1, Display instruction
ed
ee | a
aT rf) D es or]
Pe
No. button function renark
1 on/off Turn on or turn off
2 function Enter function setting
3 timing Enter time setting
4 mode Modes switching when turn on
5 “ Up when setting
6 - Down when setting
2. Display
2.1. Display description:
2.1.1. The temperature display area displays relat
anbient temperature, parameter serial nunber,
displays clock, timing,
2.1.2. The flashing perio
‘ted data such as set temperature,
etc.; the right timing display area
query parameter value, set parameter value, etc.
dof each field flashing display is 1 second; after power of
it will work normally after the full display is about 3 seconds.temperature/*°C
15 | Hot water sterilization cycle/day 10 255
Hot water sterilization retention
16 a 255
time/min
0: heat&cold /
Air conditioning mode type
31 0 255 | L:heat only / 2:cold
selection
only
0: no stop /1: on3
32 | Pump to warm shutdown type 0 255
off10 2: stop
Cooling water temperature
36 13 255
difference protection value/°C
Heating inlet and outlet water
37 | temperature difference 1B 255
protection value/°C
Maximum cooling operating
38 70 255
frequency/Rps
Maximum heating operating
39 80 255
frequency/Rpstemperature difference/*C
cooling: return water start
3 3 255
temperature difference/*C
Hot water start temperature
4 5 255
difference °C
Temperature difference when
5 1 255
cooling or heating to stop/°C
Temperature difference when
6 1 255
hot water to stop/°C
Whether power off memory is
Z. 1 255 | Lyes0:no
enabled
8 | Reserved 0 255 | Les O:no
9 | Water flow switch delay/minute i 255
10 | Fan coil linkage is enabled 0 255 | Lyes 0:no
Whether heating auxiliary
ae 1 255 | Lyes O:no
electric heating is enabled
Ambient temperature of
auxiliary heating start of Real T. = seting T. -
12 30 255
refrigeration and hot water 50°C
circuit?C
Whether auxiliary heating of
13 1 255 | Lryes O:no
hot water is enabled
14 | Hot water sterilization 65 255c
2.1.3. No key operation for 30 seconds, the brightness of the LOD display will
automatically dim,
3. Operation
3.1. On key: In the off state, press the “on/off” button to start the unit; in the on
state, press the “on/off” button to stop the unit.
3.2. Mode key: When the line controller is on, press the “Mode” key to select the unit
operation mode (cooling, heating, hot water, etc.).
3.3. Temperature setting:
3.3.1, When the remote controller is on, press the “** or *-” key to adjust the current
mode setting temperature; press and hold the “*” or *-" key for more than 0. 5 seconds
to increase or decrease rapidly.
3.3.2, In combination mode, after adjusting the temperature, the mode icon above will
flash. At this time, pressing the “function” key can switch the mode under the
combined mode and display the temperature of the corresponding mode. The
temperature setting method is the same as 3.3.1.
3.4. Key lock function: Press and hold the “+” and ”~” keys at the same time for 3 seconds
to enter or exit the key lock function. When the “lock” icon appears on the screen,
it means that the remote controller is locked. In the locked state, press and hold
the “+” and “-” keys at the same time for 3 seconds to unlock the keys.
3.5. Function setting (reserved, according to customer needs): In the power-on state,
press the “function” button, the current function flashes, press “mode” to confirm the
start or cancel, and set to go to the next function. Press the “function” key to switch
functions.
3.6, View operating parameters
3.6.1. Enter to view: press the “mode” key and ”-” key at the same time for 3 seconds
to enter the parameter setting state, the temperature display area displays the
paraneter number, and the timing area displays the parameter content;
3.6.2. View operation and exit: After entering the operating parameters, press the "*”
or ”~” key to scroll and wrap to display the various “operating parameters”; press the
“on/off” key or no key operation for 20 seconds to automatically exit the state of viewing
parameters.
