You are on page 1of 536

Technical Report

Version 1
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant,
Anantapur, Andhra Pradesh

Project reference 3006880923

Date 2020-09-30

Editor Rohith Varier

Release (techn.) Rohith Varier

Office address Siemens Ltd, SI DG SW PTI


Power Technologies International
Kalwa Works
Thane 400601, India

Restricted © Siemens Ltd, 2020 All rights reserved.

Project Reference: 3006880923 Technical Report siemens.com/power-technologies


Version 1
Siemens Ltd, SI DG SW PTI 2020-09-30 Page 1 of 536
Restricted
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Revision History

Rev. Status / Changes Date Author

Version 1 Technical Report-50MW Solar PV Plant 2020-08-02 Rohith Varier

Version 1 Final Technical Report-50MW Solar PV Plant 2020-08-07 Rohith Varier

Version 1 Final Technical Report-250MW Solar PV Plant 2020-09-30 Rohith Varier

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 2 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Table of Contents
Revision History................................................................................................................ 2

Table of Contents ............................................................................................................. 3

List of Figures ................................................................................................................... 6

List of Tables ..................................................................................................................... 9

1 Introduction ........................................................................................................ 11

2 Steady State Model of 250 MW Solar Park, Anantapur, Andhra Pradesh ...... 12
2.1 Equivalent Grid..................................................................................................... 12
2.2 Overhead Lines and Cables .................................................................................. 13
2.3 Power Transformers ............................................................................................. 14
2.4 Inverter Duty Transformers .................................................................................. 14
2.5 Inverters / Equivalent Generators ......................................................................... 15
2.6 Auxiliary Transformers ......................................................................................... 15

3 Generic Models of Photovoltaic Inverter and Park Controller ........................ 16


3.1 Renewable Energy Generator/Converter Model – REGCA1.................................. 16
3.1.1 REGCA1 – Block Diagram ....................................................................... 16
3.1.2 REGCA1 – Data Sheet............................................................................. 17
3.1.3 REGCA1 – Dynamic Data Record ............................................................ 18
3.2 Electrical Control Model for Large Scale PV – REECB1 ......................................... 19
3.2.1 REECB1 – Block Diagram ........................................................................ 19
3.2.2 REECB1 – Data Sheet ............................................................................. 20
3.2.3 REECB1 – Dynamic Data Record............................................................. 21
3.3 Generic Renewable Plant Control Model – REPCA1 ............................................. 23
3.3.1 REPCA1 – Block Diagram ........................................................................ 23
3.3.2 REPCA1 – Data Sheet ............................................................................. 24
3.3.3 REPCA1 – Dynamic Data Record ............................................................ 25
3.4 Active and Reactive Power Philosophy................................................................. 27
3.4.1 Manual Control ...................................................................................... 27
3.4.2 Automatic Control.................................................................................. 28

4 Detailed and Equivalent PSS®E Model ............................................................. 29


4.1 Detailed PSS®E Model of 250MW Solar Park ........................................................ 29
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 3 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

4.2 Equivalent PSS®E Model of 250MW Solar Park .................................................... 31

5 Power Flow Analysis .......................................................................................... 32


5.1 Normal Operating Scenario.................................................................................. 32
5.2 Night Load Operating Scenario ............................................................................ 33
5.3 Operating Scenario with grid voltage=1.1 p.u..................................................... 33
5.4 Operating Scenario with grid voltage=0.9 p.u..................................................... 34

6 Short Circuit Analysis ......................................................................................... 35


6.1 Short Circuit Study Methodology ......................................................................... 35
6.2 Short Circuit Study Results ................................................................................... 36

7 Reactive Power Analysis .................................................................................... 37


7.1 Grid Code Requirement ........................................................................................ 37
7.2 Study Approach .................................................................................................... 37
7.3 PQ Capability Curve plot of Inverter ..................................................................... 38
7.4 PQ Reactive Capability Curve plot of Solar Farm at PCC (220kV) ......................... 40
7.5 Conclusion ........................................................................................................... 42

8 Harmonic Analysis.............................................................................................. 43
8.1 Effect of harmonics on power system equipment ............................................... 43
8.2 Harmonic current and voltage limits for power system equipment as per IEEE519-
2014 standard ...................................................................................................... 45
8.2.1 Permissible Voltage Distortion Limits as per IEEE 519-2014 ................. 45
8.2.2 Permissible Current Distortion Limits as per IEEE 519-2014.................. 46
8.3 Harmonic Scenario in 250MW Solar Power Plant, Anantapur, Andhra Pradesh .. 47
8.3.1 Harmonic Model of Sungrow Solar Inverter SG3125HV-20................... 47
8.4 Results of Harmonic Analysis ............................................................................... 49
8.4.1 Total Harmonic Distortion and Individual Harmonics ............................ 50
8.4.2 Plot of Impedance vs Frequency Characteristics .................................... 64
8.5 Observations of Harmonic Analysis ..................................................................... 78
8.6 Recommendations of Harmonic Analysis............................................................. 78

9 Dynamic Stability Analysis ................................................................................ 79


9.1 Voltage Ride Through (VRT) ................................................................................. 79
9.1.1 Low Voltage Ride Through (LVRT) (Integration Time Step: 1 msec, total
time: 40 sec) .......................................................................................... 79
9.1.1.1 Results at the Point of Interconnection (POI) ........................ 80
9.1.1.2 Results at the Inverter Bus ..................................................... 82
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 4 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.1.2 High Voltage Ride Through (HVRT) (Integration Time Step: 1 msec, total
time: 40 sec) .......................................................................................... 84
9.1.2.1 Results at the Point of Interconnection (POI) ........................ 84
9.1.2.2 Results at the Inverter Bus ..................................................... 86
9.2 Frequency Ride Through ...................................................................................... 88
9.2.1 Over Frequency Ride Through (Integration Time Step: 1 msec, Total
Time:40 sec) .......................................................................................... 88
9.2.1.1 Results at the Point of Interconnection (POI) ........................ 88
9.2.1.2 Results at the Inverter Bus ..................................................... 90
9.2.2 Under Frequency Ride Through (Integration Time Step: 1 msec, total
time: 40 sec) .......................................................................................... 92
9.2.2.1 Results at the Point of Interconnection (POI) ........................ 92
9.2.2.2 Results at the Inverter Bus ..................................................... 94
9.3 Response to change in Grid Voltage .................................................................... 96
9.3.1 Results at the Point of Interconnection (POI)......................................... 96
9.3.2 Results at the Inverter Bus ..................................................................... 98

10 Conclusion ........................................................................................................ 100

11 Annexures ......................................................................................................... 101


11.1 Normal Operating Scenario- Active Power and Reactive Power Flow Results.... 101
11.2 Night Load Operating Scenario- Active Power and Reactive Power Flow Results
........................................................................................................................... 179
11.3 Grid voltage=1.1 p.u- Active Power and Reactive Power Flow Results .............. 257
11.4 Grid voltage=0.9 p.u- Active Power and Reactive Power Flow Results .............. 335
11.5 Short Circuit Study Results ................................................................................. 413

12 Literature & References ................................................................................... 536

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 5 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

List of Figures
Figure 3-1 Block Diagram of Renewable Generator/Converter Model REGCA1 ............... 16
Figure 3-2 Block Diagram of Electrical Control Model REECB1 for Large Scale PV........... 19
Figure 3-3 Block Diagram of Generic Renewable Plant Control Model REPCA1............... 23
Figure 3-4 Dynamic data and DYR record for an equivalent aggregated generator in
manual control................................................................................ 27
Figure 3-5 Dynamic data and DYR record for an equivalent aggregated generator in
automatic control ........................................................................... 28
Figure 4-1 Detailed Model of the 250MW Solar PV Model in PSS®E 34.6 version ........... 30
Figure 4-2 Equivalent Model of the 250MW Solar PV Model in PSS®E 34.6 version ....... 31
Figure 7-1 PQ Capability Diagram of SG3125HV-20 Inverter .......................................... 38
Figure 7-2 Reactive power capability of Solar park at POC .............................................. 41
Figure 8-1 Graphical Representation of Sungrow SG3125HV-20 Solar Inverter Harmonic
Model in terms of % of fundamental current ................................. 49
Figure 8-2: % Total Harmonic Distortion and % Individual Harmonics at 220kV PGCIL
Substation ....................................................................................... 51
Figure 8-3: % Total Harmonic Distortion and % Individual Harmonics at 220kV Ayana
Pooling Substation .......................................................................... 52
Figure 8-4: % Total Harmonic Distortion and % Individual Harmonics at 33kV Main HT
Panel ............................................................................................... 53
Figure 8-5: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-
1 ...................................................................................................... 54
Figure 8-6: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-
2 ...................................................................................................... 55
Figure 8-7: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-
3 ...................................................................................................... 56
Figure 8-8: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-
4 ...................................................................................................... 57
Figure 8-9: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-
5 ...................................................................................................... 58
Figure 8-10: % Total Harmonic Distortion and % Individual Harmonics at 220kV side of
Power Transformer ......................................................................... 59
Figure 8-11: % Total Harmonic Distortion and % Individual Harmonics at 33kV side of
Power Transformer ......................................................................... 60
Figure 8-12: % Total Harmonic Distortion and % Individual Harmonics at 33kV side of
Inverter Duty Transformer .............................................................. 61

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 6 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 8-13: % Total Harmonic Distortion and % Individual Harmonics at 0.6kV side of
Inverter Duty Transformer .............................................................. 62
Figure 8-14: % Total Harmonic Distortion and % Individual Harmonics at 0.6kV side of
Inverter Terminal Block ................................................................... 63
Figure 8-15: Impedance vs Frequency characteristics at 220kV PGCIL substation .......... 65
Figure 8-16: Impedance vs Frequency characteristics at 220kV Ayana Pooling substation
........................................................................................................ 66
Figure 8-17: Impedance vs Frequency characteristics at 33kV Main HT Panel ................ 67
Figure 8-18: Impedance vs Frequency characteristics at 33kV 50MW Block-1................ 68
Figure 8-19: Impedance vs Frequency characteristics at 33kV 50MW Block-2................ 69
Figure 8-20: Impedance vs Frequency characteristics at 33kV 50MW Block-3................ 70
Figure 8-21: Impedance vs Frequency characteristics at 33kV 50MW Block-4................ 71
Figure 8-22: Impedance vs Frequency characteristics at 33kV 50MW Block-5................ 72
Figure 8-23: Impedance vs Frequency characteristics at 220kV side of Power Transformer
........................................................................................................ 73
Figure 8-24: Impedance vs Frequency characteristics at 33kV side of Power Transformer
........................................................................................................ 74
Figure 8-25: Impedance vs Frequency characteristics at 33kV side of Inverter Duty
Transformer .................................................................................... 75
Figure 8-26: Impedance vs Frequency characteristics at 0.6kV side of Inverter Duty
Transformer .................................................................................... 76
Figure 8-27: Impedance vs Frequency characteristics at 0.6kV side of Inverter Terminal
Block................................................................................................ 77
Figure 9-1 Low Voltage Ride Through at POI (Simulation Time 40 sec, Integration time
step:1msec) .................................................................................... 81
Figure 9-2 Low Voltage Ride Through at Inverter (Simulation Time 40 sec, Integration
time step:1msec) ............................................................................ 83
Figure 9-3 High Voltage Ride Through at POI (Simulation Time 40 sec, Integration time
step:1msec) .................................................................................... 85
Figure 9-4 High Voltage Ride Through at Inverter (Simulation Time 40 sec, Integration
time step:1msec) ............................................................................ 87
Figure 9-5 Over Frequency Ride Through at POI (Simulation Time 40 sec, Integration time
step:1msec) .................................................................................... 89
Figure 9-6 Over Frequency Ride Through at Inverter (Simulation Time 40 sec, Integration
time step:1msec) ............................................................................ 91
Figure 9-7 Under Frequency Ride Through at POI (Simulation Time 40 sec, Integration
time step:1msec) ............................................................................ 93
Figure 9-8 Under Frequency Ride Through at Inverter (Simulation Time 40 sec, Integration
time step:1msec) ............................................................................ 95
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 7 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-9 Response to change in Grid Voltage at POI (Simulation Time 50 sec, Integration
time step:1msec) ............................................................................ 97
Figure 9-10 Response to change in Grid Voltage at Inverter (Simulation Time 50 sec,
Integration time step:1msec) ......................................................... 99

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 8 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

List of Tables
Table 2-1 Parameters of Equivalent Grid ......................................................................... 12
Table 2-2 Parameters of the Overhead line (220kV ACSR Moose Conductor) ................. 13
Table 2-3 Parameters of the Cables (Cross-Section: 33kV, 1Cx 400 mm²) ...................... 13
Table 2-4 Parameters of the Cables (Cross-Section: 33kV, 3C x 400 mm²) ..................... 13
Table 2-5 Parameters of the Cables (Cross-Section: 1.9/3.3kV, 1C x 400 mm²) .............. 13
Table 2-6 Parameters of Power Transformers .................................................................. 14
Table 2-7 Parameters of Inverter Duty Transformers ....................................................... 14
Table 2-8 Parameters of Aggregated Generators for inverter blocks .............................. 15
Table 2-9: Parameters of Auxiliary Transformers ............................................................. 15
Table 3-1 ICONs of Renewable Generator/Converter Model REGCA1 .............................. 17
Table 3-2 CONs of Renewable Generator/Converter Model REGCA1............................... 17
Table 3-3 STATEs of Renewable Generator/Converter Model REGCA1 ............................ 17
Table 3-4 VARs of Renewable Generator/Converter Model REGCA1................................ 17
Table 3-5 ICONs of Electrical Control Model REECB1 for Large Scale PV ......................... 20
Table 3-6 CONs of Electrical Control Model REECB1 for Large Scale PV .......................... 20
Table 3-7 STATEs of Electrical Control Model REECB1 for Large Scale PV ........................ 21
Table 3-8 VARs of Electrical Control Model REECB1 for Large Scale PV ........................... 21
Table 3-9 ICONs of Generic Renewable Plant Control Model REPCA1 ............................. 24
Table 3-10 CONs of Generic Renewable Plant Control Model REPCA1 ............................ 24
Table 3-11 STATEs of Generic Renewable Plant Control Model REPCA1.......................... 25
Table 3-12 VARs of Generic Renewable Plant Control Model REPCA1 ............................. 25
Table 4-1 Relevant Bus Numbers in detailed PSS®E Model.............................................. 29
Table 4-2 Relevant Bus Numbers in equivalent PSS®E Model.......................................... 31
Table 6-1 Parameters of 220kV Equivalent Grid .............................................................. 35
Table 6-2 IEC 60909 pre-fault voltage factors ................................................................. 36
Table 6-3 Switchgear Short Time Rating.......................................................................... 36
Table 7-1 Operation points of the Inverter for the study- 1 p.u. and 1.1 p.u. ................. 39
Table 7-2 Operation points of the Inverter for the study-0.9 p.u. ................................... 39
Table 7-3 Reactive Power Analysis for Grid Voltage=0.9 p.u. .......................................... 40
Table 7-4 Reactive Power Analysis for Grid Voltage=1 p.u. ............................................. 40
Table 7-5 Reactive Power Analysis for Grid Voltage=1.1 p.u. .......................................... 41

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 9 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Table 8-1 IEEE 519-2014 Voltage distortion limits (THDV) (%) ....................................... 45
Table 8-2 IEEE 519-2014 Current distortion limits for systems rated above 120 V through
69 kV ............................................................................................... 46
Table 8-3 IEEE 519-2014 Current distortion limits for systems rated above 69 kV through
161 kV ............................................................................................. 46
Table 8-4 SUN2000-95KTL Huawei Solar Inverter Model in terms of % of fundamental
current ............................................................................................ 47

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 10 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

1 Introduction
POSOCO has released a guideline document in the year 2019 which mandates the requirement
of accurate modelling of utility scale solar generation installations in India. According to the
guideline document, steady state and dynamic modeling of large-scale grid integrated solar
parks will need to be developed in detail. The solar park model will be integrated to the grid at
a point defined as point of interconnection. Once the model is integrated, various simulation
studies can be performed to study its impact on the power system operation.
Ayana Renewable Power Private Limited has requested Siemens PTI to implement generic mod-
els of photovoltaic inverters and park controllers for their upcoming 250MW solar park in
Anantapur, Andhra Pradesh, India.
This report provides a description of the generic models for renewable energy generator/con-
verter, electrical control and plant control, which may be used for RMS simulations. The follow-
ing chapters provide details including block diagrams and a parameter description necessary
for use.
This report mainly focusses on the procedure adopted for building the steady state and dynamic
models of 250MW Solar PV Plant to be commissioned in the final stage.
Based on these network models, grid compliance studies according to CEA 2019 Guidelines are
performed to determine the impact of this Solar Park at 220kV point of interconnection.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 11 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

2 Steady State Model of 250 MW Solar


Park, Anantapur, Andhra Pradesh
This section describes about the steady state model of Ayana Power’s upcoming project of
250MW Solar PV Project to be evacuated at Anantapur, Andhra Pradesh.
The point of interconnection, which is also the park controller measurement point, is at the
220kV voltage level which would be the point of interest when the final aggregated equiva-
lent model would be integrated with 400kV/220kV PGCIL substation located by N.P. Kunta.

For the detailed model, the equivalent PV generators are connected at 0.6kV voltage level.
The three-winding inverter duty transformers are considered for connection to the 33kV volt-
age level. The parameters of single components are listed in the following sections.

2.1 Equivalent Grid


The parameters of the equivalent grid as per the aggregated model are listed in Table 2-1.

Table 2-1 Parameters of Equivalent Grid

Parameter Symbol Value Unit


Short-circuit power Sk” 5100*) MVA
Short-circuit current I k” 13.38 kA
Rated voltage Vr 220 kV
Rated frequency f 50 Hz
R/X ratio R/X 0.1*) -
Voltage factor (maximum) cmax 1.10 -
Voltage factor (minimum) cmin 1.00 -
*) Assumption

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 12 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

2.2 Overhead Lines and Cables


The parameters of different cables based on cross sectional size can be found from Table 2-2
to Table 2-5.

Table 2-2 Parameters of the Overhead line (220kV ACSR Moose Conductor)

Parameter Symbol Value Unit


220kV, ACSR Moose S/C Line *)
Resistance r 1.547E-4 Ω/km
Reactance x 8.249E-4 Ω/km
Capacitance c 1.42E-3 μF/km
*) Reference: CEA Transmission Planning Criteria-2013

Table 2-3 Parameters of the Cables (Cross-Section: 33kV, 1Cx 400 mm²)

Parameter Symbol Value Unit


33kV, 1Cx400 mm²
Resistance r 0.101 Ω/km
Reactance x 0.113 Ω/km
Capacitance c 0.250 μF/km

Table 2-4 Parameters of the Cables (Cross-Section: 33kV, 3C x 400 mm²)

Parameter Symbol Value Unit


33kV, 3Cx400 mm²
Resistance r 0.1 Ω/km
Reactance x 0.1 Ω/km
Capacitance c 0.23 μF/km

Table 2-5 Parameters of the Cables (Cross-Section: 1.9/3.3kV, 1C x 400 mm²)

Parameter Symbol Value Unit


1.9/3.3kV, 1C x 400 mm²
Resistance r 0.102 Ω/km
Reactance x 0.0824 Ω/km
Capacitance c 0.78 μF/km

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 13 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

2.3 Power Transformers


The parameters of the power transformers are given in Table 2-6.

Table 2-6 Parameters of Power Transformers

Parameter Symbol Value Unit


Rated power Sr 80 MVA
HV winding VHV 220
Rated voltage kV
LV winding VLV 33
Short-circuit impedance (@ 80 MVA base) uk,HVLV 11.9095 %
Short-circuit impedance, resistive part
ur,HVLV 0.1593
(@ 80 MVA base)
Vector group - YNyn0 -

2.4 Inverter Duty Transformers


The parameters of the inverter duty transformers are given in Table 2-7.

Table 2-7 Parameters of Inverter Duty Transformers

Parameter Symbol Value Unit


6.25
Rated power Sr MVA
(3.125-3.125)
HV winding VHV 33
Rated voltage kV
LV winding VLV 0.6
Short-circuit impedance (@ 3.125 MVA uk,HVLV 7
%
base) uk,LVLV 12
Short-circuit impedance, resistive part ur,HVLV 0.9
%
(@ 3.125 MVA base) ur,LVLV 0*)
Vector group - YN0d11d11 -
*) Assumption

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 14 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

2.5 Inverters / Equivalent Generators


The inverters are represented as aggregated generators based on the number of inverter blocks
listed in Table 2-8.

Table 2-8 Parameters of Aggregated Generators for inverter blocks

Parameter Symbol Value Unit


Machine base Mbase 3.125 MVA
Rated voltage Vr 0.6 kV
Active power PGen 3.125 MW
Qmax 1.8
Reactive power Mvar
Qmin -1.8
Rsource 1000
Source impedance pu
Xsource 1000
Renewable:
Machine control mode - Standard QT, -
QB Limits

2.6 Auxiliary Transformers


The parameters of the auxiliary transformers are given in Table 2-9.
Table 2-9: Parameters of Auxiliary Transformers

Parameter Symbol Value Unit


Rated power Sr 15 kVA
HV winding VHV 0.6
Rated voltage kV
LV winding VLV 0.415
Short-circuit impedance (@ 15 kVA base) uk,HVLV 4.5 %
Vector group - YNyn0 -
Maximum Loading 8 kW
Power Factor 0.95

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 15 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3 Generic Models of Photovoltaic


Inverter and Park Controller
The following models were considered to model the photovoltaic inverters and the park con-
troller.
• REGCA1: Renewable energy generator/converter model
• REECB1: Electrical control model for large scale PV
• REPCA1: Generic renewable plant control model
The above models were taken from the PSS®E 34.6 library.
The models may be used with an integration time step between 1 ms and 20 ms. However, the
highest accuracy is achieved with an integration time step which is lower than the smallest
time constant. In this case, the smallest time constant is 6 ms (as defined in the user-defined
inverter model HWH954501, which is suitable for a balanced RMS simulation with an integra-
tion time step between 1 and 5 ms [1]). Hence, an integration time step of 1 ms is recom-
mended for the generic models.

3.1 Renewable Energy Generator/Converter Model – REGCA1


The renewable energy generator/converter is based on the PSS®E standard library model
REGCA1. This model represents a generic generator/converter.

3.1.1 REGCA1 – Block Diagram


The block diagram of the model REGCA1 is shown in Figure 3-1.

Figure 3-1 Block Diagram of Renewable Generator/Converter Model REGCA1


Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 16 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.1.2 REGCA1 – Data Sheet


The model uses the parameters given in Table 3-1 and Table 3-2. The states and variables of
the model are described in Table 3-3 and Table 3-4.

Table 3-1 ICONs of Renewable Generator/Converter Model REGCA1

ICONS Value Description


Lvplsw (Low Voltage Power Logic) switch
M 0 0: LVPL not present
1: LVPL present

Table 3-2 CONs of Renewable Generator/Converter Model REGCA1

CONs Value Description


J 0.0200 Tg, Converter time constant (s)
J+1 1.0000 Rrpwr, Low Voltage Power Logic (LVPL) ramp rate limit (pu/s)
J+2 0.8000 Brkpt, LVPL characteristic voltage 2 (pu)
J+3 0.0000 Zerox, LVPL characteristic voltage 1 (pu)
J+4 0.1077 Lvpl1, LVPL gain (pu)
1.3000 Volim, Voltage limit (pu) for high voltage reactive current manage-
J+5
ment
0.8000 Lvpnt1, High voltage point for low voltage active current manage-
J+6
ment (pu)
0.4000 Lvpnt0, Low voltage point for low voltage active current manage-
J+7
ment (pu)
-1.7000 Iolim, Current limit (pu) for high voltage reactive current manage-
J+8
ment (specified as a negative value)
0.0200 Tfltr, Voltage filter time constant for low voltage active current man-
J+9
agement (s)
0.0000 Khv, Overvoltage compensation gain used in the high voltage reac-
J+10
tive current management
J+11 999.0000 Iqrmax, Upper limit on rate of change for reactive current (pu)
J+12 -999.0000 Iqrmin, Lower limit on rate of change for reactive current (pu)
J+13 1.0000 Accel, Acceleration factor (0 < Accel <= 1)

Table 3-3 STATEs of Renewable Generator/Converter Model REGCA1

STATEs Description
K Converter lag for Ipcmd
K+1 Converter lag for Iqcmd
K+2 Voltage filter for low voltage active current management

Table 3-4 VARs of Renewable Generator/Converter Model REGCA1

VARs Description
L Previous terminal voltage
L+1 Previous terminal voltage angle
L+2 Reactive current overvoltage correction
L+3 Initial machine reactive power from power flow

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 17 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.1.3 REGCA1 – Dynamic Data Record


The dynamic data record of the model REGCA1 is entered the following way:
IBUS, ‘REGCA1’, ID, ICON(M), CON(J) to CON(J+13) /
in which
• IBUS: Number of connection bus
• ‘REGCA1’: Name of the generic model
• ID: Generator identifier
• ICON(M): Model constants (integer)
• CON(J) to CON(J+13): Model constants (real)

An exemplary DYR record for the model REGCA1 is shown below for the equivalent aggregated
generator connected to bus 6:

NOTES:
1. The other models to be used along with this model are reeca1 or reecb1 and repca1
(optional).

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 18 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.2 Electrical Control Model for Large Scale PV – REECB1


The electrical control of the solar park is based on the PSS®E standard library model REECB1 for
large scale PV. This model represents the generic electrical control of renewable generators.
The model supports power factor control, voltage control or reactive power control (which can
be controlled by an external signal). These controls can be configured in the ICON settings (see
Table 3-5).

3.2.1 REECB1 – Block Diagram


The block diagram of the model REECB1 is shown in Figure 3-2.

Figure 3-2 Block Diagram of Electrical Control Model REECB1 for Large Scale PV

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 19 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.2.2 REECB1 – Data Sheet


The model uses the parameters given in Table 3-5 and Table 3-6. The states and variables of
the model are described in Table 3-7 and Table 3-8.

