You are on page 1of 8

providing

providing insights
insights for
for today’s
today’s hvac
hvac system
system designer
designer

Engineers Newsletter
volume
volume 49–3
49–3

ASHRAE® Standard 62.1-2019 Update

Since it was first published in 1973, requires that the indoor dew point
The latest version of ASHRAE Standard
ANSI/ASHRAE Standard 62.1 Ventilation temperature be no higher than 60°F in
62.1 was published in late 2019. This
Engineers Newsletter highlights several for Acceptable Indoor Air Quality has been any space served by mechanical cooling
addenda that were incorporated into the the basis of most mechanical codes.1 This equipment. The committee’s stated
2019 version, as well as some that were standard is under continuous maintenance intent for this requirement is to “reduce
incorporated into the previous 2016 by an ASHRAE committee, whereby the risk of microbial growth in buildings
version.
changes are made via a rigorous process and their interstitial spaces because it
of issuing proposed addenda for public limits the mass of indoor water vapor
review and comment. ASHRAE currently that can condense or be absorbed into
publishes a new version of this standard mechanically cooled surfaces.”
every three years, incorporating all
addenda approved since its last 5.10 Maximum Indoor-Air Dew Point in
publication. Mechanically Cooled Buildings.
Buildings or spaces equipped with or
The 2019 version incorporates 35 addenda served by mechanical cooling equipment
which, according to the committee chair, shall be provided with dehumidification
are intended to “achieve clarity, address components and controls that limit the
misinterpretations, and improve indoor humidity to a maximum dew point
equipment and building requirements.”2 of 60°F (15°C) during both occupied and
Several of these addenda are discussed in unoccupied hours whenever the outdoor-
this EN. For the complete list, refer to air dew point is above 60°F (15°C).
Appendix O in the standard, which
includes a brief description of each and Exceptions to 5.10:
identifies the section(s) impacted. 1 Buildings or spaces that are neither
equipped with nor served by
mechanical cooling equipment.
2 Buildings or spaces equipped with
Section 5: Systems and materials, assemblies, coatings, and
furnishings that resist microbial growth
Equipment and that are not damaged by
continuously high indoor-air dew
Section 5 of the standard includes general points.
requirements related to the design of the
3 During overnight unoccupied periods
ventilation system and its components. not exceeding 12 hours, the 60°F
(15°C) dew-point limit shall not apply,
Maximum indoor dew point. Addendum provided that indoor relative humidity
AE deleted the existing Section 5.9 does not exceed 65 percent at any
(“Dehumidification Systems”) and time during those hours.
replaced it with a new section that

©2020 Trane. All Rights Reserved. 1


Figure 1. Maximum indoor dew point limit
90
85

)
85

(°F
80
180

RE
TU
RA
PE
70

EM
80 160
80

BT
UL
60
60

HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR


TB
WE
140

RH
75 50
50 75

%
65
120

DEW POINT TEMPERATURE (F°)


70 acceptable for40
4overnight
70
unnocupied periods not
100
65 exceeding 12 hours
65
(per exception30
3
3)
60 80 60
60°F DPT maximum limit
55
(occupied and unoccupied periods)20 60
55
50 50
45
45
40 40
40
35 10
35
30 30
20 25
25 20
10
0
0
30 40 50 60 70 80 90 100 110
DRY BULB TEMPERATURE (F°)