3.7.Normal Paramaters setting
3.7.1 Enter setting: press and hold the “mode” key and “+” key at the same time and hold
for 3 seconds, the temperature display area displays the parameter number and flashes,
and the timing area displays the parameter content;
3.7.2 Setting operation: After entering the setting parameters, the parameter serial
number is displayed flashing, press the “+” or “-” key to scroll and wrap to display
the various “setting parameters”, then press the “mode” key to display the parameter
content flashing, and then press “+” or “-" key to modify the current content value,
and then press the “mode” key to save the current modification, and return to the
serial number flashing display state.
3.7.3. Exit setting: Press the “ON/OFF” key or no key operation for 20 seconds will
automatically exit the parameter setting state.3.7.4, Password function (additional) : When the password is 0, it is not enabled by default.
You can directly enter the parameter setting through the combination key. If the
password is a value other than 0, enter the password input interface first, and then
enter the password correctly. Parameter setting. The initialization of the password
is initialized by the data sent by the main board, please check the communication
protocol for details.
3.8, Display fault: When the unit has a fault, the fault flashes and displays in the timing
area, the fault code and temperature are displayed cyclically, and the normal display
is restored when the fault is eliminated,
3.9. Clock settings:
3.9.1. Enter the clock setting: the line controller is turned on, long press the “timing”
button for 3 seconds, the hour part of the clock area will flash, indicating that
it has entered the clock setting state;
3.9. 2. Clock setting operation: enter the clock setting state, the hour part flashes, press
the “+” or *-" key to modify the hour part, then press the “timing” key, the minute
part flashes, press the “+” or “-” key, Modify the minutes, and then press the “timing”
button or 20 seconds of no button operation to automatically save the current settings
and exit.
3.10, Set timing control
3.10. 1 The timing control has 2 groups of timing units, 1 to 2 groups, each group of timing
units can be set to “timing start” and “timing stop”; the default is “invalid” state,
that is, timing start and timing stop have the same time.
3.10.2. Enter timing setting:
1) Press and hold the “timing” button and “+” button at the same time for 3 seconds,
the “1” and “ON” icons on the right side of the screen will display, and the hour display
areawill flash, indicating that it has entered the “1 unit timing start” setting state.
The nunber flashes at the hour, press the “+” or “~” key to modify the time, then press
the “timing” key to confirm the modification and switch to the minute setting, the
minute at the digital flash display, and then press the “+” or “~” key to modify the
time , And then press the “timing” button to confirm the modification.
Note: Press the “on/off” key during the operation to exit the timing setting, and the
set parameters will no longer be saved. Or press the “on/off” button for 3 seconds during
the operation, all timings are invalid.
2) After the “1 unit timing start” setting is completed, it will automatically enter the
“1 unit timing shutdown” setting state, the “1” and “OFF” icons are displayed, the
setting state, the hour is digital flashing, press “+” or “~ “Button to modify the tie,
then press the “timing” button to confirm the modification and transfer to the minute
setting, the digital flashes at the minute, and then press “+” or “-” to modify the
time, and then press the “timing” button to confirm the modification.
Note: Press the “on/off” key during the operation to exit the timing setting, and the
set parameters will no longer be saved. Or press the “on/off” button for 3 seconds during
the operation, all timings are invalid.
3) Press and hold the “timing” key and the “~" key at the same time to enter “period 2”,
and the setting operation of “period 2” is the same as above.
3.10.3. Exit the set timing: When setting the timing 1 or 2 state, press the “switch”
key or no key operation for 20 seconds to give up the current timing and exit the set
timing state.303_| Outer fan 2 failure
Trigger condition: The main control detects that the four-way
Hos | Four-way valve faiture | V2l¥® cannot be switched normally.
‘ourway valve failure | Recovery condition: the fault position of the four-way valve is
cleared.
bog |Drive IPM over —— IPM temperature exceeds the waming
'mperature protection | p ecovery condition: The IPM high flag of the drive is reset.
ae Trigger condition: drive feedback input over current or main
Drive input overcurrent : "
: control monitors current over currentdrive feedback compressor
b05 | protection/phase current . ;
Gvercurrent protection | PH#S® Curent overcurrent or main control monitors current over
current. Recovery condition: The unit is shut down.
Drive DC bus voltage | Trigger condition: drive feedback bus voltage is overvoltage or
06 : ae a
over-voltage protection | undervoltage. Recovery condition: The unit is shut down.