Table 3-5 ICONs of Electrical Control Model REECB1 for Large Scale PV

ICONS Value Description


Bus number for voltage control; local control if 0
M 0
For remote bus control use the plant controller model.
PFFLAG (Power factor control flag)
M+1 0 1: power factor control
0: Q control (can be controlled by an external signal)
VFLAG
M+2 0 1: Q control
0: voltage control
QFLAG
M+3 0 1: voltage or Q control
0: constant PF or Q control
PQFLAG (P/Q priority for current limit)
M+4 0 1: P priority
0: Q priority

Table 3-6 CONs of Electrical Control Model REECB1 for Large Scale PV

CONs Value Description


0.8000 Vdip (pu), Low voltage threshold to activate reactive current injec-
J
tion logic
2.0000 Vup (pu), Voltage above which reactive current injection logic is
J+1 activated
J+2 0.0060 Trv (s), Voltage filter time constant
J+3 -0.0100 dbd1 (pu), Voltage error dead band lower threshold (≤0)
J+4 0.0100 dbd2 (pu), Voltage error dead band upper threshold (≥0)
1.4100 Kqv (pu), Reactive current injection gain during over and un-
J+5
dervoltage conditions
J+6 1.7000 Iqh1 (pu), Upper limit on reactive current injection Iqinj
J+7 -1.7000 Iql1 (pu), Lower limit on reactive current injection Iqinj
0.0000 Vref0 (pu), User defined reference (if 0, model initializes it to ini-
J+8 tial terminal voltage)
J+9 0.0060 Tp (s), Filter time constant for electrical power
J+10 0.6340 QMax (pu), Limit for reactive power regulator
J+11 -0.6340 QMin (pu), Limit for reactive power regulator
J+12 1.2000 VMAX (pu), Max. limit for voltage control
J+13 0.5000 VMIN (pu), Min. limit for voltage control
J+14 1.0000 Kqp (pu), Reactive power regulator proportional gain
J+15 5.0000 Kqi (pu), Reactive power regulator integral gain
J+16 0.2000 Kvp (pu), Voltage regulator proportional gain
J+17 5.0000 Kvi (pu), Voltage regulator integral gain
J+18 0.0200 Tiq (s), Time constant on delay s4
J+19 1.3210 dPmax (pu/s) (>0) Power reference max. ramp rate
J+20 -1.3210 dPmin (pu/s) (<0) Power reference min. ramp rate
J+21 1.0570 PMAX (pu), Max. power limit
J+22 0.0000 PMIN (pu), Min. power limit
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 20 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

J+23 1.0680 Imax (pu), Maximum limit on total converter current


J+24 0.0060 Tpord (s), Power filter time constant

Table 3-7 STATEs of Electrical Control Model REECB1 for Large Scale PV

STATEs Description
K Voltage measurement filter
K+1 Real power filter
K+2 PI controller for reactive power
K+3 PI controller for voltage error
K+4 First order lag for reactive current
K+5 First order lag for Pord

Table 3-8 VARs of Electrical Control Model REECB1 for Large Scale PV

VARs Description
L Bus reference voltage (Vref0)
L+1 Power factor reference angle (pfaref), radians
L+2 Real current command (Ipcmd)
L+3 Reactive current command (Iqcmd)

3.2.3 REECB1 – Dynamic Data Record


The dynamic data record of the model REECB1 is entered the following way:
IBUS, ‘REECB1’, ID, ICON(M) to ICON(M+4), CON(J) to CON(J+24) /
in which
• IBUS: Number of connection bus
• ‘REECB1’: Name of the generic model
• ID: Generator identifier
• ICON(M) to ICON(M+4): Model constants (integer)
• CON(J) to CON(J+24): Model constants (real)

An exemplary DYR record for the model REECB1 is shown below for the equivalent aggregated
generator connected to bus 6:

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 21 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

NOTES:
1. pfaref (the power factor angle reference) value is initialized by the model based on ini-
tial real and reactive power outputs from the machine.
2. Qref is initialized by the model to a constant or can be connected to an external plant
controller model.
3. Pref is initialized by the model to a constant or can be connected to an external plant
controller model.
4. ICON(M) contains the remote bus number. If this is 0 or if the remote bus number is not
specified, then the local bus is used for control.
5. In using REECB1 to model large scale PV, the other models to be used along with this
model are REGCA1 and REPCA1 (optional).

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 22 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.3 Generic Renewable Plant Control Model – REPCA1


The plant controller of the solar park is based on the PSS®E standard library model REPCA1. This
model represents the generic control of a renewable plant.
The model supports voltage control or reactive power control (Q control) or power factor con-
trol (PF control) as reactive power control strategy, and frequency control as active power con-
trol strategy. These controls can be configured in the ICON settings (see Table 3-9).

3.3.1 REPCA1 – Block Diagram


The block diagram of the model REPCA1 is shown in Figure 3-3.

Figure 3-3 Block Diagram of Generic Renewable Plant Control Model REPCA1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 23 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.3.2 REPCA1 – Data Sheet


The model uses the parameters given in Table 3-9 and Table 3-10. The states and variables of
the model are described in Table 3-11 and Table 3-12.

Table 3-9 ICONs of Generic Renewable Plant Control Model REPCA1

ICONS Value Description


M 1 Bus number for voltage control; local control if 0
Monitored branch FROM bus number for line drop compensation
M+1 0
(if 0 generator power will be used)
Monitored branch TO bus number for line drop compensation
M+2 0
(if 0 generator power will be used)
Branch circuit id for line drop compensation (enter in single quotes)
M+3 '0'
(if 0 generator power will be used)
VCFlag (droop flag)
M+4 1 1: line drop compensation
0: with droop
RefFlag (flag for V or Q control)
M+5 1 1: V control
0: Q control
Fflag (flag to disable active power control)
1: enable active power control
M+6 1
(set Ddn and Dup to 0 to disable frequency control)
0: disable active power control

Table 3-10 CONs of Generic Renewable Plant Control Model REPCA1

CONs Value Description


J 0.0200 Tfltr, Voltage or reactive power measurement filter time constant (s)
J+1 0.5000 Kp, Reactive power PI control proportional gain (pu)
J+2 0.0050 Ki, Reactive power PI control integral gain (pu)
J+3 0.0000 Tft, Lead time constant (s)
J+4 0.2000 Tfv, Lag time constant (s)
J+5 0.7000 Vfrz, Voltage below which State s2 is frozen (pu)
J+6 0.0000 Rc, Line drop compensation resistance (pu)
J+7 0.0000 Xc, Line drop compensation reactance (pu)
J+8 0.0500 Kc, Reactive current compensation gain (pu)
J+9 0.5000 emax, Upper limit on deadband output (pu)
J+10 -0.5000 emin, Lower limit on deadband output (pu)
J+11 0.0000 dbd1, Lower threshold for reactive power control deadband (<=0)
J+12 0.0000 dbd2, Upper threshold for reactive power control deadband (>=0)
J+13 0.6340 Qmax, Upper limit on output of V/Q control (pu)
J+14 -0.6340 Qmin, Lower limit on output of V/Q control (pu)
J+15 0.7000 Kpg, Proportional gain for power control (pu)
J+16 10.0000 Kig, Proportional gain for power control (pu)
J+17 0.0200 Tp, Real power measurement filter time constant (s)
J+18 -0.0006 fdbd1, Deadband for frequency control, lower threshold (<=0)
J+19 0.0006 fdbd2, Deadband for frequency control, upper threshold (>=0)
J+20 999.0000 femax, Frequency error upper limit (pu)
J+21 -999.0000 femin, Frequency error lower limit (pu)
J+22 1.0570 Pmax, Upper limit on power reference (pu)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 24 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

J+23 0.0000 Pmin, Lower limit on power reference (pu)


J+24 0.0200 Tg, Power Controller lag time constant (s)
J+25 0.0400 Ddn, Droop for over-frequency conditions (pu)
J+26 0.0400 Dup, Droop for under-frequency conditions (pu)

Table 3-11 STATEs of Generic Renewable Plant Control Model REPCA1

STATEs Description
K Voltage measurement filter
K+1 Reactive power control filter
K+2 PI controller for reactive power
K+3 Lead-lag in reactive power path
K+4 Real power filter
K+5 PI controller for real power
K+6 Power controller for first order lag

Table 3-12 VARs of Generic Renewable Plant Control Model REPCA1

VARs Description
L Reference for voltage control (Vref)
L+1 Reactive power reference (Qref)
L+2 Frequency reference (Freq_ref)
L+3 Active power reference (Plant_ref)
L+4 Line flow P MW
L+5 Line flow Q Mvar
L+6 Line flow MVA
L+7 Q/V deadband output
L+8 Frequency deadband output

3.3.3 REPCA1 – Dynamic Data Record


The dynamic data record of the model REPCA1 is entered the following way:
IBUS, ‘REPCA1’, ID, ICON(M) to ICON(M+6), CON(J) to CON(J+26) /
in which
• IBUS: Number of connection bus
• ‘REPCA1’: Name of the generic model
• ID: Generator identifier
• ICON(M) to ICON(M+6): Model constants (integer)
• CON(J) to CON(J+26): Model constants (real)

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 25 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

An exemplary DYR record for the model REPCA1 is shown below for the equivalent aggregated
generator connected to bus 6:

NOTES:
1. The other models to be used along with this model are regca1 and reeca1 or reecb1.
2. The output (Pref) of the REPCA1 model goes as an input into the electrical control model
(reeca1).
3. If ICON (M+1) is zero, then the generator active and reactive powers are used for line -
drop compensation calculation.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 26 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.4 Active and Reactive Power Philosophy


This section describes about the philosophy for implementing the plant control model in the
dynamic data of the concerned generators.

3.4.1 Manual Control


Figure 3-4 shows the dynamic data and DYR record for a renewable machine in manual control.
For a machine in manual control, only the models REGCA1 and REECB1 are considered. REPCA1
will not be implemented in manual control mode.

Figure 3-4 Dynamic data and DYR record for an equivalent aggregated generator in manual control

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 27 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

3.4.2 Automatic Control


The objective of this project is to implement automatic control instead of manual control mode.
Figure 3-5 shows the dynamic record for a renewable machine in automatic control mode. For
a machine in automatic control the models REGCA1, REECB1 and REPCA1 are implemented.

Figure 3-5 Dynamic data and DYR record for an equivalent aggregated generator in automatic control

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 28 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

4 Detailed and Equivalent PSS®E Model


This section provides an overview of the detailed and equivalent PSS®E model of 250MW solar
park, Anantapur, Andhra Pradesh.

4.1 Detailed PSS®E Model of 250MW Solar Park


Figure 4-1 gives an overview of the detailed model of the solar park as implemented in PSS®E
34.6. Table 4-1 lists the relevant bus numbers.

Table 4-1 Relevant Bus Numbers in detailed PSS®E Model

Description Bus Number

Point of Interconnection (POI) 1


250 MW Network

Description Bus Number

INV1_IDT1_16 38
INV2_IDT1_16 39
INV1_IDT2_16 40
INV2_IDT2_16 41
INV1_IDT1_17 42
INV2_IDT1_17 43
INV1_IDT2_17 44
Equivalent INV2_IDT2_17 45
Generators INV1_IDT1_18 46
INV2_IDT1_18 47
INV1_IDT2_18 48
INV2_IDT2_18 49
INV1_IDT1_19 50
INV2_IDT1_19 51
INV1_IDT2_19 52
INV2_IDT2_19 53

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 29 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 4-1 Detailed Model of the 250MW Solar PV Model in PSS®E 34.6 version

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 30 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

4.2 Equivalent PSS®E Model of 250MW Solar Park


Figure 4-2 gives an overview of the equivalent model of the solar park as implemented in PSS®E
34.6. Table 4-2 lists the relevant bus numbers.

Table 4-2 Relevant Bus Numbers in equivalent PSS®E Model

Description Bus Number

220kV PGCIL Point of Interconnection (POI) 1

220kV Ayana Power Pooling Station 2


220kV Main Bus 3
33kV Main Bus 4
33kV Pooling Bus 5
0.6kV Inverter Bus 6

Figure 4-2 Equivalent Model of the 250MW Solar PV Model in PSS®E 34.6 version

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 31 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

5 Power Flow Analysis


Power Flow Analysis is one of the most common computational procedures used for under-
standing the steady state characteristics of power system. A power flow calculation determines
the state of the power system for a given load and generation distribution. The operation of
power systems requires such calculations to analyze the steady-state performance of the power
system under various operating conditions and to study the effects of changes in equipment
configuration. The power flow studies are used to determine the component or circuit loadings,
steady-state bus voltages, Reactive power flows, Transformer tap settings, system losses & per-
formance under emergency conditions. The power flow model is also the basis for several other
types of studies such as short-circuit and dynamic stability studies. The power flow model sup-
plies the network data and an initial steady-state condition for these studies. The output of
study determines the voltage, current, active, reactive power and power factor in a power sys-
tem. These studies will alert the user to the conditions that may cause overloads or poor voltage
levels.

5.1 Normal Operating Scenario


Normal operating scenario is defined as the power system operation for which solar park is
generating 250MW at full potential of its rated capacity. The solar inverters will be operating in
inverter control mode set at Renewable: Standard QT, QB limits.
The snapshot of power flow results obtained for equivalent model and detailed model is indi-
cated below:
SWING BUS SUMMARY:
BUS#-SCT X-- NAME --X BASKV PGEN PMAX PMIN QGEN QMAX QMIN
1 220KVPGCILSS220.00 -243.6 999.0 -999.0 53.4 999.0 -999.0
At the 220kV point of interconnection which is referred to as swing bus, it is observed that out
of 250MW solar power generation, around 243.6MW (PGEN) of power is exported and remain-
ing portion accounts for the total I^2 losses and auxiliary transformer loading.
QGEN=53.4MVAr which indicates a reactive power requirement of 53.4MVAr in the solar farm
which accounts for the inductive properties associated with transformers, lines and auxiliary
loads operating at 0.85 lagging power factor.
The comparison of equivalent model is performed with the detailed model for power flow re-
sults consisting of MW, MVAr, MVA, Losses MW, Losses MVAr in each feeder of the network
along with the voltage (in kV). These results are provided in Annexures 11.1: Normal Operating
Scenario- Active Power and Reactive Power Flow

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 32 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

5.2 Night Load Operating Scenario


Night load operating scenario refers to the power flow conditions during night load, i.e. con-
ditions of zero active power generation by solar inverters. During this condition, each of the
solar inverters will provide reactive power support to the network as per the reactive power
capability of the inverters.
The snapshot of power flow results is indicated below:
SWING BUS SUMMARY:
BUS#-SCT X-- NAME --X BASKV PGEN PMAX PMIN QGEN QMAX QMIN
1 220KVPGCILSS220.00 0.4 999.0 -999.0 -1.8 999.0 -999.0
At the 220kV point of interconnection which is referred to as swing bus, it is observed that since
there is zero solar power generation, around 0.4MW (PGEN) of power is imported from grid to
account for auxiliary transformer loads.
QGEN=-1.8MVAr which indicates a reactive power support of 1.8MVAr provided by solar invert-
ers which accounts for the inductive properties associated with transformers, lines and auxiliary
loads operating at 0.85 lagging power factor.
The detailed power flow results consisting of MW, MVAr, MVA, Losses MW, Losses MVAr in each
feeder of the network along with the voltage (in kV) is provided in Annexures 11.2: Night Load
Operating Scenario- Active Power and Reactive Power Flow Results .

5.3 Operating Scenario with grid voltage=1.1 p.u.


This operating scenario is defined as the power system operation for which 220kV pooling sta-
tion of the solar park is subjected to grid voltage=1.1 p.u.
The solar inverters will be operating in inverter control mode set at Renewable: Standard QT,
QB limits.
The snapshot of power flow results obtained for equivalent model and detailed model is indi-
cated below:
SWING BUS SUMMARY:
BUS#-SCT X-- NAME --X BASKV PGEN PMAX PMIN QGEN QMAX QMIN
1 220KVPGCILSS220.00 -241.7 999.0 -999.0 197.7 999.0 -999.0
At the 220kV point of interconnection which is referred to as swing bus, it is observed that out
of 250MW solar power generation, around 241.7MW (PGEN) of power is exported and remain-
ing portion accounts for the total I ^2 losses and auxiliary transformer loading.
QGEN=197.7MVAr which indicates a reactive power requirement of 197.7MVAr in the solar
farm. Additional lagging reactive power is to compensate for high voltage conditions in the grid
and inductive properties associated with transformers, lines and auxiliary loads operating at
0.85 lagging power factor.
The comparison of equivalent model is performed with the detailed model for power flow re-
sults consisting of MW, MVAr, MVA, Losses MW, Losses MVAr in each feeder of the network
along with the voltage (in kV). These results are provided in Annexures 11.3 Grid voltage=1.1
p.u- Active Power and Reactive Power Flow Results.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 33 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

5.4 Operating Scenario with grid voltage=0.9 p.u.


This operating scenario is defined as the power system operation for which 220kV pooling sta-
tion of the solar park is subjected to grid voltage=0.9 p.u.
The solar inverters will be operating in inverter control mode set at Renewable: Standard QT,
QB limits.
The snapshot of power flow results obtained for equivalent model and detailed model is indi-
cated below:
SWING BUS SUMMARY:
BUS#-SCT X-- NAME --X BASKV PGEN PMAX PMIN QGEN QMAX QMIN
1 220KVPGCILSS220.00 -242.1 999.0 -999.0 -74.6 999.0 -999.0
At the 220kV point of interconnection which is referred to as swing bus, it is observed that out
of 250MW solar power generation, around 242.1MW (PGEN) of power is exported and remain-
ing portion accounts for the total I ^2 losses and auxiliary transformer loading.
QGEN=-74.6MVAr which indicates a reactive power requirement of 74.6MVAr in the solar farm.
Additional leading reactive power is to compensate for low voltage conditions in the grid after
catering to the inductive properties associated with plant’s transformers, lines and auxiliary
loads operating at 0.85 lagging power factor.
The comparison of equivalent model is performed with the detailed model for power flow re-
sults consisting of MW, MVAr, MVA, Losses MW, Losses MVAr in each feeder of the network
along with the voltage (in kV). These results are provided in Annexures 11.4 Grid voltage=0.9
p.u- Active Power and Reactive Power Flow Results.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 34 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

6 Short Circuit Analysis


Short-circuit studies can be performed at the planning stage in order to help finalize the system
layout, determine voltage levels, and size of cables, transformers, and conductors. For existing
systems, fault studies are necessary in the cases of added generation, installation of extra ro-
tating loads, system layout modifications, rearrangement of protection equipment, verification
of the adequacy of existing breakers, relocation of already acquired switchgear in order to avoid
unnecessary capital expenditures. Majority of the evaluation can be conducted by performing
three phase short circuit analysis on the network.

6.1 Short Circuit Study Methodology

Short circuit model is constructed based on the parameters listed in Table 6-1 which is men-
tioned as part of Equivalent Grid parameters given in Chapter 2.

Table 6-1 Parameters of 220kV Equivalent Grid

Parameter Symbol Value Unit


Short-circuit power Sk” 5100*) MVA
Short-circuit current I k” 13.38 kA
Rated voltage Vr 220 kV
Rated frequency f 50 Hz
R/X ratio R/X 0.1*) -
Voltage factor (maximum) cmax 1.10 -
Voltage factor (minimum) cmin 1.00 -
*) Assumption

Fault calculations are carried out at various buses based on IEC 60909 method. IEC 60909-
2001 covers three-phase ac electric power systems, operating at either 50 Hz or 60 Hz. The
standard addresses three-phase, line-to-ground, line-to-line and double-line-to-ground short
circuits. Fault currents more than short term switchgear rating are highlighted in the report.
The “equivalent source” technique adopted in IEC 60909-2001 recommends applying a volt-
age factor C (C max or Cmin) to the pre-fault nominal system voltage, in order to obtain the
voltage magnitude of the equivalent source at the fault location. Table 6-2 shows c-factors
for various voltage levels. They are important in distinguishing between maximum and mini-
mum short-circuit currents and are introduced in order to account for pre-fault system load-
ing, off-nominal transformer taps, excitation of generators etc.

Initial short-circuit current, Ik" — The rms value of the AC symmetrical component of a pro-
spective short-circuit current applicable at the instant of the short circuit, if the system im-
pedances remain unchanged. The fault current is with motor contribution.
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 35 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Steady-state short-circuit current, Ik — the rms value of the short-circuit current that re-
mains after the decay of the transient phenomena.

Table 6-2 IEC 60909 pre-fault voltage factors

Nominal Voltage, Vn Max. fault currents, C max Min. fault currents, C min

Low voltage: 100V to 1000V


a) 230/400V 1 0.95
b) Other Voltages 1.05 1
Medium Voltages > 1000V to 35kV 1.1 1
High Voltages >35kV to 230kV 1.1 1

The short circuit fault currents are compared with existing short term rating of bus and based
on that conclusions are drawn. The existing short time rating of bus bar at various voltage
ratings are furnished in Table 6-3.

Table 6-3 Switchgear Short Time Rating

Location Switchgear Short Time Rating


220kV Main Bus 40kA for 1 sec
33kV Main Bus 31.5kA for 3 sec
33kV AIS Switchgear 31.5kA for 3 sec

Short circuit analysis was carried out as per IEC 60909-2001 to check the adequacy of each
switchgear boards for a three-phase fault currents.

6.2 Short Circuit Study Results

This part of the study describes the results of the calculations for three phase short circuit study
which is provided in Annexures 11.5 Short Circuit Study Results.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 36 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

7 Reactive Power Analysis


In this study, the reactive power capability of Solar Park is determined at the different required
operating conditions and checked for the fulfillment of the reactive power capability require-
ments as defined in the CEA guideline.

7.1 Grid Code Requirement


According to the CEA guideline requirements for renewable solar power plants connection, the
renewable power plants should be capable of supplying or absorbing reactive power at the
point of connection (POC). In the guideline, categories are defined for renewable according to
their operation voltage level and rated power.
According to the agreement the PV power plant shall be able to operate at a power factor be-
tween 0.95 leading (under-excited operation, i.e. import of reactive power from the network)
and 0.95 lagging (over-excited operation, i.e. export of reactive power to the network) at rated
power output. The power factor shall be measured at the POC, where the PV power plant is
connected to the HV transmission network.

7.2 Study Approach


In order to verify the reactive power capability of the Solar Park, (i.e., to investigate if the Solar
Park can fulfill the reactive power requirements at POC or not), power flow calculations for
different study cases is performed. In these study cases, the Solar Park is simulated with its
minimum and maximum reactive power output at different active power output level, and un-
der different voltage conditions at the POC. Since it is required that the voltage at the 220kV
bus bar of the POC can vary within +/-10% of the nominal voltage (according to the grid code
[1]), the following operation scenarios are defined and studied:
• Maximum reactive power generation at nominal and lower voltage condition in the net-
work
o 1.10 p.u. voltage at POC
o 1.00 p.u. voltage at POC
o 0.9 p.u. voltage at POC
• Maximum reactive power consumption under nominal and higher voltage condition in
the network
o 1.10 p.u. voltage at POC
o 1.00 p.u. voltage at POC
o 0.9 p.u. voltage at POC

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 37 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

7.3 PQ Capability Curve plot of Inverter

PQ Curve of SG3125HV-20 Inverter


3.200
3.125

2.950 2.968 2.968

2.813 2.813
2.700
-1.646, 2.656 1.646, 2.656

2.500 2.500
2.450

2.200

1.950

1.700
MW

1.450

1.200

0.950

0.700

0.450

0.200

0.000 0.000
-0.050
-2.000 -1.600 -1.200 -0.800 -0.400 0.000 0.400 0.800 1.200 1.600 2.000
Mvar

Figure 7-1 PQ Capability Diagram of SG3125HV-20 Inverter

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 38 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Based on the PQ capability curve, the calculation of the inverter working points is performed
for different voltages at POC:1.0 p.u. and 1.1 p.u.

Table 7-1 Operation points of the Inverter for the study- 1 p.u. and 1.1 p.u.

Q/Pmax
Sr. No. P/Pmax P[kW] Q[kVar]
(cap./ind.)
1 0.00 0.60 0 1875
2 0.80 0.60 2500 1875
3 0.85 0.53 2656 1646
4 0.90 0.44 2813 1362
5 0.95 0.31 2968 976
6 1.00 0.00 3125 0

Based on the PQ capability curve, the calculation of the inverter working points is performed
for voltage at POC:0.9 p.u.

Table 7-2 Operation points of the Inverter for the study-0.9 p.u.

Q/Pmax
Sr. No. P/Pmax P[kW] Q[kVar]
(cap./ind.)
1 0.00 0.54 0 1687
2 0.72 0.54 2250 1687
3 0.76 0.47 2390 1481
4 0.81 0.39 2531 1226
5 0.85 0.28 2672 878
6 0.90 0.00 2813 0

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 39 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

7.4 PQ Reactive Capability Curve plot of Solar Farm at PCC (220kV)


Based on the inverter working points used for the calculation are shown in Table 7-1 and Table
7-2, the following results are obtained as summarized.
Table 7-3 Reactive Power Analysis for Grid Voltage=0.9 p.u.

Grid Total Power Each inverter


Grid Voltage
MW MVar PF MW MVar PF
0.9 pu -2.10 124.90 0.017 0.000 1.687 -
0.9 pu 174.90 102.60 0.863 2.250 1.687 0.80
0.9 pu 186.00 85.20 0.909 2.390 1.481 0.85
0.9 pu 197.10 63.80 0.951 2.531 1.226 0.90
0.9 pu 208.10 34.50 0.987 2.672 0.878 0.95
0.9 pu 218.80 -40.60 0.983 2.813 0.000 1.00
0.9 pu -3.30 -153.50 0.021 0.000 1.687 -
0.9 pu 171.80 -190.60 0.670 2.250 -1.687 -0.80
0.9 pu 183.30 -171.60 0.730 2.390 -1.481 -0.85
0.9 pu 194.90 -148.40 0.796 2.531 -1.226 -0.90
0.9 pu 206.60 -117.30 0.870 2.672 -0.878 -0.95
0.9 pu 218.80 -40.60 0.983 2.813 0.000 -1.00

Table 7-4 Reactive Power Analysis for Grid Voltage=1 p.u.

Grid Total Power Each inverter


Grid Voltage
MW MVar PF MW MVar PF
1.0 pu -2.20 140.40 0.016 0.000 1.875 -
1.0 pu 194.70 117.60 0.856 2.500 1.875 0.80
1.0 pu 207.10 98.60 0.903 2.656 1.646 0.85
1.0 pu 219.50 74.90 0.946 2.813 1.362 0.90
1.0 pu 231.80 42.60 0.984 2.968 0.976 0.95
1.0 pu 243.80 -84.00 0.945 3.125 0.000 1.00
1.0 pu -3.20 -167.80 0.019 0.000 -1.875 -
1.0 pu 192.10 -202.60 0.688 2.500 -1.875 -0.80
1.0 pu 204.80 -182.20 0.747 2.656 -1.646 -0.85
1.0 pu 217.70 -157.20 0.811 2.813 -1.362 -0.90
1.0 pu 230.40 -123.40 0.882 2.968 -0.976 -0.95
1.0 pu 243.80 -84.00 0.945 3.125 0.000 -1.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 40 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Table 7-5 Reactive Power Analysis for Grid Voltage=1.1 p.u.

Grid Total Power Each inverter


Grid Voltage
MW MVar PF MW MVar PF
1.0 pu -2.200 152.90 0.01 0.000 1.875 -
1.0 pu 195.40 123.80 0.84 2.500 1.875 0.80
1.0 pu 207.80 105.00 0.89 2.656 1.646 0.85
1.0 pu 220.30 81.60 0.94 2.813 1.362 0.90
1.0 pu 232.60 49.70 0.98 2.968 0.976 0.95
1.0 pu 245.10 -31.40 0.99 3.125 0.000 1.00
1.0 pu -2.60 -161.70 0.02 0.000 -1.875 -
1.0 pu 193.90 -189.50 0.72 2.500 -1.875 -0.80
1.0 pu 206.50 -170.00 0.77 2.656 -1.646 -0.85
1.0 pu 219.20 -145.90 0.83 2.813 -1.362 -0.90
1.0 pu 231.80 -113.10 0.90 2.968 -0.976 -0.95
1.0 pu 244.70 -31.40 0.99 3.125 0.000 -1.00

The overall calculated reactive power capability diagram is presented in Figure 7-2.