Note that this indoor dew point limit Air-cleaning devices that generate Filters not required for sensible-only
only applies when the outdoor dew ozone are prohibited. Addendum AJ cooling coils. Section 5.9 (“Particulate
point is above 60°F. Whenever it is hot added a new section related to the use Matter Removal”) requires a filter (or
and dry outside, or cool outside, the of devices that generate ozone: air cleaner) with a MERV not less than
outdoor dew point will be below this 8 to be “provided upstream of all
threshold. 5.7 Ozone Generating Devices. The cooling coils or other devices with
use of ozone generating devices shall wetted surfaces through which air is
Also note that this limit applies during comply with the following sections. supplied to an occupiable space.”
both occupied and unoccupied hours.
However, exception 3 exempts Exception to 5.7: Electronic devices Addendum D to the 2013 version
overnight periods not exceeding 12 used exclusively for the operation of added the following exception to clarify
hours, as long as the indoor relative HVAC equipment and controls. that this filter is NOT required
humidity does not exceed 65 percent upstream of cooling coils that provide
5.7.1 Air Cleaning Devices. Air
during that time-frame. In other words, only sensible cooling and no
cleaning devices shall be listed and
the indoor dew point is allowed to rise dehumidification:
labeled in accordance with UL 2998.
above 60°F overnight as long as the
indoor relative humidity remains below Exception to 5.9: Cooling coils that are
5.7.2 Ultraviolet Devices. Ultraviolet
65 percent (Figure 1). designed, controlled, and operated to
generating devices in supply air or
provide sensible cooling only.
spaces shall not transmit 185 nm
Finally, exception 2 exempts spaces
wavelengths.
constructed with materials that resist
microbial growth or damage. Examples
listed in the standard include shower
rooms, swimming pool enclosures,
kitchens, spa rooms, and semi-cooled
warehouses.

2 Trane Engineers Newsletter volume 49-3 providing insights for today’s HVAC system designer
Addendum F deleted the existing Table The core area includes restrooms,
Section 6.2: Ventilation 6.2.5.2 (“System Ventilation elevators, mechanical space, a janitor
Rate Procedure Efficiency”) and replaced it with a new closet, and stairwells. This entire floor
“simplified procedure” for determining is served by one multiple-zone
The Ventilation Rate Procedure (VRP) is Ev (see inset on page 5). The recirculating ventilation system.
one of three procedures—each alternative calculation procedure is also
outlined in Section 6 of the standard— still available and included in Appendix Table 1 lists the design population (Pz)
that can be used to determine the A of the standard. for each zone, which are used for the
minimum outdoor airflow required for breathing-zone ventilation calculations
each zone, and then to calculate how (Vbz = Pz × Rp + Az × Ra). The sum of
To compliment this new simplified
much outdoor air must be brought in procedure, Addendum B added a new
these design zone populations is 152.
through the intake of the ventilation appendix with a table and simple However, in this case, a person is
calculation that is intended for use in expected to be either in their office (or
system.
assessing the ventilation performance of cubicle) or attending a meeting in one
a multiple-zone recirculating system in
The latter calculation differs based on of the conference rooms; not in both
an existing building, where some of the
the type of ventilation system being data needed to perform the full VRP zones at the same time. Therefore, the
designed—a single-zone system, a calculations might be difficult to obtain. design team estimates that the largest
100-percent outdoor air system, or a (peak) number of people expected to
multiple-zone recirculating system. A occupy this floor is 102; this is the
For this simplified procedure,
multiple-zone recirculating system is design system population (Ps), as
calculation of Ev is simply a function of
comprised of an air handler that defined by the standard.
the occupant diversity ratio (D), which
supplies a mixture of outdoor air and the standard defines as the total
recirculated air to more than one The occupant diversity ratio is
population (Ps) in the area served by calculated to be 0.67 for the ventilation
ventilation zone; a common example is the system divided by the sum of
a multiple-zone VAV system. system serving this example floor
design zone populations (Pz) for all plate:
zones served by the system:
New simplified procedure for
D = 102 / 152 = 0.67
calculating Ev. For a multiple-zone D = Ps / Sall zones Pz
recirculating system, the VRP
determines the system ventilation Figure 2 depicts a floor of an example,
efficiency (Ev) in order to calculate the multiple-story office building. This
design outdoor air intake flow (Vot). 23,000-ft2 floor plate consists of open-
Previous versions of the standard plan office areas (cubicles), private
included a table that could be used to offices along the East and West
lookup a default value for Ev, as well as exposures, and four conference rooms.
an appendix with an alternate
procedure for calculating Ev.