Drive heat sink | Trigger condition: The main control detects that the temperature
bO7 | temperature sensor | ofthe heat sink is too high.
failure Recovery condition: The unit is shut down.
Drive module protection | TEB2" condition: the drive reports the protection of the drive
bO1 (FO) module.
Recovery condition: The unit is shut down.
p02 Drive module hardware | Trigger condition: the drive reports hardware module protection.
protection Recovery condition: The unit is shut down.
03 | Module software | Trigger condition: the drive reports software module protection,
protection Recovery condition: The unit is shut down.
Compressor not Trigger condition: The compressor line is not connected to the
B08 ected drive module.
Recovery condition: The unit is shut down.
oro [CamPssor out of| eson ors be rotten, ny OEP
tep/or failed to start ae ae
Soe alee Recovery condition: The unit is shut down.
2, Normal parameters setting
No Max
name defaults | Min. remark
Starting temperature difference
1 5 0 | 255
of heating effluent/°C
2 | Heating: return water start 3 0 | 255A02
‘TdefTemperature
failure
sensor
AOI
‘TaoTemperature
failure
A08
TemTemperature
faiture
sensor
All
PdTemperature
failure(Mutually
exclusive with
sensor
Tem,
when there is a pressure
sensor, the fault is
enabled)
failure during cooling , Does not stop; displays the fault code
during heating, but does not stop, and replace it with Tem. When
‘Tem and Tdef fail at the same time, it will fail and stop.
HO3
EEPROM error
‘Trigger conditions: There is a problem with the EEPROM chip,
a checksum error, and the data range exceeds.
Recovery conditions: no recovery
P06
High pressure pressure
‘switch disconnect
protection
: High pressure pressure disconnection lasts
Recovery conditions: the high pressure pressure switch is closed.
for 20s.
P09
Tow pressure pressure
switch disconnect
protection
Trigger condition: The compressor is running, but does not
include special processes such as 6min before starting, oil
return, defrosting, etc. The switch is disconnected for 60s.
Recovery conditions: The switch is closed for 20s.
POL
High pressure
refrigeration protection
Trigger condition: cooling mode Pd > 40bar (with pressure
sensor) or Tem > 65° C (without pressure sensor) for 10s.
Recovery condition: Recovery after 20s when the fault is
reported.
E06
Intemal and external
machine communication
failure (split)
‘Trigger condition: The main control and the water conservancy
module did not communicate normally for 1 min.
Restoration conditions: Immediately restore communication.
Liz
Master-drive
communication failure
Trigger condition: The main control and the drive do not
communicate normally for 15s.
Restoration conditions: Immediately restore communication.
Td Over protection
Trigger condition: Td > 120°C for 10s.
Recovery conditions: Td<115°C_ for 20s.
C07
Exhaust overheating
protection
Trigger condition: (with Pd) cooling soft start is over, Td-Pd_t
< 3° for 15min. Recovery conditions: Automatic recovery
after the fault remains for 16s,
y03
Outer fan 1 failure
‘Trigger condition: drive feedback fan failure.
Recovery condition: the drive fan fault bit is cleared.3.10.4 Cancel timing setting: When entering timing setting 1 or 2 state, long press the
“switch” key for 3 seconds to cancel the set timing 1 or 2 function.
3.11. Other settings
3.111. Recycling refrigerant:
1) In the shutdown state, press and hold the “function” key and the “+” key at the same
time for more than 3 seconds to force the outdoor unit to enter the refrigerant recovery
function (the display icon is also “defrost”).
2) When the “recovery refrigerant mode is on”, press the “on/off” button to exit the
“recovery refrigerant mode”.
3.11.2, Forced defrosting: In the heating or hot water running state, simul taneously press
and hold the “function” key and “+” key for more than 3 seconds to force the outdoor
unit to enter the defrosting function.
3.11.8. Forced water pump: simultaneously press and hold the “function” key and “-” key
for more than 3 seconds to force the outdoor unit to enter the water pump function.
