You are on page 1of 104

Alfa Laval in brief

Close at hand
Alfa Laval is a leading global provider of
specialized products and engineered
solutions.

Our equipment, systems and services


are dedicated to helping customers to
optimize the performance of their Heat exchangers for Hygienic Fluid Handling Equipment, January 2021
­processes. Time and time again.

We help our customers to heat, cool,


separate and transport products such
as oil, water, chemicals, beverages,
foodstuffs, starch and pharmaceuticals.

Our worldwide organization works


closely with customers in almost 100
countries to help them stay ahead.

How to contact Alfa Laval


Contact details for all countries are
continually updated on our website.
Please visit www.alfalaval.com to
access the information.
Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB, Sweden. Alfa Laval © 2021

100001539EN-1 2101
This page is intentionally left blank
Everything
at your fingertips
Alfa Laval’s solutions for hygienic applications are the result of
continuous innovation, and our dedicated efforts to meet the
challenges faced by industries. With the Alfa Laval online
catalogue, detail of our comprehensive product range can now
be conveniently at your fingertips at all times.

Whatever you need, and wherever you are, Alfa Laval’s


components and expertise are always readily available through
our network of over 1500 channel partners, supported by our
own sales companies around the world.

Alfa Laval has a wide range of tools and resources to make life
easier. Our online catalogue is easily accessible and updated
regularly. We also offer the possibility to download 2D and 3D
drawings. Go to www.alfalaval.com/high.

At www.alfalaval.com/biopharm you can download the


comprehensive Q-doc documentation for our UltraPure
portfolio.

Our channel partners also have access to a growing pool of


resources at the Alfa Laval eBusiness portal, including full
documentation, real-time stock availability and the opportunity
to order and track shipments online. As well as being kept up to
date on the latest developments through the InSight newsletter.

Discover a world of hygienic solutions at our dedicated portals:

www.alfalaval.com/biopharm
www.alfalaval.com/food
Pumps Centrifugal Pumps Rotary Lobe Pumps Twin Screw Circumferential Piston Pump

LKH LKH UltraPure LKHex LKH Evap LKHPF LKHI LKH Multistage LKH Prime LKH Prime UltraPure SolidC SolidC UltraPure MR SRU SX OptiLobe Twin Screw SCPP

Valves Double Seat Valves Double Seal Single Seat Butterfly Diaphragm Valves Ball Valves Regulating Valves
and Valve Valves Valves

Automation

Aseptic Mixproof Unique Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof SMP-BC Unique SSV Unique SSV Unique SSV SSV Unique SSV Unique SSV Unique SSSV LKAP LKB LKB-F LKB UltraPure Unique DV-ST SBV Sanitary Unique RV-ST Unique RV-P CPM-2
Mixproof 3-body High Alloy UltraPure Large Particle Tank Outlet Horizontal Tank Change-over Aseptic Tangential Tank Outlet Manual Small Single Seat Air-Operated UltraPure

Shutter Valve Control/Check Valves Safety Valves Sample Valves Control Unit and Indication

LKC-2 LKUV-2 LKBV SB Membrane SB Micro Sample Port


MH Shutter Non-Return LKC UltraPure Air-Relief Air-Blow Safety Valve SB Anti Vacuum House SB Anti Vacuum Valve SB Pressure Relief Valve Unique Sampling Valve Sample Valve SB Micro Sample Port Type M ThinkTop V70 ThinkTop V50 ThinkTop D30 ThinkTop Basic Intrinsically safe IndiTop Unique Control LKB

Heat Gasketed Plate Heat Exchangers Fusion-Bonded


Plate Heat Exchangers
Brazed
Plate Heat Exchangers
Welded Spiral
Heat Exchangers
Welded Plate and
Block Heat Exchanger
Scraped Surface
Heat Exchangers
Tubular Heat Exchangers

Transfer

FrontLine BaseLine Industrial line TS-series AlfaCond / AlfaVap AlfaNova Brazed PHE Spiral Heat Exchanger Combabloc Free Flow Contherm Pharma-Line Pharma-X ViscoLine

Tank Dynamic Spray Heads Static Spray Balls Agitators and Mixers
Equipment

TJ 20G TJ40G SaniJet 25 UltraPure SaniMidget Retractor GJ A6 GJ 9 SaniJet 20 SaniMidget SaniMidget SB LKRK Static Spray Ball Hybrid Powder Mixer Rotary Jet Mixer LeviMag® LeviMag® UltraPure ALS ALB ALTB

Instrumentation Tank Covers Tank Accessories

Temperature Conductivity Electric Pressure Electronic Pressure Weighing Systems Pressure Potentiometric
Flow Transmitter Rotacheck Transmitter Transmitter Pressure Gauge Gauge Transmitter Level Switch UltraPure Flow Meter Transmitter Thermometer Level Transmitter Unique Flexbody LKDC-LP Type R LKD Sight Glasses Tank Feet

Installation Hygienic Tubes and Fittings Filters and Strainers Membranes Membranes Auxiliary Membrane Equipment
Service & Spare Parts
Material and Filters

Flanges, Clamps and Unions Bends, Tees and Reducers Tubes and Tube Support UltraPure Tubes & Fittings Strainers Spiral membranes Plate and Frame module Flat sheet membranes Test Units Housing ATD Couplers Safety Filters Service Kits
Pumps Centrifugal Pumps Rotary Lobe Pumps Twin Screw Circumferential Piston Pump

LKH LKH UltraPure LKHex LKH Evap LKHPF LKHI LKH Multistage LKH Prime LKH Prime UltraPure SolidC SolidC UltraPure MR SRU SX OptiLobe Twin Screw SCPP

Valves Double Seat Valves Double Seal Single Seat Butterfly Diaphragm Valves Ball Valves Regulating Valves
and Valve Valves Valves

Automation

Aseptic Mixproof Unique Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof SMP-BC Unique SSV Unique SSV Unique SSV SSV Unique SSV Unique SSV Unique SSSV LKAP LKB LKB-F LKB UltraPure Unique DV-ST SBV Sanitary Unique RV-ST Unique RV-P CPM-2
Mixproof 3-body High Alloy UltraPure Large Particle Tank Outlet Horizontal Tank Change-over Aseptic Tangential Tank Outlet Manual Small Single Seat Air-Operated UltraPure

Shutter Valve Control/Check Valves Safety Valves Sample Valves Control Unit and Indication

LKC-2 LKUV-2 LKBV SB Membrane SB Micro Sample Port


MH Shutter Non-Return LKC UltraPure Air-Relief Air-Blow Safety Valve SB Anti Vacuum House SB Anti Vacuum Valve SB Pressure Relief Valve Unique Sampling Valve Sample Valve SB Micro Sample Port Type M ThinkTop V70 ThinkTop V50 ThinkTop D30 ThinkTop Basic Intrinsically safe IndiTop Unique Control LKB

Heat Gasketed Plate Heat Exchangers Fusion-Bonded


Plate Heat Exchangers
Brazed
Plate Heat Exchangers
Welded Spiral
Heat Exchangers
Welded Plate and
Block Heat Exchanger
Scraped Surface
Heat Exchangers
Tubular Heat Exchangers

Transfer

FrontLine BaseLine Industrial line TS-series AlfaCond / AlfaVap AlfaNova Brazed PHE Spiral Heat Exchanger Combabloc Free Flow Contherm Pharma-Line Pharma-X ViscoLine

Tank Dynamic Spray Heads Static Spray Balls Agitators and Mixers
Equipment

TJ 20G TJ40G SaniJet 25 UltraPure SaniMidget Retractor GJ A6 GJ 9 SaniJet 20 SaniMidget SaniMidget SB LKRK Static Spray Ball Hybrid Powder Mixer Rotary Jet Mixer LeviMag® LeviMag® UltraPure ALS ALB ALTB

Instrumentation Tank Covers Tank Accessories

Temperature Conductivity Electric Pressure Electronic Pressure Weighing Systems Pressure Potentiometric
Flow Transmitter Rotacheck Transmitter Transmitter Pressure Gauge Gauge Transmitter Level Switch UltraPure Flow Meter Transmitter Thermometer Level Transmitter Unique Flexbody LKDC-LP Type R LKD Sight Glasses Tank Feet

Installation Hygienic Tubes and Fittings Filters and Strainers Membranes Membranes Auxiliary Membrane Equipment
Service & Spare Parts
Material and Filters

Flanges, Clamps and Unions Bends, Tees and Reducers Tubes and Tube Support UltraPure Tubes & Fittings Strainers Spiral membranes Plate and Frame module Flat sheet membranes Test Units Housing ATD Couplers Safety Filters Service Kits
Pumps Centrifugal Pumps Rotary Lobe Pumps Twin Screw Circumferential Piston Pump

LKH LKH UltraPure LKHex LKH Evap LKHPF LKHI LKH Multistage LKH Prime LKH Prime UltraPure SolidC SolidC UltraPure MR SRU SX OptiLobe Twin Screw SCPP

Valves Double Seat Valves Double Seal Single Seat Butterfly Diaphragm Valves Ball Valves Regulating Valves
and Valve Valves Valves

Automation

Aseptic Mixproof Unique Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof Unique Mixproof SMP-BC Unique SSV Unique SSV Unique SSV SSV Unique SSV Unique SSV Unique SSSV LKAP LKB LKB-F LKB UltraPure Unique DV-ST SBV Sanitary Unique RV-ST Unique RV-P CPM-2
Mixproof 3-body High Alloy UltraPure Large Particle Tank Outlet Horizontal Tank Change-over Aseptic Tangential Tank Outlet Manual Small Single Seat Air-Operated UltraPure

Shutter Valve Control/Check Valves Safety Valves Sample Valves Control Unit and Indication

LKC-2 LKUV-2 LKBV SB Membrane SB Micro Sample Port


MH Shutter Non-Return LKC UltraPure Air-Relief Air-Blow Safety Valve SB Anti Vacuum House SB Anti Vacuum Valve SB Pressure Relief Valve Unique Sampling Valve Sample Valve SB Micro Sample Port Type M ThinkTop V70 ThinkTop V50 ThinkTop D30 ThinkTop Basic Intrinsically safe IndiTop Unique Control LKB

Heat Gasketed Plate Heat Exchangers Fusion-Bonded


Plate Heat Exchangers
Brazed
Plate Heat Exchangers
Welded Spiral
Heat Exchangers
Welded Plate and
Block Heat Exchanger
Scraped Surface
Heat Exchangers
Tubular Heat Exchangers

Transfer

FrontLine BaseLine Industrial line TS-series AlfaCond / AlfaVap AlfaNova Brazed PHE Spiral Heat Exchanger Combabloc Free Flow Contherm Pharma-Line Pharma-X ViscoLine

Tank Dynamic Spray Heads Static Spray Balls Agitators and Mixers
Equipment

TJ 20G TJ40G SaniJet 25 UltraPure SaniMidget Retractor GJ A6 GJ 9 SaniJet 20 SaniMidget SaniMidget SB LKRK Static Spray Ball Hybrid Powder Mixer Rotary Jet Mixer LeviMag® LeviMag® UltraPure ALS ALB ALTB

Instrumentation Tank Covers Tank Accessories

Temperature Conductivity Electric Pressure Electronic Pressure Weighing Systems Pressure Potentiometric
Flow Transmitter Rotacheck Transmitter Transmitter Pressure Gauge Gauge Transmitter Level Switch UltraPure Flow Meter Transmitter Thermometer Level Transmitter Unique Flexbody LKDC-LP Type R LKD Sight Glasses Tank Feet

Installation Hygienic Tubes and Fittings Filters and Strainers Membranes Membranes Auxiliary Membrane Equipment
Service & Spare Parts
Material and Filters

Flanges, Clamps and Unions Bends, Tees and Reducers Tubes and Tube Support UltraPure Tubes & Fittings Strainers Spiral membranes Plate and Frame module Flat sheet membranes Test Units Housing ATD Couplers Safety Filters Service Kits
Stainless Steel and Rubber Materials

ky Technical Information
Stainless Steel and Rubber Materials

Stainless Steel
Our stainless steel material have the following demands to the contents of the most essential alloys:
Molybdenum
Descriptions Standard Chrome Cr% Nickel Ni% Mo% Carbon C%
AISI 304 ASTM A270 18.0-20.0 8.0-10.5 0.0 ≤ 0.08
AISI 304L ASTM A270 18.0-20.0 8.0-12.0 0.0 ≤ 0.03
AISI 316L ASTM A270 16.0-18.0 10.0-14.0 2.0-3.0 ≤ 0.03
1.4301 (304) EN 10088-1 (X 5CrNi18-10) 17.0-19.5 8.0-10.5 0.0 ≤ 0.07
1.4307 (304L) EN 10088-1 (X 2CrNi18-9) 17.5-19.5 8.0-10.0 0.0 ≤ 0.03
1.4401 (316) EN 10088-1 (X 5CrNiMo17-12-2) 16.5-18.5 10.0-13.0 2.0-2.5 ≤ 0.07
1.4404 (316L) EN 10088-1 (X 2CrNiMo17-12-2) 16.5-18.5 10.0-13.0 2.0-2.5 ≤ 0.03
1.4435 (316L) EN 10088-1 (X 2CrNiMo18-14-3) 17.0-19.0 12.5-15.0 2.5-3.0 ≤ 0.03
1.4571 (316TI) EN 10088-1 (X6CrNiMoTi17-12-2) 16.5-18.5 10.5-13.5 2.0-2.5 ≤ 0.08

Rubber Materials
In order to obtain the longest possible lifetime for rubber seals it is essential to choose the right quality for the actual duty. Consequently when choosing
rubber quality, the characteristics of the different rubber types should be considered. All product wetted rubber material are in conformity of FDA.

EPDM Rubber (Ethylene Propylene)


EPDM rubber is widely used within the food industry as it is resistant to most products used in this sector. Another advantage is that it may be used to a
recommend max. temperatures of 140°C (244°F). However, there is one essential limitation, EPDM is not resistant to organic and non-organic oils and
fats. The resistance to ozone is excellent.

Actylonitrile Butadiene Rubber, NBR


NBR is the rubber type most frequently used for technical purposes. It is quite resistant to most hydrocarbons, e.g oil, grease and fat. It is sufficiently
resistant to diluted lye and nitric acid and may be used to a recommend max. 95°C (203°F). As NBR is attacked by ozone it may not be exposed to
ultraviolet rays and should thus consequently be stored so that this is avoided.

Silicone Rubber, Q
The most significant quality of silicone rubber is that it can be applied from temperatures below -50°C (-58°F) to approx. + 180°C (356°F) and still
keep its elasticity. The chemical resistance is satisfactory to most products. However, undiluted lye and acids as well as hot water and steam may
destroy silicone rubber. The resistance to ozone is good.

Fluorine Rubber, FPM


FPM is often used when other rubber types are unsuited, especially at high temperatures up to approx. 180°C (356°F). The chemical resistance is good
to most products, however hot water, steam, lye, acid and alcohol should be avoided. The resistance to ozone is good.

Hydrogenated actylonitrileButadiene Rubber, HNBR


Mechanically strong and normally resistant to ozone and strong oxidizers, animal and vegetable fats, nonpolar solvents, oils and lubricants, water and
aqueous solutions. The recommend max. temperature is 130°C (266°F).

Perfluoroalkoxy polymer, PFA


PFA is very similar to PTFE, but opposite to those PFA is thermo plastic and has minimal porosity. PFA has a very high mechanical strength which
makes it a perfect choice when dealing with abbrasive products. The PFA seal offers longer service intervals. The recommend max. temperature
for the PFA seal is 90°C (194°F).
Stainless Steel and Rubber Materials

Product and chemical resistance of flexible rubber materials


The information below is intended as an aid in selecting the best rubber quality for an actual application. It is not possible to state any general lifetime
of rubber seals as many factors influence it: chemical attack, temperature, mechanical wear etc. Extreme temperatures, even within the generally
accepted limits, may worsen other kinds of attack and thus reduce the lifetime.

Ratings
1 = Unsuitable.
2 = Limited suitability.
3 = Normal suitability.
4 = High suitability.
- = Not recommended for other reasons.
The table contains data which have been complied from the results of our own tests and the recommendations of our raw material suppliers. The
data should be considered as recommendations only and will be brought up-to-date from time to time. They are based on constant contact with
the specified product.
In case of doubt or lack of information it would be advisable to consult us directly, which will enable us to investigate specific applications.
Product or process NBR1) HNBR2) EPDM3) Q4) FPM5) PTFE6)
Dairy products (milk, cream) 3 3-4 3-4 3-4 - 3-4
Dairy products (sour milk products) 3 3-4 3-4 3-4 - 3-4
Brewery products (beer, hops etc.) 3 3-4 3-4 1-2 2-3 3-4
Wine and yeast 3 3-4 4 4 2-3 3-4
Animal and vegetable fats 100°C 3 4 1-2 3 4 3-4
Water and water solutions < 70°C 3 4 4 3 2-4 3-4
Hot water and steam < 130°C 1 4 4 2 - 3-4
Concentrated fruit juices and etheral oils < 100°C 1 - 1 1 3 3-4
Non-oxydising acids < 80°C 1-2 2 3 1-2 2 3-4
Oxydising acids < 80°C - 2 3 1 2 3-4
Weak concentrate of lye < 100°C 2 3-4 4 2 2 3-4
Strong concentrate of lye < 100°C 1 2-3 3 1 1 3-4
Mineral oils < 110°C 3 4 - - 4 3-4
Aliphatic carburetted hydrogen (hexane) 3 3 1 1 4 3-4
Aromatic carburetted hydrogen (benzole) 1 2 1 1 3 3-4
Alcohols 1-3 2-3 2-3 3-4 3-4 3-4
Ester and ketones 1-2 1-2 1-2 1-2 3-4 3-4
Ether 1 2 1 1-3 3-4 3-4
Methylene chloride 1 2 1 2-3 3-4 3-4
Ozyne and atmospheric conditions 1-2 3 4 4 3-4 3-4
International designation of flexible rubber materials according to ISO R 1629.
ISO = International standard.