Figure 2. Occupancy diversity ratio (D) example

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 49-3 3
Table 1. Occupancy diversity ratio (D) example

Rp P z × Rp Az Ra A z × Ra Vbz
zone Pz cfm/p cfm ft2 cfm/ft2 cfm cfm

West private offices 6 5 30 1575 0.06 95 125

East private offices 6 5 30 1575 0.06 95 125

NW open offices 19 5 95 3800 0.06 228 323

SW open offices 19 5 95 3800 0.06 228 323

NE open offices 21 5 105 4200 0.06 252 357

SE open offices 21 5 105 4200 0.06 252 357

North conference rooms 30 5 150 600 0.06 36 186

South conference rooms 30 5 150 600 0.06 36 186

Elevator lobby 0 5 0 600 0.06 36 36

Σ Pz = 152 Σ P z × Rp = 760 Σ Az × R a = 1258

Ps = 102

D = Ps / Σall zones Pz = 102/152 Vou = D × Σall zones (Pz × Rp) + Σall zones (Az × Ra)
= 0.67 = 0.67 × 760 cfm + 1258 cfm = 1767 cfm

As mentioned, when using this Per Section 6.2.4.3.2, in order to use If minimum primary airflow setpoints
simplified procedure, the calculation of this simplified procedure, the minimum are below this threshold, then the
Ev is a function of only this occupant primary airflow setpoint for each zone alternative calculation procedure in
diversity ratio. If D is greater than or (Vpz-min) must be no lower than 1.5 Appendix A of the standard should be
equal to 0.60—which is the case in our times the design zone outdoor airflow used.
example—then Ev is equal to 0.75; but (Voz = Vbz / Ez). To demonstrate, the
if D is less than 0.60, then Ev is minimum primary airflow setpoint for
calculated using the equation in the the “West private offices” zone in our
standard (Figure 3). example must be no lower than 187
cfm in the cooling mode—assuming an
Finally, this value of system ventilation Ez-cooling of 1.0—and no lower than 233
efficiency (Ev) is used to calculate the cfm in the heating mode—assuming
design outdoor air intake flow (Vot) for an Ez-heating of 0.8 (Table 2).
the system (per Section 6.2.4.4), which
is 2356 cfm for this example:
Figure 3. Calculation of system ventilation efficiency (Ev) using the simplified procedure
Vot = Vou / Ev = 1767 cfm / 0.75

= 2356 cfm

4 Trane Engineers Newsletter volume 49-3 providing insights for today’s HVAC system designer
Table 2. Minimum primary airflow setpoints (Vpz-min)

Vbz Voz-cooling Vpz-min-cooling Voz-heating Vpz-min-heating


zone cfm Ez-cooling cfm cfm Ez-heating cfm cfm

West private offices 125 1.0 125 187 0.8 156 233

East private offices 125 1.0 125 187 0.8 156 233

NW open offices 323 1.0 323 485 0.8 404 606

SW open offices 323 1.0 323 485 0.8 404 606

NE open offices 357 1.0 357 536 0.8 446 669

SE open offices 357 1.0 357 536 0.8 446 669

North conference rooms 186 1.0 186 279 0.8 233 349

South conference rooms 186 1.0 186 279 0.8 233 349

Elevator lobby 36 1.0 36 54 0.8 45 68

In the 2019 version of ASHRAE 6.5.2.1 Zone Controls. Zone thermostatic control shall prevent reheating …
Standard 90.1, Section 6.5.2.1 was
revised to correspond with this new Exceptions to 6.5.2.1:
minimum primary airflow setpoint
2. Zones with DDC that comply with all of the following:
requirement.3 This section prevents
reheating air that has been previously (a) The airflow rate in dead band between heating and cooling does not exceed the
cooled, unless the zone controls first larger of the following:
reduce airflow to prescribed minimum (1) 20 percent of the zone design peak supply airflow
thresholds. Exception 2 used to require
airflow be reduced to 20 percent of the (1) The minimum primary airflow rate required to meet the Simplified Procedure
zone’s design supply airflow (see ventilation requirements of ASHRAE Standard 62.1 for the zone…
strike-through text). But this has now
(b) The airflow rate that is reheated, recooled, or mixed shall be less than 50% of the
been changed to require airflow be
zone design peak supply rate.
reduced to the minimum primary
airflow rate required by the simplified (c) The first stage of heating consists of modulating the zone supply air temperature set
procedure in Standard 62.1 (see point up to a maximum set point while the airflow is maintained at the dead band flow
underlined text)—which, as explained rate.
previously, is 1.5 times the design zone
outdoor airflow (Voz). (d) The second stage of heating consists of modulating the airflow rate from the dead
band flow rate up to the heating maximum flow rate

Simplified procedure

6.2.4.2 System Ventilation Efficiency. The system ventilation efficiency (Ev) shall be
determined in accordance with Section 6.2.4.3 for the Simplified Procedure or Normative
Appendix A for the Alternative Procedure.