3. 12._Combination keys
No. Combination keys function remark
1 press “+” and *-" for 3 Enter or quite
lseconds display lock down
2 | Press mode and “+” for | Enter parameter
3seconds setting mode
3 | Press mode and “-” for | Enter parameters
3seconds gury node
4 | Press clock and “+” for| Enter timer 1
Sseconds setting
5 | Press clock and “-” for | Enter timer 2
seconds setting
6 Press function and “+” for[inter force defrostforce defrost: only can ente)
Bseconds shen turn on and uder heating
mode,
7 Press function and “-” | Enter force water
‘or3seconds pump
4.Table 1 Operating parameters
Defau
No. 4 name Min. | Max. | remark
It
Outdoor ambient temperature
1 0 255 | read
Tao/*C
z Suction temperature Ts/°C 0 255 | read
3 Defrost coil temperature Tdef/°C 0 255 | read4 _ | Exhaust gas temperature Td/°C 255 | read
Opening degree of main
5 | electronic expansion valve 255 | read
PMVI/PLS
EVI_ electronic expansion valve
6 255 | read
PMV2/PLS
Inverter compressor operating
7 255 | read
frequency/Rps
8 Return water temperature /°C 255 | read
9 Hotwater ourlet temperature/°C 255 | read
10 | Compressor error code 255 | read
11 ‘| Reserved 255 | read
12 ‘| Reserved 255 | read
13 | Compressor input current 255 | read
14 | Compressor phase current 255 | read
15 | Driver input voltage 255 | read
16 | Drive bus voltage 255 | read
17 _ | Low pressure 255 | read
Low pressure corresponds to
7 . 255 | read
saturation temperature
19 | High pressure 255 | read
20 high pressure corresponds to saturation
temperature 255 | read5, Error code
code | Code name tinier
oa |? Yeap ser Taser condition: sensor short eireuit or short circuit, lasting
ro |™ .
failure ae conditions: not in short circuit or open circuit, lasting
.
or | B80 Temperature sensor
failure
wap | Tia Temperature sensor
failure
por | 1 Temperature sensor
failure
‘Trigger conditions: The water flow switch is not confirmed to be
Water flow switch oft| ‘108d: 1 minute after the pump is tumed on, the switch is not
FOS | srotection satisfied and closed for 20s; the water flow switch is confirmed
to be closed: the water flow switch is open for 20s. Recovery
conditions: Within 3min, the water flow switch is closed for 20s.
Reftigeration antifreeze | TEE" conditions: antifreeze setting is valid, cooling mode,
709 | entice giecomace | Power on, antitteeze low pressure switch is off for 3s.
: Recovery condition: antifreeze low pressure switch closed for
fen 10s
‘ A ‘ ‘Trigger conditions: cooling, starting, Twi < 5°C for 10s
1 _ | Reftigeration anti-freeze | p ecovery conditions: Two > 7°C for 10s and [Twi(now) >
aa Twilen)#2'C or Twi > 14°C or Twi failure]
Over-emperature “Trigger conditions: heating, power on, Two > 61°C for 10s.
1 | protection for heating | Recovery conditions: Two < 55°C and [Twi(now) <
effluent Twiler)-2°C or Twi < 46°C_or Twi failure]
Triggering conditions:
| 1. Cooling mode, tum on, Twi-Two = 13°C and Two < 7°C;
Flo | Insufficient water flow | 9° Heating mode, tum on, Two-Twi > 13°C and Two >
protection ATC:
Recovery conditions: |Two-Twi] < 10°C for 10s
“Trigger condition: The main control and the water conservancy
module did not communicate normally for 1 min or the sensor
Log | Intemal and extemal] 5, detecting the inlet water temperature and outlet water
communication failure | ternperature was not plugged in. Recovery conditions:
Immediate recovery on communication
Communication failure | Trigger condition: the internal machine and the wire controller
£32 | between main control | did not communicate normally for 15s without stopping
and line control Recovery conditions: Immediate recovery on communication
‘agg | TéTemperature sensor | Trigger condition: sensor short cient or short circuit, lasting
failure 60s. Recovery condition: not in short circuit or open circuit,
TsTemperature sensor| lasting 10s. In addition: 1. Tem failure does not report failure
A07 e A ‘ .
failure during heating, and does not stop; 2. Tdef failure does not report