Notes

Abbreviation
Designation of flexible rubber materials
symbol
1) Nitrile rubber N
2) Hydrogenated actylonitrile rubber H
3) Ethylene propylene rubber E
4) Silicone rubber Q
5) Fluorinated rubber F
6) Polytetraflour ethylene
Compliance and certification

We can provide documented and certified compliance with a broad spectrum of relevant international and local hygiene standards, worldwide.
This helps you Significantly reduce the engineering costs of setting up and operating standards-compliant processing plants around the world.

For special requests please contact your local Alfa Laval organisation

The mission of 3-A SSI is to enhance product safety for consumers of food, beverages, and pharmaceutical
products through the development and use of 3-A Sanitary Standards and 3-A Accepted Practices.
The 3-A Symbol is a registered mark used to identify equipment that meets 3-A Sanitary Standards for
design and fabrication.

ATEX is based on the requirement of the European Directive 94/9/EC (also known as ATEX 95 (100a)), the
Equipment Directive. The name ATEX (ATmospheres EXplosible) is commonly given to the framework for
controlling explosive atmospheres and the standards of equipment and protective systems used in them

The European Hygienic Engineering & Design Group (EHEDG) is a consortium of equipment manufacturers,
food industries, research institutes as well as public health authorities and was founded in 1989 with the aim
to promote hygiene during the processing and packing of food products.
EHEDG has authorised the use of the EHEDG Certification logo for Alfa Laval equipment complying with
O C T O B E R 2008

the EHEDG hygienic design criteria. The Certification include cleanability testing of equipment according to
the methodology described in EHEDG guidelines.

Alfa Laval Q-doc includes:


- 3.1 certificate in accordance to EN 10204 (MTR)
- Elastomer compliance declarations
- Surface finish comformity declaration
- Compliance to the Regulation (EC) No. 1935/2004

CE marking is a mandatory conformity mark for products placed on the market in the European Economic
Area (EEA). With the CE marking on a product the manufacturer ensures that the product conforms with the
essential requirements of the applicable EC directives. The letters "CE" stand for "Conformité Européenne"
("European Conformity").

The ASME BPE Certification Program is unique in the world, having resulted from widespread industry
A
S requested for standardization. It is the leading standard on how to design and build equipment and systems
M
E used in the production of biopharmaceuticals. It incorporates current best-practices for enhancing product
BPE-106 production efficiencies, lower development and manufacturing costs, and increase quality and safety, while
complying with regulations. The Certification Mark with a BPE Designator indicates that components bearing
the mark have been manufactured and certified by ASME BPE Certificate Holder.
1

1. Heat Exchangers

Our heat exchangers are developed not only to meet your demands for safety, efficiency
and hygiene, but also to ensure the careful handling of your products.

Product Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0

Brazed Plate Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1

Fusion Bonded Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2

Gasketed plate-and-frame exchangers . . . . . . . . . . . . . . . . . . . . . . . . . 1.3

Shell & tube heat exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4

Single scraped surface heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . 1.5

Double wall scraped surface heat exchanger . . . . . . . . . . . . . . . . . . . . . 1.6


Hygienic product animations
Get a look inside our products and see how it works. Mouseover the image and click to see animations. - See
more at:

http://www.alfalaval.com/products/fluid-handling/hygienic-product-animations

- Heat exchangers
Lock washer on Alfa Laval multi section hygienic Key hole bolt opening on Alfa Laval multi section
gasketed plate heat exchanger hygienic gasketed plate heat exchanger

Bearing box on Alfa Laval multi section hygienic Adjustable feet on Alfa Laval multi section hygienic
gasketed plate heat exchanger gasketed plate heat exchanger

Tightening bolt cover on Alfa Laval multi section Connection plate roller on Alfa Laval multi sec- tion
hygienic gasketed plate heat exchanger hygienic gasketed plate heat exchanger

Pressure plate roller on T-bar on Alfa Laval Elongated nuts on Alfa Laval multi section hygienic
multi section hygienic GPHE gasketed plate heat exchanger

Fixed bolt head on Alfa Laval multi section


hygienic gasketed plate heat exchanger
This page is intentionally left blank
Heat exchangers for hygienic use
The complete line
Performance
in good hands
Working with hygienic applications is a question of care, attention
to detail and dedication to outstanding performance. Alfa Laval has
a proven track record in delivering innovative solutions for hygienic
applications based on our core technologies of separation, heat
transfer and fluid handling.

Superior safety, gentle efficiency and uncompromising cleanliness


are the hallmarks of our hygienic pumps, heat exchangers, valves
and automation, tubes and fittings, and separation, filtration and
tank equipment. Which is why so many customers in the food,
biopharm and other demanding industries put process performance
and hygiene in the capable hands of our experts, sales companies
and partners worldwide.

Here you will find an overview of Alfa Laval heat exchangers for
hygienic applications. For complete technical details and product
specification, contact your local Alfa Laval supplier or visit us at
www.alfalaval.com
Gasketed plate
heat exchangers
Suitable for a wide range of applications on the frame. Their innovative design makes
in most industries, gasketed plate heat full use of our industrial experience, plus the
exchangers are a compact and efficient latest developments in material, construction
heat transfer solution. Alfa Laval’s gasketed and production methods.
models are designed for exceptional control,
which makes them ideal for heating and Holding the plates together are sturdy,
cooling duties in demanding hygienic pressure-graded frames with hygienic and
processes. labour-saving features. These offer great
flexibility for expansion or rebuilding, as well
Among the Alfa Laval advantages are our as small ports that enable CIP (cleaning-in-
unique Clip plates, whose glueless clip-on place) without specialized pumps.
gaskets can be replaced with the plates still
FrontLine
FrontLine is a top-of-the-line series of plate heat
exchangers. Able to meet the highest demands on
hygienic control, it features a superior and flexible
design that allows easy handling and modification.

Among the main applications for FrontLine are dairy


pasteurization, yoghurt cooling, UHT treatment and
work with heat-sensitive products. FrontLine frames
can be supplied in stainless steel and silver-coated
versions, and the Clip plates are available in alternative
materials for challenging food-processing tasks. In
most cases their Clip plates can be cleaned via CIP
(cleaning-in-place), using the same flow as in the
process itself.

BaseLine
With its cost-effective frame design, the BaseLine
series of plate heat exchangers is a competitive
choice for process and utility duties. Working at
pressures up to 10 bar (g), it handles not only heating
and cooling, but also pasteurization at low flow rates.

Typical BaseLine applications include simple


pasteurization, raw milk cooling, media heating/
cooling and CIP (cleaning-in-place) heating.

FusionLine
Alfa Laval FusionLine is the world’s first plate heat exchanger
with open flow channels and no contact points on the product
side. The 4–6 mm open channel makes it ideal for handling low
to medium viscosity products with fibres and particulates, such
as juices and soft drinks, prepared foods, soups and sauces.

This unique design and performance is made possible by fusion-


bonded plate cassettes on the media side, together with a
special gasket. The FusionLine combines the energy efficiency,
accessibility and modularity of plate technology with the viscous
and particulate-handling capabilities of tube technology.
AlfaCond
and AlfaVap
A smart alternative to bulky and expensive falling
film condensers and evaporators, these compact
solutions feature deep channels, large ports and
laser welding to enable vacuum and low-pressure
evaporation and condensation for aqueous and
organic systems.

The AlfaCond plate condenser is designed for


condensing vapours into liquids at low pressure.
The AlfaVap plate evaporator optimizes evaporation
processes and provides a much higher thermal
efficiency than conventional units.

M-series
M-ser
The M-series ofo plate heat exchangers
is an efficient solution
s for general heating
and cooling duties
du in hygienic applications.
In addition, the series is a perfect alterna-
tive for heating and cooling service media.

M-series
M -se
series
riries pplate
l te heat exchangers are only
pla
la
available
avai
av aila
ailabl
la ble
bl e with
w th epoxy-painted
wi e frames.

TS6-M
Thanks to its unique plate geometry,
TS6-M series of plate heat exchangers is
thermally optimized for steam condensation
duties. This makes it useful not only for
heating water, but also for heating CIP
(cleaning-in-place) solution by means of
steam.

TS6-M plate heat exchangers are available


with either stainless steel or epoxy-painted
frames.
Clip plates
Alfa Laval’s Clip plates are custom-designed for the in materials from NBR to EPDM, enabling a perfect match
efficient thermal treatment of liquid food and sensitive for the application temperature and characteristics.
hygienic products. Based on many years of practical
experience in food applications, they offer a well-balanced The plates themselves are available in many geometries
answer to complex needs. and patterns, as well as a choice of stainless steel, SMO
or titanium. Their excellent press depth and relatively few
Clip plates take their name from their glueless clip-on contact points prolong operating times, while a unique
gaskets, which can quickly and easily be removed with the distribution area ensures an uniform flow over the entire
plates still on the frame. Food-grade gaskets are available plate surface.

Standard WideStream Gemini


Well-proven and extremely heat Our WideStream Clip plates have With their double walls, our Gemini
efficient, our Standard Clip plates very few contact points, which Clip plates combine excellent heat
meet the toughest requirements in helps prevent blockage and results transfer with increased protection
food processing. They feature a in longer uninterrupted operating against the mixing of fluids. The
chevron pattern for maximum times. The plates are specially plates consist of two sheets that
strength at high working pressures, developed for the pasteurization are formed together, which prevents
with different chevron angles of fruit juices and other products the media from mixing even in the
available for optimal heat transfer containing pulp and fibres. event of a cracked plate.
at a given pressure drop.
Fusion-bonded plate heat
exchangers (AlfaNova)
AlfaNova plate heat exchangers are the first
in the world to be manufactured from 100%
stainless steel. Thanks to AlfaFusion –
Alfa Laval’s revolutionary technology for
bonding stainless steel components – they
can withstand even extreme temperatures
and pressure fatigue conditions.

Their exceptional performance suits AlfaNova


plate heat exchangers to demanding duties in
a broad range of industrial applications and
utilities. Often employed to heat water or CIP
(cleaning-in-place) solution by means of water
and steam, they can also be used for general
heating and cooling duties.

Brazed plate heat


exchangers
Alfa Laval’s brazed plate heat exchangers
are extremely compact – a result of high
heat transfer coefficients, small hold-up
volumes and the use of thin materials.
The stainless steel plates are brazed into a
package without the use of gaskets, with
copper serving as the brazing material.

Operating costs are reduced by the heat


exchangers’ high thermal efficiency, while
the rectangular shape and frontpositioned
connections make for easy installation.
Resistant to heat, pressure, vibration,
and above all corrosion, brazed heat
exchangers are perfect in utilities such
as heating water with steam.
Scraped surface and
tubular heat exchangers

Contherm
The Alfa Laval Contherm scraped surface heat
exchanger (SSHE) handles any viscous, sticky and/or
heat-sensitive process fluids as long as they are
pumpable. It is widely used within the food and
personal care industries.

Available in different versions, Contherm can handle


products with low to extremely high viscosities or those
containing particulates as well as special application
and process requirements, such as evaporation.

ViscoLine
The Alfa Laval ViscoLine range is a series of highly
efficient tubular heat exchangers designed for gentle
handling of low to medium viscosity products or
products containing particulates. Widely used in
the food and beverage industries, it is suitable for
heating, cooling, pasteurization, UHT treatment,
heat regeneration and other heat transfer duties.
UltraPure tubular
heat exchangers
The biopharm industry requires exceptional certainty, not
only when it comes to product hygiene, but also when
it comes to isolating products and media. For this reason,
Alfa Laval offers a number of specially developed, high-
quality tubular heat exchangers.

Pharma-X
Designed for point-of-use cooling in the bio-
pharm industry, the Pharma-X tube-in-tube heat
exchanger eliminates the risk of contamination
between the product and cooling media. It con-
sists of three discrete tubes arranged one within
the other, curved through 180º to create a bend
that takes up thermal expansion.

The Pharma-X heat exchanger can be used in


many application areas, including point-of-use
cooling on WFI (Water For Injection) ring mains,
cooling/heating of pure water in the biopharm
industry and cooling/heating of distilled water/
WFI for processing equipment.

PharmaLine
PharmaLine is a double tube sheet (DTS) shell-and-
tube heat exchanger that provides full drainability
and prevents the risk of cross-contamination. Its
bundle of seamless, electropolished tubes handles
the flow of product media, with service media
running outside the tubes in a crossflow.

Since the unit is flexible in design, size and material,


it can be used in any hygienic application with high
demands. Typical uses for PharmaLine are in water
systems, water for injection, purified water and CIP
(cleaning-in-place) systems. PharmaLine is also
used for general product heating and cooling duties.
Handling your hygienic
processing needs
Optimizing the performance of hygienic processes is a challenge best met
with expertise. Alfa Laval expertise is the result of years of accumulated
knowledge and a comprehensive research and development programme.

With this foundation, we work closely with our channel partners


to help companies extract the most value from raw materials,
minimize waste and emissions, and deliver safe and hygienic
products. Ultimately, our ambition is to help companies supply
quality products to consumers at competitive prices.

Alfa Laval has served as the standard bearer for the production
of hygienic products since Gustaf de Laval invented the centrifu-
gal separator to separate cream from milk more than a century
ago. That same ingenuity is applied to all our hygienic compo-
nents and solutions that safeguard the flavour, texture and
appearance of food, dairy products and beverages.

For the pharmaceutical, biopharm and personal care industries,


our contributions not only entail hygienic design and superior
performance but comprehensive documentation and solutions
that are easy to validate. Which in turn raise the quality, clean-
liness and uniformity of the final products.

Safeguarding hygienic applications requires entrusting your


processes to the safe, competent care of a reliable partner.
With Alfa Laval you are in good hands.
Service for any brand
Having Alfa Laval service your heat exchangers is more than just practical – it
makes good business sense. Alfa Laval’s local specialists know your industry
and its needs, but are also part of a global network of service and support.

Drawing on our many years of thermal transfer experience, Alfa Laval service
specialists are experts on heat exchangers, chemicals and cleaning methods.
As a result, they can service not only our own heat exchangers, but also plate
heat exchangers from other manufacturers.

Expertise in every detail


At Alfa Laval’s service centres, we handle all aspects of
heat exchanger maintenance. By restoring heat transfer
and pressure drop, we ensure quality, productivity and
energy efficiency. And by finding and stopping leakage,
we reduce production losses and protect your equipment
and the environment.

We work with specialized tools and chemicals, as well


as brand-quality spares and the best glues and mounting
procedures. Many of our services are available in
standardized packages, so that you can choose the level
that meets your needs.

AllBrands service
Through Alfa Laval’s unique AllBrands service, we can
restore any plate heat exchanger to optimal working con-
dition. This gives you a single, reliable speaking partner,
regardless of the models or brands that you use.

Our qualified specialists, decades of experience and


extensive database of solutions make Alfa Laval the
simple path to top-notch performance.
This page is intentionally left blank
1.1 Brazed Plate Heat Exchangers

The Brazed Heat Exchangers from Alfa Laval are the perfect heat exchangers for utilities
like heating-water or steam.

Application Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1.28

Product leaflets
CB16 / CB400 - Brazed Plate Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . 1.1.30
CB20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1.43
This page is intentionally left blank
Brazed Plate Heat Exchangers Application Overview
1.1
.

CB
16 18 20 30 60 110 112 200 300 400
Main duties
Dairy
Milk Cooling
Milk/cream pasteurization
Cultured milk cooling
Whey pasteurization
Ice cream pasteurization
Brewery
Wort cooling
Beer cooling
Beer pasteurization
Beverages
Clarified juices, drinks, wine
Juice/drinks with pulp/fibres
Clarified fruit & sugar conc.
Clody fruit concentrate
Other food
Low viscous products
High viscous products
Sticky/chunky/particles
Vegetable oil
Pharma
Pre-heating in water purification
In-line heater WFI/PW
Point of use cooler WFI/PW
Heating of holding tank WFI/PW
Product heating/cooling
Utilities
CIP Heating
Water heating/cooling • • • • • • • • • •

1.1.29
CB16 / CB400 Brazed Plate Heat Exchangers
1.1
.

ky Alfa Laval CB16 / CB400 - Brazed Plate Heat Exchanger


Brazed Plate Heat Exchangers

Alfa Laval CB brazed plate heat exchangers provide efficient heat


transfer with a small footprint.

