NATIONAL ELECTRIFICATION ADMINISTRATION
NEA ENGINEERING BULLETIN DX1320 July 1993
SUBJECT: SPECIFICATIONS AND DRAWINGS FOR DISTRIBUTION LINE
CONSTRUCTION, 13.2 KV and 24 KV
PR
PURPOSE:
To guide the RECS in the standard design and construction of 13.2 KV and 24 kV
distribution lines.
General:
NEA has revised Specifications and Drawings for 7.6/13.2 kv Line Construction
(August 1973), and it has been renamed NEA Engineering Bulletin DX1320,
Specifications and Drawings for Distribution Line Construction, 13.2 kV and 24 kV.
Changes include the addition of post insulator drawings and the correction of
minor errors. Some drawings were revised for conformance with the latest edition
of the Philippine Electrical Safety Code. Many of the drawings are available on
autoCAD files for use by the REC’s.
‘Specifications for Construction
1.
General
All construction work shall be done in accordance with the staking sheets, plans
and specifications, and the construction drawings. When specifying 24 kV
construction use a "V" prefix on all primary units, ie) VCI, to indicate the higher
insolation level.
The latest edition of the Philippine Electrical Safety Code shall be followed except
where local regulations are more stringent, in which case local regulations shall
govern.
Distribution of Poles
In distributing the poles, large, choice, dense poles shall be used at transformer,
dead-end, angle, and corner locations.
Pole Setting
DX1320.1