Service Information
Form 6 Recloser Control Disassembly,
Reassembly, and Testing Instructions S280-70-11
Figure 1.
Kyle® Form 6 Pole Mount, Yard Mount, and Rack Mount recloser controls.
Contents
Safety Information ..................................................... 2 Reassembly ............................................................... 8
Hazard Statement Definitions ................................ 2 Reassembly Instructions ........................................ 8
Safety Instructions .................................................. 2 Place Module in Control ......................................... 8
Product Information .................................................. 3 Before Placing the Control Into Service ................. 9
Introduction ............................................................ 3 Installation ................................................................. 9
ANSI Standards ..................................................... 3 Initial Programming Prior to Installation ................. 9
Quality Standards ................................................... 3 Testing ........................................................................10
Acceptance and Initial Inspection .......................... 3 Testing Instructions ................................................10
Handling and Storage ............................................ 3 Communication Ports .............................................10
Description ............................................................. 3 Contact Inputs/Outputs ..........................................10
Disassembly .............................................................. 4 Testing with Type MET Tester ................................11
Disassembly Instructions ....................................... 4 Additional Information ..............................................12
Open the Module ................................................... 5 Replacement Kits ...................................................12
Remove/Replace CPU Board ................................ 5 Factory-Authorized Service Centers ......................12
Remove/Replace Comms. Accsy. Board Only ....... 6 Factory Testing and Troubleshooting Classes .......12
Remove/Replace I/O Board ................................... 7
Remove/Replace Power Supply or RIF Board ...... 7
Remove/Replace Analog Board ............................. 8
!
SAFETY
!
SAFETY
FOR LIFE
SAFETY FOR LIFE FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively
promote safe practices in the use and maintenance of our products through our service literature, instructional training
programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,
marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high voltage lines and equipment and support our “Safety For Life” mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a sub- Safety Instructions
stitute for proper training or adequate experience in the
safe operation of the equipment described. Only compe- Following are general caution and warning statements
tent technicians who are familiar with this equipment that apply to this equipment. Additional statements, relat-
should install, operate, and service it. ed to specific tasks and procedures, are located through-
out the manual.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
DANGER: Hazardous voltage. Contact with
• Is trained in industry-accepted high- and low-voltage ! hazardous voltage will cause death or severe
safe operating practices and procedures. personal injury. Follow all locally approved safety pro-
• Is trained and authorized to energize, de-energize, cedures when working around high- and low-voltage
clear, and ground power distribution equipment. lines and equipment. G103.3
2
!
SAFETY S280-70-11
FOR LIFE
PRODUCT INFORMATION
Introduction Handling and Storage
Service Information S280-70-11 provides disassembly, Be careful during handling and storage of the unit to min-
reassembly, and testing instructions for the Kyle® Form 6 imize the possibility of damage. If the unit is to be stored
recloser control. for any length of time prior to installation, provide a clean,
dry storage area.
Read This Manual First
Read and understand the contents of this manual and fol- Description
low all locally approved procedures and safety practices
before installing or operating this equipment. Service Information S280-70-11 provides disassembly,
reassembly, and testing instructions for the Form 6 Rack
Additional Information Mount, Yard Mount, Pole Mount, and Triple-Single Pole
Mount recloser controls.
These instructions cannot cover all details or variations in
the equipment, procedures, or process described, nor For additional information on installing the control,
provide directions for meeting every possible contin- removing the control from service, and control testing
gency during installation, operation, or maintenance. For procedures, refer to the appropriate instructions:
additional information, contact your Cooper Power • Service Information S280-70-1 Form 6 Rack Mount
Systems sales representative. Recloser Control Installation and Operation
Instructions
ANSI Standards • Service Information S280-70-2 Form 6 Yard Mount
Kyle reclosers are designed and tested in accordance Recloser Control Installation and Operation
with the following ANSI standards: C37.60 and C37.85 Instructions
and ANSI Guide C37.61.
• Service Information S280-70-3 Form 6 Pole Mount
Recloser Control installation and Operation
Quality Standards Instructions
ISO 9001:2000-certified quality management system • Service Information S280-70-7 Form 6 Triple-Single
Pole Mount Recloser Control Installation and
Acceptance and Operation Instructions
Initial Inspection
Each unit is in good condition at the factory and when
accepted by the carrier for shipment.
