NATIONAL ELECTRIFICATION ADMINISTRATION NEA ENGINEERING BULLETIN DX1320 July 1993 SUBJECT: SPECIFICATIONS AND DRAWINGS FOR DISTRIBUTION LINE CONSTRUCTION, 13.2 KV and 24 KV PR PURPOSE: To guide the RECS in the standard design and construction of 13.2 KV and 24 kV distribution lines. General: NEA has revised Specifications and Drawings for 7.6/13.2 kv Line Construction (August 1973), and it has been renamed NEA Engineering Bulletin DX1320, Specifications and Drawings for Distribution Line Construction, 13.2 kV and 24 kV. Changes include the addition of post insulator drawings and the correction of minor errors. Some drawings were revised for conformance with the latest edition of the Philippine Electrical Safety Code. Many of the drawings are available on autoCAD files for use by the REC’s. ‘Specifications for Construction 1. General All construction work shall be done in accordance with the staking sheets, plans and specifications, and the construction drawings. When specifying 24 kV construction use a "V" prefix on all primary units, ie) VCI, to indicate the higher insolation level. The latest edition of the Philippine Electrical Safety Code shall be followed except where local regulations are more stringent, in which case local regulations shall govern. Distribution of Poles In distributing the poles, large, choice, dense poles shall be used at transformer, dead-end, angle, and corner locations. Pole Setting DX1320.1