0
96 11 1DL+1LL -0.002 6.639 3.296 0 0 0
98 11 1DL+1LL 0.001 6.639 -3.296 0 0 0
100 11 1DL+1LL 0 13.179 0 0 0 0