Applications
• HVAC heating and cooling
• Oil cooling
• Industrial heating and cooling
Benefits
• Compact
• Easytoinstall
• Self-cleaning
• Low level of service and maintenance is required
• All units are pressure and leak tested
• Gasket free
Design
The brazing material seals and holds the plates together at the
contact points ensuring optimal heat transfer efficiency and pressure
resistance. Using advanced design technologies and extensive
verification guarantees the highest performance and longest possible
service life.
Different pressure ratings are available for different needs.
Based on standard components and a modular concept, including
symmetric and asymmetric channels, each unit is custom-built to meet
.the specific requirements of each individual installation.
Examples of connections*

External threaded Internal threaded Soldering

1.1.30
Brazed Plate Heat Exchangers CB16 / CB400
1.1
Technical Data CB11/CBH11 Design pressure and temperature
CB11/CBH11 – PED approval pressure/temperature graph
Standard materials
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 7.4 + (2.14 * n)


A measure (inches) 0.29 + (0.08 * n)
Weight (kg)2 0.132 + (0.04 * n)
Weight (lb)2 0.29 + (0.09 * n)
1. n = number of plates
Designed for full vacuum.
2. Excluding connections
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
Standard data representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
Volume per channel, litres (gal) A (S1-S2): 0.02531 (0.02531)
please use the drawing generated by the Alfa Laval configurator or
A (S3-S4): 0.02431 (0.0064)
contact your local Alfa Laval representative.
Max. particle size, mm (inch) 1.2 (0.047)
Max. flowrate1 m3/h (gpm) 2.8 (12.3) Technical Data CB16/CBH16
Flow direction Parallel Standard materials
Min. number of plates 4
Max. number of plates 60 Cover plates Stainless steel
1. Water at 5 m/s (16.4 ft/s) (connection velocity) Connections Stainless steel
Plates Stainless steel
Brazing filler Copper
Dimensional drawing
Measurements in mm (inches)
Dimensions and weight 1

A measure (mm) 7 + (2.16 * n)


A measure (inches) 0.28 + (0.09 * n)
Weight (kg)2 0.14 + (0.04 * n)
Weight (lb)2 0.3 + (0.09 * n)
1. n = number of plates
2. Excluding connections

Standard data

A (S1-S2): 0.030
Volume per channel, litres (gal) (0.0078)
A (S3-S4):0.024
(0.0063)
H: 0.027 (0.0070)
Max. particle size, mm (inch) 1.1 (0.043)
Max. flowrate1 m3/h (gpm) 4.1 (18)
Flow direction Parallel
Min. number of plates 4
Max. number of plates 60
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)

1.1.31
CB16 / CB400 Brazed Plate Heat Exchangers
1.1
Design pressure and temperature
.
CB16/CBH16 – PED approval pressure/temperature graph

.
CBH16AQ – UL/CRN approval pressure/temperature graph

.
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.1.32
Brazed Plate Heat Exchangers CB16 / CB400
1.1
Technical Data CB30 Design pressure and temperature
Standard materials .
CB30 – PED approval pressure/temperature graph
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 7 + (2.31 * n)


A measure (inches) 0.51 + (0.09 * n)
Weight (kg)2 1.2 + (0.11 * n)
Weight (lb)2 2.65 + (0.24 * n)
1. n = number of plates
2. Excluding connections .
CB30 – UL approval pressure/temperature graph
Standard data

Volume per channel, litres (gal) 0.054 (0.014)


Max. particle size, mm (inch) 1 (0.039)
Max. flowrate1 m3/h (gpm) 14 (62)
Flow direction Parallel
Min. number of plates 4
Max. number of plates 150
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)
.
CBP30 – PED approval pressure/temperature graph

.
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.1.33
CB16 / CB400 Brazed Plate Heat Exchangers
1.1
Technical Data CB60/CBH60 Design pressure and temperature
Standard materials .
CB60/CBH60 – PED approval pressure/temperature graph
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

CB, CBH: 13 + (2.32 *


A measure (mm) n) 2
CBP: 17 + (2.32 * n)3
CB, CBH: 0.51 + (0.09
A measure (inches) * n) 3
CBP:0.67 + (0.09 * n) 3 .
CB, CBH:2.1 + (0.18 * CB60/CBH60 – UL approval pressure/temperature graph
Weight (kg)2 n)
CBP:2.26 + (0.18 * n)
CB, CBH: 4.63 + (0.4 *
Weight (lb)2 n)
CBP: 4.98 + (0.4 * n)
1. n = number of plates
2. Excluding reinforcements
3. Excluding reinforcements
4. Excluding connections

Standard data

Volume per channel, litres (gal) 0.103 (0.027) .


CBP60 – PED approval pressure/temperature graph
Max. particle size, mm (inch) 1 (0.039)
Max. flowrate1 m3/h (gpm) 14 (62)
Flow direction Parallel
Min. number of plates 4 .
Max. number of plates 150 Designed for full vacuum.

1. Water at 5 m/s (16.4 ft/s) (connection velocity) Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
Dimensional drawing
NOTE: Values above are to be used as an indication. For exact values,
Measurements in mm (inches)
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.1.34
Brazed Plate Heat Exchangers CB16 / CB400
1.1
Technical Data CB62/CBH62 Design pressure and temperature
CB62/CBH62 – PED approval pressure/temperature graph
Standard materials
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 13 + (1.98 * n)


A measure (inches) 0.51 + (0.08 * n)
Weight (kg)2 2.1 + (0.18 * n)
Weight (lb)2 4.63 + (0.4 * n)
1. n = number of plates
2. Excluding connections
.
CB62/CBH62 – UL approval pressure/temperature graph
Standard data

Volume per channel, litres (gal) AH (S1-S2): 0.104 (0.027)


AH (S3-S4): 0.084 (0.022)
H: 0.094 (0.024)
Max. particle size, mm (inch) 1 (0.039)
Max. flowrate1 m3/h (gpm) 8.8 (39)
Flow direction Parallel
Min. number of plates 4
Max. number of plates 150
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.
Technical Data CB65/CBH65

Standard materials
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 11.5 + (1.4 * n)


A measure (inches) 0.45 + (0.06 * n)
Weight (kg)2 2.1 + (0.14 * n)
Weight (lb)2 4.63 + (0.31 * n)
1. n = number of plates
2. Excluding connections

Standard data

Volume per channel, litres (gal) (S1-S2): 0.088 (0.023)


(S3-S4): 0.046 (0.012)
Max. particle size, mm (inch) 0.7 (0.028)
Max. flowrate1 m3/h (gpm) 8.8 (39)
Flow direction Parallel
Min. number of plates 10
Max. number of plates 150
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)
1.1.35
CB16 / CB400 Brazed Plate Heat Exchangers
1.1
Design pressure and temperature
CB65/CBH65 – PED approval pressure/temperature graph

Designed for full vacuum.


Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.
Technical Data CB110/CBH110
Standard materials

Cover plates Stainless steel


Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 15 + (2.56 * n)


A measure (inches) 0.59 + (0.1 * n)
Weight (kg)2 4.82 + (0.35 * n)
Weight (lb)2 10.63 + (0.77 * n)
1. n = number of plates
2. Excluding reinforcements

Standard data

Volume per channel, litres (gal) 0.21 (0.054)


Max. particle size, mm (inch) 1.2 (0.047)
Max. flowrate1 m3/h (gpm) 51 (224)
Flow direction Parallel
Min. number of plates 10
Max. number of plates 240
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)

1.1.36
Brazed Plate Heat Exchangers CB16 / CB400
1.1
Design pressure and temperature
.
CB110/CBH110 – PED approval pressure/temperature graph

.
CB110/CBH110– UL approval pressure/temperature graph

.
CBP110 – PED approval pressure/temperature graph

.
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.
Marine Approvals
CBM110 can be delivered with marine classification certificate (ABS,
BV, CCS, ClassNK, DNV, GL, LR, RINA, RMRS)

1.1.37
CB16 / CB400 Brazed Plate Heat Exchangers
1.1
Technical Data CB112/CBH112 Design pressure and temperature
Standard materials .
CB112/CBH112 – PED approval pressure/temperature graph
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 16 + (2.07 * n)


A measure (inches) 0.63 + (0.08 * n)
Weight (kg)2 4.82 + (0.35 * n)
Weight (lb)2 10.63 + (0.77 * n) .
1. n = number of plates CB112/CBH112 – UL approval pressure/temperature graph
2. Excluding reinforcements

Standard data

Volume per channel, litres (gal) H, L, M: 0.18 (0.046)


CB/CBH/CBP AH, AM
(S1-S2): 0.20 (0.052)
CB/CBH/CBPAH, AM
(S3-S4): 0.16 (0.041)
Max. particle size, mm (inch) 1 (0.039)
Max. flowrate1 m3/h (gpm) 51 (224) .
Flow direction Parallel CBP112 / CBXP112 – PED approval pressure/temperature graph
Min. number of plates 10
Max. number of plates 300
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)

.
CBXP112 – UL approval pressure/temperature graph

.
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.1.38
Brazed Plate Heat Exchangers CB16 / CB400
1.1
Technical Data CB200/CBH200 Design pressure and temperature
Standard materials .
CB200/CBH200 – PED approval pressure/temperature graph
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 11 + (2.7 * n)


A measure (inches) 0.43 + (0.11 * n)
Weight (kg)2 12 + (0.6 * n)
Weight (lb)2 26.46 + (1.32 * n)
1. n = number of plates
2. Excluding reinforcements
.
Designed for full vacuum.
Standard data Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
Volume per channel, litres (gal) 0.51 (0.132)
representative for more information.
Max. particle size, mm (inch) 1.8 (0.071)
Max. flowrate1 m3/h (gpm) 128 (563) NOTE: Values above are to be used as an indication. For exact values,
Flow direction Parallel please use the drawing generated by the Alfa Laval configurator or
Min. number of plates 10 contact your local Alfa Laval representative.
Max. number of plates 230 Marine Approvals
1. Water at 5 m/s (16.4 ft/s) (connection velocity) CBMH200 can be delivered with marine classification certificate (ABS,
BV, CCS, ClassNK, DNV, GL, LR, RINA, RMRS)

Dimensional drawing
Measurements in mm (inches)

1.1.39
CB16 / CB400 Brazed Plate Heat Exchangers
1.1
Technical Data CB300/CBH300 Design pressure and temperature
Standard materials .
CB300/CBH300 – PED approval pressure/temperature graph
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 11 + (2.62 * n)


A measure (inches) 0.43 + (0.1 * n)
Weight (kg)2 21 + (1.26 * n)
Weight (lb)2 46.3 + (2.78 * n)
1. n = number of plates
2. Excluding reinforcements .
CB300/CBH300 – UL approval pressure/temperature graph
Standard data

Volume per channel, litres (gal) (S1-S2): 0.69 (0.178)


(S3-S4): 0.58 (0.150)
Max. particle size, mm (inch) 1.8 (0.071)
Max. flowrate1 m3/h (gpm) 200 (880)
Flow direction Parallel
Min. number of plates 10
Max. number of plates 250
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches) .
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.1.40
Brazed Plate Heat Exchangers CB16 / CB400
1.1
Technical Data CB400 Design pressure and temperature
Standard materials .
CB400 – PED approval pressure/temperature graph
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 14 + (2.56 * n)


A measure (inches) 0.55 + (0.1 * n)
Weight (kg)2 24 + (1.35 * n)
Weight (lb)2 52.91 + (2.98 * n)
1. n = number of plates
2. Excluding reinforcements
.
Standard data CB400 – UL approval pressure/temperature graph

Volume per channel, litres (gal) 0.74 (0.19)


Max. particle size, mm (inch) 1.8 (0.071)
Max. flowrate1 m3/h (gpm) 200 (880)
Flow direction Parallel
Min. number of plates 10
Max. number of plates 270
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)

.
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.
Marine Approvals
CBM400 can be delivered with marine classification certificate (ABS,
BV, CCS, ClassNK, DNV, GL, LR, RINA, RMRS)
Technical Data CB410

Standard materials
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper

Dimensions and weight 1

A measure (mm) 14.2 + (2.17 * n)


A measure (inches) 0.56 + (0.09 * n)
Weight (kg)2 30 + (1.14 * n)
Weight (lb)2 66.14 + (2.51 * n)
1. n = number of plates
2. Excluding connections

Standard data

Volume per channel, litres (gal) 0.69 (0.1823)


Max. particle size, mm (inch) 1 (0.039)
Max. flowrate1 m3/h (gpm) 285 (1254.8)
Flow direction Parallel
Min. number of plates 10
Max. number of plates 300
1. Water at 5 m/s (16.4 ft/s) (connection velocity)
1.1.41
CB16 / CB400 Brazed Plate Heat Exchangers
1.1
Dimensional drawing Design pressure and temperature
Measurements in mm (inches) CB410 – PED approval pressure/temperature graph

Designed for full vacuum.


Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.1.42
Brazed Plate Heat Exchangers CB20
1.1
.

ky Alfa Laval CB20


Brazed plate heat exchanger

Alfa Laval CB brazed plate heat exchangers provide efficient heat


transfer with a small footprint.

.
Applications
• HVAC heating and cooling
• Refrigeration
• Oil cooling
• Industrial heating and cooling

.
Benefits
• Compact
• Easy to install
• Self-cleaning
• Low level of service and maintenance is required
• All units are pressure and leak tested
• Gasket free

.
Design
The brazing material seals and holds the plates together at thecontact
points ensuring optimal heat transfer efficiency andpressure resistance.
Using advanced design technologies andextensive verification
guarantees
. the highest performance andlongest possible service life
Based on standard components and a modular concept, eachunit
is custom-built to meet the specific requirements of eachindividual
installation.

.
Examples of connections

External thread Internal thread Soldering

Welding

1.1.43
CB20 Brazed Plate Heat Exchangers
1.1
Standard materials
Technical Data
Standard materials
Design pressure and temperature
CB20 – PED approval pressure/temperature graph
Standard materials
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler
Dimensions and weight Copper
Dimensions and weight
Dimensions and weight 1
A measure (mm) 8 + (1.5 * n)
A measure (inches) 0.31 + (0.06 * n)
Weight (kg)2 0.6 + (0.08 * n)
Weight (lb)2 1.32 + (0.18 * n)
1. 1. n = number of plates
2. 2. Standard
Excludingdata
connections

Standard data Designed for full vacuum.


Standard data Alfa Laval plate heat exchangers are available
Volume per channel, litres (gal) 0.028 (0.0072) with a wide range of pressure vessel approvals. Please
Max. particle size, mm (inch) 0.6 (0.024) contact your Alfa Laval representative for more information.
Max. flowrate1 m3/h (gpm) 8.8 (39) NOTE: Values above are to be used as an indication. For exact values,
Flow direction Parallel please use the drawing generated by the Alfa Laval configurator or
Min. number of plates 10 contact your local Alfa Laval representative.
Max. number of plates 110
1. 1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional drawing
Measurements in mm (inches)

94 (3.7)

46 (1.8) A

S4 S1

S4 S1
270 (10.6)

324 (12.8)

S3 S2

S3 S2

1.1.44
1.2 Fusion Bonded Heat Exchanger
The Brazed Heat Exchangers from Alfa Laval are the perfect heat exchangers for utilities
like heating-water or steam.

Application Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2.46

Product leaflets
AlfaNova 14, 27, 52, 76, 200 and 400 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2.47
Application Overview Fusion Bonded Heat Exchanger
.
1.2
Brazed and Fusion Bonded Heat Exchanger
AlfaNova
14 27 52 76 400
Main duties
Dairy
Milk Cooling
Milk/cream pasteurization
Cultured milk cooling
Whey pasteurization
Ice cream pasteurization
Brewery
Wort cooling
Beer cooling
Beer pasteurization
Beverages
Clarified juices, drinks, wine
Juice/drinks with pulp/fibres
Clarified fruit & sugar conc.
Clody fruit concentrate
Other food
Low viscous products
High viscous products
Sticky/chunky/particles
Vegetable oil
Pharma
Pre-heating in water purification
In-line heater WFI/PW
Point of use cooler WFI/PW
Heating of holding tank WFI/PW
Product heating/cooling
Utilities
CIP Heating • • • • •
Water heating/cooling • • • • •

1.2.46
Fusion Bonded Heat Exchanger AlfaNova 14, 27, 52, 76, 200 and 400

. 1.2

ky Alfa Laval AlfaNova 14, 27, 52, 76, 200 and 400
Fusion-bonded plate heat exchanger in 100% stainless steel

Alfa Laval AlfaNova fusion-bonded plate heat exchangers are made of


100% stainless steel. They are suitable for applications which place
high demand on cleanliness, applications where aggressive media
like ammonia are used or where copper and nickel contamination is
unaccepted.
AlfaNova provides efficient heat transfer with a small footprint, has an
extreme pressure fatigue resistance and covers high temperatures,
up to 550°C/1022°F.
Applications
Suitable for a wide range of applications, such as:
• HVAC heating and cooling
• Refrigeration
• Oil cooler
• Industrial heating and cooling
• Process heating and cooling
Benefits
• Compact
• Easytoinstall
• Self-cleaning
• Low level of service and maintenance is required
• All units are pressure and leak tested
• Gasket free
.• Copper free Examples of connections
Design .
Design The AlfaFusion filler material seals and holds the plates
together at the contact points ensuring optimal heat transfer efficiency
and pressure resistance. Using advanced design technologies and
extensive verification guarantees the highest performance and longest
possible service life.
Based on standard components and a modular concept, each unit
is custom-built to meet the specific requirements of each individual
installation.
External thread Internal thread Soldering

Welding

1.2.47
AlfaNova 14, 27, 52, 76, 200 and 400 Fusion Bonded Heat Exchanger

1.2 Technical Data AlfaNova 14 Design pressure and temperature


Standard materials AlfaNova 14 - PED approved pressure/temperature graph

Cover plates Stainless steel


Connections Stainless steel
Plates Stainless steel
AlfaFusion filler Stainless steel

Dimensions and weight 1

A measure (mm) 8 + (2.48 * n)


A measure (inches) 0.31 + (0.1 * n)
Weight (kg)2 0.4 + (0.07 * n)
Weight (lb)2 0.88 + (0.15 * n)
1. n = number of plates
2. Excluding connections AlfaNova 14 - UL approved pressure/temperature graph

Standard data

Volume per channel, litres (gal) 0.02 (0.0052)


Max. particle size, mm (inch) 1.2 (0.047)
Max. flowrate1 m3/h (gpm) 4.6 (20.2)
Flow directions Parallel
Min. number of plates 4
Max. number of plates 50
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional Drawing
mm (inches)
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.2.48
Fusion Bonded Heat Exchanger AlfaNova 14, 27, 52, 76, 200 and 400

Technical Data AlfaNova 27 Design pressure and temperature 1.2


Standard materials AlfaNova 27 - PED approved pressure/temperature graph

Cover plates Stainless steel


Connections Stainless steel
Plates Stainless steel
AlfaFusion filler Stainless steel

Dimensions and weight 1

A measure (mm) 11 + (2.42 * n)


HP: 13 + (2.42 * n)
XP: 15 + (2.42 * n)
A measure (inches) 0.43 + (0.1 * n)
Weight (kg)2 1 + (0.13 * n)
HP: 1.5 + (0.13 * n)
XP: 2 + (0.13 * n)
AlfaNova HP 27 - PED approved pressure/temperature graph
Weight (lb)2 2.2 + (0.29 * n)
HP: 3.31 + (0.29 * n)
XP: 4.41 + (0.29 * n)
1. n = number of plates
2. Excluding connections

Standard data

Volume per channel, litres (gal) 0.05 (0.013)


Max. particle size, mm (inch) 1.2 (0.047)
Max. flowrate1 m3/h (gpm) 14 (62)
Flow directions Parallel
Min. number of plates 6
Max. number of plates 100
AlfaNova XP27 - PED approved pressure/temperature graph
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional Drawing
mm (inches)

Designed for full vacuum.


Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.2.49
AlfaNova 14, 27, 52, 76, 200 and 400 Fusion Bonded Heat Exchanger

1.2 Technical Data AlfaNova 52 Design pressure and temperature


Standard materials AlfaNova 52 - PED approved pressure/temperature graph

Cover plates Stainless steel


Connections Stainless steel
Plates Stainless steel
AlfaFusion filler Stainless steel

Dimensions and weight 1

A measure (mm) 11 + (2.48 * n)


A measure (inches) 0.43 + (0.1 * n)
Weight (kg)2 1.9 + (0.22 * n)
Weight (lb)2 4.19 + (0.49 * n)
1. n = number of plates
2. Excluding connections AlfaNova HP 52- PED approved pressure/temperature graph

Standard data

Volume per channel, litres (gal) 0.095 (0.025)


Max. particle size, mm (inch) 1.2 (0.047)
Max. flowrate1 m3/h (gpm) 14 (62)
Flow directions Parallel
Min. number of plates 6
Max. number of plates 150
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional Drawing
mm (inches)
1) Min. temperature -10°C (14°F) with connection tube made of
carbon steel.

AlfaNova XP52 - PED approved pressure/temperature graph

Designed for full vacuum.


Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.2.50
Fusion Bonded Heat Exchanger AlfaNova 14, 27, 52, 76, 200 and 400

Technical Data AlfaNova 76 Design pressure and temperature 1.2


Standard materials AlfaNova 76 – PED approval pressure/temperature graph 1)

Cover plates Stainless steel


Connections Stainless steel
Plates Stainless steel
AlfaFusion filler Stainless steel

Dimensions and weight 1

A measure (mm) 11 + (2.85 * n)


A measure (inches) 0.43 + (0.11 * n)
Weight (kg)2 8 + (0.49 * n)
Weight (lb)2 17.64 + (1.08 * n)
1. n = number of plates
2. Excluding connections
1) Min. temperature -10°C (14°F) with connection tube made of
carbon steel.
Standard data 1)
AlfaNova HP 76 – PED approval pressure/temperature graph
Volume per channel, litres (gal) A) S1-S2: 0.25 (0.065)
(A) S3-S4: 0.18 (0.046)
(H, L): 0.25 (0.065)
(E): 0.18 (0.046)
Max. particle size, mm (inch) 1.2 (0.047)
Max. flowrate1 m3/h (gpm) 37 (163)
Flow directions Parallel
Min. number of plates 10
Max. number of plates 150
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional Drawing
mm (inches)
1) Min. temperature -10°C (14°F) with connection tube made of
carbon steel.

AlfaNova HP 76 – UL approval pressure/temperature graph 1)

Designed for full vacuum.


Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.
Marine approvals
AlfaNovaM HP 76 can be delivered with marine classification certificate
(ABS, BV, CCS, ClassNK, DNV, GL, LR, RINA, RMRS)

1.2.51
AlfaNova 14, 27, 52, 76, 200 and 400 Fusion Bonded Heat Exchanger

1.2 Technical Data AlfaNova 200 Design pressure and temperature


Standard materials AlfaNova 200 – PED approval pressure/temperature graph 1)

Cover plates Stainless steel


Connections Stainless steel
Plates Stainless steel
AlfaFusion filler Stainless steel

Dimensions and weight 1

A measure (mm) 9.3 + (2.85 * n)


A measure (inches) 0.37 + (0.11 * n)
Weight (kg)2 12 + (0.75 * n)
Weight (lb)2 26.46 + (1.65 * n)
1. n = number of plates
2. Excluding connections AlfaNova HP 200 – PED approval pressure/temperature graph 1)

Standard data

Volume per channel, litres (gal) 0.51 (0.13)


Max. particle size, mm (inch) 1 (0.04)
Max. flowrate1 m3/h (gpm) 128
Flow directions Parallel
Min. number of plates 10
Max. number of plates 230
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional Drawing
mm (inches)

Designed for full vacuum.


Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.2.52
Fusion Bonded Heat Exchanger AlfaNova 14, 27, 52, 76, 200 and 400

Technical Data AlfaNova 400 Design pressure and temperature 1.2


Standard materials AlfaNova 400 – PED approval pressure/temperature graph 1)

Cover plates Stainless steel


Connections Stainless steel
Plates Stainless steel
AlfaFusion filler Stainless steel

Dimensions and weight 1

A measure (mm) 14 + (2.65 * n)


A measure (inches) 0.55 + (0.1 * n)
Weight (kg)2 22 + (1.4 * n)
Weight (lb)2 48.5 + (3.09 * n)
1. n = number of plates
2. Excluding connections 1) Min temperature -45 °C (-49 °F) with connection tubes made of
carbon steel.
Standard data 1)
AlfaNova HP 400 – PED approval pressure/temperature graph
Volume per channel, litres (gal) 0.74 (0.19)
Max. particle size, mm (inch) 1.8 (0.07)
Max. flowrate1 m3/h (gpm) 200 (880)
Flow directions Parallel
Min. number of plates 10
Max. number of plates 270
1. Water at 5 m/s (16.4 ft/s) (connection velocity)

Dimensional Drawing
mm (inches)

1) Min. temperature -50°C (-58°F) with connection tube made of


carbon steel.
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide range
of pressure vessel approvals. Please contact your Alfa Laval
representative for more information.
NOTE: Values above are to be used as an indication. For exact values,
please use the drawing generated by the Alfa Laval configurator or
contact your local Alfa Laval representative.

1.2.53
This page is intentionally left blank
1.3 Gasketed plate-and-frame exchangers
Our Hygienic Heat Exchanger range is specially designed for pasteurizing and general
cooling/heating of beverages, dairy, brewery and viscous products, as well as utilities.

Application Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.57

Product leaflets
FrontLine™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.58
FrontLine™ - Widestream® Plate Heat Exchangers . . . . . . . . . . . . . . . . . . . 1.3.60
M-Serie/BaseLine/FrontLine Gemini Plate Heat Exchangers . . . . . . . . . . . . 1.3.62
T-Series Plate Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.64
Clip 3 Plate Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.66
BaseLine Plate Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.67
TS6-FMC Plate Heat Exchangers - Gasketed . . . . . . . . . . . . . . . . . . . . . . . 1.3.68
This page is intentionally left blank
Gasketed plate-and-frame exchangers Application Overview
.

Serie FrontLine BaseLine T-Series TS-Series


Plate Clip Front M TL T TL TS
1.3
3 6 6 10 10 3 6 10 15 10
Size/Type 3 6 8 10 15 6-M
M3 M6 M6M M10M P M3 T6 T10 T15 P
Main duties
Dairy
Milk Cooling • • • • • • • • • •
Milk/cream pasteurization • • • • • • • • •
Cultured milk cooling • • • • • •
Whey pasteurization • • • • • • • • •
Ice cream pasteurization • • • • •
Brewery
Wort cooling • • • • • • • • • •
Beer cooling • • • • • • • • • • •
Beer pasteurization • • • • •
Beverages
Clarified juices, drinks, wine • • • • • • • • • • •
Juice/drinks with pulp/fibres • • • • •
Clarified fruit & sugar conc. • • • • • • • • • • •
Clody fruit concentrate • • • • •
Other food
Low viscous products • • • • • • • • • •
High viscous products • • • • •
Sticky/chunky/particles
Vegetable oil • • • • • • • • • • •
Pharma
Pre-heating in water purification • • • • • • • • • • • • • •
In-line heater WFI/PW • • • • • • •
Point of use cooler WFI/PW • • • • • • •
Heating of holding tank WFI/PW • • • • • • • • • • • •
Product heating/cooling • • • • • • •
Utilities
CIP Heating • • • • • • • • • • • • • • •
Water heating/cooling • • • • • • • • • •

1.3.57
FrontLine™ Gasketed plate-and-frame exchangers

.
1.3

ky Alfa Laval FrontLine™


FrontLine™ Plate Heat Exchangers

Applications
• Pasteurisation
• General cooling/heating of dairy, brewery, beverage and food
products
• Heating/cooling in the pharmaceutical industry.
Working principle
A Plate Heat Exchanger consists of a pack of corrugated metal plates
with port holes for the passage of two fluids between which heat
transfer will take place.
The plate pack is assembled between a fixed frame plate and a
movable pressure plate and compressed by tightening bolts.
The plates are fitted with a gasket which seals the inter-plate channel
and directs the fluids into alternate channels. The number of plates is
determined by the flow rate, physical properties of the fluids and the
temperature program. Connections may be located in frame plate
and pressure plate.
Technical Data
Mechanical design pressure (g) / Temperature
FRM solid stainless steel 10 bar/150 °C
FRH* solid stainless steel 16 bar/150 °C
FRD solid stainless steel 21 bar/150 °C
RM cladded stainless steel 10 bar/150 °C
. Standard Materials
RH cladded stainless steel 16 bar/150 °C
RD cladded stainless steel 21 bar/150 °C Frame
Frame and pressure plate in solid or cladded stainless steel or surface
RMS surface coated 10 bar/150 °C
coated. All wetted parts in acid proof stainless steel. Other surfaces
RHS surface coated 16 bar/150 °C
in various grades of stainless steel. Movable nuts on tightening bolts
Complies with the European Pressure equipment Directive (PED). May in chromium plated brass.
carry the CE mark depending on the design conditions. Complies with
Alfa Laval Sound Engineering Standard (ALS). Plate Types
Front6, Front8, Front10 and Front15.
* Not applicable for Front 15
Other plates of the FrontLine™ series are the WideStream® and
Connections Gemini plates.
DIN, SMS, Tri-CLAMP, B.S./RJT and IDF/ISO male parts. Others on
Plates
request
Stainless steel AISI 316 orTitanium
Frame plate
Gaskets
Nitrile-FDA or EPDM-FDA.
The FrontLine™ plates are supplied with glue-free Clip-On gaskets,
which are easy to replace even with the plates still hanging in the
frame. The material of gaskets are selected for safe use in connection
with pharmaceutical and food products.

.
5100-0001

B
A
B
A
B
A
Pressure plate

Flow principle of FrontLine plate heat exchanger

1.3.58
Gasketed plate-and-frame exchangers FrontLine™

Dimensions
B 1.3
C

D
*E

TD 900-025
*F

J K
*1)

Front 6 Front 8 Front 10 Front 15


Measurements [mm]
B 370 492 670 803
C 129 220 324 400
D 859 1,095 1,324 1,524
E* 1,420 1,850 2,167 2,605
F* 400 500 500 700
J 520 670 850 970
K* min 1,000 1,440 1,400 1,588
K* max 2,500 3,860 5,000 6,400
* Variable dimension depending on various components.
1) Adjustable feet ± 40 mm

Connection [mm]
Diameter 51 76 76/101.6 101.6/150
Capacity [l/h]
Pasteurization 15,000 35,000 65,000 100,000
Heating/Cooling 15,000 35,000 65,000 150,000
Water 30,000 75,000 130,000 200,000
Plates
Plate pattern Chevron Chevron Chevron Chevron
Surface [m2] 0.18 0.38 0.62 0.91
Overall dim. [mm] 1,000 x 250 1,250 x 375 1,500 x 500 1,750 x 625
Port dim. [mm] 55 80 105 150
Thickness [mm] 0.5/0.6/0.7 0.5/0.6/0.7 0.5/0.6/0.7 0.5/0.6/0.7
Overall length varies depending on numbers of plates and connecting plates. Recommended free space around the unit is 1.5 meter at sides and
frame head end.

1.3.59
FrontLine™ - Widestream ® Gasketed plate-and-frame exchangers

.
1.3

ky Alfa Laval FrontLine™ - Widestream® Plate Heat Exchangers


For some, the Perfect Life is Natural Fruit Juices

Application
Pasteurisation and general cooling/heating of fruit juices and other
liquid food products which contain pulp or fibres.
Working principle
A plate heat exchanger consists of a pack of corrugated metal plates
with port holes for the passage of two fluids between which heat
transfer will take place.
The plate pack is assembled between a fixed frame plate and a
movable pressure plate and compressed by tightening bolts.
The plates are fitted with a gasket which seals the inter-plate channel
and directs the fluids into alternate channels. The number of plates
is determined by the flow rate, physical properties of the fluids and
the temperature program.
Connections may be located in frame plate and pressure plate and if
multi section PHE, also in connection plate.

The WideStream ® plate


The WideStream® plate has a special pattern with few contact points,
which allows products containing pulp & fibres to pass without
blocking the passages. This results in long operational times without
interruptions. The ports have a diameter enabling cleaning in place
(CIP) with the same flow used in the process itself. The minimum
of contact points between the WideStream® plates results in easy
.
cleaning with short cleaning cycles. The plate pattern is designed for Technical Data
efficient backflushing with free reverse flow. Mechanical design pressure (g) / Temperature
The WideStream® plate can be used together with other plates in FRM / RM – 7 bar/150 °C
the same heat exchanger frame. Complies with European Pressure Equipment Directive (PED), may
carry the CE mark depending on the design conditions.
Standard Materials
Plates Connections
Stainless steel AISI 316 - thickness 0.7 mm DIN, SMS, Tri-CLAMP, B.S./RJT and IDF/ISO male parts. Others on
Titanium - thickness 0.9 mm request

Gaskets Plates
High Temperature Nitrile-FDA. Clip-On design.
Front 6 Front 8
Frame WideStream® WideStream®
Frame and pressure plate in solid or cladded stainless steel. All wetted Plate pattern parallel parallel
parts in acid proof stainless steel. Other surfaces in various grades of Surface [m2] 0.18 0.38
stainless steel. Movable nuts on tightening bolts in chromium plated Overall dim. [mm] 1,000 x 250 1,250 x 375
brass. Port dim. [mm] 55 80
Thickness [mm] 0.7/0.9 0.7/0.9
Options
A. Thermometer pocket and nib with ventilation cock1)
B. Thermometer pocket1)
C. Connection for 51 mm pressure transmitter1)
D. Protection sheet
E. Bolt protections of stainless steel
F. 3-A finish
G. Connections in titanium or SMO (frame and pressure plate)
H. Extended legs
I. Extra standard wrench or pneumatic tightening tool
J. Test certificates and material certificate
K. Testing by authorized inspection companies
All options are not available on all models.
1) At through pass corners in connection plates.

1.3.60
Gasketed plate-and-frame exchangers FrontLine™ - Widestream ®

Dimensions
B 1.3
C
D
*E

TD 900-025
*F

J K
*1)

1) Adjustable feet ± 50 mm

Front 6 Front 8
WideStream ® WideStream ®
Measurements [mm]
B 370 500
C 129 220
D 859 1,095
E 1,420* 1,850*
F 400* 500*
J 520 670
K 1,000-2,500 1,400-3,800
Overall length varies depending on numbers of plates and connecting
plates. Recommended free space around the unit is 1.5 meter at
sides and frame head end.
Connection [mm]
Diameter 51 76
Max. capacity [l/h] - velocity max. 2.0 m/s
Orange juice - 10 brix
Pasteurization 7,000 25,000
Heating 2° to 20°C 20,000 32,500
Cooling 25° to 2°C 15,000 32,500

1.3.61
M-Serie/BaseLine/FrontLine Gemini Gasketed plate-and-frame exchangers

.
1.3

ky Alfa Laval M-Serie/BaseLine/FrontLine Gemini Plate Heat Exchangers


Cross-contamination safe double wall plates

Application
General cooling/heating for pharmaceutical, brewery and beverage
applications when a mix-proof design is required. To secure the
cross-contamination safe feature, water or water-like fluids are
recommended.

Working principles
Channels are formed between the plates and the corner ports are
arranged so that the two media flow through alternate channels.
A unique distribution area provides an efficient flow over the plate
surface. The heat is transferred through the plate between the
channels, and a complete counter-current flow is created for the
highest possible efficiency. The chevron corrugation of the plates
provides the passage between the plates, supports each plate against
the adjacent one and enhances turbulence. The high turbulence
resulting in efficient heat transfer and high surface shear forces to
minimise fouling and the build-up of biofilm. The plates are reversible
and have a parallel flow, which means that only one type of gasket
is needed.
Gemini plates
The Gemini plates consist of two plates with a small air gap in between.
The Gemini double wall plates will give a cross-contamination safe
design, as a crack in a plate will not result in mixing of the two media.
.Standard materials Technical specifications
Plates Plate material
Stainless steel AISI 316 Stainless steel AISI 316/316L. Surface finish Ra<0.3 µm.
Thickness for all Front Gemini plates 2 x 0.4 mm (in the cold formed area Ra<0,8 µm)

Gaskets Gasket material


High temperature Nitrile-FDA Clip-on design. EPDM (FDA compliance and USP Class VI), Nitrile (FDA compliance).