Upon receipt, inspect the carton for signs of damage.
Unpack the unit(s) and inspect it thoroughly for damage
incurred during shipment. If damage is discovered, file a
claim with the carrier immediately.
3
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
DISASSEMBLY
Form 6 Recloser Control This step applies to Form 6 Pole and Yard mount controls.
Disassembly Instructions 3. Remove module from cabinet as applicable.
These instructions describe the disassembly of the Form A. For complete scheme structure and verification
6 recloser control. refer to appropriate instructions:
• Service Information S280-70-4 Form 6 Control
CAUTION: Recloser misoperation. The control must Schemes section
be removed from service prior to performing any main-
tenance, testing, or programming changes. Failure to • Service Information S280-70-9 Form 6-TS
comply can result in misoperation (unintentional oper- Control Schemes section
ation) of the recloser. T216.2 B. Disconnect SCADA communications to the Form 6
control.
1. Remove the Form 6 Control from Service. Refer to C. Remove all applicable connecting wires from
appropriate Service Information Instructions: module.
• Service Information S280-70-1 Form 6 Rack Mount D. Remove the 7/16 inch grounding nut and lock-
Control Installation and Operation Instructions washers located on the bottom of the control mod-
Remove the Control from Service section ule (Figure 2).
• Service Information S280-70-2 Form 6 Yard Mount E. Remove the four mounting nuts that secure the
Control Installation and Operation Instructions front of the module to the cabinet (Figure 3).
Remove the Control from Service section
• Service Information S280-70-3 Form 6 Pole Mount CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
Remove the Control from Service section 2 4 6 8 10 12 14 16 18 RS232 DTE TTL IRIG-B 2-Wire RS485
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
Operation Instructions Remove the Control from CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
10 9 8 7 6 5 4 3 2 1
Grounding Nut
IMPORTANT: Isolate all power connections to the and Lockwashers
4
!
SAFETY S280-70-11
FOR LIFE
2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12
1. Remove CPU board. Refer to Form 6 Recloser CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
Figure 5.
Form 6 control back plate.
5
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
Shield Tabs
Bezel Tabs
Capacitor
Input/Output Board
Analog Board
Figure 6.
Internal view of the Form 6 pole mount recloser control module.
6
!
SAFETY S280-70-11
FOR LIFE
7. Slide mounting plate into card guide and carefully Removal/Replacement of I/O Board
push the assembly into the module.
1. Remove the I/O circuit board. Refer to Form 6
Recloser Control Disassembly Instructions section.
IMPORTANT: Do not damage the capacitor or any
other electrical components on the Bezel tabs 2. Remove the TB3 and TB4 terminal block strips or
(Figure 6). cover plate from the back of the control module
(Figure 2).
8. Replace the TB1 terminal block strip. 3. Carefully pull I/O board outward so as not to damage
9. Attach fiber/wire cover plate over the communications any of the electrical components.
port on the back panel using two screws and washers. 4. Unscrew the five screws on top of the I/O board using
10. Configure communications board with applicable a Phillips-head screwdriver to release it from the
switches, and program as necessary. mounting plate.
5. Lift I/O board from shield.
CAUTION: Equipment misoperation. Do not 6. Install new I/O board onto mounting plate and replace
! connect this control to an energized recloser until the five screws.
all control settings have been properly programmed
and verified. Refer to the programming information for 7. Slide mounting plate into card guide and carefully line
this control. Failure to comply can result in control and up terminal strip to opening on the back plate.
recloser misoperation, equipment damage, and per- 8. Replace the TB3 and TB4 terminal block strips.
sonal injury. G110.3
7
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
8
!
SAFETY S280-70-11
FOR LIFE
Prior to placing the Form 6 recloser control into service, CAUTION: Equipment misoperation. Check mini-
installation procedures must be properly completed and mum trip values prior to changing an alternate profile.
verified. Failure to do so may cause misoperation of the control
under load conditions. T280.0
For information on placing the control into service refer to
the appropriate instructions:
IMPORTANT: Program all protection profiles.
• Service Information S280-70-1 Form 6 Rack Mount
Unused alternate profiles should be programmed with
Control Installation and Operation Instructions
the same settings as one of the applicable profiles.