Reactive Power Capability


1.2

0.8

0.6 Grid Code


P/Pmax

U=100%
0.4 U=110%
U=90%
0.2

0
-0.99 -0.66 -0.33 0 0.33 0.66 0.99
-0.2
Inductive
Q/Pmax
Q-Import

Figure 7-2 Reactive power capability of Solar park at POC

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 41 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

7.5 Conclusion
Then, based on this model and load flow calculations, the reactive power capability of the Solar
Park is calculated under different voltage at POC (0.9 p.u.,1p.u. and 1.1p.u.). The results are
illustrated as PQ-diagram and compared with the grid code requirement Figure 7-2.
According the study results, the solar park can cover the operating range defined within the
triangle as shown in Figure 7-2, so that the grid code requirement will be fulfilled.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 42 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

8 Harmonic Analysis
Power electronic devices will introduce the distorted current in the power system, which may
not only increase power losses of electrical facilities, but also cause the malfunction of commu-
nication devices. Besides, resonance may also cause serious problem such as over voltage in
the power system. Therefore, it becomes more and more important to perform the harmonic
power flow analysis for the system with power electronic devices.
The major harmonic sources in the power systems are as below:
• Power electronic converters
• Rectifiers
• Invertors
• Motor drives
• Arc furnaces

8.1 Effect of harmonics on power system equipment


The harmonic currents and voltage produce an impact on the network elements, which are
describe as below:
Transformers: The effect of harmonics on transformers is twofold: one current harmonics
cause an increase in copper losses and stray flux losses, second; voltage harmonics cause an
increase in iron losses. The overall effect is an increase in the transformer heating, as compared
to purely sinusoidal (fundamental) operation.
Stray losses are eddy-current losses due to stray electromagnetic flux in the windings, core,
core clamps, magnetic shields, tank wall, and other structural parts of the transformer. The
winding stray loss includes winding conductor strand eddy-current loss and the loss due to
circulating currents between strands or parallel winding circuits. This loss will rise in proportion
to the square of the load current and the square of frequency. The temperature will also rise in
the structural parts because of eddy currents, again approximately as the square of the load
current and the square of the frequency.
IEEE C57.12.00-1987 proposes a limit on the harmonics in transformer current. As per IEEE
C57.12.00-1987, the upper limit of the current distortion factor is 5% at rated current. The
recommended practice also gives the maximum rms overvoltages that the transformer should
be able to withstand in the steady state: 5% at rated load and 10% at no load. The harmonic
currents in the applied voltage must not result in a total rms voltage exceeding these ratings.
Switchgear & Relaying: As with other types of equipment, harmonic currents can increase
heating and losses in switchgear, thereby reducing steady-state current carrying capability and
shortening the life of some insulating components.
Fuses suffer a derating because of the heat generated by harmonics during normal operation.
There are currently no standards for the level of harmonic currents that switching devices or
fuses are required to interrupt or to carry. All tests are performed at rated supply frequency.
The effects of harmonics on relay operation are as follows:
1) Relays exhibit a tendency to operate slower and/or with higher pickup values, rather than
operate faster and/or with lower pickup values.
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 43 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

2) Static under frequency relays are susceptible to substantial changes in operating character-
istics.
3) In most cases, the changes in operating characteristics are relatively small over the moder-
ate range of distortion expected during normal operation (e.g., 5% harmonic factor).
4) For different manufacturers, overvoltage and overcurrent relays exhibit different changes
in operating characteristics.
5) Depending on harmonic content, operating torques of relays are sometimes reversed.
6) Balanced beam impedance relays show both overreach and under reach, depending on the
distortion.
7) Harmonics sometimes impair the high-speed operation of differential relays. Some tests
demonstrate that the relays could exhibit complete restraint.
In general, harmonic levels required to cause misoperation of relays are greater than the levels
recommended in IEEE 519. Distortion factors of 10-20% generally are required to cause prob-
lems in relay operation.
Solid-state tripping devices on low-voltage circuit breakers respond to rms current values only.
There will be no nuisance tripping due to harmonic currents in these devices.
Power Electronic devices: Power electronic equipment is susceptible to maloperation caused
by harmonic distortion. This equipment is often dependent upon accurate determination of
voltage zero crossings or other aspects of the voltage wave shape. Harmonic distortion can
result in a shifting of the voltage zero crossing or the point at which one phase-to-phase voltage
becomes greater than another phase-to-phase voltage. These are both critical points for many
types of electronic circuit controls, and maloperation can result from these shifts.
Capacitors: A major concern arising from the use of capacitors in a power system is the possi-
bility of system resonance. The result of the increased heating and voltage stress brought about
by harmonics is a shortened capacitor life.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 44 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

8.2 Harmonic current and voltage limits for power system equipment
as per IEEE519-2014 standard
Managing harmonics in a power system is considered a joint responsibility involving both end-
users and system owners and operators, harmonic limits are recommended for both voltages
and currents. The recommended values in this clause are based on the fact that some level of
voltage distortion is generally acceptable and both system owners or operators and users must
work cooperatively to keep actual voltage distortion below objectionable levels. The underlying
assumption of these recommended limits is that by limiting harmonic current injections by us-
ers, voltage distortion can be kept below objectionable levels. In the event that limiting har-
monic currents alone does not result in acceptable levels of voltage distortion, system owners
or operators should take action to modify system characteristics so that voltage distortion levels
are acceptable. The acceptable voltage distortion levels form the basis of the harmonic voltage
limits in Table 8-1.
The recommended limits in this clause apply only at the point of common coupling and should
not be applied to either individual piece of equipment or at locations within a user’s facility. In
most cases, harmonic voltages and currents at these locations could be found to be significantly
greater than the limits recommended at the PCC due to the lack of diversity, cancellation, and
other phenomena that tend to reduce the combined effects of multiple harmonic sources to
levels below their algebraic summation.
However, all the available cures cannot eliminate harmonics completely and it can only be lim-
ited to acceptable levels. The so called acceptable levels are mentioned in the below sections
as per IEEE 519-2014 standard.
8.2.1 Permissible Voltage Distortion Limits as per IEEE 519-2014

At the PCC, system owners or operators should limit line-to-neutral voltage harmonics as shown
in Table 8-1.
Table 8-1 IEEE 519-2014 Voltage distortion limits (THDV) (%)

All values should be in percent of the rated power frequency voltage at the PCC and it applies
to voltage harmonics whose frequencies are integer multiples of the power frequency.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 45 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

8.2.2 Permissible Current Distortion Limits as per IEEE 519-2014

The limits in this sub clause apply to users connected to systems where the rated voltage at the
PCC is 120 V to 69 kV and from 69 kV to 161 kV. At the PCC, users should limit their harmonic
currents as shown in Table 8-2 and Table 8-3.
All values should be in percent of the maximum demand current, IL. This current value is estab-
lished at the PCC and should be taken as the sum of the currents corresponding to the maxi-
mum demand during each of the twelve previous months divided by 12 and it applies to har-
monic currents whose frequencies are integer multiples of the power frequency.
Table 8-2 IEEE 519-2014 Current distortion limits for systems rated above 120 V through 69 kV

Table 8-3 IEEE 519-2014 Current distortion limits for systems rated above 69 kV through 161 kV

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 46 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

8.3 Harmonic Scenario in 250MW Solar Power Plant, Anantapur, An-


dhra Pradesh
This section contains the harmonic scenario in the 250MW Solar Power Plant and its impact on
the power system network.

8.3.1 Harmonic Model of Sungrow Solar Inverter SG3125HV-20


Harmonics in Sungrow Solar Inverter SG3125HV-20 are created by the inverter current sources,
which are also called current waves. The frequencies (harmonic order) and the magnitudes of
those current waves depend exclusively on the nature of the equipment. The 5th harmonic has
a frequency five times the fundamental and the 7th is seven times the fundamental. The har-
monic is actually the power source at the high frequency. Since the harmonics exist in the cur-
rent drawn, the source is treated as a current source. Unlike the voltage source, the ideal cur-
rent source has infinity internal impedance and prefers zero load impedance to maintain the
current.
To understand the level of harmonic distortion, current sources are injected, in which harmonic
currents from 3rd order to 50th order as a % of fundamental current. Harmonics analysis in the
250MW solar park network is depicted by modeling the harmonic characteristics of inverters at
all SPPs and ICOGs as per the data provided in pdf document: “SUNGROW Harmonic Test Report
for SG3125HV-20”.
As shown in Table 8-4, current distortions for harmonic current (I) is indicated in percentage of
fundamental currents. The current harmonic injection is modeled as per the design data and
may not exactly replicate the harmonic scenario in the network. Exact measurements may be
performed in future during operational stage in order to investigate if the limits of TDD are
maintained as per IEEE 519-2014 standard mentioned in Table 8-2 and Table 8-3.
As this stage, it is possible to investigate the individual THDv and overall THDv of the network
as per current injection given in Table 8-4. Limits of individual and overall THDv will be verified
for any violations as per IEEE 519-2014 standard mentioned in Table 8-1.
Table 8-4 SUN2000-95KTL Huawei Solar Inverter Model in terms of % of fundamental current

Harmonic
Harmonic Limits
Frequency Max I (%) L1 (%) L2 (%) L3 (%)
Order (%)
(Hz)
2 100 0.08 0.07 0.08 0.07 1
3 150 0.06 0.04 0.06 0.03 4
4 200 0.06 0.05 0.05 0.06 1
5 250 0.47 0.46 0.47 0.47 4
6 300 0.02 0.01 0.02 0.01 1
7 350 0.22 0.2 0.22 0.21 4
8 400 0.05 0.05 0.05 0.05 1
9 450 0.01 0.01 0.01 0.01 4
10 500 0.05 0.05 0.05 0.05 0.5
11 550 0.08 0.08 0.08 0.08 2
12 600 0.01 0.01 0.01 0.01 0.5
13 650 0.07 0.07 0.07 0.07 2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 47 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Harmonic
Harmonic Limits
Frequency Max I (%) L1 (%) L2 (%) L3 (%)
Order (%)
(Hz)
14 700 0.06 0.06 0.06 0.06 0.5
15 750 0.01 0.01 0.01 0.01 2
16 800 0.06 0.06 0.06 0.06 0.5
17 850 0.07 0.06 0.07 0.06 1.5
18 900 0.01 0.00 0.01 0.01 0.5
19 950 0.08 0.08 0.08 0.07 1.5
20 1000 0.06 0.06 0.06 0.06 0.5
21 1050 0.01 0.01 0.01 0.01 1.5
22 1100 0.08 0.07 0.07 0.08 0.5
23 1150 0.1 0.09 0.1 0.09 0.6
24 1200 0.02 0.01 0.02 0.01 0.5
25 1250 0.13 0.11 0.13 0.12 0.6
26 1300 0.07 0.07 0.06 0.06 0.5
27 1350 0.02 0.01 0.02 0.01 0.6
28 1400 0.09 0.07 0.07 0.09 0.5
29 1450 0.09 0.09 0.09 0.08 0.6
30 1500 0.02 0.01 0.02 0.01 0.5
31 1550 0.08 0.07 0.08 0.08 0.6
32 1600 0.1 0.1 0.07 0.07 0.5
33 1650 0.01 0.01 0.01 0.01 0.6
34 1700 0.11 0.08 0.09 0.11 --
35 1750 0.04 0.04 0.04 0.03 --
36 1800 0.02 0.00 0.02 0.01 --
37 1850 0.02 0.01 0.02 0.02 --
38 1900 0.08 0.07 0.08 0.06 --
39 1950 0.01 0.00 0.01 0.01 --
40 2000 0.04 0.03 0.04 0.04 --
41 2050 0.03 0.02 0.02 0.03 -
42 2100 0.01 0 0 0.01 -
43 2150 0.11 0.02 0.02 0.11 -
44 2200 0.03 0.03 0.03 0.03 -
45 2250 0.02 0 0 0.02 -
46 2300 0.06 0.05 0.06 0.04 -
47 2350 0.04 0.01 0.01 0.04 -
48 2400 0.01 0 0 0.01 -
49 2450 0.1 0.01 0.01 0.1 -
50 2500 0.06 0.06 0.06 0.02 -

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 48 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

The graphical representation plot of SG3125HV-20 Sungrow Solar Inverter Harmonic Model at
different frequencies from 2nd order to 50th order in terms of % of fundamental current har-
monic currents is indicated in Figure 8-1.
Max I (%)

0.5
0.45
0.4
0.35
0.3
0.25
0.2
0.15
0.1
0.05
0

Figure 8-1 Graphical Representation of Sungrow SG3125HV-20 Solar Inverter Harmonic Model in terms of %
of fundamental current

8.4 Results of Harmonic Analysis


Harmonics calculates the network impedance between a starting frequency and an end fre-
quency considered in the model. For the purpose of accuracy in simulation, the initial frequency
is considered as 50Hz and the end frequency is considered as 2500Hz. The frequency step is
considered in the bandwidth between 5Hz and 50 Hz, based on which resonances in the fre-
quency band will be documented.
The individual harmonic voltage distortion in % and frequency impedance characteristics is
plotted for certain critical buses which indicate the presence of harmonics in the system. Indi-
vidual harmonic levels are compared with the acceptable harmonic levels. As per requirements
mentioned in IEEE519-2014 standards, a maximum permissible harmonic level associated with
the chosen standard is indicated in dotted line which will be compared with the calculated
harmonic currents.
Based on the simulation, the following results are determined:
• Harmonic voltage and current distribution, including voltage and current distribution at
basic frequency
• Frequency band for network inlet impedance at all points in a network
• Frequency band for coupling impedance between all points in a network

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 49 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

8.4.1 Total Harmonic Distortion and Individual Harmonics


This section provides the Total Harmonic Distortion (THD) and Individual Harmonic Distortion
in percentage of fundamental current. They are plotted at the following locations as indicated
from Figure 8-2 to Figure 8-14.
• 220kV PGCIL Substation
• 220kV Ayana Pooling Substation
• 33kV Main HT Panel
• 33kV 50MW Block-1
• 33kV 50MW Block-2
• 33kV 50MW Block-3
• 33kV 50MW Block-4
• 33kV 50MW Block-5
• 220kV side of Power Transformer
• 33kV side of Power Transformer
• 33kV side of Inverter Duty Transformer
• 0.6kV side of Inverter Duty Transformer
• 0.6kV Inverter Terminal Block

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 50 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 220KVPGCILSS


10

220KVPGCILSS - THD, Vr > 161 kV


1

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

220KVPGCILSS

Figure 8-2: % Total Harmonic Distortion and % Individual Harmonics at 220kV PGCIL Substation

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 51 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 220KVPOOLING


10

220KVPOOLING - THD, Vr > 161 kV


1

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

220KVPOOLING

Figure 8-3: % Total Harmonic Distortion and % Individual Harmonics at 220kV Ayana Pooling Substation

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 52 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 33KMAINHTPNL


10

33KMAINHTPNL - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

33KMAINHTPNL

Figure 8-4: % Total Harmonic Distortion and % Individual Harmonics at 33kV Main HT Panel

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 53 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 50MWBLK1_1


10

50MWBLK1_1 - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

50MWBLK1_1

Figure 8-5: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 54 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 50MWBLK2_1


10

50MWBLK2_1 - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

50MWBLK2_1

Figure 8-6: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 55 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 50MWBLK3_1


10

50MWBLK3_1 - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

50MWBLK3_1

Figure 8-7: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-3

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 56 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 50MWBLK4_1


10

50MWBLK4_1 - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

50MWBLK4_1

Figure 8-8: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-4

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 57 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: 50MWBLK5_1


10

50MWBLK5_1 - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

50MWBLK5_1

Figure 8-9: % Total Harmonic Distortion and % Individual Harmonics at 33kV 50MW Block-5

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 58 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: HV_POWERTR-1


10

HV_POWERTR-1 - THD, Vr > 161 kV


1

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

HV_POWERTR-1

Figure 8-10: % Total Harmonic Distortion and % Individual Harmonics at 220kV side of Power Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 59 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: LV_POWERTR-1


10

LV_POWERTR-1 - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

LV_POWERTR-1

Figure 8-11: % Total Harmonic Distortion and % Individual Harmonics at 33kV side of Power Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 60 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: HV_IDT1_1


10

HV_IDT1_1 - THD, 1 kV < Vr <= 69 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

HV_IDT1_1

Figure 8-12: % Total Harmonic Distortion and % Individual Harmonics at 33kV side of Inverter Duty Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 61 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: LV1_IDT1_1


10

LV1_IDT1_1 - THD, Vr <= 1 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

LV1_IDT1_1

Figure 8-13: % Total Harmonic Distortion and % Individual Harmonics at 0.6kV side of Inverter Duty Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 62 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

u rel [%] Harmonic - Node Level: INV1_IDT1_1


10

INV1_IDT1_1 - THD, Vr <= 1 kV

0.1

0.01

0.001

THD
0.0001 n [1]
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52

INV1_IDT1_1

Figure 8-14: % Total Harmonic Distortion and % Individual Harmonics at 0.6kV side of Inverter Terminal Block

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 63 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

8.4.2 Plot of Impedance vs Frequency Characteristics


This section provides the Total Harmonic Distortion (THD) and Individual Harmonic Distortion
in percentage of fundamental current. They are plotted at the following locations as indicated
from Figure 8-15 to Figure 8-27.
• 220kV PGCIL Substation
• 220kV Ayana Pooling Substation
• 33kV Main HT Panel
• 33kV 50MW Block-1
• 33kV 50MW Block-2
• 33kV 50MW Block-3
• 33kV 50MW Block-4
• 33kV 50MW Block-5
• 220kV side of Power Transformer
• 33kV side of Power Transformer
• 33kV side of Inverter Duty Transformer
• 0.6kV side of Inverter Duty Transformer
• 0.6kV Inverter Terminal Block

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 64 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 220KVPGCILSS


1000

100

10

1 f [Hz]
10 100 1000 10000

Figure 8-15: Impedance vs Frequency characteristics at 220kV PGCIL substation

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 65 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 220KVPOOLING


1000

100

10

1 f [Hz]
10 100 1000 10000

Figure 8-16: Impedance vs Frequency characteristics at 220kV Ayana Pooling substation

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 66 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 33KMAINHTPNL


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-17: Impedance vs Frequency characteristics at 33kV Main HT Panel

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 67 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 50MWBLK1_1


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-18: Impedance vs Frequency characteristics at 33kV 50MW Block-1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 68 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 50MWBLK2_1


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-19: Impedance vs Frequency characteristics at 33kV 50MW Block-2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 69 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 50MWBLK3_1


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-20: Impedance vs Frequency characteristics at 33kV 50MW Block-3

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 70 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 50MWBLK4_1


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-21: Impedance vs Frequency characteristics at 33kV 50MW Block-4

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 71 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: 50MWBLK5_1


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-22: Impedance vs Frequency characteristics at 33kV 50MW Block-5

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 72 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: HV_POWERTR-1


1000

100

10

1 f [Hz]
10 100 1000 10000

Figure 8-23: Impedance vs Frequency characteristics at 220kV side of Power Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 73 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: LV_POWERTR-1


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-24: Impedance vs Frequency characteristics at 33kV side of Power Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 74 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: HV_IDT1_1


100

10

0.1 f [Hz]
10 100 1000 10000

Figure 8-25: Impedance vs Frequency characteristics at 33kV side of Inverter Duty Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 75 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: LV1_IDT1_1


1

0.1

0.01

0.001 f [Hz]
10 100 1000 10000

Figure 8-26: Impedance vs Frequency characteristics at 0.6kV side of Inverter Duty Transformer

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 76 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Z [Ohm] Impedance: INV1_IDT1_1


1

0.1

0.01

0.001 f [Hz]
10 100 1000 10000

Figure 8-27: Impedance vs Frequency characteristics at 0.6kV side of Inverter Terminal Block

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 77 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

8.5 Observations of Harmonic Analysis


The harmonic analysis is conducted for normal operating scenario in the absence of any addi-
tional reactive power compensation devices. The total harmonic distortion in voltage is calcu-
lated at strategic locations at 220kV, 33kV and 0.6kV voltage levels which determines the over-
all behavior of the network. As shown, the overall THD levels are compared with threshold
limits associated with IEEE 519-2014.
Following are the observations:
1. At 220kV Point of Interconnection, parallel resonance is observed at 1000Hz and its har-
monic distortion is below the threshold limit of 1% which is the exact permissible limit.
Overall THD voltage is around 0.025% which is also below the permissible limit of 1.5%.
Similar characteristics are observed at 220kV Ayana Pooling Station.
2. At 220kV side of power transformers, parallel resonance is observed at 1000Hz and its har-
monic distortion is below the threshold limit of 1% which is the exact permissible limit.
Additionally, series resonance is observed at around 1500Hz, but due to distortion being
within limits, the impact is ignored. Overall THD voltage is around 0.025% which is also
below the permissible limit of 1.5%.
3. At 33kV Main HT Panel, parallel resonance is observed at 1000Hz and its harmonic distor-
tion is below the threshold limit of 3% which is the exact permissible limit. Overall THD
voltage is around 0.07% which is also below the permissible limit of 5%. Similar character-
istics are observed at 33kV Main 50MW Blocks and 33kV side of power transformers etc.
4. At 0.6kV solar inverter blocks, no resonance condition is observed at any frequency and all
individual harmonic distortions are well within limits of 5%. The overall THD voltage at the
inverter buses is around 0.08% which is also within the threshold limits of 8%.

8.6 Recommendations of Harmonic Analysis


Harmonic Analysis is conducted using the design data of inverter datasheet as per CEA Guide-
lines report document. Although no significant violations in harmonic levels are observed with
respect to IEEE-519 2014 standards, it is recommended to conduct harmonic measurements at
certain strategic locations like 220kV Point of Interconnection, 33kV HT Panels and a typical
0.6kV inverter blocks to validate the findings according to design data.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 78 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9 Dynamic Stability Analysis


High penetration of renewable generation presents challenges in the planning and operations
of power systems. Ensuring adequate frequency and voltage response is one such concern as
the generation mix changes with increasing penetration of non-synchronous variable genera-
tion and planned retirement or displacement of fossil-fueled generation.
The grid code compliance for the modelled solar plant is checked for most clauses of the Indian
Grid Code (Authority, February 2019). The major compliance checked are Low Voltage Ride
Through (LVRT)/High Voltage Ride Through (HVRT) and Frequency and Active Power Regulation
for a time period of 40 seconds.

9.1 Voltage Ride Through (VRT)


Bulk transmission system faults result in voltage depression over an extended area, both during
the duration of the fault, as well as during post-fault dynamic behavior. In the post-fault period,
high voltages may also occur over a wide area due to dynamic “backswing”. These voltage de-
viations at the bulk transmission level tend to propagate over a wide area to the distribution
systems to which the inverters are connected. Without VRT requirements, a potentially large
amount of solar generators capacity could be tripped simultaneously as a result of a bulk grid
event that stresses the grid. The primary purpose of VRT requirements is preservation of bulk
grid security by avoiding aggravation of bulk system disturbances. (Reigh Walling (Energy
Systems Consulting, LLC), Abraham Ellis and Sigifredo Gonzalez (Sandia National Laboratories),
, 2014)

9.1.1 Low Voltage Ride Through (LVRT) (Integration Time Step: 1 msec, total time: 40
sec)
LVRT describes the requirement that generating plants must continue to operate through short
periods of low grid voltage and not disconnect from the grid. The basis for the requirement is
that during a fault on the system, the immediate disconnection of a large facility would be
counterproductive.
As per the CEA Guidelines (Authority, February 2019), the generating station connected to the
grid shall remain connected to the grid when voltage at the interconnection point in one or all
phases dips as depicted by the thick line in the diagram below:

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 79 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

The voltage change in the grid is implemented as per the table shown below. The response of
the model as a consequence of the voltage change is documented.

Time Event Description

t=0.0 sec Event Initiated

t=5.0 sec Voltage change to 0.15 pu

t=5.30 sec Voltage restored to 1.0 pu

t=10.0 sec Voltage change to 0.85 pu

t=13 sec Voltage restored to 1.0 pu

9.1.1.1 Results at the Point of Interconnection (POI)


The following quantities are plotted:
• Voltage at POI in [pu]
• Active power at POI in [MW]
• Reactive power at POI in [Mvar]
Figure 9-1 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 80 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-1 Low Voltage Ride Through at POI (Simulation Time 40 sec, Integration time step:1msec)

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 81 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.1.1.2 Results at the Inverter Bus


The following quantities are plotted:
• Voltage in [pu]
• Active power in [MW]
• Reactive power in [Mvar]
Figure 9-2 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 82 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-2 Low Voltage Ride Through at Inverter (Simulation Time 40 sec, Integration time step:1msec)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 83 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.1.2 High Voltage Ride Through (HVRT) (Integration Time Step: 1 msec, total time:
40 sec)
HVRT describes the requirement that generating plants must continue to operate through short
periods of high grid voltage and not disconnect from the grid.
As per the CEA Guidelines, the generating station connected to the grid shall remain con-
nected to the grid when voltage at the interconnection point in any or all phases (asymmet-
rical or symmetrical overvoltage conditions) rises above the values shown in the table be-
low:

The voltage change in the grid is implemented as per the table shown below. The response of
the model because of the voltage change is documented.

Time Event Description

t=0.0 sec Event Initiated

t=5.0 sec Voltage change to 1.1 pu

t=10.0 sec Voltage restored to 1.15 pu

t=12.0 sec Voltage change to 1.25 pu

t=12.2 sec Voltage restored to 1.0 pu

9.1.2.1 Results at the Point of Interconnection (POI)


The following quantities are plotted:
• Voltage at POI in [pu]
• Active power at POI in [MW]
• Reactive power at POI in [Mvar]
Figure 9-3 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 84 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-3 High Voltage Ride Through at POI (Simulation Time 40 sec, Integration time step:1msec)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 85 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.1.2.2 Results at the Inverter Bus


The following quantities are plotted:
• Voltage in [pu]
• Active power in [MW]
• Reactive power in [Mvar]
Figure 9-4 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 86 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-4 High Voltage Ride Through at Inverter (Simulation Time 40 sec, Integration time step:1msec)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 87 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.2 Frequency Ride Through


Frequency is effectively uniform across an entire interconnection, or portion of an interconnec-
tion in the case of a grid breakup following an exceptionally severe contingency. (There can be
low-magnitude, short-duration frequency variations at specific locations due to dynamic angu-
lar swings; these variations are of insufficient magnitude to be of relevance to this discussion.)
The frequency of the interconnection is determined by the instantaneous balance of load and
generation, and any disturbance causing loss of load, transmission or generation can pertur-
bate the grid frequency. (Reigh Walling (Energy Systems Consulting, LLC), Abraham Ellis and
Sigifredo Gonzalez (Sandia National Laboratories), , 2014)
As per standard practices, the droop is considered to be 4%.