6.2.4.3 Simplified Procedure

6.2.4.3.1 System Ventilation Efficiency. System ventilation efficiency (Ev) shall be


determined in accordance with Equation 6-7 or 6-8.

Ev = 0.88 × D + 0.22 for D < 0.60 (Equation 6-7)


Ev = 0.75 for D ≥ 0.60 (Equation 6-8)

6.2.4.3.2 Zone Minimum Primary Airflow. For each zone, the minimum primary
airflow (Vpz-min) shall be determined in accordance with Equation 6-9.

Vpz-min = Voz × 1.5 (Equation 6-9)

6.2.4.4 Outdoor Air Intake. The design outdoor air intake flow (Vot) shall be
determined in accordance with Equation 6-10.

Vot = Vou / Ev (Equation 6-10)

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 49-3 5
Demand-controlled ventilation and sources of CO2 other than occupants, distribution effectiveness (Ez). In
occupied standby mode. Section or with CO2 removal mechanisms, such addition to changes that improve
6.2.6 (“Dynamic Reset”) explicitly as gaseous air cleaners. clarity, this table now includes default
permits resetting the outdoor air intake values for stratified air systems (such
flow (Vot), or zone ventilation airflow 6.2.6.1.1 For DCV zones in the as displacement ventilation or
(Voz), in response to the current occupied mode, breathing zone underfloor air distribution systems) and
population. This energy-saving control outdoor airflow (Vbz) shall be reset in personalized ventilation systems (such
strategy is often referred to as response to current population. as where the ventilation outlet is
demand-controlled ventilation (DCV), Current population estimates used in incorporated into furniture).
and is typically implemented using a DCV control calculations shall not
carbon dioxide (CO2) sensor, an result in ventilation rates that are less This addendum also added a new
occupancy sensor (motion detector), or than those required by the actual appendix that includes an alternate
some other means of counting or population during any one-hour time procedure for calculating Ez.
estimating the number of people in a period.
zone. Alignment with Standard 170 and
6.2.6.1.2 For DCV zones in the FGI guidelines. Most health care
Addenda P and R to the 2013 version occupied mode, breathing zone facilities are designed and constructed
clarified requirements for when DCV is outdoor airflow (Vbz) shall be not less according to guidelines published by
implemented, and introduced the term than the building component (Ra × Az) the Facility Guidelines Institute (FGI).
“occupied standby mode” to the for the zone. For outpatient facilities, the FGI
standard. According to the definitions guidelines require some types of
6.2.6.1.3 Where CO2 sensors are spaces to comply with ASHRAE/ASHE
in Section 3 of the standard:
used for DCV, the CO2 sensors shall Standard 170, Ventilation of Health
• Occupied mode refers to when a be certified by the manufacturer to be Care Facilities.4,5 But for other types of
zone is scheduled to be occupied. accurate within ±75 ppm at outpatient spaces—notably psychiatric,
This is typically defined by the concentrations of both 600 and 1000 urgent care, physical therapy, imaging,
scheduling function in a building ppm when measured at sea level at and dental—the FGI guidelines require
automation system (BAS) or 77°F (25°C). Sensors shall be factory compliance with local codes, which are
programmable thermostat. calibrated and certified by the typically based on Standard 62.1.
• Occupied standby mode refers to manufacturer to require calibration not
when a zone is scheduled to be more frequently than once every five To fill this gap, and to better align with
occupied, but an occupancy sensor years. Upon detection of sensor Standard 170 and the FGI guidelines,
located in that zone indicates that failure, the system shall provide a addendum AF added minimum
no occupants are currently present. signal that resets the ventilation ventilation rates for these types of
system to supply the required outpatient spaces to Table 6-1 in
Whenever a zone is in occupied mode, minimum quantity of outdoor air (Vbz) Standard 62.1.
Section 6.2.6.1.2 requires that the to the breathing zone for the design
outdoor airflow delivered to the zone population (Pz). In addition, addendum AS added
breathing zone be no less than the language to clarify that the ventilation
building component of the ventilation 6.2.6.1.4 For DCV zones in the rates from Standard 170 are to be used
rate (Ra × Az). However, for certain occupied standby mode, breathing for any occupancy categories that are
occupancy categories, if an occupancy zone outdoor airflow shall be included in that standard.
sensor is installed in the zone, Section permitted to be reduced to zero for
the occupancy categories indicated Air cleaning for ozone. Section 6.1.4.3
6.2.6.1.4 allows outdoor airflow to be
“OS” in Table 6-1, provided that requires the installation, operation, and
reduced to zero whenever the zone is
airflow is restored to Vbz whenever maintenance of an air-cleaning device
in occupied standby mode (no
occupancy is detected. that removes ozone for locations
occupants present). Table 6-1 in the
where the outdoor ozone
standard includes a column to indicate
In addition, addendum AL to the 2016 concentration is expected to exceed
which occupancy categories are
version added new requirements (in 0.100 ppm.
permitted to implement this “occupied
Section 6.2.6.1.3) for the accuracy of
standby mode.” Addendum K changed this threshold to
carbon dioxide (CO2) sensors, when
6.2.6.1 Demand Control Ventilation they are used for DCV. align with current classifications
(DCV). DCV shall be permitted as an
defined by the U.S. Environmental
optional means of dynamic reset.
Zone air distribution effectiveness Protection Agency (EPA).6 As such, air
(Ez). Addendum AH expanded cleaning for ozone is only required in
Exception to 6.2.6.1: CO2-based DCV Table 6-4 in the standard, which locations classified as “serious” or
shall not be applied in zones with indoor includes default values for zone air higher.