Frame Connections
Frame and pressure plate in solid or cladded stainless steel. All wetted Clamp, DIN, ISO, SMS, B.S., flanges, others on request.
parts in acid proof stainless steel. Other surfaces in various grades of Mechanical design pressure/temperature
stainless steel. Movable nuts on tightening bolts in chromium plated 10 barg/160 °C (depending on gasket material).
brass.
Pressure Vessel Codes
M-Series
PED and ASME
BaseLine
PED

Options
a. 3.1 according to EN 10204
b. Electro-polishing
c. Pressure test certificate
d. Protection sheet
e. Adjustable feet
All options are not available on all models

1.3.62
Gasketed plate-and-frame exchangers M-Serie/BaseLine/FrontLine Gemini

Dimensions
Measurements [mm] 1.3
B B
C C
D
E

D
*E
F

TD 900-018
TD 900-025_1

*F
H
G
J H

Dimensions M3-G M6-MG Front


[mm] M-Series BaseLine M-Series BaseLine Front6 Front8 Front10
B 180 180 320 304 370 500 670
C 60 60 140 140 129 220 324
D 357 357 640 640 859 1,095 1,324
E 480 545 920 920 1,420** 1,850** 2,167**
F 61.5 141* 140 181* 400** 500** 500**
G 176 290
H 550 250-510 515-1635 575-1925 1,000-2,500 1,400-3,800 1,400-5,000
J 520 670 850
Connection ø 32 25 50 50 55 80 105
Unpressed plate 0.50 + 0.25 0.50 + 0.25 2 x 0.4 2 x 0.4 2 x 0.4 2 x 0.4 2 x 0.4
thickness
* Measurement for fixed feet. Adjustable feet are also available.
** Adjustable feet ± 40 mm

1.3.63
T-Series Gasketed plate-and-frame exchangers

.
1.3

ky Alfa Laval T-Series Plate Heat Exchangers


For Your Utility Heating and Cooling
Applications
For your utility heating and cooling duties the industrial plate heat
exchangers of Alfa Laval can be used. These are detailed in the
following product sheets

.
Working principle
Channels are formed between the plates and the corner ports are
arranged so that the two media flow through alternate channels.
The heat is transferred through the plate between the channels, and
complete counter-current flow is created for highest possible efficiency.
The corrugation of the plates provides the passage between the
plates, supports each plate against the adjacent one and enhances
the turbulence, resulting in efficient heat transfer

. .

Standard Materials
Frame plate Mild steel, Epoxy painted
Nozzles Carbon steel Pipe: Alloy 316, Titanium
Plates Stainless steel: AISI 316 or Titanium
Gaskets Nitrile, EPDM, FKM, HeatSeal
TD 900-032

Dimensions
Flow principle of an T6, T10 and T15 plate heat exchanger Type H W h
( ), ( )
T6 [mm] [mm] [mm]
T6-FM 870 320 120
T6-FG 870 320 120
T6-FD 940 330 130
T6-ZM 827.5 298 102.5
T10
719 (28.3)

T10-FM 1,054 470 190


T10-FG 1,054 470 190
H

T10-FD 1,054 470 190


T10-ZM 957 420 128
T15
T15-FM 1,833 610 270
T15-FG 1,871 650 248.5
h

T15-FS 1,871 650 248.5


W 410 - 1930
The number of tightening bolts may vary depending on pressure rating.

1.3.64
Gasketed plate-and-frame exchangers T-Series

Pressure vessel codes, PED, ASME, pvcALS™ Mechanical design pressure (g) / temperature
Technical Data 1.3
Type Pressure vessel code Mechanical design pressure Temperature
T6
T6-FM pvcALS™ 1.2MPa 200°C
T6-FG pvcALS™ 1.8MPa 200°C
T6-FG PED 2.0MPa 200°C
T6-FG ASME 162 psig 482°F
T6-FD PED, pvcALS™ 3.1MPa 200°C
T6-FD ASME 345 psig 482°F
T6-ZM pvcALS™ 1.0MPa 110°C
T10
T10-FM PED, pvcALS™ 1.0MPa 180°C
T10-FG PED, pvcALS™ 1.5MPa 150°C
T10-FG ASME 151psig 482°F
T10-FD PED, pvcALS™ 2.5MPa 200°C
T10-FD ASME 304 psig 482°F
T10-ZM pvcALS™ 1.0MPa 110°C
T15
T15-FM PED, pvcALS™ 1.04MPa 200°C
T15-FG PED, pvcALS™ 1.6MPa 200°C
T15-FS PED, pvcALS™ 3.8MPa 200°C
*) Frame FG also approved for 1.2 MPa/200ºC to allow use in steam systems without safety valves.

1.3.65
Clip 3 Gasketed plate-and-frame exchangers

.
1.3

ky Alfa Laval Clip 3 Plate Heat Exchangers


First Choice in Hygienic Applications - at low Capacity

Application
Pasteurization and general cooling/heating of dairy and brewery
products, fruit juices and similar food products.

Working principle
The heat exchanger consists of a number of corrugated plates
clamped together in a frame and sealed at the edges by means of
gaskets.
The plates have ports at the corners and the gaskets are so arranged
that the two media flow through alternate passages between the
plates. The two media are separated by the plates and cannot be
mixed. Heat is transferred through the plates, from the hot medium
to the cold.
One unit can contain several heat exchangers, separated by
connection plates with interchangeable connections.

Standard Materials
Plates
Stainless steel AISI 316.

Gaskets
Nitrile-FDA,Clip-On design.

Frame
D LC
.Connection plates of mild steel, clad with stainless steel in glass E A
blasted finish. Nuts of chromium plated brass. All other parts of
stainless steel.

Technical Data
Plates
C
*H

Actual heating surface 0.058 m2


Connections
All connections 25 mm TD 900-043
*B

SMS or DIN male parts. LT


Other union standards on request. F
*1)
G
Mechanical design pressure (g) / Temperature
Frame RM - 10 bar/150°C Dimensions [mm]
Complies with European Pressure Equipment Directive (PED), may B = 213 F = 230
carry the CE mark depending on the design conditions.
C = 570 G = 250
Capacity D = 195 H = 818
Pasteurization 2,500 l/h E = 72 *1) = Adjustable feet +/- 15 mm

Heating/cooling 4,500 l/h


Water 8,000 l/h Overall length varies depending on numbers of plates and connecting
plates. Recommended free space around the unit is 1 meter at sides
and sufficient space at the frame head end to pull out the bolts.

1.3.66
Gasketed plate-and-frame exchangers BaseLine

.
1.3

ky Alfa Laval BaseLine Plate Heat Exchangers


The best Choice for Duties in Process and Utilities

Application
Cooling and heating of dairy, brewery, beverage and viscous products
and pasteurization in some applications.
Working principle
The plate heat exchanger consists of a pack of corrugated metal
plates with portholes for the passage of two fluids between which
heat transfer will take place.
The plate pack is assembled between a frame plate and a pressure
plate and compressed by tightening bolts.
The plates are fitted with a gasket which seals the channel and directs
the fluids into alternate channels. The number of plates are determined
by the flow rate, physical properties of the fluids, pressure drop and
temperature program. The plate corrugations promote fluid turbulence
and support the plates against differential pressure.

Gaskets
The plates are supplied with glue-free Clip-On gaskets, which are easy
to replace even with the plates still standing in the frame.

Plate Types
M3, M3G, M6, M6M, M6MG, M10B, M10M, TL10B and TL10P
Standard Materials
Plates Stainless steel AISI 304, AISI 316 or titanium
. Dimensions
Gaskets Nitrile-FDA, EPDM or EPDM-FDA.
B
Clip-On design. C
Frame Frame and pressure plate in solid stainless steel for Base
3, 6 and 10. Outer surfaces in various grades of stainless
steel. Movable nuts on tightening bolts in chromium
plated brass
D
E

Technical Data
Mechanical design pressure (g) / Temperature
10 bar/160°C
F

According to European pressure vessel directive (PED). TD 900-018

Complies with Alfa Laval Sound Engineering Standard (ALS). H


G
.
Dimensions [mm] BASE-3 BASE-6 BASE-10 BASE-11
B 180 304 446 473
C 60 140 223 218
D 357 640 719 1338
E 545 909 1053 2087
F 141 181 214 430
G 176 290 430 590
H 250-510 575-1,925 700-2,200 1,100-3,000
Connection [mm]
Diameter 25 51 76/101.6 76/101.6
Capacity [l/h]
Pasteurization - 11,000 15,000 45,000
Heating/Cooling 4,500 15,000 65,000 70,000
Water 8,800 35,000 130,000 130,000
1) Adjustable feet ± 30 mm on BASE-3, BASE-6 and BASE-10.
Flow principle of a plate heat exchanger 2) Adjustable feet ± 50 mm on BASE-11
The number of tightening bolts vary for different types. Recommended
free space around the unit is 1.0 meter at sides and frame head end.

1.3.67
TS6-FMC Gasketed plate-and-frame exchangers

.
1.3

ky Alfa Laval TS6-FMC Plate Heat Exchangers - Gasketed


In all stainless steel and designed for steam

Application
Heating of water or CIP (cleaning in place) solutions by means of
steam. General heating and cooling duties.
Working Principles
Channels are formed between the plates and the corner ports are
arranged so that the two media flow through alternate channels.
The heat is transferred through the plate between the channels,
and complete counter-current flow is created for highest possible
efficiency. The corrugation of the plates provides the passage between
the plates, supports each plate against the adjacent one and enhances
the turbulence, resulting in efficient heat transfer.

Technical Data
Mechanical design pressure (g) / Temperature
FMC 1.0 Mpa/175°C
Maximum heat transfer surface
13 m2
Particulars required for quotation
- Flow rates or heat load
- Temperature program
- Physical properties of liquids in question (if not water)
- Desired working pressure
-. Maximum permitted pressure drop Standard Materials
- Available steam pressure Frame plate
Typical capacities Frame and pressure plate in solid stainless steel AISI 316L
Liquid flow rate Nozzles
Up to 20 kg/s, depending on media, permitted pressure drop and Stainless steel AISI 316L
temperature program.
Plates
Water heating by steam Stainless steel AISI 316
200 - 1,800 kW
Gaskets
Frame type Nitrile, EPDM or HeatSeal F™
FMC
Connections
Plate types Flange 65 mm DIN 2501 PN10
TS6M Hygienic connections 76 mm. DIN, SMS, Tri-Clamp, B.S./RJT and
IDF/ISO male parts.

1.3.68
1.4 Shell & tube heat exchangers
Our Pharma-line and ViscoLine tubular heat exchangers are especially designed to meet
the whole requirement range in hygienic heat exchange from standard CIP duties, viscous
food processing to the highest hygienic demands in pharma applications.

Application Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.71

Product leaflets
Pharma-line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.72
Pharma-line S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.76
Alfa Laval Point of Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.79
ViscoLine™ Monotube Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.82
ViscoLine™ CIP unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.84
Alfa Laval ViscoLine™ Multitube Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.86
ViscoLine™ Annular Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.88
Multitube Heat Exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.90
This page is intentionally left blank
Shell & tube heat exchangers Application Overview
.

Shell &
Tube in Tube
Tube
Alfa Laval Point of Use Pharma-line 1.4
Main duties
Dairy
Milk Cooling
Milk/cream pasteurization
Cultured milk cooling
Whey pasteurization
Ice cream pasteurization
Brewery
Wort cooling
Beer cooling
Beer pasteurization
Beverages
Clarified juices, drinks, wine
Juice/drinks with pulp/fibres
Clarified fruit & sugar conc.
Clody fruit concentrate
Other food
Low viscous products
High viscous products
Sticky/chunky/particles
Vegetable oil
Pharma
Pre-heating in water purification •
In-line heater WFI/PW •
Point of use cooler WFI/PW • •
Heating of holding tank WFI/PW
CIP heater •
Product heating/cooling •
Utilities
CIP Heating
Water heating/cooling
Glycol cooling
CO2 heating/cooling
Refrigeration

1.4.71
Pharma-line Shell & tube heat exchangers

1.4
ky Alfa Laval Pharma-line
Double tube sheet shell and tube heat exchanger

Introduction
Pharma-line is a double tube sheet shell & tube heat exchanger
intended for heating and cooling of pharmaceutical water systems.
.
Application
The Pharma-line is a high-quality tubular heat exchanger designed to
operate in the pharmaceutical and biotech industries.
There are different executions available for different duties and
demands. All Pharma-line products are designed in-line with
regulations within this industry and is compliant with USP and cGMP
requirements
It is suitable for heating and cooling of products intended for the
pharmaceutical industry, mainly Water For Injection (WFI) and Purified
Water (PW) and some non-viscous pharmaceutical products.

.
Benefits
• Designed with focus on hygienic demands
• Leak detection by double tube sheet design
• Q-doc as standard

.
Technical data (standard)
Heat transfer area: 0.1 – 8.5m² (1.07 – 91.5 sqft)
Flow rate: Pharma-line S & Pharma-line P 0.3m³/h – approx. 42m³/h (79 gph – approx. 11100 gph)
Pharma-line P non-standard for higher flow rate available on request
Design temperature: Pharma-line S -10°C – 150°C (14°F – 302°F)
Pharma-line P -10°C – 200°C (14°F – 392°F)
Design pressure: Pharma-line S FV/10 barg (FV/145 psig)
Pharma-line P FV/15barg(FV/218psig)
Pressure equipment certification: PED, Chinese TSG
ASME VIII, only Pharma-line P (U-stamp as option)

Material data
Product wetted parts: stainless steel 316L
Other parts: Stainless steel 304
Gasket: PTFE (FDA compliance and USP class IV certified)
Surface finish product wetted parts: Mechanically polished Ra<0,8µm (Only Pharma-line P)
Mechanically polished with Ra<0.5µm
Electropolished with Ra<0,4µm

1.4.72
Shell & tube heat exchangers Pharma-line

Standard design and configuration Documentation


The Pharma-line double tube sheet shell & tube heat exchanger series All Pharma-line products are delivered along with Alfa Laval Q-doc
is designed with a focus on the hygienic standards, performance and including:
reliability to meet the Pharmaceutical industries demands. • Approved drawings 1.4
The standard configuration of Pharma-line is a U-tube design that • welding procedures (WPS), welder qualification (WPQ), weld log
suits most applications. A U-tube design means less footprint needed, • 3.1 Material certificates, pressure & product wetted steel parts
compare to a straight tubular heat exchanger. • Gaskets FDA compliance and USP class VI certificates
There are no dead areas in the Pharma-line and it is fully drainable on • Liquid penetrant test report
the product side. The tubes used in the heat exchanger are seamless • Dimensional control report
with smooth and controlled surface to minimize risk of contamination. • Pressure test certificate signed by Notified body
• Identification (technical sign)
All products wetted parts, the tube, chamber, product connections are
• Quality system certificate
made of 316L stainless steel. The gasket in contact with the product
• Declaration of compliance
is made of PTFE material which is FDA compliant and USP class VI
• CE documents
certified.
• Instruction Manual
Pharma-line is available in 2 different product ranges:

.
Pharma-line S
- standardized products with predefined options. Are available with
pressure equipment certification, PED or Chinese TSG. The unit
can either be non-insulated or insulated with mineral wood (ASTM
C795) with stainless steel 304 cladding.
- Pharma-line S is equipped with movable legs to facilitate installation,
the product can be installed either horizontally or vertically.
Pharma-line P
- available with standard selection with several options to select
among and as a complete customized design available upon
request.
- Options Pharma-line P
• Insulation mineral wool (ASTM C795) with stainless steel 304
cladding
• Removable tube bundle
• Passivation
• 1 pass, 2-pass or 4-pass designs
• Connections standard and sizes
1. Product side: Clamp: ASME BPE, DIN32676, DIN11864,
ISO2852
2. Utility side: Flanges: ANSI B16.5 (150lbs, 300 lbs),
DIN2635/EN1092-1

• Pressure equipment certification, PED, ASME, TSG

1.4.73
Pharma-line Shell & tube heat exchangers

Dimensional drawing, Pharma-line S


Measures are approximate
Nozzle size Nozzle size
1.4 Type OD A B C
Tube flanges
Pharma-line S 1 mm mm mm mm mm mm
Pharma-line S 1-0.1 73 1” DN50 1150 225 350
Pharma-line S 1-0.3 89 1” DN50 1150 225 350
Pharma-line S 1-0.4 102 1” DN50 1150 225 350
Pharma-line S 1-0.6 114 1 1/2” DN50 1150 230 350
Pharma-line S 1-0.7 140 2” DN80 1150 260 410
Pharma-line S 1-0.8 114 1 1½” DN50 1150 256 347
Pharma-line S 1-1.1 140 2” DN80 1150 260 410
Pharma-line S 1-1.2 168 2” DN80 1150 260 410
Pharma-line S 1-1.9 168 2” DN80 1155 291 409
Pharma-line S 1-2,1 219 2” DN125 1165 310 521
Pharma-line S 1-2,5 219 3” DN150 1165 312 521
Pharma-line S 2
Pharma-line S 2-0.3 73 1” DN50 2150 225 350
Pharma-line S 2-0.6 89 1” DN50 2150 225 350
Pharma-line S 2-1.0 102 1” DN50 2150 225 350
Pharma-line S 2-1.3 114 1 1/2” DN50 2150 230 350
Pharma-line S 2-1.4 140 2” DN80 2150 260 410
Pharma-line S 2-1.7 114 1 ½” DN50 2150 256 347
Pharma-line S 2-2.4 140 2” DN80 2150 260 410
Pharma-line S 2-2.6 168 2” DN80 2150 260 410
Pharma-line S 2-4,1 168 2” DN80 2155 291 409
Pharma-line S 2-4,8 219 2” DN125 2166 310 521
Pharma-line S 2-5,5 219 3” DN150 2165 312 521
Pharma-line S 3
Pharma-line S 3-0.4 73 1” DN50 3150 225 350
Pharma-line S 3-1.0 89 1” DN50 3159 225 350
Pharma-line S 3-1.6 102 1” DN50 3150 225 350
Pharma-line S 3-2.0 114 1 1/2” DN50 3150 230 350
Pharma-line S 3-2.2 140 2” DN80 3150 260 410
Pharma-line S 3-2.7 114 1½” DN50 3150 256 347
Pharma-line S 3-3.7 140 2” DN80 3150 260 410
Pharma-line S 3-4.0 168 2” DN80 3200 260 410
Pharma-line S 3-6,4 168 2” DN80 3155 291 409
Pharma-line S 3-7,4 219 2” DN125 3165 310 521
Pharma-line S 3-8,5 219 3” DN150 3165 312 521