9.2.1 Over Frequency Ride Through (Integration Time Step: 1 msec, Total Time:40
sec)
As per the CEA Guidelines (Authority, February 2019), the generating station shall be capable
of operation at a maximum frequency of 52 HZ without being disconnected from the grid. For
frequency ranges higher than 50.5 HZ, from time to time, it must be possible to activate the
control system to provide active power support of at least 10% of the maximum active power.
This report documents the variation of frequency of 2 Hz for the time duration of 5 seconds
with the change in active and reactive power in the same time period, along with variation in
the voltage.
Time Event Description

t=0.0 sec Event Initiated

t=10.0 sec Frequency change to 52 Hz

t=15.0 sec Frequency restored to 50 Hz

9.2.1.1 Results at the Point of Interconnection (POI)


The following quantities are plotted:
• Frequency Variation (PU)
• Active power at POI in [MW*100]
• Reactive power at POI in [Mvar*100]
Figure 9-5 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 88 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-5 Over Frequency Ride Through at POI (Simulation Time 40 sec, Integration time step:1msec)

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 89 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.2.1.2 Results at the Inverter Bus


The following quantities are plotted:
• Frequency variation (PU)
• Active power in [MW*100]
• Reactive power in [Mvar*100]
Figure 9-6 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 90 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-6 Over Frequency Ride Through at Inverter (Simulation Time 40 sec, Integration time step:1msec)

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 91 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.2.2 Under Frequency Ride Through (Integration Time Step: 1 msec, total time: 40
sec)

As per the CEA Guidelines (Authority, February 2019), the generating station shall be capable
of operation at a minimum frequency of 47.5 HZ without being disconnected from the grid.
For frequency ranges less than 49.5 HZ, from time to time, it must be possible to activate the
control system to provide active power support of at least 10% of the maximum active power.
This report documents the variation of frequency of 2.5 Hz for the time duration of 5 seconds
with the change in active and reactive power in the same time period, along with variation in
the voltage. The generating plant is taken to be operating at 100 MW power

Time Event Description

t=0.0 sec Event Initiated

t=10.0 sec Frequency change to 47.5 Hz

t=15.0 sec Frequency restored to 47.5 Hz

9.2.2.1 Results at the Point of Interconnection (POI)


The following quantities are plotted:
• Frequency variation (PU)
• Active power at POI in [MW*100]
• Reactive power at POI in [Mvar*100]
Figure 9-7 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 92 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-7 Under Frequency Ride Through at POI (Simulation Time 40 sec, Integration time step:1msec)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 93 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.2.2.2 Results at the Inverter Bus


The following quantities are plotted:
• Frequency variation (PU)
• Active power in [MW*100]
• Reactive power in [Mvar*100]
Figure 9-8 shows the results for a simulation time of 40 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 94 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-8 Under Frequency Ride Through at Inverter (Simulation Time 40 sec, Integration time step:1msec)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 95 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.3 Response to change in Grid Voltage


Reactive capability on transmission systems is typically deployed in voltage regulation mode.
The transmission system operator provides a voltage schedule and the inverter adjusts its reac-
tive output to keep the voltage close to the set point level.
The voltage change in the grid is implemented as per the table shown below. The response of
the model as a consequence of the voltage change is documented.
Time Event Description

t=0.0 sec Event Initiated

t=10.0 sec Voltage change to 0.9 pu

t=20.0 sec Voltage restored to 1.0 pu

t=30.0 sec Voltage change to 1.1 pu

T=40.0 sec Voltage restored to 1.0 pu

9.3.1 Results at the Point of Interconnection (POI)


The following quantities are plotted:
• Voltage at POI in [pu]
• Active power at POI in [MW*100]
• Reactive power at POI in [Mvar*100]
• Frequency variation (PU)
Figure 9-9 shows the results for a simulation time of 60 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 96 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-9 Response to change in Grid Voltage at POI (Simulation Time 50 sec, Integration time step:1msec)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 97 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

9.3.2 Results at the Inverter Bus


The following quantities are plotted:
• Voltage in [pu]
• Active power in [MW*100]
• Reactive power in [Mvar*100]
• Frequency variation (PU)
Figure 9-10 shows the results for a simulation time of 60 seconds.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 98 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Figure 9-10 Response to change in Grid Voltage at Inverter (Simulation Time 50 sec, Integration time
step:1msec)
Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 99 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

10 Conclusion
The dynamic model of the 250MW Solar Park located at Anantapur, Andhra Pradesh, India,
considers the generic models REGCA1 (Renewable Energy Generator/Converter Model), REECB1
(Electrical Control Model for Large Scale PV) and REPCA1 (Generic Renewable Plant Control
Model) from the PSS®E 34.6 library to model the photovoltaic inverters and the park controller.
The developed dynamic model meets the expected functional requirements and can be used
for dynamic simulations in PSS®E.
The given parameters of the generic models REGCA1, REECB1, and REPCA1 are not final. They
should be tuned and updated according to final requirements or site tests.
A simulation time step of 1ms is recommended for highest accuracy of the results.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 100 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

11 Annexures
This section provides the detailed study results from power flow and short circuit analysis.

11.1 Normal Operating Scenario- Active Power and Reactive Power


Flow Results
This section provides the detailed power flow results for normal operating scenario. These re-
sults include MW, MVAr, MVA, Losses MW, Losses MVAr in each feeder of the network along
with the voltage (in kV).

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 101 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 1 220KVPGCILSS220.00 CKT MW MVAR MVA % 1.0000PU 0.00 X--- LOSSES ---X X-
--- AREA -----X X---- ZONE -----X 1
FROM GENERATION -243.6 53.4R 249.4 71 220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 -243.6 53.4 249.4 0.00 0.00
1 1

BUS 2 220KVPOOLING220.00 CKT MW MVAR MVA % 1.0000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 2
220.00KV MW MVAR
1 1
TO 1 220KVPGCILSS220.00 1 243.6 -53.4 249.4 0.00 0.00
1 1
TO 3 HV_POWERTR-1220.00 1 -61.1 13.3 62.5 0.00 0.00
1 1
TO 4 HV_POWERTR-2220.00 1 -61.0 13.3 62.4 0.00 0.00
1 1
TO 5 HV_POWERTR-3220.00 1 -60.9 13.4 62.3 0.00 0.00
1 1
TO 6 HV_POWERTR-4220.00 1 -60.7 13.4 62.2 0.00 0.00
1 1

BUS 3 HV_POWERTR-1220.00 CKT MW MVAR MVA % 1.0000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 3
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 61.1 -13.3 62.5 0.00 0.00
1 1
TO 7 LV_POWERTR-133.000 1 -61.1 13.3 62.5 1.0000LK 0.08 5.81
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 102 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 4 HV_POWERTR-2220.00 CKT MW MVAR MVA % 1.0000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 4
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 61.0 -13.3 62.4 0.00 0.00
1 1
TO 8 LV_POWERTR-233.000 1 -61.0 13.3 62.4 1.0000LK 0.08 5.80
1 1

BUS 5 HV_POWERTR-3220.00 CKT MW MVAR MVA % 1.0000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 5
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.9 -13.4 62.3 0.00 0.00
1 1
TO 9 LV_POWERTR-333.000 1 -60.9 13.4 62.3 1.0000LK 0.08 5.78
1 1

BUS 6 HV_POWERTR-4220.00 CKT MW MVAR MVA % 1.0000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 6
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.7 -13.4 62.2 0.00 0.00
1 1
TO 10 LV_POWERTR-433.000 1 -60.7 13.4 62.2 1.0000LK 0.08 5.76
1 1

BUS 7 LV_POWERTR-133.000 CKT MW MVAR MVA % 0.9857PU 5.31 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 7
32.527KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 103 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3 HV_POWERTR-1220.00 1 61.1 -7.5 61.6 1.0000UN 0.08 5.81


1 1
TO 11 33KMAINHTPNL33.000 1 -61.1 7.5 61.6 0.01 0.01
1 1

BUS 8 LV_POWERTR-233.000 CKT MW MVAR MVA % 0.9856PU 5.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 8
32.524KV MW MVAR
1 1
TO 4 HV_POWERTR-2220.00 1 61.0 -7.5 61.5 1.0000UN 0.08 5.80
1 1
TO 11 33KMAINHTPNL33.000 1 -61.0 7.5 61.5 0.02 0.02
1 1

BUS 9 LV_POWERTR-333.000 CKT MW MVAR MVA % 0.9855PU 5.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 9
32.521KV MW MVAR
1 1
TO 5 HV_POWERTR-3220.00 1 60.9 -7.6 61.4 1.0000UN 0.08 5.78
1 1
TO 11 33KMAINHTPNL33.000 1 -60.9 7.6 61.4 0.03 0.03
1 1

BUS 10 LV_POWERTR-433.000 CKT MW MVAR MVA % 0.9854PU 5.28 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 10
32.518KV MW MVAR
1 1
TO 6 HV_POWERTR-4220.00 1 60.8 -7.7 61.3 1.0000UN 0.08 5.76
1 1
TO 11 33KMAINHTPNL33.000 1 -60.8 7.7 61.3 0.03 0.04
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 104 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 11 33KMAINHTPNL33.000 CKT MW MVAR MVA % 0.9858PU 5.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 11
32.533KV MW MVAR
1 1
TO 7 LV_POWERTR-133.000 1 61.1 -7.5 61.6 0.01 0.01
1 1
TO 8 LV_POWERTR-233.000 1 61.1 -7.6 61.5 0.02 0.02
1 1
TO 9 LV_POWERTR-333.000 1 61.0 -7.7 61.4 0.03 0.03
1 1
TO 10 LV_POWERTR-433.000 1 60.9 -7.8 61.4 0.03 0.04
1 1
TO 12 50MWBLK2_1 33.000 1 -24.4 3.1 24.6 0.01 0.01
1 1
TO 13 50MWBLK2_2 33.000 1 -24.4 2.9 24.6 0.01 0.01
1 1
TO 70 HV_AUXTRPSS 33.000 1 0.1 0.0 0.1 0.00 0.00
1 1
TO 101 50MWBLK4_1 33.000 1 -24.4 2.9 24.6 0.01 0.01
1 1
TO 102 50MWBLK4_2 33.000 1 -24.5 2.8 24.6 0.01 0.01
1 1
TO 201 50MWBLK3_1 33.000 1 -24.4 3.1 24.6 0.01 0.01
1 1
TO 202 50MWBLK3_2 33.000 1 -24.4 3.0 24.6 0.01 0.01
1 1
TO 301 50MWBLK1_1 33.000 1 -24.4 3.0 24.6 0.01 0.01
1 1
TO 302 50MWBLK1_2 33.000 1 -24.4 3.1 24.6 0.01 0.01
1 1
TO 401 50MWBLK5_1 33.000 1 -24.4 3.3 24.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 105 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 402 50MWBLK5_2 33.000 1 -24.4 3.2 24.6 0.01 0.01


1 1

BUS 12 50MWBLK2_1 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 12
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.1 24.6 0.01 0.01
1 1
TO 14 HV_IDT1_16 33.000 1 -12.2 1.6 12.3 0.03 0.03
1 1
TO 16 HV_IDT1_17 33.000 1 -12.2 1.5 12.3 0.03 0.03
1 1

BUS 13 50MWBLK2_2 33.000 CKT MW MVAR MVA % 0.9862PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 13
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.0 24.6 0.01 0.01
1 1
TO 18 HV_IDT1_18 33.000 1 -12.2 1.5 12.3 0.02 0.02
1 1
TO 20 HV_IDT1_19 33.000 1 -12.2 1.5 12.3 0.01 0.01
1 1

BUS 14 HV_IDT1_16 33.000 CKT MW MVAR MVA % 0.9884PU 5.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 14
32.618KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 12.2 -1.7 12.4 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_16 WND 1 1 -6.1 0.9 6.2 99 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 106 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

BUS 16 HV_IDT1_17 33.000 CKT MW MVAR MVA % 0.9880PU 5.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 16
32.604KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 12.2 -1.7 12.4 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_17 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_17 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 18 HV_IDT1_18 33.000 CKT MW MVAR MVA % 0.9876PU 5.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 18
32.590KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 12.2 -1.6 12.3 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_18 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_18 WND 1 1 -6.1 0.8 6.2 1.0000LK 0.11 0.50

BUS 20 HV_IDT1_19 33.000 CKT MW MVAR MVA % 0.9872PU 5.42 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 20
32.577KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 12.2 -1.5 12.3 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_19 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_19 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 22 LV1_IDT1_16 0.6000 CKT MW MVAR MVA % 0.9982PU 40.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 22

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 107 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5989KV MW MVAR
1 1
TO 38 INV1_IDT1_160.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 54 HV_AUXTR1_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 2 1 3.1 -0.2 3.1 100 1.0000LK 30.00LK 0.11 0.50

BUS 23 LV2_IDT1_16 0.6000 CKT MW MVAR MVA % 0.9986PU 40.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 23
0.5991KV MW MVAR
1 1
TO 39 INV2_IDT1_160.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 3 1 3.1 -0.2 3.1 100 1.0000LK 30.00LK 0.11 0.50

BUS 24 LV1_IDT2_16 0.6000 CKT MW MVAR MVA % 0.9982PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 24
0.5989KV MW MVAR
1 1
TO 40 INV1_IDT2_160.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_16 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 25 LV2_IDT2_16 0.6000 CKT MW MVAR MVA % 0.9986PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 25
0.5991KV MW MVAR
1 1
TO 41 INV2_IDT2_160.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 55 HV_AUXTR2_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 108 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 26 LV1_IDT1_17 0.6000 CKT MW MVAR MVA % 0.9982PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 26
0.5989KV MW MVAR
1 1
TO 42 INV1_IDT1_170.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 56 HV_AUXTR1_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 27 LV2_IDT1_17 0.6000 CKT MW MVAR MVA % 0.9986PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 27
0.5991KV MW MVAR
1 1
TO 43 INV2_IDT1_170.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 28 LV1_IDT2_17 0.6000 CKT MW MVAR MVA % 0.9982PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 28
0.5989KV MW MVAR
1 1
TO 44 INV1_IDT2_170.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_17 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 29 LV2_IDT2_17 0.6000 CKT MW MVAR MVA % 0.9986PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 29
0.5991KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 109 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 45 INV2_IDT2_170.6000 1 -3.1 0.2 3.1 0.00 0.00


1 1
TO 57 HV_AUXTR2_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_17 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 30 LV1_IDT1_18 0.6000 CKT MW MVAR MVA % 0.9982PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 30
0.5989KV MW MVAR
1 1
TO 46 INV1_IDT1_180.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 58 HV_AUXTR1_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 2 1 3.1 -0.2 3.1 100 1.0000LK 0.11 0.50

BUS 31 LV2_IDT1_18 0.6000 CKT MW MVAR MVA % 0.9985PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 31
0.5991KV MW MVAR
1 1
TO 47 INV2_IDT1_180.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 32 LV1_IDT2_18 0.6000 CKT MW MVAR MVA % 0.9982PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 32
0.5989KV MW MVAR
1 1
TO 48 INV1_IDT2_180.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_18 WND 2 1 3.1 -0.2 3.1 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 110 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 33 LV2_IDT2_18 0.6000 CKT MW MVAR MVA % 0.9985PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 33
0.5991KV MW MVAR
1 1
TO 49 INV2_IDT2_180.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 59 HV_AUXTR2_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_18 WND 3 1 3.1 -0.1 3.1 1.0000LK 0.11 0.50

BUS 34 LV1_IDT1_19 0.6000 CKT MW MVAR MVA % 0.9982PU 10.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 34
0.5989KV MW MVAR
1 1
TO 50 INV1_IDT1_190.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 60 HV_AUXTR1_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 2 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 35 LV2_IDT1_19 0.6000 CKT MW MVAR MVA % 0.9985PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 35
0.5991KV MW MVAR
1 1
TO 51 INV2_IDT1_190.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 36 LV1_IDT2_19 0.6000 CKT MW MVAR MVA % 0.9982PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 36
0.5989KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 111 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 52 INV1_IDT2_190.6000 1 -3.1 0.1 3.1 0.01 0.00


1 1
TO 3WNDTR IDT2_TR_19 WND 2 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 37 LV2_IDT2_19 0.6000 CKT MW MVAR MVA % 0.9985PU 10.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 37
0.5991KV MW MVAR
1 1
TO 53 INV2_IDT2_190.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 61 HV_AUXTR2_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_19 WND 3 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 38 INV1_IDT1_160.6000 CKT MW MVAR MVA % 1.0000PU 40.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 38
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 39 INV2_IDT1_160.6000 CKT MW MVAR MVA % 1.0000PU 40.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 39
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 23 LV2_IDT1_16 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 40 INV1_IDT2_160.6000 CKT MW MVAR MVA % 1.0000PU 10.31 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 40
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 112 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 24 LV1_IDT2_16 0.6000 1 3.1 -0.2 3.1 0.01 0.00


1 1

BUS 41 INV2_IDT2_160.6000 CKT MW MVAR MVA % 1.0000PU 10.28 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 41
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 42 INV1_IDT1_170.6000 CKT MW MVAR MVA % 1.0000PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 42
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 43 INV2_IDT1_170.6000 CKT MW MVAR MVA % 1.0000PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 43
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 27 LV2_IDT1_17 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 44 INV1_IDT2_170.6000 CKT MW MVAR MVA % 1.0000PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 44
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 28 LV1_IDT2_17 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 113 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 45 INV2_IDT2_170.6000 CKT MW MVAR MVA % 1.0000PU 10.25 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 45
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 29 LV2_IDT2_17 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 46 INV1_IDT1_180.6000 CKT MW MVAR MVA % 1.0000PU 10.23 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 46
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 47 INV2_IDT1_180.6000 CKT MW MVAR MVA % 1.0000PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 47
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 31 LV2_IDT1_18 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 48 INV1_IDT2_180.6000 CKT MW MVAR MVA % 1.0000PU 10.24 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 48
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 32 LV1_IDT2_18 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 49 INV2_IDT2_180.6000 CKT MW MVAR MVA % 1.0000PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 49
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 114 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 33 LV2_IDT2_18 0.6000 1 3.1 -0.1 3.1 0.00 0.00


1 1

BUS 50 INV1_IDT1_190.6000 CKT MW MVAR MVA % 1.0000PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 50
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 51 INV2_IDT1_190.6000 CKT MW MVAR MVA % 1.0000PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 51
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 35 LV2_IDT1_19 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 52 INV1_IDT2_190.6000 CKT MW MVAR MVA % 1.0000PU 10.20 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 52
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 36 LV1_IDT2_19 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 53 INV2_IDT2_190.6000 CKT MW MVAR MVA % 1.0000PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 53
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 115 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 54 HV_AUXTR1_160.6000 CKT MW MVAR MVA % 0.9982PU 40.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 54
0.5989KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 62 LV_AUXTR1_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 55 HV_AUXTR2_160.6000 CKT MW MVAR MVA % 0.9986PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 55
0.5991KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 63 LV_AUXTR2_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 56 HV_AUXTR1_170.6000 CKT MW MVAR MVA % 0.9982PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 56
0.5989KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 64 LV_AUXTR1_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 57 HV_AUXTR2_170.6000 CKT MW MVAR MVA % 0.9986PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 57
0.5991KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 116 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 29 LV2_IDT2_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 65 LV_AUXTR2_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 58 HV_AUXTR1_180.6000 CKT MW MVAR MVA % 0.9982PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 58
0.5989KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 66 LV_AUXTR1_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 59 HV_AUXTR2_180.6000 CKT MW MVAR MVA % 0.9985PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 59
0.5991KV MW MVAR
1 1
TO 33 LV2_IDT2_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 67 LV_AUXTR2_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 60 HV_AUXTR1_190.6000 CKT MW MVAR MVA % 0.9982PU 10.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 60
0.5989KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 68 LV_AUXTR1_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 117 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 61 HV_AUXTR2_190.6000 CKT MW MVAR MVA % 0.9985PU 10.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 61
0.5991KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 69 LV_AUXTR2_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 62 LV_AUXTR1_160.4150 CKT MW MVAR MVA % 0.9900PU 38.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 62
0.4108KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 54 HV_AUXTR1_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 63 LV_AUXTR2_160.4150 CKT MW MVAR MVA % 0.9904PU 8.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 63
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 55 HV_AUXTR2_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 64 LV_AUXTR1_170.4150 CKT MW MVAR MVA % 0.9900PU 8.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 64
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 56 HV_AUXTR1_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 118 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 65 LV_AUXTR2_170.4150 CKT MW MVAR MVA % 0.9904PU 8.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 65
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 57 HV_AUXTR2_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 66 LV_AUXTR1_180.4150 CKT MW MVAR MVA % 0.9900PU 8.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 66
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 58 HV_AUXTR1_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 67 LV_AUXTR2_180.4150 CKT MW MVAR MVA % 0.9904PU 8.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 67
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 59 HV_AUXTR2_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 68 LV_AUXTR1_190.4150 CKT MW MVAR MVA % 0.9900PU 8.71 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 68
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 60 HV_AUXTR1_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 119 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 69 LV_AUXTR2_190.4150 CKT MW MVAR MVA % 0.9904PU 8.71 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 69
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 61 HV_AUXTR2_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 70 HV_AUXTRPSS 33.000 CKT MW MVAR MVA % 0.9858PU 5.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 70
32.533KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.1 -0.0 0.1 0.00 0.00
1 1
TO 71 LV_AUXTRPSS 0.4150 1 0.1 0.0 0.1 1.0000LK 0.00 0.00
1 1

BUS 71 LV_AUXTRPSS 0.4150 CKT MW MVAR MVA % 0.9819PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 71
0.4075KV MW MVAR
1 1
TO LOAD-PQ 0.1 0.0 0.1
TO 70 HV_AUXTRPSS 33.000 1 -0.1 -0.0 0.1 1.0000UN 0.00 0.00
1 1

BUS 101 50MWBLK4_1 33.000 CKT MW MVAR MVA % 0.9862PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 101
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.5 -2.9 24.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 120 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 103 HV_IDT1_11 33.000 1 -12.2 1.5 12.3 0.02 0.02


1 1
TO 104 HV_IDT1_14 33.000 1 -12.2 1.4 12.3 0.01 0.01
1 1

BUS 102 50MWBLK4_2 33.000 CKT MW MVAR MVA % 0.9862PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 102
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.5 -2.9 24.6 0.01 0.01
1 1
TO 105 HV_IDT1_15 33.000 1 -12.2 1.4 12.3 0.00 0.00
1 1
TO 106 HV_IDT1_20 33.000 1 -12.2 1.5 12.3 0.01 0.01
1 1

BUS 103 HV_IDT1_11 33.000 CKT MW MVAR MVA % 0.9872PU 5.42 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 103
32.578KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 12.2 -1.5 12.3 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_11 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_11 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 104 HV_IDT1_14 33.000 CKT MW MVAR MVA % 0.9867PU 5.39 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 104
32.562KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 12.2 -1.5 12.3 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_14 WND 1 1 -6.1 0.7 6.2 98 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 121 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_14 WND 1 1 -6.1 0.7 6.2 98 1.0000LK 0.11 0.50

BUS 105 HV_IDT1_15 33.000 CKT MW MVAR MVA % 0.9865PU 5.37 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 105
32.554KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 12.2 -1.4 12.3 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 1 1 -6.1 0.7 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_15 WND 1 1 -6.1 0.7 6.2 98 1.0000LK 0.11 0.50

BUS 106 HV_IDT1_20 33.000 CKT MW MVAR MVA % 0.9870PU 5.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 106
32.569KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 12.2 -1.5 12.3 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_20 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_20 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 107 LV1_IDT1_11 0.6000 CKT MW MVAR MVA % 0.9982PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 107
0.5989KV MW MVAR
1 1
TO 123 INV1_IDT1_110.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 139 HV_AUXTR1_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 2 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 108 LV2_IDT1_11 0.6000 CKT MW MVAR MVA % 0.9985PU 10.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 108

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 122 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5991KV MW MVAR
1 1
TO 124 INV2_IDT1_110.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 109 LV1_IDT2_11 0.6000 CKT MW MVAR MVA % 0.9982PU 10.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 109
0.5989KV MW MVAR
1 1
TO 125 INV1_IDT2_110.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_11 WND 2 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 110 LV2_IDT2_11 0.6000 CKT MW MVAR MVA % 0.9985PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 110
0.5991KV MW MVAR
1 1
TO 126 INV2_IDT2_110.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 140 HV_AUXTR2_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_11 WND 3 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 111 LV1_IDT1_14 0.6000 CKT MW MVAR MVA % 0.9982PU 10.07 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 111
0.5989KV MW MVAR
1 1
TO 127 INV1_IDT1_140.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 141 HV_AUXTR1_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 123 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT1_TR_14 WND 2 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 112 LV2_IDT1_14 0.6000 CKT MW MVAR MVA % 0.9985PU 10.07 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 112
0.5991KV MW MVAR
1 1
TO 128 INV2_IDT1_140.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_14 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 113 LV1_IDT2_14 0.6000 CKT MW MVAR MVA % 0.9982PU 10.07 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 113
0.5989KV MW MVAR
1 1
TO 129 INV1_IDT2_140.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_14 WND 2 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 114 LV2_IDT2_14 0.6000 CKT MW MVAR MVA % 0.9985PU 10.07 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 114
0.5991KV MW MVAR
1 1
TO 130 INV2_IDT2_140.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 142 HV_AUXTR2_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_14 WND 3 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 115 LV1_IDT1_15 0.6000 CKT MW MVAR MVA % 0.9982PU 10.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 115
0.5989KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 124 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 131INV1_IDT1_150.6000 1 -3.1 0.1 3.1 0.01 0.00


1 1
TO 143 HV_AUXTR1_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 2 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 116 LV2_IDT1_15 0.6000 CKT MW MVAR MVA % 0.9985PU 10.05 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 116
0.5991KV MW MVAR
1 1
TO 132 INV2_IDT1_150.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 117 LV1_IDT2_15 0.6000 CKT MW MVAR MVA % 0.9982PU 10.05 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 117
0.5989KV MW MVAR
1 1
TO 133 INV1_IDT2_150.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_15 WND 2 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 118 LV2_IDT2_15 0.6000 CKT MW MVAR MVA % 0.9985PU 10.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 118
0.5991KV MW MVAR
1 1
TO 134 INV2_IDT2_150.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 144 HV_AUXTR2_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_15 WND 3 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 125 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 119 LV1_IDT1_20 0.6000 CKT MW MVAR MVA % 0.9982PU 10.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 119
0.5989KV MW MVAR
1 1
TO 135 INV1_IDT1_200.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 145 HV_AUXTR1_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 2 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 120 LV2_IDT1_20 0.6000 CKT MW MVAR MVA % 0.9985PU 10.09 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 120
0.5991KV MW MVAR
1 1
TO 136 INV2_IDT1_200.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 121 LV1_IDT2_20 0.6000 CKT MW MVAR MVA % 0.9982PU 10.09 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 121
0.5989KV MW MVAR
1 1
TO 137 INV1_IDT2_200.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_20 WND 2 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 122 LV2_IDT2_20 0.6000 CKT MW MVAR MVA % 0.9985PU 10.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 122
0.5991KV MW MVAR
1 1
TO 138 INV2_IDT2_200.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 126 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 146 HV_AUXTR2_200.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_20 WND 3 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 123 INV1_IDT1_110.6000 CKT MW MVAR MVA % 1.0000PU 10.20 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 123
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 124 INV2_IDT1_110.6000 CKT MW MVAR MVA % 1.0000PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 124
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 108 LV2_IDT1_11 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 125 INV1_IDT2_110.6000 CKT MW MVAR MVA % 1.0000PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 125
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 109 LV1_IDT2_11 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 126 INV2_IDT2_110.6000 CKT MW MVAR MVA % 1.0000PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 126
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 127 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 127 INV1_IDT1_140.6000 CKT MW MVAR MVA % 1.0000PU 10.16 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 127
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 128 INV2_IDT1_140.6000 CKT MW MVAR MVA % 1.0000PU 10.15 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 128
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 112 LV2_IDT1_14 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 129 INV1_IDT2_140.6000 CKT MW MVAR MVA % 1.0000PU 10.16 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 129
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 113 LV1_IDT2_14 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 130 INV2_IDT2_140.6000 CKT MW MVAR MVA % 1.0000PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 130
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 131 INV1_IDT1_150.6000 CKT MW MVAR MVA % 1.0000PU 10.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 131
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 128 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 115 LV1_IDT1_15 0.6000 1 3.1 -0.1 3.1 0.01 0.00


1 1

BUS 132 INV2_IDT1_150.6000 CKT MW MVAR MVA % 1.0000PU 10.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 132
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 116 LV2_IDT1_15 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 133 INV1_IDT2_150.6000 CKT MW MVAR MVA % 1.0000PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 133
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 117 LV1_IDT2_15 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 134 INV2_IDT2_150.6000 CKT MW MVAR MVA % 1.0000PU 10.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 134
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 135 INV1_IDT1_200.6000 CKT MW MVAR MVA % 1.0000PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 135
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 129 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 136 INV2_IDT1_200.6000 CKT MW MVAR MVA % 1.0000PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 136
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 120 LV2_IDT1_20 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 137 INV1_IDT2_200.6000 CKT MW MVAR MVA % 1.0000PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 137
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 121 LV1_IDT2_20 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 138 INV2_IDT2_200.6000 CKT MW MVAR MVA % 1.0000PU 10.16 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 138
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 139 HV_AUXTR1_110.6000 CKT MW MVAR MVA % 0.9982PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 139
0.5989KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 147 LV_AUXTR1_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 140 HV_AUXTR2_110.6000 CKT MW MVAR MVA % 0.9985PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 140