• Service Information S280-70-2 Form 6 Yard Mount Default settings on unused alternate profiles can cause
Control Installation and Operation Instructions unnecessary outages if they are below normal system
• Service Information S280-70-3 Form 6 Pole Mount requirements.
Control installation and Operation Instructions
• Service Information S280-70-7 Form 6 Triple-Single
Pole Mount Control Installation and Operation
Initial Programming Prior to
Instructions Installation
The control must be programmed with all necessary
operating settings, all alternate profiles, and parameters
prior to operation with an energized recloser.
Note: Initial programming of the control is the responsibility of
a qualified technician or engineer familiar with control
functions and programming parameters required for the
specific recloser installation.
The control must be programmed with the Form 6
ProView interface software. Refer to the appropriate con-
trol programming guide for information:
• S280-70-4 Form 6 Control Programming Guide
• S280-70-9 Form 6 Triple-Single Pole Mount Control
Programming Guide
9
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
TESTING
Form 6 Recloser Control Testing For information on testing refer to the appro priate
instructions:
Instructions
• Service Information S280-70-1 Form 6 Rack Mount
These instructions describe the testing of the Form 6 Control Installation and Operation Instructions
recloser control.
• Service Information S280-70-2 Form 6 Yard Mount
Communication Ports Control Installation and Operation Instructions
Verify that the communication settings have been appropri- • Service Information S280-70-3 Form 6 Pole Mount
ately configured for your selected communication protocol. Control Installation and Operation Instructions
For information on configuring communications refer to • Service Information S280-70-7 Form 6 Triple-Single
the appropriate instructions: Pole Mount Control Installation and Operation
Instructions
• S280-70-4 Form 6 Control Programming Guide
• S280-70-9 Form 6 Triple-Single Control
Programming Guide
*Location of CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
Contact Input/Outputs
1 3 5 7 9 11 13 15 17 19
TB1 J1 RS232 J2 IRIG-B J3 RS485
1 3 5 7 9 11 13 15 17 19 21 1 3 5 7 9 11 13
2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
TB5
RECLOSER INTERFACE CONNECTIONS
A
1
D
3
F
5 7 TB6
10 9 8 7 6 5 4 3 2 1
• • • • • • • • • •
TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
the ProView™ software to verify that all contact outputs I(1-2) I(3-4) I(5-6) I(SEF) V(1-2) V(3-4) V(5-6) V1
TABLE 2
Operating Voltage Requirements for Standard and Optional
Supervisory Inputs for Form 6 Pole Mount Recloser Control
Minimum
Module Nominal Operating
Mfg. No.* Input Voltage Current Time
10
!
SAFETY S280-70-11
FOR LIFE
• • • • • • • • • •
TB2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Figure 9.
Module Mfg. No. location on back of Form 6 rack
and yard mount control.
010028KM
Figure 10.
Kyle Type MET electronic recloser control tester.
®
11
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
ADDITIONAL INFORMATION
Factory Testing and
CAUTION: This equipment requires routine
!inspection and maintenance to ensure proper Troubleshooting Classes
operation. If it is not maintained, it can fail to operate The factory service department offers a basic testing and
properly. Improper operation can cause equipment troubleshooting course for the Form 6 microprocessor-
damage and possible personal injury. G105.1 based recloser control. This course, taught by experi-
enced service technicians, is held at the factory’s in-
house training facility. For additional information, contact
Replacement Kits your Cooper Power Systems representative.
Replacement kits for the Kyle Form 6 recloser controls
are available through the factory Service Department. To Type MET Recloser Control Tester
order these kits, refer to the Replacement Parts price list A 30-minute video cassette program KSPV7 Kyle® Type
S260-01 through S280-01 for catalog numbers and pric- MET Electronic Recloser Control Tester Operation and
ing. Contact your Cooper Power Systems representative Testing Procedures is available as a supplemental train-
for additional information and order procedures. ing aid for service personnel.
Factory-Authorized Service
Centers
Factory-authorized service centers are located through-
out the continental United States to provide mainte-
nance, repair and testing services for Kyle controls and
reclosers. For further information, contact your Cooper
Power Systems representative.
!