You are on page 1of 2

Prysmian Gl. Calculations p.

9/20
Phase A & C:
EAC=I*sqrt((3*Y^2+(XM-A)^2))/2
Phase B: IXM
Y =XM + A
XM = 2*PI()*f (0.1404 log10(S/rm)) [μΩ/ft]
A = 2*PI()*f (0.1404 log10(2)) [μΩ/ft]

S
frq 50 Hz
Lengm 500 m
Lengft 1640.42
dia 53 dia
rm 24 mm dia
A 13.27782
XM 28.45381 Conductor
S 106
Y 41.73163 Shield
I 900
VoltAC 54.52063
voltAB 42.00858
2*rm
cond.dia 37.6 mm iec 228
ins.thick 10kV 3.4 mm iec 502
ins.semi.con 1 mm
shld.thick 0.5 mm
under jack.dia 47.4 ts = 0,035 D + 1,0
jacket th. 2.659
overall dia 52.718

You might also like