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 130 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5991KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 148 LV_AUXTR2_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 141 HV_AUXTR1_140.6000 CKT MW MVAR MVA % 0.9982PU 10.07 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 141
0.5989KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 149 LV_AUXTR1_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 142 HV_AUXTR2_140.6000 CKT MW MVAR MVA % 0.9985PU 10.07 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 142
0.5991KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 150 LV_AUXTR2_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 143 HV_AUXTR1_150.6000 CKT MW MVAR MVA % 0.9982PU 10.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 143
0.5989KV MW MVAR
1 1
TO 115 LV1_IDT1_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 131 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 151 LV_AUXTR1_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 144 HV_AUXTR2_150.6000 CKT MW MVAR MVA % 0.9985PU 10.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 144
0.5991KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 152 LV_AUXTR2_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 145 HV_AUXTR1_200.6000 CKT MW MVAR MVA % 0.9982PU 10.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 145
0.5989KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 153 LV_AUXTR1_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 146 HV_AUXTR2_200.6000 CKT MW MVAR MVA % 0.9985PU 10.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 146
0.5991KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 154 LV_AUXTR2_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 147 LV_AUXTR1_110.4150 CKT MW MVAR MVA % 0.9900PU 8.71 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 147

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 132 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 139 HV_AUXTR1_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 148 LV_AUXTR2_110.4150 CKT MW MVAR MVA % 0.9904PU 8.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 148
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 140 HV_AUXTR2_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 149 LV_AUXTR1_140.4150 CKT MW MVAR MVA % 0.9900PU 8.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 149
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 141 HV_AUXTR1_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 150 LV_AUXTR2_140.4150 CKT MW MVAR MVA % 0.9904PU 8.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 150
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 142 HV_AUXTR2_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 151 LV_AUXTR1_150.4150 CKT MW MVAR MVA % 0.9900PU 8.65 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 151

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 133 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 143 HV_AUXTR1_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 152 LV_AUXTR2_150.4150 CKT MW MVAR MVA % 0.9904PU 8.65 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 152
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 144 HV_AUXTR2_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 153 LV_AUXTR1_200.4150 CKT MW MVAR MVA % 0.9900PU 8.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 153
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 145 HV_AUXTR1_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 154 LV_AUXTR2_200.4150 CKT MW MVAR MVA % 0.9904PU 8.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 154
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 146 HV_AUXTR2_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 201 50MWBLK3_1 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 201

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 134 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.1 24.6 0.01 0.01
1 1
TO 203 HV_IDT1_5 33.000 1 -12.2 1.6 12.3 0.04 0.04
1 1
TO 204 HV_IDT1_6 33.000 1 -12.2 1.5 12.3 0.03 0.03
1 1

BUS 202 50MWBLK3_2 33.000 CKT MW MVAR MVA % 0.9862PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 202
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.0 24.6 0.01 0.01
1 1
TO 205 HV_IDT1_7 33.000 1 -12.2 1.5 12.3 0.02 0.02
1 1
TO 206 HV_IDT1_9 33.000 1 -12.2 1.5 12.3 0.02 0.02
1 1

BUS 203 HV_IDT1_5 33.000 CKT MW MVAR MVA % 0.9886PU 5.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 203
32.623KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 12.2 -1.8 12.4 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_5 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_5 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

BUS 204 HV_IDT1_6 33.000 CKT MW MVAR MVA % 0.9880PU 5.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 204

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 135 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

32.604KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 12.2 -1.7 12.4 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_6 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_6 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 205 HV_IDT1_7 33.000 CKT MW MVAR MVA % 0.9877PU 5.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 205
32.593KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 12.2 -1.6 12.3 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_7 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_7 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 206 HV_IDT1_9 33.000 CKT MW MVAR MVA % 0.9873PU 5.43 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 206
32.582KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 12.2 -1.6 12.3 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_9 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_9 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 207 LV1_IDT1_5 0.6000 CKT MW MVAR MVA % 0.9982PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 207
0.5989KV MW MVAR
1 1
TO 223 INV1_IDT1_5 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 136 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 239 HV_AUXTR1_5 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT1_TR_5 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 208 LV2_IDT1_5 0.6000 CKT MW MVAR MVA % 0.9986PU 10.23 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 208
0.5991KV MW MVAR
1 1
TO 224INV2_IDT1_5 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_5 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 209 LV1_IDT2_5 0.6000 CKT MW MVAR MVA % 0.9982PU 10.23 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 209
0.5989KV MW MVAR
1 1
TO 225 INV1_IDT2_5 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_5 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 210 LV2_IDT2_5 0.6000 CKT MW MVAR MVA % 0.9986PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 210
0.5991KV MW MVAR
1 1
TO 226 INV2_IDT2_5 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 240 HV_AUXTR2_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_5 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 211 LV1_IDT1_6 0.6000 CKT MW MVAR MVA % 0.9982PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 211

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 137 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5989KV MW MVAR
1 1
TO 227 INV1_IDT1_6 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 241 HV_AUXTR1_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 212 LV2_IDT1_6 0.6000 CKT MW MVAR MVA % 0.9986PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 212
0.5991KV MW MVAR
1 1
TO 228 INV2_IDT1_6 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 213 LV1_IDT2_6 0.6000 CKT MW MVAR MVA % 0.9982PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 213
0.5989KV MW MVAR
1 1
TO 229 INV1_IDT2_6 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_6 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 214 LV2_IDT2_6 0.6000 CKT MW MVAR MVA % 0.9986PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 214
0.5991KV MW MVAR
1 1
TO 230 INV2_IDT2_6 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 242 HV_AUXTR2_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 138 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_6 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 215 LV1_IDT1_7 0.6000 CKT MW MVAR MVA % 0.9982PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 215
0.5989KV MW MVAR
1 1
TO 231 INV1_IDT1_7 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 243 HV_AUXTR1_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 2 1 3.1 -0.2 3.1 100 1.0000LK 0.11 0.50

BUS 216 LV2_IDT1_7 0.6000 CKT MW MVAR MVA % 0.9986PU 10.15 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 216
0.5991KV MW MVAR
1 1
TO 232 INV2_IDT1_7 0.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 217 LV1_IDT2_7 0.6000 CKT MW MVAR MVA % 0.9982PU 10.15 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 217
0.5989KV MW MVAR
1 1
TO 233 INV1_IDT2_7 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_7 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 218 LV2_IDT2_7 0.6000 CKT MW MVAR MVA % 0.9986PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 218
0.5991KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 139 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 234INV2_IDT2_7 0.6000 1 -3.1 0.1 3.1 0.00 0.00


1 1
TO 244 HV_AUXTR2_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_7 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 219 LV1_IDT1_9 0.6000 CKT MW MVAR MVA % 0.9982PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 219
0.5989KV MW MVAR
1 1
TO 235 INV1_IDT1_9 0.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 245 HV_AUXTR1_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 2 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 220 LV2_IDT1_9 0.6000 CKT MW MVAR MVA % 0.9985PU 10.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 220
0.5991KV MW MVAR
1 1
TO 236 INV2_IDT1_9 0.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 221 LV1_IDT2_9 0.6000 CKT MW MVAR MVA % 0.9982PU 10.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 221
0.5989KV MW MVAR
1 1
TO 237 INV1_IDT2_9 0.6000 1 -3.1 0.1 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_9 WND 2 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 140 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 222 LV2_IDT2_9 0.6000 CKT MW MVAR MVA % 0.9985PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 222
0.5991KV MW MVAR
1 1
TO 238 INV2_IDT2_9 0.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 246 HV_AUXTR2_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_9 WND 3 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 223 INV1_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 223
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 207 LV1_IDT1_5 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 224 INV2_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.31 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 224
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 208 LV2_IDT1_5 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 225 INV1_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 225
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 209 LV1_IDT2_5 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 141 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 226 INV2_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 226
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 227 INV1_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 227
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 228 INV2_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 228
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 212 LV2_IDT1_6 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 229 INV1_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 229
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 213 LV1_IDT2_6 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 230 INV2_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.25 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 230
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 142 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 214 LV2_IDT2_6 0.6000 1 3.1 -0.2 3.1 0.00 0.00


1 1

BUS 231 INV1_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.24 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 231
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 232 INV2_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.23 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 232
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 216 LV2_IDT1_7 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 233 INV1_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.24 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 233
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 217 LV1_IDT2_7 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 234 INV2_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 234
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 143 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 235 INV1_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 235
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 236 INV2_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.20 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 236
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 220 LV2_IDT1_9 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 237 INV1_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 237
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 221 LV1_IDT2_9 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 238 INV2_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 238
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 222 LV2_IDT2_9 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 239 HV_AUXTR1_5 0.6000 CKT MW MVAR MVA % 0.9982PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 239
0.5989KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 144 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 207 LV1_IDT1_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 247 LV_AUXTR1_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 240 HV_AUXTR2_5 0.6000 CKT MW MVAR MVA % 0.9986PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 240
0.5991KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 248 LV_AUXTR2_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 241 HV_AUXTR1_6 0.6000 CKT MW MVAR MVA % 0.9982PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 241
0.5989KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 249 LV_AUXTR1_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 242 HV_AUXTR2_6 0.6000 CKT MW MVAR MVA % 0.9986PU 10.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 242
0.5991KV MW MVAR
1 1
TO 214 LV2_IDT2_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 250 LV_AUXTR2_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 145 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 243 HV_AUXTR1_7 0.6000 CKT MW MVAR MVA % 0.9982PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 243
0.5989KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 251 LV_AUXTR1_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 244 HV_AUXTR2_7 0.6000 CKT MW MVAR MVA % 0.9986PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 244
0.5991KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 252 LV_AUXTR2_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 245 HV_AUXTR1_9 0.6000 CKT MW MVAR MVA % 0.9982PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 245
0.5989KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 253 LV_AUXTR1_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 246 HV_AUXTR2_9 0.6000 CKT MW MVAR MVA % 0.9985PU 10.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 246
0.5991KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 146 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 222 LV2_IDT2_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 254 LV_AUXTR2_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 247 LV_AUXTR1_5 0.4150 CKT MW MVAR MVA % 0.9901PU 8.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 247
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 239 HV_AUXTR1_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 248 LV_AUXTR2_5 0.4150 CKT MW MVAR MVA % 0.9904PU 8.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 248
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 240 HV_AUXTR2_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 249 LV_AUXTR1_6 0.4150 CKT MW MVAR MVA % 0.9901PU 8.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 249
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 241 HV_AUXTR1_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 250 LV_AUXTR2_6 0.4150 CKT MW MVAR MVA % 0.9904PU 8.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 250

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 147 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 242 HV_AUXTR2_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 251 LV_AUXTR1_7 0.4150 CKT MW MVAR MVA % 0.9900PU 8.75 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 251
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 243 HV_AUXTR1_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 252 LV_AUXTR2_7 0.4150 CKT MW MVAR MVA % 0.9904PU 8.75 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 252
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 244 HV_AUXTR2_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 253 LV_AUXTR1_9 0.4150 CKT MW MVAR MVA % 0.9900PU 8.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 253
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 245 HV_AUXTR1_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 254 LV_AUXTR2_9 0.4150 CKT MW MVAR MVA % 0.9904PU 8.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 254

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 148 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 246 HV_AUXTR2_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 301 50MWBLK1_1 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 301
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.1 24.6 0.01 0.01
1 1
TO 303 HV_IDT1_10 33.000 1 -12.2 1.5 12.3 0.02 0.02
1 1
TO 304 HV_IDT1_8 33.000 1 -12.2 1.6 12.3 0.03 0.03
1 1

BUS 302 50MWBLK1_2 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 302
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.2 24.6 0.01 0.01
1 1
TO 305 HV_IDT1_13 33.000 1 -12.2 1.6 12.3 0.03 0.03
1 1
TO 306 HV_IDT1_12 33.000 1 -12.2 1.6 12.3 0.03 0.03
1 1
TO 360 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 303 HV_IDT1_10 33.000 CKT MW MVAR MVA % 0.9875PU 5.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 303

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 149 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

32.588KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 12.2 -1.6 12.3 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_10 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_10 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 304 HV_IDT1_8 33.000 CKT MW MVAR MVA % 0.9881PU 5.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 304
32.607KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 12.2 -1.7 12.4 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_8 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_8 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 305 HV_IDT1_13 33.000 CKT MW MVAR MVA % 0.9881PU 5.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 305
32.609KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 12.2 -1.7 12.4 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_13 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_13 WND 1 1 -6.1 0.8 6.2 98 1.0000LK 0.11 0.50

BUS 306 HV_IDT1_12 33.000 CKT MW MVAR MVA % 0.9885PU 5.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 306
32.620KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 12.2 -1.7 12.4 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_12 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 150 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_12 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

BUS 307 LV1_IDT1_10 0.6000 CKT MW MVAR MVA % 0.9982PU 10.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 307
0.5989KV MW MVAR
1 1
TO 323 INV1_IDT1_100.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 339 HV_AUXTR1_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 2 1 3.1 -0.2 3.1 100 1.0000LK 0.11 0.50

BUS 308 LV2_IDT1_10 0.6000 CKT MW MVAR MVA % 0.9986PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 308
0.5991KV MW MVAR
1 1
TO 324 INV2_IDT1_100.6000 1 -3.1 0.1 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 3 1 3.1 -0.1 3.1 101 1.0000LK 0.11 0.50

BUS 309 LV1_IDT2_10 0.6000 CKT MW MVAR MVA % 0.9982PU 10.14 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 309
0.5989KV MW MVAR
1 1
TO 325 INV1_IDT2_100.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_10 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 310 LV2_IDT2_10 0.6000 CKT MW MVAR MVA % 0.9986PU 10.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 310
0.5991KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 151 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 326INV2_IDT2_100.6000 1 -3.1 0.1 3.1 0.00 0.00


1 1
TO 340 HV_AUXTR2_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_10 WND 3 1 3.1 -0.1 3.1 100 1.0000LK 0.11 0.50

BUS 311 LV1_IDT1_8 0.6000 CKT MW MVAR MVA % 0.9982PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 311
0.5989KV MW MVAR
1 1
TO 327 INV1_IDT1_8 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 341 HV_AUXTR1_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 312 LV2_IDT1_8 0.6000 CKT MW MVAR MVA % 0.9986PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 312
0.5991KV MW MVAR
1 1
TO 328 INV2_IDT1_8 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 313 LV1_IDT2_8 0.6000 CKT MW MVAR MVA % 0.9982PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 313
0.5989KV MW MVAR
1 1
TO 329 INV1_IDT2_8 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_8 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 152 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 314 LV2_IDT2_8 0.6000 CKT MW MVAR MVA % 0.9986PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 314
0.5991KV MW MVAR
1 1
TO 330 INV2_IDT2_8 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 342 HV_AUXTR2_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_8 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 315 LV1_IDT1_13 0.6000 CKT MW MVAR MVA % 0.9982PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 315
0.5989KV MW MVAR
1 1
TO 331 INV1_IDT1_130.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 343 HV_AUXTR1_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 316 LV2_IDT1_13 0.6000 CKT MW MVAR MVA % 0.9986PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 316
0.5991KV MW MVAR
1 1
TO 332 INV2_IDT1_130.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 317 LV1_IDT2_13 0.6000 CKT MW MVAR MVA % 0.9982PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 317
0.5989KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 153 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 333 INV1_IDT2_130.6000 1 -3.1 0.2 3.1 0.01 0.00


1 1
TO 3WNDTR IDT2_TR_13 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 318 LV2_IDT2_13 0.6000 CKT MW MVAR MVA % 0.9986PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 318
0.5991KV MW MVAR
1 1
TO 334INV2_IDT2_130.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 344 HV_AUXTR2_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_13 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 319 LV1_IDT1_12 0.6000 CKT MW MVAR MVA % 0.9982PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 319
0.5989KV MW MVAR
1 1
TO 335 INV1_IDT1_120.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 345 HV_AUXTR1_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 320 LV2_IDT1_12 0.6000 CKT MW MVAR MVA % 0.9986PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 320
0.5991KV MW MVAR
1 1
TO 336 INV2_IDT1_120.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 154 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 321 LV1_IDT2_12 0.6000 CKT MW MVAR MVA % 0.9982PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 321
0.5989KV MW MVAR
1 1
TO 337 INV1_IDT2_120.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_12 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 322 LV2_IDT2_12 0.6000 CKT MW MVAR MVA % 0.9986PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 322
0.5991KV MW MVAR
1 1
TO 338 INV2_IDT2_120.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 346 HV_AUXTR2_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_12 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 323 INV1_IDT1_100.6000 CKT MW MVAR MVA % 1.0000PU 10.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 323
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 3.1 -0.1 3.1 0.01 0.00
1 1

BUS 324 INV2_IDT1_100.6000 CKT MW MVAR MVA % 1.0000PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 324
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 308 LV2_IDT1_10 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 155 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 325 INV1_IDT2_100.6000 CKT MW MVAR MVA % 1.0000PU 10.23 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 325
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 309 LV1_IDT2_10 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 326 INV2_IDT2_100.6000 CKT MW MVAR MVA % 1.0000PU 10.20 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 326
FROM GENERATION 3.1 -0.1R 3.1 100 0.6000KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 3.1 -0.1 3.1 0.00 0.00
1 1

BUS 327 INV1_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 327
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 328 INV2_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 328
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 312 LV2_IDT1_8 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 329 INV1_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.28 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 329
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 156 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 313 LV1_IDT2_8 0.6000 1 3.1 -0.2 3.1 0.01 0.00


1 1

BUS 330 INV2_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 330
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 331 INV1_IDT1_130.6000 CKT MW MVAR MVA % 1.0000PU 10.28 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 331
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 332 INV2_IDT1_130.6000 CKT MW MVAR MVA % 1.0000PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 332
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 316 LV2_IDT1_13 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 333 INV1_IDT2_130.6000 CKT MW MVAR MVA % 1.0000PU 10.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 333
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 317 LV1_IDT2_13 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 157 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 334 INV2_IDT2_130.6000 CKT MW MVAR MVA % 1.0000PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 334
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 335 INV1_IDT1_120.6000 CKT MW MVAR MVA % 1.0000PU 10.31 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 335
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 336 INV2_IDT1_120.6000 CKT MW MVAR MVA % 1.0000PU 10.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 336
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 320 LV2_IDT1_12 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 337 INV1_IDT2_120.6000 CKT MW MVAR MVA % 1.0000PU 10.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 337
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 321 LV1_IDT2_12 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 338 INV2_IDT2_120.6000 CKT MW MVAR MVA % 1.0000PU 10.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 338
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 158 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 322 LV2_IDT2_12 0.6000 1 3.1 -0.2 3.1 0.00 0.00


1 1

BUS 339 HV_AUXTR1_100.6000 CKT MW MVAR MVA % 0.9982PU 10.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 339
0.5989KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 347 LV_AUXTR1_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 340 HV_AUXTR2_100.6000 CKT MW MVAR MVA % 0.9986PU 10.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 340
0.5991KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 348 LV_AUXTR2_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 341 HV_AUXTR1_8 0.6000 CKT MW MVAR MVA % 0.9982PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 341
0.5989KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 349 LV_AUXTR1_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 342 HV_AUXTR2_8 0.6000 CKT MW MVAR MVA % 0.9986PU 10.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 342

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 159 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5991KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 350 LV_AUXTR2_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 343 HV_AUXTR1_130.6000 CKT MW MVAR MVA % 0.9982PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 343
0.5989KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 351 LV_AUXTR1_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 344 HV_AUXTR2_130.6000 CKT MW MVAR MVA % 0.9986PU 10.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 344
0.5991KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 352 LV_AUXTR2_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 345 HV_AUXTR1_120.6000 CKT MW MVAR MVA % 0.9982PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 345
0.5989KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 160 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 353 LV_AUXTR1_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 346 HV_AUXTR2_120.6000 CKT MW MVAR MVA % 0.9986PU 10.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 346
0.5991KV MW MVAR
1 1
TO 322 LV2_IDT2_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 354 LV_AUXTR2_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 347 LV_AUXTR1_100.4150 CKT MW MVAR MVA % 0.9900PU 8.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 347
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 339 HV_AUXTR1_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 348 LV_AUXTR2_100.4150 CKT MW MVAR MVA % 0.9904PU 8.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 348
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 340 HV_AUXTR2_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 349 LV_AUXTR1_8 0.4150 CKT MW MVAR MVA % 0.9901PU 8.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 349
0.4109KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 161 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 341 HV_AUXTR1_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 350 LV_AUXTR2_8 0.4150 CKT MW MVAR MVA % 0.9904PU 8.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 350
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 342 HV_AUXTR2_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 351 LV_AUXTR1_130.4150 CKT MW MVAR MVA % 0.9901PU 8.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 351
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 343 HV_AUXTR1_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 352 LV_AUXTR2_130.4150 CKT MW MVAR MVA % 0.9904PU 8.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 352
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 344 HV_AUXTR2_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 353 LV_AUXTR1_120.4150 CKT MW MVAR MVA % 0.9901PU 8.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 353
0.4109KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 162 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 345 HV_AUXTR1_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 354 LV_AUXTR2_120.4150 CKT MW MVAR MVA % 0.9904PU 8.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 354
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 346 HV_AUXTR2_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 360 HV_AUXTR33 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 360
32.543KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 361 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 361 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 0.9815PU 4.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 361
0.4073KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 360 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 401 50MWBLK5_1 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 401

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 163 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.3 24.6 0.01 0.01
1 1
TO 403 HV_IDT1_1 33.000 1 -12.2 1.7 12.3 0.05 0.05
1 1
TO 404 HV_IDT1_2 33.000 1 -12.2 1.6 12.3 0.04 0.04
1 1

BUS 402 50MWBLK5_2 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 402
32.543KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.4 -3.3 24.6 0.01 0.01
1 1
TO 405 HV_IDT1_3 33.000 1 -12.2 1.6 12.3 0.04 0.04
1 1
TO 406 HV_IDT1_4 33.000 1 -12.2 1.6 12.3 0.04 0.04
1 1
TO 460 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 403 HV_IDT1_1 33.000 CKT MW MVAR MVA % 0.9894PU 5.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 403
32.649KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 12.2 -1.9 12.4 0.05 0.05
1 1
TO 3WNDTR IDT1_TR_1 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_1 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 164 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 404 HV_IDT1_2 33.000 CKT MW MVAR MVA % 0.9890PU 5.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 404
32.637KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 12.2 -1.8 12.4 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_2 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_2 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

BUS 405 HV_IDT1_3 33.000 CKT MW MVAR MVA % 0.9890PU 5.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 405
32.635KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 12.2 -1.8 12.4 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_3 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_3 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

BUS 406 HV_IDT1_4 33.000 CKT MW MVAR MVA % 0.9891PU 5.57 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 406
32.642KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 12.2 -1.8 12.4 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_4 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50
TO 3WNDTR IDT2_TR_4 WND 1 1 -6.1 0.9 6.2 98 1.0000LK 0.11 0.50

BUS 407 LV1_IDT1_1 0.6000 CKT MW MVAR MVA % 0.9982PU 10.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 407
0.5989KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 165 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 423INV1_IDT1_1 0.6000 1 -3.1 0.2 3.1 0.01 0.00


1 1
TO 439 HV_AUXTR1_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 408 LV2_IDT1_1 0.6000 CKT MW MVAR MVA % 0.9986PU 10.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 408
0.5991KV MW MVAR
1 1
TO 424 INV2_IDT1_1 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 409 LV1_IDT2_1 0.6000 CKT MW MVAR MVA % 0.9983PU 10.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 409
0.5990KV MW MVAR
1 1
TO 425 INV1_IDT2_1 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_1 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 410 LV2_IDT2_1 0.6000 CKT MW MVAR MVA % 0.9986PU 10.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 410
0.5991KV MW MVAR
1 1
TO 426 INV2_IDT2_1 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 440 HV_AUXTR2_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_1 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 166 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 411 LV1_IDT1_2 0.6000 CKT MW MVAR MVA % 0.9982PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 411
0.5989KV MW MVAR
1 1
TO 427 INV1_IDT1_2 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 441 HV_AUXTR1_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 412 LV2_IDT1_2 0.6000 CKT MW MVAR MVA % 0.9986PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 412
0.5991KV MW MVAR
1 1
TO 428 INV2_IDT1_2 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 413 LV1_IDT2_2 0.6000 CKT MW MVAR MVA % 0.9982PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 413
0.5989KV MW MVAR
1 1
TO 429 INV1_IDT2_2 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_2 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 414 LV2_IDT2_2 0.6000 CKT MW MVAR MVA % 0.9986PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 414
0.5991KV MW MVAR
1 1
TO 430 INV2_IDT2_2 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 167 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 442 HV_AUXTR2_2 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_2 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 415 LV1_IDT1_3 0.6000 CKT MW MVAR MVA % 0.9982PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 415
0.5989KV MW MVAR
1 1
TO 431INV1_IDT1_3 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 443 HV_AUXTR1_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 416 LV2_IDT1_3 0.6000 CKT MW MVAR MVA % 0.9986PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 416
0.5991KV MW MVAR
1 1
TO 432 INV2_IDT1_3 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 417 LV1_IDT2_3 0.6000 CKT MW MVAR MVA % 0.9982PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 417
0.5989KV MW MVAR
1 1
TO 433 INV1_IDT2_3 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 3WNDTR IDT2_TR_3 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 418 LV2_IDT2_3 0.6000 CKT MW MVAR MVA % 0.9986PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 418

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 168 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5991KV MW MVAR
1 1
TO 434 INV2_IDT2_3 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 444 HV_AUXTR2_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_3 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 419 LV1_IDT1_4 0.6000 CKT MW MVAR MVA % 0.9982PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 419
0.5989KV MW MVAR
1 1
TO 435 INV1_IDT1_4 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1
TO 445 HV_AUXTR1_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 420 LV2_IDT1_4 0.6000 CKT MW MVAR MVA % 0.9986PU 10.28 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 420
0.5991KV MW MVAR
1 1
TO 436 INV2_IDT1_4 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 421 LV1_IDT2_4 0.6000 CKT MW MVAR MVA % 0.9982PU 10.28 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 421
0.5989KV MW MVAR
1 1
TO 437 INV1_IDT2_4 0.6000 1 -3.1 0.2 3.1 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 169 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_4 WND 2 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 422 LV2_IDT2_4 0.6000 CKT MW MVAR MVA % 0.9986PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 422
0.5991KV MW MVAR
1 1
TO 438 INV2_IDT2_4 0.6000 1 -3.1 0.2 3.1 0.00 0.00
1 1
TO 446 HV_AUXTR2_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_4 WND 3 1 3.1 -0.2 3.1 101 1.0000LK 0.11 0.50

BUS 423 INV1_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.39 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 423
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 424 INV2_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.38 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 424
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 408 LV2_IDT1_1 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 425 INV1_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 425
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 409 LV1_IDT2_1 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 170 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 426 INV2_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.37 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 426
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 427 INV1_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.35 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 427
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 428 INV2_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 428
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 412 LV2_IDT1_2 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 429 INV1_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.36 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 429
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 413 LV1_IDT2_2 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 430 INV2_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 430

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 171 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR


1 1
TO 414 LV2_IDT2_2 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 431 INV1_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.35 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 431
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 432 INV2_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 432
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 416 LV2_IDT1_3 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 433 INV1_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.36 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 433
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 417 LV1_IDT2_3 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 434 INV2_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.33 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 434
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 172 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 435 INV1_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.37 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 435
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 436 INV2_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.36 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 436
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 420 LV2_IDT1_4 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 437 INV1_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.38 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 437
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 421 LV1_IDT2_4 0.6000 1 3.1 -0.2 3.1 0.01 0.00
1 1

BUS 438 INV2_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.35 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 438
FROM GENERATION 3.1 -0.2R 3.1 100 0.6000KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 3.1 -0.2 3.1 0.00 0.00
1 1

BUS 439 HV_AUXTR1_1 0.6000 CKT MW MVAR MVA % 0.9982PU 10.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 439

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 173 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5989KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 447 LV_AUXTR1_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 440 HV_AUXTR2_1 0.6000 CKT MW MVAR MVA % 0.9986PU 10.29 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 440
0.5991KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 448 LV_AUXTR2_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 441 HV_AUXTR1_2 0.6000 CKT MW MVAR MVA % 0.9982PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 441
0.5989KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 449 LV_AUXTR1_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 442 HV_AUXTR2_2 0.6000 CKT MW MVAR MVA % 0.9986PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 442
0.5991KV MW MVAR
1 1
TO 414 LV2_IDT2_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 174 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 450 LV_AUXTR2_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 443 HV_AUXTR1_3 0.6000 CKT MW MVAR MVA % 0.9982PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 443
0.5989KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 451 LV_AUXTR1_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 444 HV_AUXTR2_3 0.6000 CKT MW MVAR MVA % 0.9986PU 10.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 444
0.5991KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 452 LV_AUXTR2_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 445 HV_AUXTR1_4 0.6000 CKT MW MVAR MVA % 0.9982PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 445
0.5989KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 453 LV_AUXTR1_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 446 HV_AUXTR2_4 0.6000 CKT MW MVAR MVA % 0.9986PU 10.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 446

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 175 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5991KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 454 LV_AUXTR2_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 447 LV_AUXTR1_1 0.4150 CKT MW MVAR MVA % 0.9901PU 8.90 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 447
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 439 HV_AUXTR1_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 448 LV_AUXTR2_1 0.4150 CKT MW MVAR MVA % 0.9904PU 8.90 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 448
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 440 HV_AUXTR2_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 449 LV_AUXTR1_2 0.4150 CKT MW MVAR MVA % 0.9901PU 8.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 449
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 441 HV_AUXTR1_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 176 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 450 LV_AUXTR2_2 0.4150 CKT MW MVAR MVA % 0.9904PU 8.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 450
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 442 HV_AUXTR2_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 451 LV_AUXTR1_3 0.4150 CKT MW MVAR MVA % 0.9901PU 8.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 451
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 443 HV_AUXTR1_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 452 LV_AUXTR2_3 0.4150 CKT MW MVAR MVA % 0.9904PU 8.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 452
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 444 HV_AUXTR2_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 453 LV_AUXTR1_4 0.4150 CKT MW MVAR MVA % 0.9901PU 8.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 453
0.4109KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 445 HV_AUXTR1_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 177 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 454 LV_AUXTR2_4 0.4150 CKT MW MVAR MVA % 0.9904PU 8.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 454
0.4110KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 446 HV_AUXTR2_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 460 HV_AUXTR33 33.000 CKT MW MVAR MVA % 0.9861PU 5.34 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 460
32.543KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 461 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 461 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 0.9815PU 4.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 461
0.4073KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 460 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 178 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

11.2 Night Load Operating Scenario- Active Power and Reactive


Power Flow Results
This section provides the detailed power flow results for night load operating scenario. These
results include MW, MVAr, MVA, Losses MW, Losses MVAr in each feeder of the network along
with the voltage (in kV).