6 Trane Engineers Newsletter volume 49-3 providing insights for today’s HVAC system designer
6.3.2 Contaminant Concentration. For
Section 6.3: Indoor Air each contaminant of concern, a Summary
Quality Procedure concentration limit and its
corresponding exposure period and an This EN discussed some of the 35
The Indoor Air Quality Procedure appropriate reference to a cognizant addenda which were incorporated into
(IAQP) is another allowable procedure authority shall be specified. For each the 2019 version of ASHRAE Standard
outlined in Section 6 of the standard. contaminant mixture of concern, the 62.1. The complete list can be found in
ratio of the concentration of each Appendix O of the standard.
While the ASHRAE committee has contaminant to its concentration limit
been working on a major revision to shall be determined, and the sum of To receive e-mail notification of
this procedure for some time, the these ratios shall be no greater than proposed addenda being issued for
proposed addendum is still being one. public review, you can subscribe to the
discussed and did not make it into the ASHRAE Listserve at
2019 version. A previous EN described www.ashrae.org/technical-resources/
the steps required for compliance with free-resources/listserves.
the IAQP.7 Section 6.4: Natural By John Murphy, Trane. To subscribe or view
previous issues of the Engineers Newsletter visit
Consideration for contaminant Ventilation Procedure trane.com and select the Training & Support from
the drop down menu. Send comments to
mixtures. The first step in the IAQP is ENL@trane.com.
to identify each “contaminant of Addenda L and T resulted in a
concern” for the space, both indoor significant revision to the Natural
and outdoor sources. Addendum J to Ventilation Procedure (NVP), which is
the 2013 version added a new the final allowable procedure outlined
requirement to also consider the in Section 6 of the standard. References
combined effects that multiple [1] ANSI/ASHRAE, Standard 62.1-2019, Ventilation
Users of the NVP can choose between for Acceptable Indoor Air Quality. Atlanta:
contaminants of concern (called a
a prescriptive compliance path or an ASHRAE. 2019.
“contaminant mixture”) have on an
“engineered system” compliance path.
individual organ system. [2] “Updated Standard 62.1 Simplifies, Improves
The prescriptive compliance path Calculations and Procedures.” HVAC&R
For each contaminant mixture, the Industry Newsletter. ASHRAE. 31 October
dictates the location and minimum
design team must calculate the ratio of 2019.
required size of natural ventilation
the concentration of each individual
openings, based on the floor area to be [3] ANSI/ASHRAE/IES, Standard 90.1-2019,
contaminant divided by its Energy Standard for Buildings Except Low-
ventilated and ceiling height. But any
concentration limit, and the sum of Rise Residential Buildings. Atlanta: ASHRAE.
zone designed for natural ventilation
these ratios shall be no greater than 2019.
must also include a mechanical
one.8
ventilation system—designed using [4] Guidelines for Design and Construction of
6.3.1 Contaminant Sources. Each either the VRP or IAQP—unless the Outpatient Facilities. Facility Guidelines
openings are permanently open or are Institute (FGI). 2018.
contaminant of concern, for purposes of
the design, shall be identified. For each equipped with controls that prevent [5] ANSI/ASHRAE/ASHE, Standard 170-2017,
contaminant of concern, indoor sources them from being closed during periods Ventilation of Health Care Facilities. Atlanta:
and outdoor sources shall be identified, of expected occupancy. ASHRAE. 2017.
and the emission rate for each
The engineered system compliance [6] “Nonattainment Areas for Criteria Pollutants.”
contaminant of concern from each U.S. Environmental Protection Agency.
source shall be determined. Where two
path offers greater flexibility to design
www.epa.gov/green-book
or more contaminants of concern target
the natural ventilation system, as long
the same organ system, these
as sufficient outdoor airflow— [7] Stanke, D. “Minimum Outdoor Airflow Using