T1
M1
T2
C

5300-0010

M2
B
A

Item Service Facing


T1 Tube inlet Tri-clamp
T2 Tube outlet Tri-clamp
M1 Shell inlet Weld neck flange
M2 Shell outlet Weld neck flange

1.4.74
Shell & tube heat exchangers Pharma-line

Dimensional drawing Pharma-line P


Standard units, measurements are approximate
Type OD A B C
Pharma-line P 1 mm mm mm mm 1.4
Pharma-line P 1-0.1 76 1200 180 860
Pharma-line P 1-0.3 89 1200 190 860
Pharma-line P 1-0.4 102 1200 190 860
Pharma-line P 1-0.6 114 1200 200 860
Pharma-line P 1-0.7 140 1200 210 860
Pharma-line P 1-0.8 114 1200 200 860
Pharma-line P 1-1.1 140 1200 210 860
Pharma-line P 1-1.2 168 1200 220 860
Pharma-line S 1-1.9 168 1200 291 860
Pharma-line S 1-2,1 219 1200 310 860
Pharma-line P 1-2.5 219 1200 253 860
Pharma-line P 2
Pharma-line P 2-0.3 76 2200 180 1860
Pharma-line P 2-0.6 89 2200 190 1860
Pharma-line P 2-1.0 102 2200 190 1860
Pharma-line P 2-1.3 114 2200 200 1860
Pharma-line P 2-1.4 140 2200 210 1860
Pharma-line P 2-1.7 114 2200 200 1860
Pharma-line P 2-2.4 140 2200 210 1860
Pharma-line P 2-2.6 168 2200 220 1860
Pharma-line S 2-4,1 168 2155 291 1860
Pharma-line S 2-4,8 219 2164 310 1860
Pharma-line P 2-5.5 219 2200 253 1860
Pharma-line P 3
Pharma-line P 3-0.4 73 3200 180 2860
Pharma-line P 3-1.0 89 3200 190 2860
Pharma-line P 3-1.6 102 3200 190 2860
Pharma-line P 3-2.0 114 3200 200 2860
Pharma-line P 3-2.2 140 3200 210 2860
Pharma-line P 3-2.7 114 3200 200 2860
Pharma-line P 3-3.7 140 3200 210 2860
Pharma-line P 3-4.0 168 3200 220 2860
Pharma-line S 3-6,4 168 3155 291 2860
Pharma-line S 3-7,4 219 3164 310 2860
Pharma-line P 3-8.5 219 3200 253 2860

Item Service Facing


T1 Tube inlet Tri-clamp
T2 Tube outlet Tri-clamp
M1 Shell inlet Weld neck flange
M2 Shell outlet Weld neck flange

1.4.75
Pharma-line S Shell & tube heat exchangers

1.4
ky Alfa Laval Pharma-line S
Double tube sheet shell and tube heat exchanger

Applications
The Pharma-line S is used in pharmaceutical water systems; Water
For Injection (WFI) and Purified Water (PW) and for heating or cooling
of pharmaceutical products.

.
Working principles
The Pharma-line S is designed in line with ASME BPE, USP and
cGMP requirements. In the Pharma-line the risk of mixing between the
product and the heating or cooling (service) medium is eliminated as
a result of the double tube sheet design. The product flows in the
tubes while the service medium flows in a cross flow around the tubes,
inside the shell. The service medium is sealed in the shell by the first
tube sheet and the second tube sheet seals the product. In the event
of a leak, the leakage of either fluid is easily visually detected.

5300-0011

.
Tube sheets

Fig. 1. Double tube sheets prevent cross contamination between the


product and the heating/cooling medium.

Standard range
The Alfa Laval Pharma-line is a high quality double tube sheet shell
& tube heat exchanger designed for use in the pharmaceutical and
biotechnology industries. It is available in a number of standard sizes
and meets the stringent hygiene standard imposed both by control
authorities and industry.
The Pharma-line S is available in 21 models, all with U-tube designs
that suit most applications.
Within the product range Pharma-line there are 2 series available:
Pharma-line S - Standard design
Pharma-line P - Standard design and a custom design available on
request

.
Installation
The movable legs facilitate flexible positioning. The Pharma-line S can
be installed either horizontally or vertically, depending on the specific
demands. For an easy installation, lifting lugs are fastened on the units.

1.4.76
Shell & tube heat exchangers Pharma-line S

Technical data
Heat transfer area 0.1 m2 – 8.5 m2
Design temperature -10°C -150°C
Design pressure FV/10 barg 1.4
Pressure vessel codes PED. Chinese TSG and manufacturing license available
Welding according to SS-EN-IOS 15614-1, EN 287-1, EN-1418 ASME IX
Surface finish product wetted parts Mechanically polished with Ra<0.5 µm. and Electropolish with Ra<0.4 µm

Physical data
Product wetted steel parts 316L (seamless tubes)
Gaskets PTFE (FDA compliance & USP class VI certified)
Connections NAC plate to connect to tri clamp on tube side and flanges on service side

Options Insulation Mineral wool (ASTM C795) with stainless steel 304 cladding

Hygienic design
The Pharma-line S has no dead legs and is fully drainable on the
product side. All product wetted parts in Pharma-line S are either
mechanically or electropolished. The Pharma-line S tubes are
seamless and U-tubes are bent to a larger radius than required in
ASME BPE. The Pharma-line S is easy to clean and can be steam
sterilized. Gaskets come with a USP class VI certificate and are in
compliance with FDA.

.
Documentation

The Pharma-line is delivered along with Alfa Laval Q-Doc including:


• Approved drawings and calculations signed by Notified body
• List of welders, welding procedure and welder qualification
• 3.1 Material certificates, pressure and product wetted steel parts
• FDA compliance and USP class VI certificates, gaskets
• Liquid penetrant test report and procedure
• Surface roughness certificate
• Dimension control report
• Pressure test certificate, signed by Notified body
• Identification (technical sign)
• Quality system certificate
• CE-Documents

1.4.77
Pharma-line S Shell & tube heat exchangers

Standard units, measurements (approximate) [mm]

Shell OD Nozzles size Nozzle size


1.4 Type (mm) Tube flange A B C
Pharma-line S 1 [mm]
Pharma-line S 1 - 0.1 76 1" DN50 1150 225 195
Pharma-line S 1 - 0.3 89 1" DN50 1150 225 195
Pharma-line S 1 - 0.4 101 1" DN50 1150 225 195
Pharma-line S 1 - 0.6 114 1 ½" DN50 1150 230 195
Pharma-line S 1 - 0.7 141 2" DN80 1150 260 245
Pharma-line S 1-0.8 114 1 ½" DN50 1150 256 347
Pharma-line S 1 - 1.1 141 2" DN80 1150 260 245
Pharma-line S 1 - 1.2 168 2" DN80 1150 260 245
Pharma-line S 1-1.9 168 2" DN80 1155 291 409
Pharma-line S 1-2,1 219 2" DN125 1165 310 521
Pharma-line S 1-2,5 219 2" DN150 1165 312 521
Pharma-line S 2 [mm]
Pharma-line S 2 - 0.3 76 1" DN50 2150 225 195
Pharma-line S 2 - 0.6 89 1" DN50 2150 225 195
Pharma-line S 2 - 1.0 101 1" DN50 2150 225 195
Pharma-line S 2 - 1.3 114 1 1½" DN50 2150 230 195
Pharma-line S 2 - 1.4 141 2" DN80 2150 260 245
Pharma-line S 2-1.7 114 1 ½” DN50 2150 256 347
Pharma-line S 2 - 2.4 141 2" DN80 2150 260 245
Pharma-line S 2 - 2.6 168 2" DN80 2150 260 245
Pharma-line S 2-4,1 168 2” DN80 2155 291 409
Pharma-line S 2-4,8 219 2” DN125 2166 310 521
Pharma-line S 2-5,5 219 3” DN150 2165 312 521
Pharma-line S 3 [mm]
Pharma-line S 3 - 0.4 76 1" DN50 3150 225 195
Pharma-line S 3 - 1.0 89 1" DN50 3150 225 195
Pharma-line S 3 - 1.6 101 1" DN50 3150 225 195
Pharma-line S 3 - 2.0 114 1 ½" DN50 3150 230 195
Pharma-line S 3 - 2.2 141 2" DN80 3150 260 245
Pharma-line S 3-2.7 114 1 ½” DN50 3150 256 347
Pharma-line S 3 - 3.7 141 2" DN80 3150 260 245
Pharma-line S 3 - 4.0 168 2" DN80 3150 260 245
Pharma-line S 3-6,4 168 2” DN80 3155 291 409
Pharma-line S 3-7,4 219 2” DN125 3165 310 521
Pharma-line S 3-8,5 219 3” DN150 3165 310 521

T1
M1
T2
C

5300-0010

M2
B
A

.
Nozzle schedule

Item Service Facing Standard and dimension


T1 Tube inlet NAC plate for Tri-clamp Suitable for ASME BPE
T2 Tube outlet NAC plate for Tri-clamp Suitable for ASME BPE
M1 Shell inlet Weld neck flange DIN2635/EN1092-1
M2 Shell outlet Weld neck flange DIN2635/EN1092-1

1.4.78
Shell & tube heat exchangers Alfa Laval

ky Alfa Laval Point of Use 1.4

Alfa Laval PoU cooler module for pharmaceutical water system

Introduction
Alfa Laval PoU is a compact point of use cooler module for cooling of
pharmaceutical water. The heat exchanger has a unique design with
no internal welds to avoid any cross contamination between product
and utility. Alfa Laval PoU meets the stringent hygienic standard
imposed by both authorities and industry.

.
Alfa Laval PoU is supplied as a complete module including heat
exchanger, pitot tube, valves and cabinet. Alfa Laval PoU is designed
to remain sanitized - when not in use (standby mode)

Application
For quick and easy installation, Alfa Laval PoU is supplied as a
complete module with a pitot tube arrangement for installation in
the distribution loop. Installed Alfa Laval PoU can be regarded as a
sub-loop of the main distribution loop.

.
Alfa Laval PoU is suitable for cooling Water For Injection (WFI) and
Purified Water (PW).

.
If needed, Alfa Laval PoU can be steam sterilized.

Benefits
.• Designed and manufactured in line with ASME BPE
• Easy to install, Plug-and-Play module
• Low pressure drop in distribution loop
• No internal welds
• Quick response and minimized waste of WFI/PW
• Comprehensive documentation as a standard

Technical data (standard)


Heat transfer area: 0.3 – 0,7m² (3.2–7.5 US sqft)
Max. Flow rate: Cold sampling 1000 l/h (264 US gph)
Hot sampling 1800 l/h (475 US gph)
Design temperature: 150°C (302°F)
Design pressure: Pneumatic user point valve (PTFE diaphragm): FV/6 barg (FV/87 psig)
Pneumatic user point valve (EPDM diaphragm): FV/10 barg (FV/145 psig)
Manual user point valve (PTFE/EPDM diaphragm): FV/10 barg (FV/145 psig)
Weight of module: 22-46 kg

Material data
Product wetted parts: stainless steel 316L, seamless tubes
PoU module: Insulation: Armaflex
Cabinet: Stainless steel 304L
Surface finish product wetted parts: Electropolished with Ra<0.5µm

1.4.79
Alfa Laval Shell & tube heat exchangers

Standard design and configuration Working principles


Alfa Laval PoU is a compact tube-in-tube design. It is designed with Stand-by mode
focus on high hygienic standards in line with ASME BPE. The design With continuous circulation in the module/subloop it is possible to
1.4 features full drainability, no internal welds, no dead legs, no crevices avoid draining and thereby keeping the main distribution loop closed
and all product wetted parts are electropolished. towards the environment. The module/subloop is kept sanitized.
Alfa Laval PoU pitot tube arrangement ensures that throttling valves are The design of pitot tube arrangement [1] ensures that the product
not needed for the sub-loop, significantly reducing the total pressure is kept circulating in the point of use cooler even in stand-by mode.
drop in the distribution loop. With continuous circulation in the heat exchanger it is possible to
Alfa Laval PoU is available in three different sizes; PoU200, PoU300, avoid draining and thereby keeping the water loop closed towards the
and PoU400. environment. The sub loop is kept sanitized. The design of pitot tube
These are supplied as compete modules with a manual or pneumatic arrangement [1] ensures that the WFI/PW is kept circulating in the
user point valve. Alfa Laval PoU is supplied as a complete module module in stand-by mode. Figure 1
including heat exchanger, pitot tube, valves and cabinet. .
Within the standard configurations there are many different options to Cooling mode
select among, as example pneumatic or manual point of use valve, In cooling mode the recirculation is stopped, cooling media is turned on
and different sizes of pitot tubes with ASME BPE, ISO2037, ISO1127 and when the user point is opened WFI/PW is available within seconds.
standards. The pitot tubes have option with isolation valves and return For cooling of water for injection in manual module (the module with
bend. manual point of use valve the following steps should be done:
. - Turn the air switch on [2] from stand-by mode to cooling mode.
Documentation The cooling water valve [4] will automatically will be open and the
Alfa Laval PoU is delivered along with Q-doc, a standard recirculation valve close [3].
documentation including drawings, material certificates, instruction - Open the point of use valve [5] carefully and cold water for injection
manual, pressure test report, WPS, WPQ, weldlog etc.. is available within seconds. Figure 2

1.4.80
Shell & tube heat exchangers Alfa Laval

1.4
1 1

3
Open Close
2
Off On

4
Open
Close

Figure 1. Stand-by mode Figure 2. Cooling mode

1.4.81
ViscoLine™ Monotube Unit Shell & tube heat exchangers

1.4
ky Alfa Laval ViscoLine™ Monotube Unit
The tubular heat exchanger series from Alfa Laval

Intro
The ViscoLine Monotube hygienic tube-in-tube heat exchanger is
ideally suited for the heating, cooling and pasteurization of products
with low and average viscosity, and products that contain fibers and
big particulates.

.
Applications
ViscoLine Monotube heat exchangers are used for grape mash, diced
tomato, diced vegetable and diced fruits and also sauces and soups
that contain big particles.

.
Benefits
• Maintenance free
• High working pressures
• High working temperatures
• Easy to expand
• Easy to inspect and clean

.
Design
The ViscoLine Monotube heat exchanger consists of a single tube
mounted inside an outer shell tube. The product medium flows
.inside this tube, and the service medium around it. It is a fully welded
construction with a bellow on shell tube to absorb thermal expansion.
ViscoLine Monotube modules are normally connected in series and
mounted on support frame or full frame.
.

Working principles
The product medium inside the tube flows in counter current to the
service medium. The product tube is corrugated or it can be smooth.
The shell tube is always corrugated.

.
Options
• Protection sheets
• Thermal insulation
• Video inspection
• X-Rays measurements & certificates
• NDT testing & certificates
• Frame angled for self-drainage

1.4.82
Shell & tube heat exchangers ViscoLine™ Monotube Unit

Designation Material 1
VLO 51/76-6-316L/304-C : Product side
Stainless steel AISI 316L
VLO ViscoLine Monotube (tubes)
51 Outer diameter of product tube Service side Stainless steel AISI 304 or AISI 316L 1.4
76 Outer diameter of service shell (shell) (optional)
6 Module length (m) Stainless steel AISI 304 (units can be angled
316L Material product side (tube) Frame
304 Material service side (shell)
for self-draining on request)
C Corrugated inner tube
NBR, EPDM, FKM, PTFE and others on
Gaskets
S Smooth inner tube request.

1Other materials are available on request such as SAF 2205, SAF


All types are also available in 3 meter length
2507, etc for the inner tubes, tube sheet and bends.
.
Technical data .
The Viscoline Monotube Unit is designed for a pressure of 15 bar (217 The ViscoLines can be manufactured with different surface finish and
PSI) on the product side (tube) and 10 bar (145 PSI) on the service can be electropolished if required
side (shell), depending on the connections. The unit can, however,
accommodate higher pressure ratings, depending on component
thickness as connection type.

.
Connections available for both product side (tube) and service side
(shell) include: SMS, DIN 11851, DIN 11864, Tri-Clamps, Flange and
other on request.

.
The ViscoLine Monotube unit complies with the European Pressure
Equipment Directive (PED 2014/68/EU), and is entitled to bear the
CE mark. Where the CE mark is not required, Viscoline would be
manufactured according to Sound Engineering Practice (SEP) and
Good Manufacturing Practise (GMP, EC 2023/2006). Other design
codes are available as well such as ASME VIII Div.1 and others
would be on request like SELO’s China Manufacturer License (SELO
approval).
It is designed to operate at a temperature of 190°C (374 °F) although
higher temperatures are also met.
All units can be provided with an expansion joint to absorb thermal
expansion stress.

1.4.83
ViscoLine™ CIP unit Shell & tube heat exchangers

1.4
ky ViscoLine™ CIP unit
Tubular heat exchanger for low viscosity food and cleaning-in-place

Intro
The Viscoline™ CIP unit is the Alfa Laval tubular heat exchanger
specially designed for the heating of water or CIP (NaOH, HNO3,…)
solutions using steam or hot water as heating media.

.
Applications
• Heating of water or CIP solutions by means of steam
• Processing low viscosity products, containing fibers and small
particulates
• General heating and cooling applications

.
Benefits
• Low maintenance and operating costs
• High working pressures
• High working temperatures
• Easy to be inspected and cleaned
• Easy to be assembled/disassembled.

.
Design
The three standard sizes of the ViscoLine CIP units are stocked items.
Counter flanges are included in the scope of supply.
. All tubes are connected in parallel and in counter-current flow to the
. service medium. The product tubes are corrugated. The service media
shell is smooth.
VLC model Item number
VLC20x16/104-2 9680168330
VLC31x16/129-2 9680168331
VLC37x16/154-3 9680168334

Note that vertical installation is recommended for steam to water


heating in order to drain the condensate.