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 179 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 1 220KVPGCILSS220.00 CKT MW MVAR MVA % 1.0000PU 0.00 X--- LOSSES ---X X-
--- AREA -----X X---- ZONE -----X 1
FROM GENERATION 0.4 -1.8R 1.9 1 220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 0.4 -1.8 1.9 0.00 0.00
1 1

BUS 2 220KVPOOLING220.00 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 2
220.00KV MW MVAR
1 1
TO 1 220KVPGCILSS220.00 1 -0.4 1.8 1.8 0.00 0.00
1 1
TO 3 HV_POWERTR-1220.00 1 0.1 -0.4 0.5 0.00 0.00
1 1
TO 4 HV_POWERTR-2220.00 1 0.1 -0.4 0.5 0.00 0.00
1 1
TO 5 HV_POWERTR-3220.00 1 0.1 -0.4 0.5 0.00 0.00
1 1
TO 6 HV_POWERTR-4220.00 1 0.1 -0.4 0.5 0.00 0.00
1 1

BUS 3 HV_POWERTR-1220.00 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 3
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 -0.1 0.4 0.5 0.00 0.00
1 1
TO 7 LV_POWERTR-133.000 1 0.1 -0.4 0.5 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 180 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 4 HV_POWERTR-2220.00 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 4
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 -0.1 0.4 0.5 0.00 0.00
1 1
TO 8 LV_POWERTR-233.000 1 0.1 -0.4 0.5 1.0000LK 0.00 0.00
1 1

BUS 5 HV_POWERTR-3220.00 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 5
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 -0.1 0.4 0.5 0.00 0.00
1 1
TO 9 LV_POWERTR-333.000 1 0.1 -0.4 0.5 1.0000LK 0.00 0.00
1 1

BUS 6 HV_POWERTR-4220.00 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 6
220.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 -0.1 0.4 0.5 0.00 0.00
1 1
TO 10 LV_POWERTR-433.000 1 0.1 -0.4 0.5 1.0000LK 0.00 0.00
1 1

BUS 7 LV_POWERTR-133.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 7
33.022KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 181 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3 HV_POWERTR-1220.00 1 -0.1 0.4 0.5 1.0000UN 0.00 0.00


1 1
TO 11 33KMAINHTPNL33.000 1 0.1 -0.4 0.5 0.00 0.00
1 1

BUS 8 LV_POWERTR-233.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 8
33.022KV MW MVAR
1 1
TO 4 HV_POWERTR-2220.00 1 -0.1 0.4 0.5 1.0000UN 0.00 0.00
1 1
TO 11 33KMAINHTPNL33.000 1 0.1 -0.4 0.5 0.00 0.00
1 1

BUS 9 LV_POWERTR-333.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 9
33.022KV MW MVAR
1 1
TO 5 HV_POWERTR-3220.00 1 -0.1 0.4 0.5 1.0000UN 0.00 0.00
1 1
TO 11 33KMAINHTPNL33.000 1 0.1 -0.4 0.5 0.00 0.00
1 1

BUS 10 LV_POWERTR-433.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 10
33.022KV MW MVAR
1 1
TO 6 HV_POWERTR-4220.00 1 -0.1 0.4 0.5 1.0000UN 0.00 0.00
1 1
TO 11 33KMAINHTPNL33.000 1 0.1 -0.4 0.5 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 182 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 11 33KMAINHTPNL33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 11
33.022KV MW MVAR
1 1
TO 7 LV_POWERTR-133.000 1 -0.1 0.4 0.4 0.00 0.00
1 1
TO 8 LV_POWERTR-233.000 1 -0.1 0.4 0.4 0.00 0.00
1 1
TO 9 LV_POWERTR-333.000 1 -0.1 0.3 0.4 0.00 0.00
1 1
TO 10 LV_POWERTR-433.000 1 -0.1 0.3 0.3 0.00 0.00
1 1
TO 12 50MWBLK2_1 33.000 1 0.0 -0.2 0.2 0.00 0.00
1 1
TO 13 50MWBLK2_2 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 70 HV_AUXTRPSS 33.000 1 0.1 0.0 0.1 0.00 0.00
1 1
TO 101 50MWBLK4_1 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 102 50MWBLK4_2 33.000 1 0.0 0.1 0.1 0.00 0.00
1 1
TO 201 50MWBLK3_1 33.000 1 0.0 -0.2 0.2 0.00 0.00
1 1
TO 202 50MWBLK3_2 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 301 50MWBLK1_1 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 302 50MWBLK1_2 33.000 1 0.1 -0.2 0.2 0.00 0.00
1 1
TO 401 50MWBLK5_1 33.000 1 0.0 -0.3 0.3 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 183 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 402 50MWBLK5_2 33.000 1 0.1 -0.3 0.3 0.00 0.00


1 1

BUS 12 50MWBLK2_1 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 12
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 0.1 0.1 0.00 0.00
1 1
TO 14 HV_IDT1_16 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 16 HV_IDT1_17 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1

BUS 13 50MWBLK2_2 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 13
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 0.0 0.0 0.00 0.00
1 1
TO 18 HV_IDT1_18 33.000 1 0.0 -0.0 0.0 0.00 0.00
1 1
TO 20 HV_IDT1_19 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 14 HV_IDT1_16 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 14
33.022KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 184 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 16 HV_IDT1_17 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 16
33.021KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_17 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 18 HV_IDT1_18 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 18
33.021KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_18 WND 1 1 0.0 0.0 0.0 1.0000LK 0.00 0.00

BUS 20 HV_IDT1_19 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 20
33.021KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_19 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 22 LV1_IDT1_16 0.6000 CKT MW MVAR MVA % 1.0000PU 29.99 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 22

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 185 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 38 INV1_IDT1_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 54 HV_AUXTR1_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 30.00LK 0.00 0.00

BUS 23 LV2_IDT1_16 0.6000 CKT MW MVAR MVA % 1.0000PU 30.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 23
0.6000KV MW MVAR
1 1
TO 39 INV2_IDT1_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 30.00LK 0.00 0.00

BUS 24 LV1_IDT2_16 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 24
0.6000KV MW MVAR
1 1
TO 40 INV1_IDT2_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_16 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 25 LV2_IDT2_16 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 25
0.6000KV MW MVAR
1 1
TO 41 INV2_IDT2_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 55 HV_AUXTR2_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 186 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 26 LV1_IDT1_17 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 26
0.6000KV MW MVAR
1 1
TO 42 INV1_IDT1_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 56 HV_AUXTR1_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 27 LV2_IDT1_17 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 27
0.6000KV MW MVAR
1 1
TO 43 INV2_IDT1_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 28 LV1_IDT2_17 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 28
0.6000KV MW MVAR
1 1
TO 44 INV1_IDT2_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_17 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 29 LV2_IDT2_17 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 29
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 187 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 45 INV2_IDT2_170.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 57 HV_AUXTR2_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_17 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 30 LV1_IDT1_18 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 30
0.6000KV MW MVAR
1 1
TO 46 INV1_IDT1_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 58 HV_AUXTR1_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 31 LV2_IDT1_18 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 31
0.6000KV MW MVAR
1 1
TO 47 INV2_IDT1_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 32 LV1_IDT2_18 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 32
0.6000KV MW MVAR
1 1
TO 48 INV1_IDT2_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_18 WND 2 1 -0.0 -0.0 0.0 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 188 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 33 LV2_IDT2_18 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 33
0.6000KV MW MVAR
1 1
TO 49 INV2_IDT2_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 59 HV_AUXTR2_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_18 WND 3 1 -0.0 -0.0 0.0 1.0000LK 0.00 0.00

BUS 34 LV1_IDT1_19 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 34
0.6000KV MW MVAR
1 1
TO 50 INV1_IDT1_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 60 HV_AUXTR1_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 35 LV2_IDT1_19 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 35
0.6000KV MW MVAR
1 1
TO 51 INV2_IDT1_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 36 LV1_IDT2_19 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 36
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 189 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 52 INV1_IDT2_190.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_19 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 37 LV2_IDT2_19 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 37
0.6000KV MW MVAR
1 1
TO 53 INV2_IDT2_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 61 HV_AUXTR2_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_19 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 38 INV1_IDT1_160.6000 CKT MW MVAR MVA % 1.0000PU 29.99 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 38
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 39 INV2_IDT1_160.6000 CKT MW MVAR MVA % 1.0000PU 30.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 39
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 23 LV2_IDT1_16 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 40 INV1_IDT2_160.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 40
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 190 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 24 LV1_IDT2_16 0.6000 1 0.0 -0.0 0.0 0.00 0.00


1 1

BUS 41 INV2_IDT2_160.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 41
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 42 INV1_IDT1_170.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 42
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 43 INV2_IDT1_170.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 43
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 27 LV2_IDT1_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 44 INV1_IDT2_170.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 44
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 28 LV1_IDT2_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 191 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 45 INV2_IDT2_170.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 45
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 29 LV2_IDT2_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 46 INV1_IDT1_180.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 46
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 47 INV2_IDT1_180.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 47
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 31 LV2_IDT1_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 48 INV1_IDT2_180.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 48
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 32 LV1_IDT2_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 49 INV2_IDT2_180.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 49
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 192 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 33 LV2_IDT2_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1

BUS 50 INV1_IDT1_190.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 50
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 51 INV2_IDT1_190.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 51
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 35 LV2_IDT1_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 52 INV1_IDT2_190.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 52
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 36 LV1_IDT2_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 53 INV2_IDT2_190.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 53
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 193 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 54 HV_AUXTR1_160.6000 CKT MW MVAR MVA % 1.0000PU 29.99 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 54
0.6000KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 62 LV_AUXTR1_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 55 HV_AUXTR2_160.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 55
0.6000KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 63 LV_AUXTR2_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 56 HV_AUXTR1_170.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 56
0.6000KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 64 LV_AUXTR1_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 57 HV_AUXTR2_170.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 57
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 194 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 29 LV2_IDT2_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 65 LV_AUXTR2_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 58 HV_AUXTR1_180.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 58
0.6000KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 66 LV_AUXTR1_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 59 HV_AUXTR2_180.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 59
0.6000KV MW MVAR
1 1
TO 33 LV2_IDT2_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 67 LV_AUXTR2_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 60 HV_AUXTR1_190.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 60
0.6000KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 68 LV_AUXTR1_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 195 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 61 HV_AUXTR2_190.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 61
0.6000KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 69 LV_AUXTR2_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 62 LV_AUXTR1_160.4150 CKT MW MVAR MVA % 0.9918PU 28.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 62
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 54 HV_AUXTR1_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 63 LV_AUXTR2_160.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 63
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 55 HV_AUXTR2_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 64 LV_AUXTR1_170.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 64
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 56 HV_AUXTR1_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 196 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 65 LV_AUXTR2_170.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 65
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 57 HV_AUXTR2_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 66 LV_AUXTR1_180.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 66
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 58 HV_AUXTR1_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 67 LV_AUXTR2_180.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 67
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 59 HV_AUXTR2_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 68 LV_AUXTR1_190.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 68
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 60 HV_AUXTR1_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 197 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 69 LV_AUXTR2_190.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 69
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 61 HV_AUXTR2_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 70 HV_AUXTRPSS 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 70
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.1 -0.0 0.1 0.00 0.00
1 1
TO 71 LV_AUXTRPSS 0.4150 1 0.1 0.0 0.1 1.0000LK 0.00 0.00
1 1

BUS 71 LV_AUXTRPSS 0.4150 CKT MW MVAR MVA % 0.9968PU -0.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 71
0.4137KV MW MVAR
1 1
TO LOAD-PQ 0.1 0.0 0.1
TO 70 HV_AUXTRPSS 33.000 1 -0.1 -0.0 0.1 1.0000UN 0.00 0.00
1 1

BUS 101 50MWBLK4_1 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 101
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 198 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 103 HV_IDT1_11 33.000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 104 HV_IDT1_14 33.000 1 0.0 0.1 0.1 0.00 0.00
1 1

BUS 102 50MWBLK4_2 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 102
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 105 HV_IDT1_15 33.000 1 0.0 0.1 0.1 0.00 0.00
1 1
TO 106 HV_IDT1_20 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 103 HV_IDT1_11 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 103
33.021KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_11 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 104 HV_IDT1_14 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 104
33.021KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_14 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 199 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_14 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 105 HV_IDT1_15 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 105
33.021KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_15 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 106 HV_IDT1_20 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 106
33.021KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_20 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 107 LV1_IDT1_11 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 107
0.6000KV MW MVAR
1 1
TO 123 INV1_IDT1_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 139 HV_AUXTR1_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 108 LV2_IDT1_11 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 108

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 200 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 124 INV2_IDT1_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 109 LV1_IDT2_11 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 109
0.6000KV MW MVAR
1 1
TO 125 INV1_IDT2_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_11 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 110 LV2_IDT2_11 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 110
0.6000KV MW MVAR
1 1
TO 126 INV2_IDT2_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 140 HV_AUXTR2_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_11 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 111 LV1_IDT1_14 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 111
0.6000KV MW MVAR
1 1
TO 127 INV1_IDT1_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 141 HV_AUXTR1_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 201 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT1_TR_14 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 112 LV2_IDT1_14 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 112
0.6000KV MW MVAR
1 1
TO 128 INV2_IDT1_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_14 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 113 LV1_IDT2_14 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 113
0.6000KV MW MVAR
1 1
TO 129 INV1_IDT2_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_14 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 114 LV2_IDT2_14 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 114
0.6000KV MW MVAR
1 1
TO 130 INV2_IDT2_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 142 HV_AUXTR2_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_14 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 115 LV1_IDT1_15 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 115
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 202 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 131INV1_IDT1_150.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 143 HV_AUXTR1_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 116 LV2_IDT1_15 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 116
0.6000KV MW MVAR
1 1
TO 132 INV2_IDT1_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 117 LV1_IDT2_15 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 117
0.6000KV MW MVAR
1 1
TO 133 INV1_IDT2_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_15 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 118 LV2_IDT2_15 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 118
0.6000KV MW MVAR
1 1
TO 134 INV2_IDT2_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 144 HV_AUXTR2_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_15 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 203 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 119 LV1_IDT1_20 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 119
0.6000KV MW MVAR
1 1
TO 135 INV1_IDT1_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 145 HV_AUXTR1_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 120 LV2_IDT1_20 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 120
0.6000KV MW MVAR
1 1
TO 136 INV2_IDT1_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 121 LV1_IDT2_20 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 121
0.6000KV MW MVAR
1 1
TO 137 INV1_IDT2_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_20 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 122 LV2_IDT2_20 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 122
0.6000KV MW MVAR
1 1
TO 138 INV2_IDT2_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 204 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 146 HV_AUXTR2_200.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_20 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 123 INV1_IDT1_110.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 123
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 124 INV2_IDT1_110.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 124
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 108 LV2_IDT1_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 125 INV1_IDT2_110.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 125
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 109 LV1_IDT2_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 126 INV2_IDT2_110.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 126
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 205 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 127 INV1_IDT1_140.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 127
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 128 INV2_IDT1_140.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 128
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 112 LV2_IDT1_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 129 INV1_IDT2_140.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 129
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 113 LV1_IDT2_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 130 INV2_IDT2_140.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 130
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 131 INV1_IDT1_150.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 131
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 206 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 115 LV1_IDT1_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1

BUS 132 INV2_IDT1_150.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 132
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 116 LV2_IDT1_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 133 INV1_IDT2_150.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 133
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 117 LV1_IDT2_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 134 INV2_IDT2_150.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 134
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 135 INV1_IDT1_200.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 135
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 207 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 136 INV2_IDT1_200.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 136
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 120 LV2_IDT1_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 137 INV1_IDT2_200.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 137
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 121 LV1_IDT2_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 138 INV2_IDT2_200.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 138
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 139 HV_AUXTR1_110.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 139
0.6000KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 147 LV_AUXTR1_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 140 HV_AUXTR2_110.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 140

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 208 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 148 LV_AUXTR2_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 141 HV_AUXTR1_140.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 141
0.6000KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 149 LV_AUXTR1_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 142 HV_AUXTR2_140.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 142
0.6000KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 150 LV_AUXTR2_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 143 HV_AUXTR1_150.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 143
0.6000KV MW MVAR
1 1
TO 115 LV1_IDT1_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 209 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 151 LV_AUXTR1_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 144 HV_AUXTR2_150.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 144
0.6000KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 152 LV_AUXTR2_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 145 HV_AUXTR1_200.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 145
0.6000KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 153 LV_AUXTR1_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 146 HV_AUXTR2_200.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 146
0.6000KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 154 LV_AUXTR2_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 147 LV_AUXTR1_110.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 147

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 210 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 139 HV_AUXTR1_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 148 LV_AUXTR2_110.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 148
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 140 HV_AUXTR2_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 149 LV_AUXTR1_140.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 149
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 141 HV_AUXTR1_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 150 LV_AUXTR2_140.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 150
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 142 HV_AUXTR2_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 151 LV_AUXTR1_150.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 151

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 211 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 143 HV_AUXTR1_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 152 LV_AUXTR2_150.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 152
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 144 HV_AUXTR2_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 153 LV_AUXTR1_200.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 153
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 145 HV_AUXTR1_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 154 LV_AUXTR2_200.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 154
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 146 HV_AUXTR2_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 201 50MWBLK3_1 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 201

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 212 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 0.1 0.2 0.00 0.00
1 1
TO 203 HV_IDT1_5 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 204 HV_IDT1_6 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1

BUS 202 50MWBLK3_2 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 202
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 0.0 0.0 0.00 0.00
1 1
TO 205 HV_IDT1_7 33.000 1 0.0 -0.0 0.0 0.00 0.00
1 1
TO 206 HV_IDT1_9 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 203 HV_IDT1_5 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 203
33.022KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_5 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_5 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 204 HV_IDT1_6 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 204

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 213 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

33.021KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_6 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 205 HV_IDT1_7 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 205
33.021KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_7 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 206 HV_IDT1_9 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 206
33.021KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_9 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 207 LV1_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 207
0.6000KV MW MVAR
1 1
TO 223 INV1_IDT1_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 214 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 239 HV_AUXTR1_5 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT1_TR_5 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 208 LV2_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 208
0.6000KV MW MVAR
1 1
TO 224INV2_IDT1_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_5 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 209 LV1_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 209
0.6000KV MW MVAR
1 1
TO 225 INV1_IDT2_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_5 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 210 LV2_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 210
0.6000KV MW MVAR
1 1
TO 226 INV2_IDT2_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 240 HV_AUXTR2_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_5 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 211 LV1_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 211

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 215 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 227 INV1_IDT1_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 241 HV_AUXTR1_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 212 LV2_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 212
0.6000KV MW MVAR
1 1
TO 228 INV2_IDT1_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 213 LV1_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 213
0.6000KV MW MVAR
1 1
TO 229 INV1_IDT2_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_6 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 214 LV2_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 214
0.6000KV MW MVAR
1 1
TO 230 INV2_IDT2_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 242 HV_AUXTR2_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 216 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_6 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 215 LV1_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 215
0.6000KV MW MVAR
1 1
TO 231 INV1_IDT1_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 243 HV_AUXTR1_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 216 LV2_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 216
0.6000KV MW MVAR
1 1
TO 232 INV2_IDT1_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 217 LV1_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 217
0.6000KV MW MVAR
1 1
TO 233 INV1_IDT2_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_7 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 218 LV2_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 218
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 217 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 234INV2_IDT2_7 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 244 HV_AUXTR2_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_7 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 219 LV1_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 219
0.6000KV MW MVAR
1 1
TO 235 INV1_IDT1_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 245 HV_AUXTR1_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 220 LV2_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 220
0.6000KV MW MVAR
1 1
TO 236 INV2_IDT1_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 221 LV1_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 221
0.6000KV MW MVAR
1 1
TO 237 INV1_IDT2_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_9 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 218 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 222 LV2_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 222
0.6000KV MW MVAR
1 1
TO 238 INV2_IDT2_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 246 HV_AUXTR2_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_9 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 223 INV1_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 223
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 207 LV1_IDT1_5 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 224 INV2_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 224
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 208 LV2_IDT1_5 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 225 INV1_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 225
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 209 LV1_IDT2_5 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 219 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 226 INV2_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 226
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 227 INV1_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 227
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 228 INV2_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 228
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 212 LV2_IDT1_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 229 INV1_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 229
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 213 LV1_IDT2_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 230 INV2_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 230
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 220 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 214 LV2_IDT2_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1

BUS 231 INV1_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 231
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 232 INV2_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 232
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 216 LV2_IDT1_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 233 INV1_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 233
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 217 LV1_IDT2_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 234 INV2_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 234
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 221 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 235 INV1_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 235
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 236 INV2_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 236
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 220 LV2_IDT1_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 237 INV1_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 237
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 221 LV1_IDT2_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 238 INV2_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 238
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 222 LV2_IDT2_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 239 HV_AUXTR1_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 239
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 222 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 207 LV1_IDT1_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 247 LV_AUXTR1_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 240 HV_AUXTR2_5 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 240
0.6000KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 248 LV_AUXTR2_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 241 HV_AUXTR1_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 241
0.6000KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 249 LV_AUXTR1_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 242 HV_AUXTR2_6 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 242
0.6000KV MW MVAR
1 1
TO 214 LV2_IDT2_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 250 LV_AUXTR2_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 223 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 243 HV_AUXTR1_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 243
0.6000KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 251 LV_AUXTR1_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 244 HV_AUXTR2_7 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 244
0.6000KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 252 LV_AUXTR2_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 245 HV_AUXTR1_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 245
0.6000KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 253 LV_AUXTR1_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 246 HV_AUXTR2_9 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 246
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 224 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 222 LV2_IDT2_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 254 LV_AUXTR2_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 247 LV_AUXTR1_5 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 247
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 239 HV_AUXTR1_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 248 LV_AUXTR2_5 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 248
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 240 HV_AUXTR2_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 249 LV_AUXTR1_6 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 249
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 241 HV_AUXTR1_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 250 LV_AUXTR2_6 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 250

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 225 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 242 HV_AUXTR2_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 251 LV_AUXTR1_7 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 251
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 243 HV_AUXTR1_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 252 LV_AUXTR2_7 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 252
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 244 HV_AUXTR2_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 253 LV_AUXTR1_9 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 253
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 245 HV_AUXTR1_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 254 LV_AUXTR2_9 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 254

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 226 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 246 HV_AUXTR2_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 301 50MWBLK1_1 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 301
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 0.1 0.1 0.00 0.00
1 1
TO 303 HV_IDT1_10 33.000 1 0.0 -0.0 0.0 0.00 0.00
1 1
TO 304 HV_IDT1_8 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1

BUS 302 50MWBLK1_2 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 302
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.1 0.1 0.2 0.00 0.00
1 1
TO 305 HV_IDT1_13 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 306 HV_IDT1_12 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 360 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 303 HV_IDT1_10 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 303

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 227 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

33.021KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_10 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 304 HV_IDT1_8 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 304
33.021KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_8 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 305 HV_IDT1_13 33.000 CKT MW MVAR MVA % 1.0006PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 305
33.021KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_13 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 306 HV_IDT1_12 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 306
33.022KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 228 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_12 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 307 LV1_IDT1_10 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 307
0.6000KV MW MVAR
1 1
TO 323 INV1_IDT1_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 339 HV_AUXTR1_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 308 LV2_IDT1_10 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 308
0.6000KV MW MVAR
1 1
TO 324 INV2_IDT1_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 309 LV1_IDT2_10 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 309
0.6000KV MW MVAR
1 1
TO 325 INV1_IDT2_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_10 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 310 LV2_IDT2_10 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 310
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 229 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 326INV2_IDT2_100.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 340 HV_AUXTR2_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_10 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 311 LV1_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 311
0.6000KV MW MVAR
1 1
TO 327 INV1_IDT1_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 341 HV_AUXTR1_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 312 LV2_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 312
0.6000KV MW MVAR
1 1
TO 328 INV2_IDT1_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 313 LV1_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 313
0.6000KV MW MVAR
1 1
TO 329 INV1_IDT2_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_8 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 230 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 314 LV2_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 314
0.6000KV MW MVAR
1 1
TO 330 INV2_IDT2_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 342 HV_AUXTR2_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_8 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 315 LV1_IDT1_13 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 315
0.6000KV MW MVAR
1 1
TO 331 INV1_IDT1_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 343 HV_AUXTR1_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 316 LV2_IDT1_13 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 316
0.6000KV MW MVAR
1 1
TO 332 INV2_IDT1_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 317 LV1_IDT2_13 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 317
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 231 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 333 INV1_IDT2_130.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_13 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 318 LV2_IDT2_13 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 318
0.6000KV MW MVAR
1 1
TO 334INV2_IDT2_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 344 HV_AUXTR2_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_13 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 319 LV1_IDT1_12 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 319
0.6000KV MW MVAR
1 1
TO 335 INV1_IDT1_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 345 HV_AUXTR1_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 320 LV2_IDT1_12 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 320
0.6000KV MW MVAR
1 1
TO 336 INV2_IDT1_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 232 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 321 LV1_IDT2_12 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 321
0.6000KV MW MVAR
1 1
TO 337 INV1_IDT2_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_12 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 322 LV2_IDT2_12 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 322
0.6000KV MW MVAR
1 1
TO 338 INV2_IDT2_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 346 HV_AUXTR2_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_12 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 323 INV1_IDT1_100.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 323
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 324 INV2_IDT1_100.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 324
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 308 LV2_IDT1_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 233 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 325 INV1_IDT2_100.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 325
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 309 LV1_IDT2_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 326 INV2_IDT2_100.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 326
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

