B8309 to B8373 Inter-

trip, interlocks and TX device trips.


Inter‐trip 
Inter‐trip  TX  TX 
6.6kV CB  6.6kV CB  690V CB  690V CB  from 
Function 6.6kV E/S to down  winding  pressure                                                     Remarks
position status position status down‐
stream temp trip relief trip
stream

6.6kV CB close test open open none test open none none none

6.6kV CB close service open open none service open none none none

690V CB close service close open none service open none none none

closes then 
6.6kV CB no close service open open none service none none none
opens

6.6kV & 690V CB trip service close open none service closed trip none none

6.6kV & 690V CB trip service closed open none service closed none trip none

6.6kV & 690V CB trip service closed open none service closed none none trip

Inter‐trip  Inter‐trip  TX  TX 


6.6kV CB  6.6kV CB  690V CB  690V CB 
Function 6.6kV E/S to down  from  winding  pressure                                                        Remarks
position status position status
stream down‐ temp trip relief trip

6.6kV & 690V CB trip service close open trip service closed none none none

no 
6.6kV CB no close service open open none service trip none none
operation

no 
6.6kV CB no close service open open none service none trip none
operation

no 
6.6kV CB no close service open open none service none none trip
operation
690v CB no close ‐ 
test open closed none service open none none none
elect.
690v cb trip through ‐ 
test open closed none service open none none none
mech.

690v cb               
elect. No close,          test open closed none test open none none none
mech. Trip through