.
The ViscoLine™ CIP unit complies with the European Pressure
Equipment Directive (PED 2014/68/EU), and is entitled to bear the
CE mark.

.
Options
• Thermal insulation.

.
Working principle
The heat exchanger is formed by a tube bundle (welded at both ends
onto flat tube plates) inside a shell. Product medium flows inside the
tubes of the bundle and the service medium between and around
these tubes. This makes it compact and easy to install.

1.4.84
Shell & tube heat exchangers ViscoLine™ CIP unit

Dimensional drawing

A
1.4
B

5600-0001

VLC Dimensions (mm) Connections Volume in litre


Model A B C Shell Side Tube Side Shell Side Tube Side
VLC 20x16/104-2 2.234 1.776 115 OD 76.1 SMS 63.5 7.33 6.03
VLC 31x16/129-2 2.239 1.76 138 OD 101.6 SMS 76.1 8.14 8.14
VLC 37x16/154-3 3.265 2.76 150 OD 101.6 SMS101.6 19.77 16.85

Configuration Technical data

VLC 20x16/104-2.0-316L/304-C Max. operating pressure


VLC ViscoLine CIP Tube side 15 bar (217 PSI)
20 Number of product tubes Shell side 10 bar (145 PSI)
16 Outer diameter of product tubes (mm) Complies with the European Pressure Equipment Directive (PED).
104 Outer diameter of service shell (mm) Design temperature -20/190°C (-4/374°F)
2.0 Module length (mm)
316L Material tube side Connections
304 Material shell side Product side (tubes) ISO 2037 SMS
C Corrugated product tubes Service side (shell) Flange EN 1092-1

Materials
Product side (tubes) 1.4404 (316L)
Service side (shell) 1.4301 (304)

1.4.85
Alfa Laval ViscoLine™ Multitube Unit Shell & tube heat exchangers

1.4
ky Alfa Laval ViscoLine™ Multitube Unit
The tubular heat exchanger series from Alfa Laval

Intro
The ViscoLine Multitube hygienic heat exchanger is ideally suited for the
heating, cooling and pasteurization of products with low and medium
viscosity, and products that contain fibres and small particulates.

.
Applications
ViscoLine Multitube heat exchangers are used in conjunction with
a wide range of products, including milk, cream water, yellow fats,
whole egg, egg white, egg yolk, fruit puree, baby food, many kind of
fruit juices containing pulp and fibers, fruit concentrates, beer mash,
tomato juice and nectar, protein solutions, yeast and soft drinks.

.
Benefits
• Low maintenance costs
• High working pressure
• High working temperatures
• Easy to expand
• Easy to clean
.
Design
The ViscoLine Multitube unit consists of a bundle of tubes mounted
.
inside an outer shell, and welded onto tube plates at both ends. The Options
product medium flows inside these tubes, and the service medium • Protection sheets
between and around them. • Thermal insulation
• Video inspection
. • X-Rays measurements & certificates
All the product tubes are connected in parallel and in such a way • NDT testing & certificates
that the flow is counter-current in relation to the service medium. • Frame angled for self-drainage
If required, these product tubes can feature a corrugated surface.
Otherwise the inner tubes would be smooth and designed particularly .
for fouling or viscous fluids. The service media shell could be either Configuration
smooth or corrugated.
VLM19x25/154-6.0-316L/304-C
.
VLM ViscoLine Multitube
The eccentric reducers can be welded, clamped or flanged.
19 Number of product tubes
. 25 Outer diameter of product tubes
ViscoLine Multitube modules are normally connected in series and 154 Outer diameter of service shell
grouped on a common frame. The installation is maintenance free, 6.01 Module length (m)
thus eliminating any need for spare parts. AISI316L Material product side (tube)
AISI304 Material service side (shell)
C Corrugated inner tubes
S Smooth inner tubes
1Also available in 3 meter length

Working principle
ViscoLine Multitube is a highly tubular heat exchanger that incorporates
corrugated tubes or other advanced profiles designed to increase
turbulence in the flow of the fluid. This substantially increases the
overall heat transfer coefficient.

1.4.86
Shell & tube heat exchangers Alfa Laval ViscoLine™ Multitube Unit

Technical data
The Viscoline Multitube Unit is designed for a pressure of 15 bar (217
PSI) on the product side (tubes) and 10 bar (145 PSI) on the service
side (shell), depending on the connections. The unit can, however, 1.4
accommodate higher pressure ratings, depending on component
thickness as connection type.
.
Connections for both product side (tubes) and service side (shell)
include: SMS, DIN 11851, DIN 11864, Tri-Clamps, Flange and others.

.
The ViscoLine Multitube unit complies with the European Pressure
Equipment Directive (PED 2014/68/EU), and is entitled to bear the
CE mark. Where the CE mark is not required, Viscoline would be
manufactured according to Sound Engineering Practice (SEP) and
Good Manufacturing Practise (GMP, EC 2023/2006). Other design
codes are available as well such as ASME VIII Div.1 and others
would beon request like SELO’s China Manufacturer License (SELO
approval).
ViscoLine heat exchangers are available with different surface finish
. and can be electropolished if required.
It is designed to operate at a temperature of 190°C (374°F) although
higher temperatures are also met.

.
All units can be provided with an expansion joint to absorb thermal
expansion stress.

Material1
Product side (tubes) Stainless steel AISI 316L
Service side (shell) Stainless steel AISI 304 or AISI 316L
(optional)
Frame Stainless steel AISI 304
Gaskets NBR, EPDM, FKM, PTFE and others
on request
1Other material available on request such as SAF 2205, SAF 2507,
SMO 254 for inner tubes, tube sheet and bends

1.4.87
ViscoLine™ Annular Unit Shell & tube heat exchangers

1.4
ky Alfa Laval ViscoLine™ Annular Unit
The tubular heat exchanger series from Alfa Laval

Intro
The ViscoLine annular heat exchanger is ideal for the heating, cooling
and pasteurization of non-Newtonian products with high viscosity, and
products that contain particulates.

Applications
The heat exchanger are most commonly used in conjunction with
low acid products with average to high viscosity, such as tomato
concentrate, banana paste, sourdough, chocolate sauce, mayonnaise,
malt extract and tomato-based sauces in general.
Benefits
• Low maintenance costs
• High working pressures
• High working temperatures
• Easy to expan
• Easy to inspect and clean

.
Design
The ViscoLine annular heat exchanger unit consists of four concentric
tubes. The product medium flows in between two service channels,
and is heated or cooled from the inside and outside at the same time.

. Connections available for both product side (tubes) and service side
(shell) include: SMS, DIN 11851, DIN 11864, Tri-Clamps, Flange and
other on request.
The ViscoLine units can be manufactured with different surface finish
The unit features easy, full inspection of the product side by removing and can be electropolished if required.
the tube insert. .
. Working principles
The outer shell is corrugated and the other three concentric tubes The product medium runs in between the second and the third
are not corrugated, smooth. If required, the product tube can be concentric tube and is counter-current relation to the service medium.
corrugated. The only spare parts needed are the O-rings in the header. There is
a maximum gap on the product side of 49.2 mm (1.9 inches) and a
. minimum gap of 5.8 mm (0.2 inches).
ViscoLine annular heat exchangers are connected in series on product
side and in parallel on water/service side and grouped on support
frame or full frame.
.
The ViscoLine annular unit is designed for a pressure of 15 bar (217
PSI) on the product side (tubes) and 10 bar (145 PSI) on the service
side (shell), depending on the connections. The unit can, however,
accommodate higher pressure ratings up to 100 bar, depending on
component thickness as connection

.
The ViscoLine annular unit complies with the European Pressure
Equipment Directive (PED 2014/68/EU), and is entitled to bear the
CE mark. Where the CE mark is not required, Viscoline would be
manufactured according to Sound Engineering Practice (SEP). Other
design codes are available as well such as ASME VIII Div.1 and others
would be on request like SELO’s China Manufacturer License (SELO
approval). It is designed to operate at a temperature of 190°C (374 °F)
although higher temperatures are also met.
.
All units can be provided with an expansion joint to absorb thermal
expansion stress.
Static mixers can be included to increase turbulence and guarantee an
homogeneous thermal treatment.
.

1.4.88
Shell & tube heat exchangers ViscoLine™ Annular Unit

1.4

Technical data

Material
Product side Stainless steel AISI 316L
(tubes)
Service side Stainless steel AISI 304 or AISI 316L (optional)
(shell)
Frame Stainless steel AISI 304 (units can be angled for
selfdraining on request)
Gaskets NBR, EPDM, FKM, PTFE and others on request.

Other material available on request is SAF 2507 on product side.


Product bends in AISI 316L.
Options
• Protection sheets.
• Thermal insulation.
• Video inspection.
• X-Rays measurements & certificates.
• NDT testing & certificates.
• Angled frame for self-drainage..
.
Configuration

VLA 129/114/70/52-6.0-316L/304
VLA ViscoLine annular
52 1st tube diameter
70 2nd tube diameter
114.3 3rd tube diameter
129 4th and outer diameter of service shell
6.0 module length (meter)
316L material product side (tube)
304 material service side (shell)

1.4.89
Multitube Heat Exchangers Shell & tube heat exchangers

1.4
ky Alfa Laval Multitube Heat Exchangers
Auxiliary Membrane Filtration Equipment

Multitube heat exchangers are used to heat or cool products in


membrane filtration plants. These heat exchangers are made of
stainless steel (AISI 316L), in a hygienic design. All materials comply
with FDA regulations.
The multitube heat exchangers are available in two standard sizes: 1
m2 and 2 m2. They consist of an external pipe placed around 34 pipes
(1 m2) or 60 pipes (2 m2). The cooling/heating medium flows on the
outside of these pipes.
Customized dimensions and connections are available on request.

Technical Data

Multitube Heat Exchanger - 1 m 2


Example of cooling capacity: 1 kW/°C, 15 m3/h product flow, 1 cP
viscosity, and 1 m3/h cooling flow.
L1
L3 L2
G
DN1

H H
DN1

TD 710-052 G

Multitube Heat Exchanger - 2 m 2


Example of cooling capacity: 2.3 kW/°C, 75 m3/h product flow, 1 cP
viscosity, and 3 m3/h cooling flow.
L1
L3 L2
DN2
.
DN1

H
H
DN1

TD 710-087
DN2

1 m2 2 m2
Code no.
104878 104880
Maximum pressure
Product 30 bar (3.0 MPa) 30 bar (3.0 MPa)
Medium 10 bar (1.0 MPa) 10 bar (1.0 MPa)
Temperature
Min. 1°C 1°C
Max. 80°C 80°C
Heat transfer area 1 m2 2 m2
Liquid volume in litres
Product 3 8
Medium 4 6
Weight kg 15 24
L1 (mm) 1200 1254
L2 (mm) 930 870
L3 (mm) 135 192
H (mm) 58 90
Product DN1‘ Diameter 51 mm 2" ISO 2852 clamp Diameter 76 mm 3" ISO 2852 clamp
Medium
DN2 - Diameter 51 mm 2" ISO 2852 clamp
G 1" BSP female -
Number of pipes 34 60

1.4.90
1.5 Single scraped surface heat exchanger
Contherm scraped surface heat exchangers are the ultimate heat transfer solution for heat
sensitive, sticky, abrasive, particulate laden, crystallizing/phase changing or other difficult to
treat products in food, dairy, cosmetic, chemical, and other industries

Product leaflets
Contherm® Core Scraped-Surface Heat Exchanger . . . . . . . . . . . . . . . . . . 1.5.92
Contherm® Scraped-Surface Heat Exchanger (SSHE) . . . . . . . . . . . . . . . . 1.5.94
Contherm HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5.96
Convap® Scraped-Surface Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5.98
Contherm ® Core Scraped-Surface Heat Exchanger Single scraped surface heat exchanger

1.5
ky Alfa Laval Contherm® Core Scraped-Surface Heat Exchanger
For low to medium viscosity products

Applications
Scraped-surface heat exchangers (SSHE) are at the heart of both
continuous and semi-continuous viscous food and personal care
processes. The Contherm® Core SSHE provides exceptional thermal
efficiency, which is a prerequisite for viscous processing. Contherm
Core ensures higher throughput, uniform heat transfer and more
economical operation, compared to other heat exchangers.
Contherm Core is designed specifically to process low to medium
viscosity products, such as soups, sauces, ketchup, fruit purees,
dressings, baby food and desserts as well as skin lotions, facial cream
and shampoo.
Contherm Core features and benefits
• The 6x11 model offers 0.15 m2 (1.62 ft2.) larger surface area than
other scraped-surface heat exchangers in the market
• Features the same proven critical core components of the
Contherm including the heat transfer cylinder, seals and blades
• The Contherm Core can handle up to 50,000 cps and
25 mm (1 inch) particles
• Optional flushed seals allow for aseptic processing
Design
When processing less complicated low to medium viscosity
products, sometimes a more simple scraped-surface heat exchanger
solution
. is needed. Based on the traditional Contherm and exact
“core” components, Contherm Core was developed to provide a
cost-effective, simple design with the quality and reliability expected
from Alfa Laval.
This design ensures easy installation and reliable operation adding up
to an increased product lifetime and return on investment.
Contherm Core is only available in a horizontal installation frame and
with an option to stack three Contherm Core units on top of each
other. The frame set-up requires only a minimum of interconnecting
pipework and is made of bead-blasted 304 stainless steel.

1.5.92
Single scraped surface heat exchanger Contherm ® Core Scraped-Surface Heat Exchanger

Proven Contherm components


Up to 7.5 kW (10 HP) Direct
• Heat exchanger cylinder
coupled gear reducer (Up to 350 Center port • Seals
RPM) heads • Blades No hydraulic lift

1.5

Motor mounting flange Bolted mounting drive end Smaller diameter 2 piece outer Bolted mounting non-drive end
stainless steel trim sheet

Specifications
• Models 6x9 (0.85 m2 (9 ft2)) and 6x11 (1 m2 (11 ft2))
• 316/316L stainless steel cylinder
• FDA approved Alfalon® III scraping blades
• 76 mm (3 inch) or 114 mm (4.5 inch) staggered rotors
• Single or double mechanical carbon seals
• 51 mm (2 inches) SMS, DIN or Tri-Clamp connections
• Center port product heads for bidirectional product flow
• Up to 7.5 kW (10 HP) motor and directly coupled gear reducer
• Simplified mounting frame (optional)

Three Contherm Core units on frame

Working principle
Product is pumped into the Contherm heat exchange cylinder. As
it flows through the cylinder, it is continuously mixed and removed
from the cylinder’s precisely finished wall by the scraping blades. This
scraping action results in thin film product heating or cooling, a surface
free from fouling deposits, and a corresponding high heat transfer
rate. The drive can be adjusted for varied rotor speeds – an important
feature when a number of different products are to be processed.
Heating or cooling media flows in the annular space between the
Contherm’s heat exchange cylinder and the insulated jacket.
When liquid media is used, a spiral coil is installed in the annulus to
provide higher heat transfer efficiency. When utilizing steam or flooded
expansion refrigerants such as liquid ammonia or Freon, the coil within
the Contherm Core annulus is removed. The use of these refrigerants
requires other ancillary equipment such as refrigeration accumulators
and control valves, products that Alfa Laval can provide.
On start-up, air is completely purged from the Contherm. At the end
of a processing run, the product can be drained or pushed by water,
resulting in minimal product loss.
The Contherm’s maximum flow rate is application specific and
determined by the temperature program, nature of the product and
type of duty.

1.5.93
Contherm ® Scraped-Surface Heat Exchanger (SSHE) Single scraped surface heat exchanger

1.5
ky Alfa Laval Contherm® Scraped-Surface Heat Exchanger (SSHE)
Heat Transfer Solution for Low to High Fouling Products

Applications
The Contherm® scraped-surface heat exchanger (SSHE) has found
use within many different processes and applications for manufacturing
food, chemicals, pharmaceuticals, cosmetics, health and beauty
products, etc. It is particularly suited for processing viscous, heat
sensitive, sticky or chunky (containing particulates) products that are
to be pumped.
It can be used in a broad range of processing environments, including:
aseptic, heating, slush-freezing, sterilization, cooling, pasteurization,
crystallization and phase change.

Design
The standard design of Contherm includes:
• Standard execution is vertically mounted on a column. The column
needs to be secured to either a wall or the ceiling.
• Rotor is driven by electrical motor installed on upper end of the unit.
• Rotor is placed on ball bearings. Mechanical seals at each end of
Contherm prevent product leakage and external contamination.
• Rotating scraping blades are secured to pins welded to the rotor.
• A hydraulic lifting device provides an easy way to lower the rotor
and blades for maintenance and inspection.
• Tangential inlet/outlet ports provide gentler handling of the product,
resulting in better product integrity and quality, by allowing product
. to enter and exit cylinder in same direction as the turning rotor. Flow Rate
• It is designed to comply with the most stringent industry standards. The Contherm’s maximum flow rate is application specific and
USDA and 3A hygienic design certifications are available for special determined by the temperature program, nature of the product, and
executions. type of duty.
• Contherm is manufactured according to ASME and PED. Other
pressure vessel codes are available on request.
The Contherm SSHE can operate with a large flexible range of media
types, such as: steam, thermal oil, water, glycol, brine, Freon™ or
ammonia and other liquified gas refrigerants.
Working principle
Product enters the cylinder through the lower product head and flows
upwards through the cylinder. At the same time, the heating/cooling
media travels in counter-current flow through the narrow annular
channel between the heat transfer wall and the insulated jacket.
Rotating blades continuously remove product from the cylinder wall in
order to ensure uniform transfer of heat between media and product.
An optional coil in the annulus increases media velocity, adding to
the heat transfer efficiency.
Product exits the cylinder through the upper tangential port. On
start-up, air is completely purged from the Contherm. At the end of a
processing run, the product can be drained or “chased-out” by water
resulting in minimal product loss.
Scraper configuration, rotor diameter and rotor speed can be varied to
suit the properties of the particular product flowing through the cylinder.
Numerous Contherm configurations are available. Trained,
knowledgeable Alfa Laval staff are able to customize each Contherm
unit by selecting the appropriate materials, features and options to
meet each customer’s exact requirements.

