You are on page 1of 2

CSM-321S

2C SPLIT CORE CURRENT TRANSDUCER


 DESCRIPTION
Product designed using Hall Effect theory with fast output

MWH-10
response characteristic. With Opening like structure, it is
safe and convenience to install in any kind of current
measuring system. Widely use in DC/AC current including
current bipolar and DC pulse conversion for monitoring and
control.
 FEATURES

CSM- CSM-321S CSM- CSM-321S CSM- 2C Current Tran. CSM-


● Split core CT with Clamp, easy installation
● Wide Range of Inputs fulfilling all needs
● Direct connect AC or DC current (0~30A/~500A max) with DC 24V
Aux. Power only, loop powered is not included
● Compact, DIN rail mounting

 ORDERING INFORMATION
Input Input Output
2C− range Frequency − signal − Aux power

CODE INPUT RANGE CODE INPUT RANGE CODE FREQUENCY CODE OUTPUT CODE AUX POWER
A6 0 ~ 30 A AB 0 ~ 150 A* 5 50Hz ±3Hz A4 0 ~ 20 mA D2 DC 24 V
A7 0 ~ 50 A* AC 0 ~ 200 A* 6 60Hz ±3Hz A5 4 ~ 20 mA Loop Powered
LP
A8 0 ~ 80 A AD 0 ~ 300 A* D DC V2 0~5V (Just For AC only)
AA 0 ~ 100 A* AE 0 ~ 500 A V3 0 ~ 10 V

SPECIFICATIONS  ADJUSTMENT
Measuring Current
Measure: Hall Effect CT
Measuring range: Specify AC/DC , input range, frequency
30A,50A,80A,100A,150A,200A,300A,500A
Accuracy: ≤± 0.5% of FS
Response time: ≤ 250mSec
Max burden capacity: ≤ 20times, not exceeding 500A

Analogue output
Ripples: 0~50% of rated: ≤ 0.25% of FS
51~100% of rated: ≤ 0.2% of FS
Isolation: Between measuring current(input) and output
Output: Voltage: 0~5V / 0~10V; current: 0~20mA / 4~20mA
Please specify range when ordering
Span adjustment: ≤ 5% of FS
Zero adjustment: ≤ 5% of FS
Output Load: Voltage: 0~5/~10V: ≥ 2500Ω;

2 Series
Current: 4(0)~20mA: ≤ 250Ω max output:4~20 mA

Electrical Safety
Dielectric strength: AC 2.0 KV,1Min, between input / output(Aux) / case
Insulation resistance: ≥100M ohm at 500Vdc, between input / output(Aux)
/ case  DIMENSIONS CSM-321S CSM-
Isolation: Between input / output(Aux)
36.5 Unit: mm
25.0
Power
Aux power: DC 24V  10% or 2 wire Loop Powered(AC only)
Power consumptions: Smaller then 2.0VA
89.0
Current
Environmental 83.0 87.0 transducers
Ø29(0/0.5~500
Operating temp.: -10~55˚C 62.0
A)

Operating humidity: 20~95 %RH, non-condensing


Temp. coefficient: ≤200 PPM/˚C
Storage temp.: -10~70 ˚C
Enclosure: IEC 529 (IP52); Case: IP20

Mechanical 4 - M3 x 5 3Φ x 2 35.0 Rail


83.5
Dimensions: 36.5mm(W) x 87mm(H) x 83.5mm(D) 88.5
Window Ф29mm
Case material: ABS (UL 94V-0)
Installation: DIN rail mounting (35mm)
Wiring terminal: 5A/300Vac, M2.0, 0.5~1.3mm2(22~16AWG)
Weight: About 150g

2C-2011-08-15 B2-03-1/2
CSM-321S

 INSTALLATION
ABS casing is quite fragile, when installing please bend wire to fit
MWH-10

in hole.
1 Front 2 Pull up 3 Put in wire
CSM-
2C Current Tran.

4 Push Down 5 Finish


CSM- CSM-321S CSM- CSM-321S CSM-

 CONNECTION DIAGRAM
When wiring,please ensure Aux voltage is correct and wiring match
specify terminal numbers。For safety of equipments and transducer
fuse or breaker is recommended.
Connection diagram may change without notice, please
follow diagram on unit if it differ.

DC Aux Power
Source
NL

Load 5 6 7 8 9
V+ GN Eo Io
2 Series

Aux power
mA
24Vdc

Wiring terminal:
2
5A/300Vac, M2.0, 0.5~1.3mm (22~16AWG)
CSM-321S CSM-

2 Wier Loop Powered (Just for ACA only)


Source
NL

Load 5 6 7 8 9
V+ GN Eo Io

Output
mA
Loop power 4 ~2 0m A
24Vdc

Wiring terminal:
2
5A/300Vac, M2.0, 0.5~1.3mm (22~16AWG)

B2-03-2/2 2C-2011-08-15

You might also like