contaminants shall be considered to be


calculated using either the VRP or the IAQ Procedure” Engineers Newsletter.
IAQP—reaches the breathing zone. ADM-APN042-EN. Trane. 2011.
a contaminant mixture.
[8] Trane. Compliance with the IAQ Procedure of
ASHRAE Standard 62.1-2016 white paper.
EDU-SLB038-EN. 2019.

7 Trane Engineers Newsletter volume 49-3 providing insights for today’s HVAC system designer
Download the New Version of Check out the latest Engineers Newsletter LIVE programs now
TRACE® 3D Plus available online!
Impact of DOAS Dew Point on Space Humidity. Dedicated outdoor-air systems
New features provide improved
(DOAS) are used in a variety of building types to provide ventilation; and when the
capabilities and performance that
outdoor air is dehumidified, a DOAS can help prevent high space humidity levels.
reduces the time you spend creating
But many of the systems designed and installed today are not dehumidifying
and analyzing models
adequately. This ENL will demonstrate how space humidity levels are affected by
New features and enhancements: the DOAS discharge-air conditions, at both full load and part load.

• Adjustable solar positioning for Indoor Agriculture: HVAC System Design Considerations. Conditioning spaces
shading visualization and analysis for plants instead of humans introduces new challenges. This ENL will discuss
• New options for partition modeling plants, the dehumidification challenges they pose, and how precision cooling for
that can significantly speed-up indoor agriculture is different compared to comfort cooling. We’ll also discuss
simulations common air- and waterside system configurations used to maintain space
conditions to ensure a healthy crop.
• New tools for drawing angled
buildings even faster You will find these and more under Training & Support—Self-Paced Learning on the
NEW Trane.com website!
• Ability to model adiabatic surfaces
that make it easy for retrofit or
partial building analyses Coming Soon...
• Residential and indoor agriculture Decarbonize HVAC Systems (October). Many municipalities are taking action to
themes have been added to the reduce their carbon emissions which includes the reduction, or removal, of natural
library gas for heating. The HVAC industry will face the challenge of heating buildings with
• Various quality, performance, and electric heat. This ENL will cover the motivation to electrify, areas currently effected
scaling improvements by this trend, and potential systems to meet electrification needs.

Visit Trane.com—Products—Design & Applying VRF for a Complete Building Solution (November) This ENL builds
Analysis Software, for more information upon the 2014 VRF program “Applying Variable Refrigerant Flow” with detailed
and to download the latest version. discussions on several considerations. Topics will include: when to use heat
recovery instead of heat pump configurations, how to scale VRF systems to include
other building systems, ventilation delivery, humidity management and more.

For additional information on Variable Refrigerant Flow (VRF)


technology, visit Trane.com/VRF to view and download the
latest VRF System Catalog.

This newsletter is for informational purposes only and does not constitute legal advice.
Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.

All trademarks referenced are the trademarks of their respective owners.

For more information, contact your local Trane


office or e-mail us at comfort@trane.com

8 Trane Engineers Newsletter volume 49-3 ADM-APN075-EN (September 2020)

You might also like