1.5.94
Single scraped surface heat exchanger Contherm ® Scraped-Surface Heat Exchanger (SSHE)

Technical Information
Working temperature range:
B
Product side: . . . . . . . . . . . . . . . . . -35°C to +170°C
Media side: . . . . . . . . . . . . . . . . . . -35°C to +170°C C
Maximum working pressure:
Product side: . . . . . . . . . . . . . . . . . 20 bar and full vacuum D 1.5
Media side: . . . . . . . . . . . . . . . . . . 17 bar
Connections - product side: E
A
51 mm DIN, Tri-clamp, SMS, other
76 mm DIN, Tri-clamp, SMS, other F
Connections - media side:
51 mm Upper - NPT or flange
5401-0001
37 mm Upper - Lower NPT or flange
Materials
The heating surface is made in 316 L stainless steel, honed to a very G
high finish on the inner surface. The scraping blades are made of
Alfalon® III, Nylon and Teflon material.
The seals are made of single carbon mechanical, carbon flushed /
aseptic, hard face and hard face flushed / aseptic. Suitable materials
will be selected for special applications.
Optional Features H
The following optional design features are available: K
J
• Alternative mounting configurations, including a horizontal option
for use in facilities with limited ceiling height A = Product outlet
• Control panel with automatic maintainance status feature to prevent B = Motor
product freezing if flow is interrupted C = Blade
• Refrigeration (accumulator) or heating/cooling valve packages. D = Heat transfer surface
• Rotors in different sizes: 76 mm diameter, 102 mm diameter, 114 E = Rotor
mm diameter, 127 mm diameter F = Heating/cooling media port (in) (Refrigerant - out)
• 27 barg product-side pressure rating is available G = Insulation
H = Heating/cooling media port (out) (Refrigerant in)
J = Rotor lifting device
K = Product inlet
D
E
B

C Heating Net* Floor


Model surface A B C D E weight space
5401-0002 [m 2] [mm] [mm] [mm] [mm] [mm] [kg] [m 2]
6x 3 0.279 854 2,502 864 933 717 140 0.33
6x 6 0.557 1,387 3,645 864 933 1,326 234 0.33
A

6x 9 0.836 1,997 4,864 864 933 1,936 274 0.33


6 x 11 1.020 2,355 5,689 864 933 2,205 306 0.33

* The height may vary depending on the size of the motor

1.5.95
Contherm HP Single scraped surface heat exchanger

1.5
ky Alfa Laval Contherm HP
New robust design widens the range of applications
Intro
The Contherm HP is designed for medium to extreme viscosity
applications that require or produce especially high product pressures.
The robust design can handle 41 bar (600 psi), which is twice the
pressure rating of the traditional Contherm.

.
Applications
The Contherm™ HP scraped-surface heat exchanger (SSHE) has
found use within many different processes and applications for
manufacturing food, chemicals, pharmaceuticals, cosmetics, health
and beauty products, etc. It is particularly suited for processing
viscous, heat sensitive, sticky or chunky (containing particulates)
products that are to be pumped. It finds it strength in high pressure
application such as like margarine, shortening, confectionary masses
or nut butter processing, where process wise higher design pressures
are necessary. On the other side, it offers a more simplistic design for
servicing, as it has a self-aligning motor/ gear box, which makes a
coupling not needed.

.
Features and benefits compared with other scraped-surface heat
exchangers
By far the most robust Contherm, suitable for the most extreme
. .
applications. Contherm HP can be equipped with all of the features of
• More performance Robust designs with multiple material options
a traditional Contherm, but is engineered to handle system pressures
optimize heat transfer and product throughput, giving long-lasting
up to 41 bar (600 psi). A unique, self-aligning rotor design protects
mechanical performance
Contherm HP from accelerated wear and does not require the use of
• More safety, more savings Each vertical Contherm HP has its own
couplings to connect the shaft to an electric gear motor. In addition
hydraulic system, allowing for fast, easy and safe inspection as well
to a new exterior, these design features simplify installation, saving
as service with minimal labour costs.
you time and money.
.
.
• More robust Withstands up to 41.4 bar (600 PSI) of product Working principle
pressure - twice as much as a standard single-wall scraped-surface Product enters the cylinder through the lower product head and flows
heat exchanger upwards through the cylinder. At the same time, the heating/cooling
• More simplicity A new self-aligning motor/gear box assembly media travel in a counter-current flow through the narrow annular
eliminates the use of coupling components for simpler, easier, channel .
faster installation. Rotating blades that meet the wall through centrifugal force
• More space Like the traditional Contherm, Contherm HP can be continuously remove product from the cylinder wall in order to ensure
installed both horizontally and vertically, offering flexibility to meet uniform transfer of heat from the media to the product. An optional
specific preferences or space limitations. Contherm HP can be coil in the annulus increases media velocity, adding to the heat transfer
installed either horizontally or vertically depending on customer efficiency.
preference. Product exits the cylinder through the upper tangential port. Product
• More versatile Contherm HP can handle products with or without flow and rotor speed can be varied to suit the properties of the
particles and viscosities well in excess of 100,000 cP. It is the particular product flowing through the cylinder.
most versatile heat transfer solution on the market, with limitless
opportunities for full-line utilization in any production environment
• More flexible Continuous scraping action makes Contherm HP
easy to clean with relatively low hold-up volumes. It can flexibly
transition from one product to the next, meaning minimal product
loss and downtime.

1.5.96
Single scraped surface heat exchanger Contherm HP

Technical Data

Mechanical features
Certification ASME, PED, 3A, Cryogenic
Motor options (power) 5.5 to 7.5 kW / 7.5 to 10 HP
11 kW / 15 HP 1.5
15 or more kW / 20 or more HP
Surface area 0.28m2 (3 ft2)
0.56m2 (6 ft2)
0.84m2 (9 ft2)
1.0m2 (11 ft2)
Seals Single mechanical or flushed / aseptic
Hard face single or hard face flushed
Inboard seal
Huhnseal
Industrial packing gland

Product side
Material cylinder 316 L Stainless steel
316 L HIPEX Stainless steel
Duplex 2205
Nickel
Unique coatings Chrome
Triple - chrome
Alfaloy
Pressure 41 bar (600 psi)
Temperature -35°C to +170°C (-30°F to 338°F)
Rotor diameter 51 mm (2 inch) diameter
76 mm (3 inch) diameter
102 mm (4 inch) diameter
114 mm (4.5 inch) diameter
126 mm (5 inch) diameter
Blades ALFA-LON III, ALFA-LON IV
ALFA-LON III-S (metal detectable)
Nylon
PEEK
Stainless steel

Media side
Pressure 250 psi (17 bar)
Temperature -35°C to +170°C (-30°F to 338°F)

High
capacity per unit

Contherm® Max
Surface area/

Contherm® Core Contherm®/ Contherm®HP


Low

Low Viscosity/application diffículty High/Extreme

Our customers’ processes and applications are by no means identical, and the same is true of the Contherm range of scraped-surface heat
exchangers. For products that are easy to process, a basic Contherm design consisting of polymer blades and single mechanical seals would be a
suitable solution. Whereas for highly demanding products and processes, the materials and components need to be more rugged and more durable
in order to ensure dependable operation.

1.5.97
Convap ® Scraped-Surface Evaporator Single scraped surface heat exchanger

1.5
ky Alfa Laval Convap® Scraped-Surface Evaporator
Removing moisture from viscous products

Application
Convap® is a specially modified Contherm® unit designed as a
continuous scraped-surface evaporator. This makes it particularly
suited for concentrating viscous, sticky and/or heat sensitive products
that tend to cause fouling in static types of heat exchanger.
Convap can effectively concentrate products to extremely high solids
levels, in some cases up to 99%. And it is often used to process
products that rapidly become viscous as they undergo concentration.
Convap can function as a preevaporator to any dryer type, as it makes
the overall process from concentration to drying of a product more
efficient.
Typical Convap applications include the production of purées, mashes,
pulps, concentrate and pastes from fruits and vegetables. Convap
units are also suitable for processing a wide selection of confectionery,
protein solutions such as whey protein, lecithin, sugar solutions,
chemical and pharmaceutical solutions, and for concentrating plant
waste materials into heavy slurry for easy disposal. Convap units can
also be used for concentrating coffee and other extracts.

Design
The standard Convap scraped-surface evaporator is based on a
modular design and is normally mounted vertically on a wall or column.
The modular design permits the deployment of one to four Convap
.units configured in parallel or up to two units in series to meet specific Materials
capacity requirements. Convap heat exchanger cylinders can also be The cylinder heating surface can be made of 316 L stainless steel, 316
configured so that several units use a shared separator vessel and L HIPEX stainless steel, corrosion-resistant alloy or nickel, with unique
condenser. Each Convap is assembled from standard, pre-fabricated coatings such as chrome, triple-chrome and Alfaloy.
components.
The scraping blades are available in configurations that include
The major components of a standard Convap unit are: Alfalon®III, Alfalon® III-S (metal detectable), PEEK, stainless steel and
• Scraped-surface heat exchange cylinder corrosion-resistant alloy. All blades can be fitted as slotted or spring
• Vapour dome loaded.
• Separator vessel
The seals are available in configurations that include single carbon
• A 4-bladed rotor configuration to prevent product burn-on
mechanical, carbon flushed / aseptic, hard face and hard face
flushed / aseptic, Huhnseal, and high torque / flushed, depending
Specifications on application.
Working temperature Optional features
Product side: . . . -35°C to +170°C The following optional design features are available for Convap units:
Media side: . . . . -35°C to +170°C • Control panel with automatic maintenance status features for
Maximum working pressure expansion refrigerant applications
Product side: . . . 20 bar and full vacuum • Rotors in different sizes: 76 mm diameter, 102 mm diameter, 114
Connections mm diameter and available in unique designs such as high-torque
Product side: . . . 51 mm DIN, Tri-clamp, SMS, other 76 mm DIN, spline and heavy-duty blade pins
Tri-clamp, SMS, other • Motors in a range of different power configurations and in
Media side: . . . . 51 mm Upper - NPT or flange 37 mm Upper - explosion-proof design
NPT or flange • Condenser
• Spray ball mounted in separator vessel, CIP pump and pressure
sensor for concentrate flow

1.5.98
Single scraped surface heat exchanger Convap ® Scraped-Surface Evaporator

A H
L

F
1.5
J M

G
E
N

D
C
5505-0001

B 5505-0000

A= Vapour outlet H= Motor


B= Concentrated product out J= Vapour dome
C= Product inlet K= Insulation
D= Heating media port (out) L= Heat transfer surface
E= Heating media port (in) M= Blade
F= Spray ball system for CIP N= Rotor
G= Separator vessel

How it works L PT
Just as in Contherm units, the product is pumped (B) into the lower
end of the Convap heat exchanger cylinder (A). The heating medium F
flows in the annular space between the heat transfer wall and the E
insulated jacket. Mechanical agitation, provided by the revolving C
blades, creates the convection conditions essential for efficient heat D
transfer. The scraping blades continuously remove the product film N
from the precision- /finished cylinder wall.
A
The Convap rotor, driven by a motor on the upper end of the unit,
spins the heavier liquid droplets towards the cylinder wall. This action P
M
ensures a continuous re-wetting of the heat transfer surface and the
removal of vapour, as well as preventing product burn-on. H
B
G
The Convap is normally operated under vacuum. Vaporization J
occurs in the Convap scraped-surface heat exchanger cylinder (A). 5505-0002

The separator (D), connected to the Convap by a custom-designed


vapour dome (C), allows the separation of the concentrate from the
K
vapour phase. In the separation vessel, the vapour exits the top to a
condenser (E) driven by a vacuum pump (G), while the concentrated A= Heat exchanger cylinder H= Concentrated product out
product exits at the bottom, forced by a concentrate removal pump (J). B= Feed pump J= Concentrate removal pump
As an option, separator vessel can be fitted with a spray ball head for C= Vapour dome K= CIP bypass pump
effective CIP cleaning in between batches. A pressure sensor (L) can D= Separator vessel L= Pressure sensor
be fitted on the top of the separator vessel and a level transmitter can E= Condenser M= Product
be fitted on the concentrated product out piping. A loop for a CIP F= Vapour outlet N= Water out
bypass pump (K) can also be implemented. G= Vacuum pump P= Water in

Convap Model Heating surface [m 2]


6x3 0.28
6x6 0.56
6x9 0.84

1.5.99
This page is intentionally left blank
1.6 Double wall scraped surface heat
exchanger
Contherm scraped surface heat exchangers are the ultimate heat transfer solution for heat
sensitive, sticky, abrasive, particulate laden, crystallizing/phase changing or other difficult to
treat products in food, dairy, cosmetic, chemical, and other industries

Product leaflet
Contherm Max scraped-surface heat exchanger . . . . . . . . . . . . . . . . . . . . . 1.6.102
Contherm Max scraped-surface heat exchanger Double wall scraped surface heat exchanger

ky Alfa Laval Contherm Max scraped-surface heat exchanger


Double-wall design offers high capacity and small footprint
1.6

Design
The Contherm Max double-wall scraped-surface heat exchanger
(SSHE) features 4.5 times more surface area than the largest
traditional-size Contherm. The Contherm Max utilizes both an inner
and outer heat transfer surface, ensuring a low-shear 2-inch (51 mm)
product path.

.
The highly engineered scraping cage assembly and blades minimize
the power required to achieve effective scraping.
.
The Contherm Max is is a stand-alone unit that only takes up a small
amount of space, because it is installed vertically, and does not need
to be fi xed to adjacent structures such as a wall or ceiling.

.
Features and benefits compared with other scraped-surface heat
exchangers
• Large surface area with capacity equivalent to three traditional-size
scraped surface heat exchangers
• Low pressure drop and low shear environment that ensure gentle
treatment for shear-sensitive or particulate products
• One single mechanical seal per unit, resulting in signifi cant savings
. on maintenance costs .
• Small footprint, with no need for signifi cant rigging – thus reducing
installation costs
D
. C
Applications
The Contherm Max is ideal for applications that require high throughput
B
as well as the uniform heat transfer of viscous, sticky and heat sensitive
products that would tend to foul other types of non-scraped heat
A
exchangers.

.
The unique design of the Contherm Max and the product path
created by the two heat transfer walls make it particularly suitable
for high-quality products that require low shear or contain large
particulate pieces. This makes these heat exchangers well-suited
for use in the manufacture of a wide variety of prepared foods such
G
as soups, sauces, starch-based condiments, baby food, desserts,
fruit, vegetable purées and concentrates with or without particles, E
confectionery creams, cream cheese and spreadable cheese products. F
. A: Product path
Examples of non-food uses can include pet food and personal care B: Outer heat transfer surface
products such as skin creams, lotions, gels, petroleum jelly and C: Inner heat transfer surface
shampoo. D: Rotating scraping assembly
E: Outer/inner scraping blades
F: Bottom tangential product entry
G: Heating or cooling media flowing within inner and outer
heat exchangers

1.6.102
Double wall scraped surface heat exchanger Contherm Max scraped-surface heat exchanger

Application Contherm Max Contherm Traditional-size SSHE


Throughput capacity per units
Particulate processing
Low shear, gentle treatment
Thermal efficiency per area
Viscosity
Rapid, flexible product transitions 1.6

How it works
Product enters at the bottom tangential entry port, and exits at the top
of the Contherm Max. Steam or liquid heating or cooling media flow
from top to bottom in a counter-current path at high velocity, in order
to optimize heat transfer to the product.

.
A highly engineered rotating scraping assembly, fitted with blades that
continuously remove fouling material from both inner and outer walls,
is mounted within the product path. The rotating scraping assembly
can vary in speed to ensure the most effective scraping and best
product quality.

.
At the end of production, the product can be drained or removed by
water, resulting in minimal product loss. The Contherm Max can then
be Cleaned in Place (CIP) using recommended guidelines for cleaning.
.

Equipment specifications

Mechanical Surface area Maximum Maximum media Maximum Number of Hold-up volume Mounting
design product pressure temperature seals/blades per
pressure rating unit
Contherm Max 4.5 m2 48 sq ft2 15 Bar/ 220 psi 8 Bar/ 220 psi 150°C/302°F 1/48 130 liter/ 34.5 gal Vertical
Contherm 0.56-1 m2/ 6-11 27 Bar/397 ps 17 Bar/250 ps 170°C/338°F 2/up to 16 29 liter/up to 8 gal Vertical or
Traditional-size sq ft2 horizontal
SSHE

• Heat transfer surfaces made of 316L stainless steel


• Scraping blades made of ALFA-LON III FDA- and
EU-compliant material.
• Single or flushed (aseptic) mechanical seal assembly
• Connections:
Product – 4” (102 mm)
Outer Media – 3” (76 mm) Flange
Inner Media – 1½” (38 mm) Flange
• 20 HP (15 kW), 3-phase, 50/60 Hz, 400/460 volt motor
Frequency inverters are recommended to optimize
thermal efficiency and product quality

1.6.103
Alfa Laval in brief

Close at hand
Alfa Laval is a leading global provider of
specialized products and engineered
solutions.

Our equipment, systems and services


are dedicated to helping customers to
optimize the performance of their Heat exchangers for Hygienic Fluid Handling Equipment, January 2021
­processes. Time and time again.

We help our customers to heat, cool,


separate and transport products such
as oil, water, chemicals, beverages,
foodstuffs, starch and pharmaceuticals.

Our worldwide organization works


closely with customers in almost 100
countries to help them stay ahead.

How to contact Alfa Laval


Contact details for all countries are
continually updated on our website.
Please visit www.alfalaval.com to
access the information.
Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB, Sweden. Alfa Laval © 2021

100001539EN-1 2101

You might also like