Professional Documents
Culture Documents
Dse4510 20 Mkii Data Sheet
Dse4510 20 Mkii Data Sheet
DSE4510/20 MKII
SPECIFICATIONS
DC SUPPLY
CONTINUOUS VOLTAGE RATING
AUTO START AND AUTO MAINS FAILURE 8 V to 35 V Continuous
CONTROL MODULES
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
(ALTERNATOR FREQUENCY & CAN SPEED SENSING) supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
DSE4510 MKII DSE4520 MKII during cranking.
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
KEY FEATURES • 4 configurable digital inputs • Overload protection at supply voltage
• Auto Start and AMF mode in one • Configurable staged loading • Mains/generator A/C system
module (DSE4520 MKII only) outputs selection OUTPUT B (START)
10 A short term, 5 A continuous,
• J1939-75 support and CAN alarm • 3 engine maintenance alarms • Output timer for external audible at supply voltage
ignore function • Engine speed protection alarm
• Alternator frequency & CAN speed • Engine hours counter • Accommodates a wide range of AUXILIARY OUTPUTS C, D, E & F
sensing in one variant • Engine pre-heat senders and temperatures 2 A DC at supply voltage
• Largest back-lit icon display in its • Engine run-time scheduler GENERATOR
class (configurable as text display) • Engine idle control for starting & KEY BENEFITS VOLTAGE RANGE
• Heated display option stopping • Ultimate size to feature ratio 15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
• Real time clock provides accurate • Tier 4 engine instrumentation • Automatically transfers between
event logging screens mains (utility) and generator FREQUENCY RANGE
• Fully configurable via the fascia or • Battery voltage monitoring (DSE4520 MKII only) 3.5 Hz to 75 Hz
PC using USB communication • Start on low battery voltage • Hours counter provides accurate
DIMENSIONS
• Extremely efficient power save • Configurable remote start input information for monitoring and OVERALL
mode • 1 alternative configuration maintenance periods 140 mm x 113 mm x 43 mm
• 3 phase generator sensing • Comprehensive warning, electrical • User-friendly set-up and button 5.5’’ x 4.4” x 1.7”
• 3 phase mains (utility) sensing trip or shutdown protection upon layout for ease of use PANEL CUT-OUT
(DSE4520 MKII only) fault condition • Multiple parameters are monitored 118 mm x 92 mm
• Compatible with 600 V ph to ph • LCD alarm indication simultaneously which are clearly 4.6’’ x 3.6”
nominal systems • Coolant temperature pre-alarm displayed on the largest back-lit MAXIMUM PANEL THICKNESS
• Generator/load power monitoring • Event log (50) icon display in its class 8 mm
(kW, kV A, kV Ar, pf) • Fuel solenoid pulling circuit • The module can be configured to 0.3”
• Accumulated power monitoring • On-screen line diagram on/off suit a wide range of applications
STORAGE TEMPERATURE RANGE
(kW h, kVA h, kVAr h) functionality • Uses DSE Configuration -40 °C to +85 °C
• Generator overload protection (kW) • Configurable CAN instrumentation Suite PC Software for simplified -40 °F to +185 °F
• Generator/load current monitoring (10) configuration
OPERATING TEMPERATURE RANGE
and protection • Water in fuel digital input • Compatible with a wide range of -30 °C to +70 °C
• Fuel and start outputs (configurable • Tank bund alarm digital input CAN engines including Tier 4 -22 °F to +158 °F
when using CAN) • Generator at rest output • Licence-free PC software
-40 °C to +70 °C (for heated display variant)
• 4 configurable DC outputs • ECU periodic wake-up for • IP65 rating (with optional gasket)
-40 °F to +158 °F (for heated display variant)
• 5 V output information retrieval offers increased resistance to water
• Configurable fuel & crank outputs • Back-light power-save mode ingress
• 3 configurable analogue/digital • Adjustable delay crank timer OPTIONAL PARTS
inputs • Pre/post heat functionality
PART PART NUMBER
IP65 Gasket 020-282
RELATED MATERIALS
TITLE PART NO.
DSE4510/20 MKII Installation Instructions 053-190
DSE4510/20 MKII Operator Manual 057-260
DSE4510/20 MKII Configuration Suite PC Manual 057-258
DSE4510/20 MKII
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
AUTO START AND AUTO MAINS FAILURE EMC Generic Immunity Standard for
the Industrial Environment
CONTROL MODULES
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
Mains (Utility) Failure Control Module sensing) engine support for diesel, 4510-05 Auto Start with real time clock TEMPERATURE
are suitable for a wide variety of single gas and petrol engines all in one BS EN 60068-2-1
gen-set applications. variant. With a number of flexible 4510-06 Auto Start with real time clock & Ab/Ae Cold Test -30 ºC
heated display BS EN 60068-2-2
inputs, outputs and protections, the Bb/Be Dry Heat +70 ºC
Whilst maintaining functions included module can be easily adapted to suit 4520-05 Auto Mains Failure with real time
within higher end controllers, such as a wide range of applications. clock VIBRATION
BS EN 60068-2-6
generator or load power monitoring,
4520-06 Auto Mains Failure with real time Ten sweeps in each of three major axes
the DSE45xx MKII range of especially Through USB Communication both clock & heated display 5 Hz to 8 Hz at +/-7.5 mm,
compact controllers provide the user modules can be easily configured 8 Hz to 500 Hz at 2 gn
with the ultimate size to feature ratio. using the DSE Configuration Suite PC 4520-05 Auto Mains Failure with real time
clock HUMIDITY
Software or can be fully configured BS EN 60068-2-30
Monitoring engine speed, oil pressure, through the module’s front panel 4520-07 Auto Mains Failure with real time Db Damp Heat Cyclic 20/55 ºC
coolant temperature, frequency, editor. clock at 95% RH 48 Hours
BS EN 60068-2-78
voltage, current, power and fuel level, Cab Damp Heat Static 40 ºC
the modules will give comprehensive All DSE products are supported by the at 93% RH 48 Hours
engine and alternator protection. This DSE global technical support team
will be indicated on the largest back-lit which gives our customers and end SHOCK
BS EN 60068-2-27
LCD icon display in its class via an users access to 24 hour system help Three shocks in each of three major axes
array of warning, electrical trip and and advice. 15 gn in 11 mS
shutdown alarms.
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
4 4 3
DEUTZ
DSE4510/20 MKII ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) DC OUTPUT GENERATOR/ DC OUTPUT GENERATOR CHARGE FUEL & START ELECTRONIC
SENSING DSE4520 MKII 1 OF 4 LOAD CURRENT DSE4510 MKII 1 OF 4 SENSING ALTERNATOR OUTPUTS ENGINE CAN
(DSE4520 MKII) DSE4520 MKII 1 OF 4 (Flexible with CAN)
VOLTS VOLTS
D+ +
+ + W/ L
ISSUE 3