BUS 327 INV1_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 327
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 328 INV2_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 328
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 312 LV2_IDT1_8 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 329 INV1_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 329
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 234 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 313 LV1_IDT2_8 0.6000 1 0.0 -0.0 0.0 0.00 0.00


1 1

BUS 330 INV2_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 330
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 331 INV1_IDT1_130.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 331
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 332 INV2_IDT1_130.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 332
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 316 LV2_IDT1_13 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 333 INV1_IDT2_130.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 333
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 317 LV1_IDT2_13 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 235 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 334 INV2_IDT2_130.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 334
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 335 INV1_IDT1_120.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 335
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 336 INV2_IDT1_120.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 336
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 320 LV2_IDT1_12 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 337 INV1_IDT2_120.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 337
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 321 LV1_IDT2_12 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 338 INV2_IDT2_120.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 338
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 236 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 322 LV2_IDT2_12 0.6000 1 0.0 -0.0 0.0 0.00 0.00


1 1

BUS 339 HV_AUXTR1_100.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 339
0.6000KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 347 LV_AUXTR1_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 340 HV_AUXTR2_100.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 340
0.6000KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 348 LV_AUXTR2_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 341 HV_AUXTR1_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 341
0.6000KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 349 LV_AUXTR1_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 342 HV_AUXTR2_8 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 342

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 237 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 350 LV_AUXTR2_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 343 HV_AUXTR1_130.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 343
0.6000KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 351 LV_AUXTR1_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 344 HV_AUXTR2_130.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 344
0.6000KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 352 LV_AUXTR2_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 345 HV_AUXTR1_120.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 345
0.6000KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 238 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 353 LV_AUXTR1_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 346 HV_AUXTR2_120.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 346
0.6000KV MW MVAR
1 1
TO 322 LV2_IDT2_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 354 LV_AUXTR2_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 347 LV_AUXTR1_100.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 347
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 339 HV_AUXTR1_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 348 LV_AUXTR2_100.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 348
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 340 HV_AUXTR2_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 349 LV_AUXTR1_8 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 349
0.4116KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 239 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 341 HV_AUXTR1_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 350 LV_AUXTR2_8 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 350
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 342 HV_AUXTR2_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 351 LV_AUXTR1_130.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 351
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 343 HV_AUXTR1_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 352 LV_AUXTR2_130.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 352
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 344 HV_AUXTR2_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 353 LV_AUXTR1_120.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 353
0.4116KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 240 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 345 HV_AUXTR1_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 354 LV_AUXTR2_120.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 354
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 346 HV_AUXTR2_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 360 HV_AUXTR33 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 360
33.022KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 361 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 361 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 0.9961PU -0.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 361
0.4134KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 360 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 401 50MWBLK5_1 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 401

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 241 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.0 0.3 0.3 0.00 0.00
1 1
TO 403 HV_IDT1_1 33.000 1 0.0 -0.2 0.2 0.00 0.00
1 1
TO 404 HV_IDT1_2 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1

BUS 402 50MWBLK5_2 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 402
33.022KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.1 0.3 0.3 0.00 0.00
1 1
TO 405 HV_IDT1_3 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 406 HV_IDT1_4 33.000 1 0.0 -0.1 0.1 0.00 0.00
1 1
TO 460 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 403 HV_IDT1_1 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 403
33.022KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_1 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 242 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 404 HV_IDT1_2 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 404
33.022KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_2 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 405 HV_IDT1_3 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 405
33.022KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_3 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 406 HV_IDT1_4 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 406
33.022KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 -0.0 -0.1 0.1 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00
TO 3WNDTR IDT2_TR_4 WND 1 1 0.0 0.0 0.0 1 1.0000LK 0.00 0.00

BUS 407 LV1_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 407
0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 243 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 423INV1_IDT1_1 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 439 HV_AUXTR1_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 408 LV2_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 408
0.6000KV MW MVAR
1 1
TO 424 INV2_IDT1_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 409 LV1_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 409
0.6000KV MW MVAR
1 1
TO 425 INV1_IDT2_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_1 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 410 LV2_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 410
0.6000KV MW MVAR
1 1
TO 426 INV2_IDT2_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 440 HV_AUXTR2_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_1 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 244 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 411 LV1_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 411
0.6000KV MW MVAR
1 1
TO 427 INV1_IDT1_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 441 HV_AUXTR1_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 412 LV2_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 412
0.6000KV MW MVAR
1 1
TO 428 INV2_IDT1_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 413 LV1_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 413
0.6000KV MW MVAR
1 1
TO 429 INV1_IDT2_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_2 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 414 LV2_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 414
0.6000KV MW MVAR
1 1
TO 430 INV2_IDT2_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 245 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 442 HV_AUXTR2_2 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_2 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 415 LV1_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 415
0.6000KV MW MVAR
1 1
TO 431INV1_IDT1_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 443 HV_AUXTR1_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 416 LV2_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 416
0.6000KV MW MVAR
1 1
TO 432 INV2_IDT1_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 417 LV1_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 417
0.6000KV MW MVAR
1 1
TO 433 INV1_IDT2_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_3 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 418 LV2_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 418

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 246 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 434 INV2_IDT2_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 444 HV_AUXTR2_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_3 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 419 LV1_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 419
0.6000KV MW MVAR
1 1
TO 435 INV1_IDT1_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 445 HV_AUXTR1_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 420 LV2_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 420
0.6000KV MW MVAR
1 1
TO 436 INV2_IDT1_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 421 LV1_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 421
0.6000KV MW MVAR
1 1
TO 437 INV1_IDT2_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 247 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_4 WND 2 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 422 LV2_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 422
0.6000KV MW MVAR
1 1
TO 438 INV2_IDT2_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 446 HV_AUXTR2_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_4 WND 3 1 -0.0 -0.0 0.0 1 1.0000LK 0.00 0.00

BUS 423 INV1_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 423
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 424 INV2_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 424
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 408 LV2_IDT1_1 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 425 INV1_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 425
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 409 LV1_IDT2_1 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 248 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 426 INV2_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 426
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 427 INV1_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 427
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 428 INV2_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 428
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 412 LV2_IDT1_2 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 429 INV1_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 429
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 413 LV1_IDT2_2 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 430 INV2_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 430

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 249 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR


1 1
TO 414 LV2_IDT2_2 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 431 INV1_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 431
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 432 INV2_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 432
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 416 LV2_IDT1_3 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 433 INV1_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 433
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 417 LV1_IDT2_3 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 434 INV2_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 434
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 250 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 435 INV1_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 435
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 436 INV2_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 436
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 420 LV2_IDT1_4 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 437 INV1_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 437
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 421 LV1_IDT2_4 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 438 INV2_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 438
FROM GENERATION 0.0 -0.0R 0.0 1 0.6000KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 0.0 -0.0 0.0 0.00 0.00
1 1

BUS 439 HV_AUXTR1_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 439

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 251 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 447 LV_AUXTR1_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 440 HV_AUXTR2_1 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 440
0.6000KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 448 LV_AUXTR2_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 441 HV_AUXTR1_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 441
0.6000KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 449 LV_AUXTR1_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 442 HV_AUXTR2_2 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 442
0.6000KV MW MVAR
1 1
TO 414 LV2_IDT2_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 252 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 450 LV_AUXTR2_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 443 HV_AUXTR1_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 443
0.6000KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 451 LV_AUXTR1_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 444 HV_AUXTR2_3 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 444
0.6000KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 452 LV_AUXTR2_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 445 HV_AUXTR1_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 445
0.6000KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 453 LV_AUXTR1_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 446 HV_AUXTR2_4 0.6000 CKT MW MVAR MVA % 1.0000PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 446

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 253 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6000KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 454 LV_AUXTR2_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 447 LV_AUXTR1_1 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 447
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 439 HV_AUXTR1_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 448 LV_AUXTR2_1 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 448
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 440 HV_AUXTR2_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 449 LV_AUXTR1_2 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 449
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 441 HV_AUXTR1_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 254 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 450 LV_AUXTR2_2 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 450
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 442 HV_AUXTR2_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 451 LV_AUXTR1_3 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 451
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 443 HV_AUXTR1_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 452 LV_AUXTR2_3 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 452
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 444 HV_AUXTR2_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 453 LV_AUXTR1_4 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 453
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 445 HV_AUXTR1_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 255 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 454 LV_AUXTR2_4 0.4150 CKT MW MVAR MVA % 0.9919PU -1.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 454
0.4116KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 446 HV_AUXTR2_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 460 HV_AUXTR33 33.000 CKT MW MVAR MVA % 1.0007PU -0.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 460
33.022KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 461 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 461 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 0.9961PU -0.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 461
0.4134KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 460 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 256 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

11.3 Grid voltage=1.1 p.u- Active Power and Reactive Power Flow Re-
sults
This section provides the detailed power flow results for the operating scenario when 220kV
pooling station of the solar park is subjected to grid voltage=1.1 p.u.. These results include MW,
MVAr, MVA, Losses MW, Losses MVAr in each feeder of the network along with the voltage (in
kV).

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 257 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 1 220KVPGCILSS220.00 CKT MW MVAR MVA % 1.1000PU 0.00 X--- LOSSES ---X X-
--- AREA -----X X---- ZONE -----X 1
FROM GENERATION -241.7 197.7R 312.3 89 242.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 -241.7 197.7 312.3 0.00 0.00
1 1

BUS 2 220KVPOOLING220.00 CKT MW MVAR MVA % 1.1000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 2
242.00KV MW MVAR
1 1
TO 1 220KVPGCILSS220.00 1 241.7 -197.7 312.3 0.00 0.00
1 1
TO 3 HV_POWERTR-1220.00 1 -60.6 49.4 78.2 0.00 0.00
1 1
TO 4 HV_POWERTR-2220.00 1 -60.5 49.4 78.1 0.00 0.00
1 1
TO 5 HV_POWERTR-3220.00 1 -60.4 49.4 78.0 0.00 0.00
1 1
TO 6 HV_POWERTR-4220.00 1 -60.2 49.4 77.9 0.00 0.00
1 1

BUS 3 HV_POWERTR-1220.00 CKT MW MVAR MVA % 1.1000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 3
242.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.6 -49.4 78.2 0.00 0.00
1 1
TO 7 LV_POWERTR-133.000 1 -60.7 49.4 78.2 1.0000LK 0.10 7.53
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 258 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 4 HV_POWERTR-2220.00 CKT MW MVAR MVA % 1.1000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 4
242.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.5 -49.4 78.1 0.00 0.00
1 1
TO 8 LV_POWERTR-233.000 1 -60.5 49.4 78.1 1.0000LK 0.10 7.51
1 1

BUS 5 HV_POWERTR-3220.00 CKT MW MVAR MVA % 1.1000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 5
242.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.4 -49.4 78.0 0.00 0.00
1 1
TO 9 LV_POWERTR-333.000 1 -60.4 49.4 78.0 1.0000LK 0.10 7.49
1 1

BUS 6 HV_POWERTR-4220.00 CKT MW MVAR MVA % 1.1000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 6
242.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.2 -49.4 77.9 0.00 0.00
1 1
TO 10 LV_POWERTR-433.000 1 -60.2 49.4 77.9 1.0000LK 0.10 7.47
1 1

BUS 7 LV_POWERTR-133.000 CKT MW MVAR MVA % 1.0375PU 4.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 7
34.238KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 259 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3 HV_POWERTR-1220.00 1 60.8 -41.9 73.8 1.0000UN 0.10 7.53


1 1
TO 11 33KMAINHTPNL33.000 1 -60.8 41.9 73.8 0.02 0.02
1 1

BUS 8 LV_POWERTR-233.000 CKT MW MVAR MVA % 1.0375PU 4.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 8
34.238KV MW MVAR
1 1
TO 4 HV_POWERTR-2220.00 1 60.6 -41.9 73.7 1.0000UN 0.10 7.51
1 1
TO 11 33KMAINHTPNL33.000 1 -60.6 41.9 73.7 0.02 0.03
1 1

BUS 9 LV_POWERTR-333.000 CKT MW MVAR MVA % 1.0375PU 4.57 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 9
34.237KV MW MVAR
1 1
TO 5 HV_POWERTR-3220.00 1 60.5 -41.9 73.6 1.0000UN 0.10 7.49
1 1
TO 11 33KMAINHTPNL33.000 1 -60.5 41.9 73.6 0.03 0.04
1 1

BUS 10 LV_POWERTR-433.000 CKT MW MVAR MVA % 1.0375PU 4.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 10
34.236KV MW MVAR
1 1
TO 6 HV_POWERTR-4220.00 1 60.3 -42.0 73.5 1.0000UN 0.10 7.47
1 1
TO 11 33KMAINHTPNL33.000 1 -60.3 42.0 73.5 0.04 0.05
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 260 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 11 33KMAINHTPNL33.000 CKT MW MVAR MVA % 1.0376PU 4.61 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 11
34.240KV MW MVAR
1 1
TO 7 LV_POWERTR-133.000 1 60.8 -41.9 73.8 0.02 0.02
1 1
TO 8 LV_POWERTR-233.000 1 60.7 -42.0 73.8 0.02 0.03
1 1
TO 9 LV_POWERTR-333.000 1 60.5 -42.0 73.7 0.03 0.04
1 1
TO 10 LV_POWERTR-433.000 1 60.4 -42.1 73.6 0.04 0.05
1 1
TO 12 50MWBLK2_1 33.000 1 -24.2 16.8 29.5 0.01 0.01
1 1
TO 13 50MWBLK2_2 33.000 1 -24.3 16.9 29.6 0.01 0.01
1 1
TO 70 HV_AUXTRPSS 33.000 1 0.1 0.0 0.1 0.00 0.00
1 1
TO 101 50MWBLK4_1 33.000 1 -24.3 16.9 29.6 0.01 0.01
1 1
TO 102 50MWBLK4_2 33.000 1 -24.3 17.0 29.6 0.01 0.01
1 1
TO 201 50MWBLK3_1 33.000 1 -24.2 16.7 29.5 0.01 0.01
1 1
TO 202 50MWBLK3_2 33.000 1 -24.3 16.9 29.5 0.01 0.01
1 1
TO 301 50MWBLK1_1 33.000 1 -24.2 16.8 29.5 0.01 0.01
1 1
TO 302 50MWBLK1_2 33.000 1 -24.2 16.8 29.4 0.01 0.01
1 1
TO 401 50MWBLK5_1 33.000 1 -24.2 16.6 29.4 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 261 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 402 50MWBLK5_2 33.000 1 -24.2 16.6 29.3 0.01 0.01


1 1

BUS 12 50MWBLK2_1 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 12
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 -16.8 29.5 0.01 0.01
1 1
TO 14 HV_IDT1_16 33.000 1 -12.1 8.4 14.7 0.04 0.04
1 1
TO 16 HV_IDT1_17 33.000 1 -12.1 8.4 14.8 0.04 0.04
1 1

BUS 13 50MWBLK2_2 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 13
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 -16.9 29.6 0.01 0.01
1 1
TO 18 HV_IDT1_18 33.000 1 -12.1 8.4 14.8 0.03 0.03
1 1
TO 20 HV_IDT1_19 33.000 1 -12.1 8.5 14.8 0.02 0.02
1 1

BUS 14 HV_IDT1_16 33.000 CKT MW MVAR MVA % 1.0384PU 4.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 14
34.268KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 12.2 -8.5 14.9 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_16 WND 1 1 -6.1 4.3 7.4 119 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 262 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 16 HV_IDT1_17 33.000 CKT MW MVAR MVA % 1.0383PU 4.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 16
34.263KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 12.2 -8.5 14.9 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_17 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_17 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 18 HV_IDT1_18 33.000 CKT MW MVAR MVA % 1.0381PU 4.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 18
34.258KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 12.2 -8.5 14.9 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_18 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_18 WND 1 1 -6.1 4.3 7.4 1.0000LK 0.15 0.66

BUS 20 HV_IDT1_19 33.000 CKT MW MVAR MVA % 1.0380PU 4.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 20
34.254KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 12.2 -8.5 14.9 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_19 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_19 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 22 LV1_IDT1_16 0.6000 CKT MW MVAR MVA % 1.0064PU 39.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 22

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 263 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6038KV MW MVAR
1 1
TO 38 INV1_IDT1_160.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 54 HV_AUXTR1_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 2 1 3.1 -1.8 3.6 115 1.0000LK 30.00LK 0.15 0.66

BUS 23 LV2_IDT1_16 0.6000 CKT MW MVAR MVA % 1.0065PU 39.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 23
0.6039KV MW MVAR
1 1
TO 39 INV2_IDT1_160.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 3 1 3.1 -1.8 3.6 115 1.0000LK 30.00LK 0.15 0.66

BUS 24 LV1_IDT2_16 0.6000 CKT MW MVAR MVA % 1.0064PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 24
0.6039KV MW MVAR
1 1
TO 40 INV1_IDT2_160.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_16 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 25 LV2_IDT2_16 0.6000 CKT MW MVAR MVA % 1.0064PU 9.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 25
0.6038KV MW MVAR
1 1
TO 41 INV2_IDT2_160.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 55 HV_AUXTR2_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 264 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 26 LV1_IDT1_17 0.6000 CKT MW MVAR MVA % 1.0062PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 26
0.6037KV MW MVAR
1 1
TO 42 INV1_IDT1_170.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 56 HV_AUXTR1_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 27 LV2_IDT1_17 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 27
0.6038KV MW MVAR
1 1
TO 43 INV2_IDT1_170.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 28 LV1_IDT2_17 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 28
0.6038KV MW MVAR
1 1
TO 44 INV1_IDT2_170.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_17 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 29 LV2_IDT2_17 0.6000 CKT MW MVAR MVA % 1.0063PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 29
0.6038KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 265 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 45 INV2_IDT2_170.6000 1 -3.1 1.8 3.6 0.01 0.00


1 1
TO 57 HV_AUXTR2_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_17 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 30 LV1_IDT1_18 0.6000 CKT MW MVAR MVA % 1.0061PU 9.73 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 30
0.6036KV MW MVAR
1 1
TO 46 INV1_IDT1_180.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 58 HV_AUXTR1_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 31 LV2_IDT1_18 0.6000 CKT MW MVAR MVA % 1.0061PU 9.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 31
0.6037KV MW MVAR
1 1
TO 47 INV2_IDT1_180.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 32 LV1_IDT2_18 0.6000 CKT MW MVAR MVA % 1.0061PU 9.73 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 32
0.6037KV MW MVAR
1 1
TO 48 INV1_IDT2_180.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_18 WND 2 1 3.1 -1.8 3.6 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 266 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 33 LV2_IDT2_18 0.6000 CKT MW MVAR MVA % 1.0061PU 9.73 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 33
0.6037KV MW MVAR
1 1
TO 49 INV2_IDT2_180.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 59 HV_AUXTR2_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_18 WND 3 1 3.1 -1.8 3.6 1.0000LK 0.15 0.66

BUS 34 LV1_IDT1_19 0.6000 CKT MW MVAR MVA % 1.0059PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 34
0.6036KV MW MVAR
1 1
TO 50 INV1_IDT1_190.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 60 HV_AUXTR1_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 35 LV2_IDT1_19 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 35
0.6036KV MW MVAR
1 1
TO 51 INV2_IDT1_190.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 36 LV1_IDT2_19 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 36
0.6036KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 267 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 52 INV1_IDT2_190.6000 1 -3.1 1.8 3.6 0.01 0.01


1 1
TO 3WNDTR IDT2_TR_19 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 37 LV2_IDT2_19 0.6000 CKT MW MVAR MVA % 1.0060PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 37
0.6036KV MW MVAR
1 1
TO 53 INV2_IDT2_190.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 61 HV_AUXTR2_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_19 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 38 INV1_IDT1_160.6000 CKT MW MVAR MVA % 1.0074PU 39.96 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 38
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 39 INV2_IDT1_160.6000 CKT MW MVAR MVA % 1.0073PU 39.94 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 39
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 23 LV2_IDT1_16 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 40 INV1_IDT2_160.6000 CKT MW MVAR MVA % 1.0074PU 9.97 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 40
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 268 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 24 LV1_IDT2_16 0.6000 1 3.1 -1.8 3.6 0.01 0.01


1 1

BUS 41 INV2_IDT2_160.6000 CKT MW MVAR MVA % 1.0072PU 9.93 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 41
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 42 INV1_IDT1_170.6000 CKT MW MVAR MVA % 1.0072PU 9.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 42
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 43 INV2_IDT1_170.6000 CKT MW MVAR MVA % 1.0071PU 9.90 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 43
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 27 LV2_IDT1_17 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 44 INV1_IDT2_170.6000 CKT MW MVAR MVA % 1.0073PU 9.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 44
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 28 LV1_IDT2_17 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 269 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 45 INV2_IDT2_170.6000 CKT MW MVAR MVA % 1.0071PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 45
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 29 LV2_IDT2_17 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 46 INV1_IDT1_180.6000 CKT MW MVAR MVA % 1.0071PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 46
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 47 INV2_IDT1_180.6000 CKT MW MVAR MVA % 1.0069PU 9.85 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 47
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 31 LV2_IDT1_18 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 48 INV1_IDT2_180.6000 CKT MW MVAR MVA % 1.0071PU 9.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 48
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 32 LV1_IDT2_18 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 49 INV2_IDT2_180.6000 CKT MW MVAR MVA % 1.0069PU 9.85 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 49
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 270 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 33 LV2_IDT2_18 0.6000 1 3.1 -1.8 3.6 0.01 0.00


1 1

BUS 50 INV1_IDT1_190.6000 CKT MW MVAR MVA % 1.0069PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 50
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 51 INV2_IDT1_190.6000 CKT MW MVAR MVA % 1.0068PU 9.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 51
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 35 LV2_IDT1_19 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 52 INV1_IDT2_190.6000 CKT MW MVAR MVA % 1.0070PU 9.84 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 52
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 36 LV1_IDT2_19 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 53 INV2_IDT2_190.6000 CKT MW MVAR MVA % 1.0068PU 9.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 53
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 271 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 54 HV_AUXTR1_160.6000 CKT MW MVAR MVA % 1.0064PU 39.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 54
0.6038KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 62 LV_AUXTR1_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 55 HV_AUXTR2_160.6000 CKT MW MVAR MVA % 1.0064PU 9.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 55
0.6038KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 63 LV_AUXTR2_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 56 HV_AUXTR1_170.6000 CKT MW MVAR MVA % 1.0062PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 56
0.6037KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 64 LV_AUXTR1_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 57 HV_AUXTR2_170.6000 CKT MW MVAR MVA % 1.0063PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 57
0.6038KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 272 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 29 LV2_IDT2_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 65 LV_AUXTR2_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 58 HV_AUXTR1_180.6000 CKT MW MVAR MVA % 1.0061PU 9.73 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 58
0.6036KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 66 LV_AUXTR1_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 59 HV_AUXTR2_180.6000 CKT MW MVAR MVA % 1.0061PU 9.73 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 59
0.6037KV MW MVAR
1 1
TO 33 LV2_IDT2_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 67 LV_AUXTR2_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 60 HV_AUXTR1_190.6000 CKT MW MVAR MVA % 1.0059PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 60
0.6036KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 68 LV_AUXTR1_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 273 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 61 HV_AUXTR2_190.6000 CKT MW MVAR MVA % 1.0060PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 61
0.6036KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 69 LV_AUXTR2_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 62 LV_AUXTR1_160.4150 CKT MW MVAR MVA % 0.9982PU 38.44 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 62
0.4143KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 54 HV_AUXTR1_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 63 LV_AUXTR2_160.4150 CKT MW MVAR MVA % 0.9983PU 8.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 63
0.4143KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 55 HV_AUXTR2_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 64 LV_AUXTR1_170.4150 CKT MW MVAR MVA % 0.9981PU 8.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 64
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 56 HV_AUXTR1_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 274 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 65 LV_AUXTR2_170.4150 CKT MW MVAR MVA % 0.9982PU 8.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 65
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 57 HV_AUXTR2_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 66 LV_AUXTR1_180.4150 CKT MW MVAR MVA % 0.9980PU 8.36 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 66
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 58 HV_AUXTR1_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 67 LV_AUXTR2_180.4150 CKT MW MVAR MVA % 0.9980PU 8.36 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 67
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 59 HV_AUXTR2_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 68 LV_AUXTR1_190.4150 CKT MW MVAR MVA % 0.9978PU 8.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 68
0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 60 HV_AUXTR1_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 275 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 69 LV_AUXTR2_190.4150 CKT MW MVAR MVA % 0.9979PU 8.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 69
0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 61 HV_AUXTR2_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 70 HV_AUXTRPSS 33.000 CKT MW MVAR MVA % 1.0376PU 4.61 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 70
34.240KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.1 -0.0 0.1 0.00 0.00
1 1
TO 71 LV_AUXTRPSS 0.4150 1 0.1 0.0 0.1 1.0000LK 0.00 0.00
1 1

BUS 71 LV_AUXTRPSS 0.4150 CKT MW MVAR MVA % 1.0339PU 3.99 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 71
0.4290KV MW MVAR
1 1
TO LOAD-PQ 0.1 0.0 0.1
TO 70 HV_AUXTRPSS 33.000 1 -0.1 -0.0 0.1 1.0000UN 0.00 0.00
1 1

BUS 101 50MWBLK4_1 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 101
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 -17.0 29.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 276 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 103 HV_IDT1_11 33.000 1 -12.1 8.5 14.8 0.02 0.02


1 1
TO 104 HV_IDT1_14 33.000 1 -12.2 8.5 14.8 0.01 0.01
1 1

BUS 102 50MWBLK4_2 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 102
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 -17.0 29.7 0.01 0.01
1 1
TO 105 HV_IDT1_15 33.000 1 -12.2 8.5 14.8 0.01 0.01
1 1
TO 106 HV_IDT1_20 33.000 1 -12.1 8.5 14.8 0.02 0.02
1 1

BUS 103 HV_IDT1_11 33.000 CKT MW MVAR MVA % 1.0380PU 4.75 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 103
34.255KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 12.2 -8.5 14.9 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_11 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_11 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 104 HV_IDT1_14 33.000 CKT MW MVAR MVA % 1.0379PU 4.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 104
34.249KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 12.2 -8.5 14.9 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_14 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 277 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_14 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 105 HV_IDT1_15 33.000 CKT MW MVAR MVA % 1.0378PU 4.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 105
34.247KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 12.2 -8.5 14.9 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_15 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_15 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 106 HV_IDT1_20 33.000 CKT MW MVAR MVA % 1.0379PU 4.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 106
34.252KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 12.2 -8.5 14.9 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_20 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_20 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 107 LV1_IDT1_11 0.6000 CKT MW MVAR MVA % 1.0060PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 107
0.6036KV MW MVAR
1 1
TO 123 INV1_IDT1_110.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 139 HV_AUXTR1_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 108 LV2_IDT1_11 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 108

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 278 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6036KV MW MVAR
1 1
TO 124 INV2_IDT1_110.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 109 LV1_IDT2_11 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 109
0.6036KV MW MVAR
1 1
TO 125 INV1_IDT2_110.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_11 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 110 LV2_IDT2_11 0.6000 CKT MW MVAR MVA % 1.0060PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 110
0.6036KV MW MVAR
1 1
TO 126 INV2_IDT2_110.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 140 HV_AUXTR2_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_11 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 111 LV1_IDT1_14 0.6000 CKT MW MVAR MVA % 1.0058PU 9.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 111
0.6035KV MW MVAR
1 1
TO 127 INV1_IDT1_140.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 141 HV_AUXTR1_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 279 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT1_TR_14 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 112 LV2_IDT1_14 0.6000 CKT MW MVAR MVA % 1.0059PU 9.65 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 112
0.6035KV MW MVAR
1 1
TO 128 INV2_IDT1_140.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_14 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 113 LV1_IDT2_14 0.6000 CKT MW MVAR MVA % 1.0058PU 9.65 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 113
0.6035KV MW MVAR
1 1
TO 129 INV1_IDT2_140.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_14 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 114 LV2_IDT2_14 0.6000 CKT MW MVAR MVA % 1.0058PU 9.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 114
0.6035KV MW MVAR
1 1
TO 130 INV2_IDT2_140.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 142 HV_AUXTR2_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_14 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 115 LV1_IDT1_15 0.6000 CKT MW MVAR MVA % 1.0057PU 9.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 115
0.6034KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 280 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 131INV1_IDT1_150.6000 1 -3.1 1.8 3.6 0.01 0.01


1 1
TO 143 HV_AUXTR1_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 116 LV2_IDT1_15 0.6000 CKT MW MVAR MVA % 1.0058PU 9.63 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 116
0.6035KV MW MVAR
1 1
TO 132 INV2_IDT1_150.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 117 LV1_IDT2_15 0.6000 CKT MW MVAR MVA % 1.0058PU 9.63 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 117
0.6035KV MW MVAR
1 1
TO 133 INV1_IDT2_150.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_15 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 118 LV2_IDT2_15 0.6000 CKT MW MVAR MVA % 1.0057PU 9.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 118
0.6034KV MW MVAR
1 1
TO 134 INV2_IDT2_150.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 144 HV_AUXTR2_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_15 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 281 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 119 LV1_IDT1_20 0.6000 CKT MW MVAR MVA % 1.0059PU 9.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 119
0.6035KV MW MVAR
1 1
TO 135 INV1_IDT1_200.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 145 HV_AUXTR1_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 120 LV2_IDT1_20 0.6000 CKT MW MVAR MVA % 1.0059PU 9.68 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 120
0.6036KV MW MVAR
1 1
TO 136 INV2_IDT1_200.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 121 LV1_IDT2_20 0.6000 CKT MW MVAR MVA % 1.0059PU 9.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 121
0.6035KV MW MVAR
1 1
TO 137 INV1_IDT2_200.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_20 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 122 LV2_IDT2_20 0.6000 CKT MW MVAR MVA % 1.0059PU 9.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 122
0.6035KV MW MVAR
1 1
TO 138 INV2_IDT2_200.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 282 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 146 HV_AUXTR2_200.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_20 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 123 INV1_IDT1_110.6000 CKT MW MVAR MVA % 1.0069PU 9.84 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 123
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 124 INV2_IDT1_110.6000 CKT MW MVAR MVA % 1.0068PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 124
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 108 LV2_IDT1_11 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 125 INV1_IDT2_110.6000 CKT MW MVAR MVA % 1.0070PU 9.85 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 125
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 109 LV1_IDT2_11 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 126 INV2_IDT2_110.6000 CKT MW MVAR MVA % 1.0068PU 9.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 126
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 283 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 127 INV1_IDT1_140.6000 CKT MW MVAR MVA % 1.0068PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 127
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 128 INV2_IDT1_140.6000 CKT MW MVAR MVA % 1.0067PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 128
FROM GENERATION 3.1 -1.8L 3.6 115 0.6040KV MW MVAR
1 1
TO 112 LV2_IDT1_14 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 129 INV1_IDT2_140.6000 CKT MW MVAR MVA % 1.0068PU 9.80 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 129
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 113 LV1_IDT2_14 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 130 INV2_IDT2_140.6000 CKT MW MVAR MVA % 1.0066PU 9.76 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 130
FROM GENERATION 3.1 -1.8L 3.6 115 0.6040KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 131 INV1_IDT1_150.6000 CKT MW MVAR MVA % 1.0067PU 9.76 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 131
FROM GENERATION 3.1 -1.8L 3.6 115 0.6040KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 284 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 115 LV1_IDT1_15 0.6000 1 3.1 -1.8 3.6 0.01 0.01


1 1

BUS 132 INV2_IDT1_150.6000 CKT MW MVAR MVA % 1.0066PU 9.75 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 132
FROM GENERATION 3.1 -1.8L 3.6 115 0.6039KV MW MVAR
1 1
TO 116 LV2_IDT1_15 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 133 INV1_IDT2_150.6000 CKT MW MVAR MVA % 1.0067PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 133
FROM GENERATION 3.1 -1.8L 3.6 115 0.6040KV MW MVAR
1 1
TO 117 LV1_IDT2_15 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 134 INV2_IDT2_150.6000 CKT MW MVAR MVA % 1.0065PU 9.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 134
FROM GENERATION 3.1 -1.8L 3.6 115 0.6039KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 135 INV1_IDT1_200.6000 CKT MW MVAR MVA % 1.0068PU 9.81 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 135
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 285 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 136 INV2_IDT1_200.6000 CKT MW MVAR MVA % 1.0067PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 136
FROM GENERATION 3.1 -1.8L 3.6 115 0.6040KV MW MVAR
1 1
TO 120 LV2_IDT1_20 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 137 INV1_IDT2_200.6000 CKT MW MVAR MVA % 1.0069PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 137
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 121 LV1_IDT2_20 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 138 INV2_IDT2_200.6000 CKT MW MVAR MVA % 1.0067PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 138
FROM GENERATION 3.1 -1.8L 3.6 115 0.6040KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 139 HV_AUXTR1_110.6000 CKT MW MVAR MVA % 1.0060PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 139
0.6036KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 147 LV_AUXTR1_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 140 HV_AUXTR2_110.6000 CKT MW MVAR MVA % 1.0060PU 9.69 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 140

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 286 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6036KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 148 LV_AUXTR2_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 141 HV_AUXTR1_140.6000 CKT MW MVAR MVA % 1.0058PU 9.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 141
0.6035KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 149 LV_AUXTR1_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 142 HV_AUXTR2_140.6000 CKT MW MVAR MVA % 1.0058PU 9.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 142
0.6035KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 150 LV_AUXTR2_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 143 HV_AUXTR1_150.6000 CKT MW MVAR MVA % 1.0057PU 9.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 143
0.6034KV MW MVAR
1 1
TO 115 LV1_IDT1_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 287 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 151 LV_AUXTR1_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 144 HV_AUXTR2_150.6000 CKT MW MVAR MVA % 1.0057PU 9.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 144
0.6034KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 152 LV_AUXTR2_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 145 HV_AUXTR1_200.6000 CKT MW MVAR MVA % 1.0059PU 9.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 145
0.6035KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 153 LV_AUXTR1_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 146 HV_AUXTR2_200.6000 CKT MW MVAR MVA % 1.0059PU 9.67 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 146
0.6035KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 154 LV_AUXTR2_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 147 LV_AUXTR1_110.4150 CKT MW MVAR MVA % 0.9979PU 8.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 147

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 288 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 139 HV_AUXTR1_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 148 LV_AUXTR2_110.4150 CKT MW MVAR MVA % 0.9979PU 8.32 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 148
0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 140 HV_AUXTR2_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 149 LV_AUXTR1_140.4150 CKT MW MVAR MVA % 0.9977PU 8.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 149
0.4140KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 141 HV_AUXTR1_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 150 LV_AUXTR2_140.4150 CKT MW MVAR MVA % 0.9977PU 8.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 150
0.4140KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 142 HV_AUXTR2_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 151 LV_AUXTR1_150.4150 CKT MW MVAR MVA % 0.9976PU 8.25 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 151

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 289 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4140KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 143 HV_AUXTR1_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 152 LV_AUXTR2_150.4150 CKT MW MVAR MVA % 0.9976PU 8.25 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 152
0.4140KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 144 HV_AUXTR2_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 153 LV_AUXTR1_200.4150 CKT MW MVAR MVA % 0.9978PU 8.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 153
0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 145 HV_AUXTR1_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 154 LV_AUXTR2_200.4150 CKT MW MVAR MVA % 0.9978PU 8.30 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 154
0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 146 HV_AUXTR2_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 201 50MWBLK3_1 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 201

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 290 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 -16.8 29.5 0.01 0.01
1 1
TO 203 HV_IDT1_5 33.000 1 -12.1 8.4 14.7 0.05 0.05
1 1
TO 204 HV_IDT1_6 33.000 1 -12.1 8.4 14.8 0.04 0.04
1 1

BUS 202 50MWBLK3_2 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 202
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 -16.9 29.6 0.01 0.01
1 1
TO 205 HV_IDT1_7 33.000 1 -12.1 8.4 14.8 0.03 0.03
1 1
TO 206 HV_IDT1_9 33.000 1 -12.1 8.5 14.8 0.02 0.02
1 1

BUS 203 HV_IDT1_5 33.000 CKT MW MVAR MVA % 1.0385PU 4.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 203
34.270KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 12.2 -8.5 14.9 0.05 0.05
1 1
TO 3WNDTR IDT1_TR_5 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_5 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 204 HV_IDT1_6 33.000 CKT MW MVAR MVA % 1.0383PU 4.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 204

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 291 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

34.263KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 12.2 -8.5 14.9 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_6 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_6 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 205 HV_IDT1_7 33.000 CKT MW MVAR MVA % 1.0382PU 4.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 205
34.259KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 12.2 -8.5 14.9 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_7 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_7 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 206 HV_IDT1_9 33.000 CKT MW MVAR MVA % 1.0381PU 4.76 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 206
34.256KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 12.2 -8.5 14.9 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_9 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_9 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 207 LV1_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0064PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 207
0.6039KV MW MVAR
1 1
TO 223 INV1_IDT1_5 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 292 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 239 HV_AUXTR1_5 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT1_TR_5 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 208 LV2_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0065PU 9.84 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 208
0.6039KV MW MVAR
1 1
TO 224INV2_IDT1_5 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_5 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 209 LV1_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0065PU 9.84 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 209
0.6039KV MW MVAR
1 1
TO 225 INV1_IDT2_5 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_5 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 210 LV2_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0065PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 210
0.6039KV MW MVAR
1 1
TO 226 INV2_IDT2_5 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 240 HV_AUXTR2_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_5 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 211 LV1_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0062PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 211

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 293 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6037KV MW MVAR
1 1
TO 227 INV1_IDT1_6 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 241 HV_AUXTR1_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 212 LV2_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 212
0.6038KV MW MVAR
1 1
TO 228 INV2_IDT1_6 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 213 LV1_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 213
0.6038KV MW MVAR
1 1
TO 229 INV1_IDT2_6 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_6 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 214 LV2_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0063PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 214
0.6038KV MW MVAR
1 1
TO 230 INV2_IDT2_6 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 242 HV_AUXTR2_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 294 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_6 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 215 LV1_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0061PU 9.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 215
0.6037KV MW MVAR
1 1
TO 231 INV1_IDT1_7 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 243 HV_AUXTR1_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 216 LV2_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0062PU 9.75 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 216
0.6037KV MW MVAR
1 1
TO 232 INV2_IDT1_7 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 217 LV1_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0062PU 9.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 217
0.6037KV MW MVAR
1 1
TO 233 INV1_IDT2_7 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_7 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 218 LV2_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0061PU 9.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 218
0.6037KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 295 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 234INV2_IDT2_7 0.6000 1 -3.1 1.8 3.6 0.01 0.00


1 1
TO 244 HV_AUXTR2_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_7 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 219 LV1_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 219
0.6036KV MW MVAR
1 1
TO 235 INV1_IDT1_9 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 245 HV_AUXTR1_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 220 LV2_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0061PU 9.71 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 220
0.6036KV MW MVAR
1 1
TO 236 INV2_IDT1_9 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 221 LV1_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0060PU 9.71 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 221
0.6036KV MW MVAR
1 1
TO 237 INV1_IDT2_9 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_9 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 296 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 222 LV2_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 222
0.6036KV MW MVAR
1 1
TO 238 INV2_IDT2_9 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 246 HV_AUXTR2_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_9 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 223 INV1_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0074PU 9.97 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 223
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 207 LV1_IDT1_5 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 224 INV2_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0073PU 9.96 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 224
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 208 LV2_IDT1_5 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 225 INV1_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0075PU 9.98 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 225
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 209 LV1_IDT2_5 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 297 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 226 INV2_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0073PU 9.95 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 226
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 227 INV1_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0072PU 9.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 227
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 228 INV2_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0071PU 9.90 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 228
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 212 LV2_IDT1_6 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 229 INV1_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0073PU 9.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 229
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 213 LV1_IDT2_6 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 230 INV2_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0070PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 230
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 298 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 214 LV2_IDT2_6 0.6000 1 3.1 -1.8 3.6 0.01 0.00


1 1

BUS 231 INV1_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0071PU 9.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 231
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 232 INV2_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0070PU 9.86 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 232
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 216 LV2_IDT1_7 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 233 INV1_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0071PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 233
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 217 LV1_IDT2_7 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 234 INV2_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0069PU 9.85 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 234
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 299 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 235 INV1_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0070PU 9.85 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 235
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 236 INV2_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0069PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 236
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 220 LV2_IDT1_9 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 237 INV1_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0070PU 9.86 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 237
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 221 LV1_IDT2_9 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 238 INV2_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0068PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 238
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 222 LV2_IDT2_9 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 239 HV_AUXTR1_5 0.6000 CKT MW MVAR MVA % 1.0064PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 239
0.6039KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 300 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 207 LV1_IDT1_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 247 LV_AUXTR1_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 240 HV_AUXTR2_5 0.6000 CKT MW MVAR MVA % 1.0065PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 240
0.6039KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 248 LV_AUXTR2_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 241 HV_AUXTR1_6 0.6000 CKT MW MVAR MVA % 1.0062PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 241
0.6037KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 249 LV_AUXTR1_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 242 HV_AUXTR2_6 0.6000 CKT MW MVAR MVA % 1.0063PU 9.77 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 242
0.6038KV MW MVAR
1 1
TO 214 LV2_IDT2_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 250 LV_AUXTR2_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 301 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 243 HV_AUXTR1_7 0.6000 CKT MW MVAR MVA % 1.0061PU 9.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 243
0.6037KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 251 LV_AUXTR1_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 244 HV_AUXTR2_7 0.6000 CKT MW MVAR MVA % 1.0061PU 9.74 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 244
0.6037KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 252 LV_AUXTR2_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 245 HV_AUXTR1_9 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 245
0.6036KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 253 LV_AUXTR1_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 246 HV_AUXTR2_9 0.6000 CKT MW MVAR MVA % 1.0060PU 9.70 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 246
0.6036KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 302 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 222 LV2_IDT2_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 254 LV_AUXTR2_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 247 LV_AUXTR1_5 0.4150 CKT MW MVAR MVA % 0.9983PU 8.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 247
0.4143KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 239 HV_AUXTR1_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 248 LV_AUXTR2_5 0.4150 CKT MW MVAR MVA % 0.9984PU 8.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 248
0.4143KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 240 HV_AUXTR2_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 249 LV_AUXTR1_6 0.4150 CKT MW MVAR MVA % 0.9981PU 8.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 249
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 241 HV_AUXTR1_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 250 LV_AUXTR2_6 0.4150 CKT MW MVAR MVA % 0.9982PU 8.40 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 250

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 303 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 242 HV_AUXTR2_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 251 LV_AUXTR1_7 0.4150 CKT MW MVAR MVA % 0.9980PU 8.37 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 251
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 243 HV_AUXTR1_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 252 LV_AUXTR2_7 0.4150 CKT MW MVAR MVA % 0.9980PU 8.37 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 252
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 244 HV_AUXTR2_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 253 LV_AUXTR1_9 0.4150 CKT MW MVAR MVA % 0.9979PU 8.33 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 253
0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 245 HV_AUXTR1_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 254 LV_AUXTR2_9 0.4150 CKT MW MVAR MVA % 0.9979PU 8.33 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 254

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 304 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4141KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 246 HV_AUXTR2_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 301 50MWBLK1_1 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 301
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 -16.9 29.5 0.01 0.01
1 1
TO 303 HV_IDT1_10 33.000 1 -12.1 8.4 14.8 0.03 0.03
1 1
TO 304 HV_IDT1_8 33.000 1 -12.1 8.4 14.8 0.04 0.04
1 1

BUS 302 50MWBLK1_2 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 302
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 -16.8 29.5 0.01 0.01
1 1
TO 305 HV_IDT1_13 33.000 1 -12.1 8.4 14.8 0.04 0.04
1 1
TO 306 HV_IDT1_12 33.000 1 -12.1 8.4 14.7 0.04 0.04
1 1
TO 360 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 303 HV_IDT1_10 33.000 CKT MW MVAR MVA % 1.0381PU 4.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 303

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 305 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

34.258KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 12.2 -8.5 14.9 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_10 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_10 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 304 HV_IDT1_8 33.000 CKT MW MVAR MVA % 1.0383PU 4.84 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 304
34.264KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 12.2 -8.5 14.9 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_8 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_8 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 305 HV_IDT1_13 33.000 CKT MW MVAR MVA % 1.0383PU 4.84 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 305
34.265KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 12.2 -8.5 14.9 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_13 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_13 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 306 HV_IDT1_12 33.000 CKT MW MVAR MVA % 1.0384PU 4.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 306
34.269KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 12.2 -8.5 14.9 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_12 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 306 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_12 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 307 LV1_IDT1_10 0.6000 CKT MW MVAR MVA % 1.0061PU 9.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 307
0.6036KV MW MVAR
1 1
TO 323 INV1_IDT1_100.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 339 HV_AUXTR1_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 308 LV2_IDT1_10 0.6000 CKT MW MVAR MVA % 1.0061PU 9.73 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 308
0.6037KV MW MVAR
1 1
TO 324 INV2_IDT1_100.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 309 LV1_IDT2_10 0.6000 CKT MW MVAR MVA % 1.0061PU 9.73 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 309
0.6037KV MW MVAR
1 1
TO 325 INV1_IDT2_100.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_10 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 310 LV2_IDT2_10 0.6000 CKT MW MVAR MVA % 1.0061PU 9.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 310
0.6036KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 307 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 326INV2_IDT2_100.6000 1 -3.1 1.8 3.6 0.01 0.00


1 1
TO 340 HV_AUXTR2_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_10 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 311 LV1_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 311
0.6038KV MW MVAR
1 1
TO 327 INV1_IDT1_8 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 341 HV_AUXTR1_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 312 LV2_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0063PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 312
0.6038KV MW MVAR
1 1
TO 328 INV2_IDT1_8 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 313 LV1_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0063PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 313
0.6038KV MW MVAR
1 1
TO 329 INV1_IDT2_8 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_8 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 308 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 314 LV2_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 314
0.6038KV MW MVAR
1 1
TO 330 INV2_IDT2_8 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 342 HV_AUXTR2_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_8 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 315 LV1_IDT1_13 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 315
0.6038KV MW MVAR
1 1
TO 331 INV1_IDT1_130.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 343 HV_AUXTR1_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 316 LV2_IDT1_13 0.6000 CKT MW MVAR MVA % 1.0064PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 316
0.6038KV MW MVAR
1 1
TO 332 INV2_IDT1_130.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 317 LV1_IDT2_13 0.6000 CKT MW MVAR MVA % 1.0063PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 317
0.6038KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 309 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 333 INV1_IDT2_130.6000 1 -3.1 1.8 3.6 0.01 0.01


1 1
TO 3WNDTR IDT2_TR_13 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 318 LV2_IDT2_13 0.6000 CKT MW MVAR MVA % 1.0063PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 318
0.6038KV MW MVAR
1 1
TO 334INV2_IDT2_130.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 344 HV_AUXTR2_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_13 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 319 LV1_IDT1_12 0.6000 CKT MW MVAR MVA % 1.0064PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 319
0.6038KV MW MVAR
1 1
TO 335 INV1_IDT1_120.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 345 HV_AUXTR1_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 320 LV2_IDT1_12 0.6000 CKT MW MVAR MVA % 1.0065PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 320
0.6039KV MW MVAR
1 1
TO 336 INV2_IDT1_120.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 310 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 321 LV1_IDT2_12 0.6000 CKT MW MVAR MVA % 1.0065PU 9.83 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 321
0.6039KV MW MVAR
1 1
TO 337 INV1_IDT2_120.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_12 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 322 LV2_IDT2_12 0.6000 CKT MW MVAR MVA % 1.0064PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 322
0.6039KV MW MVAR
1 1
TO 338 INV2_IDT2_120.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 346 HV_AUXTR2_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_12 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 323 INV1_IDT1_100.6000 CKT MW MVAR MVA % 1.0070PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 323
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 324 INV2_IDT1_100.6000 CKT MW MVAR MVA % 1.0069PU 9.85 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 324
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 308 LV2_IDT1_10 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 311 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 325 INV1_IDT2_100.6000 CKT MW MVAR MVA % 1.0071PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 325
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 309 LV1_IDT2_10 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 326 INV2_IDT2_100.6000 CKT MW MVAR MVA % 1.0069PU 9.84 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 326
FROM GENERATION 3.1 -1.8L 3.6 115 0.6041KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 327 INV1_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0072PU 9.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 327
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 328 INV2_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0071PU 9.91 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 328
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 312 LV2_IDT1_8 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 329 INV1_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0073PU 9.93 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 329
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 312 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 313 LV1_IDT2_8 0.6000 1 3.1 -1.8 3.6 0.01 0.01


1 1

BUS 330 INV2_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0071PU 9.90 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 330
FROM GENERATION 3.1 -1.8L 3.6 115 0.6042KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 331 INV1_IDT1_130.6000 CKT MW MVAR MVA % 1.0073PU 9.93 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 331
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 332 INV2_IDT1_130.6000 CKT MW MVAR MVA % 1.0071PU 9.91 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 332
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 316 LV2_IDT1_13 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 333 INV1_IDT2_130.6000 CKT MW MVAR MVA % 1.0073PU 9.94 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 333
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 317 LV1_IDT2_13 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 313 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 334 INV2_IDT2_130.6000 CKT MW MVAR MVA % 1.0071PU 9.90 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 334
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 335 INV1_IDT1_120.6000 CKT MW MVAR MVA % 1.0074PU 9.96 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 335
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 336 INV2_IDT1_120.6000 CKT MW MVAR MVA % 1.0073PU 9.95 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 336
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 320 LV2_IDT1_12 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 337 INV1_IDT2_120.6000 CKT MW MVAR MVA % 1.0074PU 9.97 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 337
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 321 LV1_IDT2_12 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 338 INV2_IDT2_120.6000 CKT MW MVAR MVA % 1.0072PU 9.94 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 338
FROM GENERATION 3.1 -1.8L 3.6 115 0.6043KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 314 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 322 LV2_IDT2_12 0.6000 1 3.1 -1.8 3.6 0.01 0.00


1 1

BUS 339 HV_AUXTR1_100.6000 CKT MW MVAR MVA % 1.0061PU 9.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 339
0.6036KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 347 LV_AUXTR1_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 340 HV_AUXTR2_100.6000 CKT MW MVAR MVA % 1.0061PU 9.72 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 340
0.6036KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 348 LV_AUXTR2_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 341 HV_AUXTR1_8 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 341
0.6038KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 349 LV_AUXTR1_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 342 HV_AUXTR2_8 0.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 342

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 315 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6038KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 350 LV_AUXTR2_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 343 HV_AUXTR1_130.6000 CKT MW MVAR MVA % 1.0063PU 9.78 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 343
0.6038KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 351 LV_AUXTR1_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 344 HV_AUXTR2_130.6000 CKT MW MVAR MVA % 1.0063PU 9.79 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 344
0.6038KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 352 LV_AUXTR2_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 345 HV_AUXTR1_120.6000 CKT MW MVAR MVA % 1.0064PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 345
0.6038KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 316 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 353 LV_AUXTR1_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 346 HV_AUXTR2_120.6000 CKT MW MVAR MVA % 1.0064PU 9.82 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 346
0.6039KV MW MVAR
1 1
TO 322 LV2_IDT2_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 354 LV_AUXTR2_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 347 LV_AUXTR1_100.4150 CKT MW MVAR MVA % 0.9980PU 8.35 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 347
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 339 HV_AUXTR1_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 348 LV_AUXTR2_100.4150 CKT MW MVAR MVA % 0.9980PU 8.35 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 348
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 340 HV_AUXTR2_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 349 LV_AUXTR1_8 0.4150 CKT MW MVAR MVA % 0.9982PU 8.41 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 349
0.4142KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 317 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 341 HV_AUXTR1_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 350 LV_AUXTR2_8 0.4150 CKT MW MVAR MVA % 0.9982PU 8.41 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 350
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 342 HV_AUXTR2_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 351 LV_AUXTR1_130.4150 CKT MW MVAR MVA % 0.9982PU 8.42 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 351
0.4142KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 343 HV_AUXTR1_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 352 LV_AUXTR2_130.4150 CKT MW MVAR MVA % 0.9982PU 8.42 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 352
0.4143KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 344 HV_AUXTR2_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 353 LV_AUXTR1_120.4150 CKT MW MVAR MVA % 0.9983PU 8.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 353
0.4143KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 318 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 345 HV_AUXTR1_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 354 LV_AUXTR2_120.4150 CKT MW MVAR MVA % 0.9983PU 8.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 354
0.4143KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 346 HV_AUXTR2_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 360 HV_AUXTR33 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 360
34.243KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 361 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 361 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 1.0333PU 3.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 361
0.4288KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 360 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 401 50MWBLK5_1 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 401

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 319 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 -16.7 29.4 0.01 0.01
1 1
TO 403 HV_IDT1_1 33.000 1 -12.1 8.3 14.7 0.06 0.06
1 1
TO 404 HV_IDT1_2 33.000 1 -12.1 8.3 14.7 0.05 0.05
1 1

BUS 402 50MWBLK5_2 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 402
34.243KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 -16.7 29.4 0.01 0.01
1 1
TO 405 HV_IDT1_3 33.000 1 -12.1 8.3 14.7 0.05 0.05
1 1
TO 406 HV_IDT1_4 33.000 1 -12.1 8.3 14.7 0.06 0.06
1 1
TO 460 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 403 HV_IDT1_1 33.000 CKT MW MVAR MVA % 1.0388PU 4.97 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 403
34.279KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 12.2 -8.5 14.9 0.06 0.06
1 1
TO 3WNDTR IDT1_TR_1 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.65
TO 3WNDTR IDT2_TR_1 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.65

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 320 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 404 HV_IDT1_2 33.000 CKT MW MVAR MVA % 1.0386PU 4.93 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 404
34.275KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 12.2 -8.5 14.9 0.05 0.05
1 1
TO 3WNDTR IDT1_TR_2 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.65
TO 3WNDTR IDT2_TR_2 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.65

BUS 405 HV_IDT1_3 33.000 CKT MW MVAR MVA % 1.0386PU 4.93 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 405
34.274KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 12.2 -8.5 14.9 0.05 0.05
1 1
TO 3WNDTR IDT1_TR_3 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66
TO 3WNDTR IDT2_TR_3 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.66

BUS 406 HV_IDT1_4 33.000 CKT MW MVAR MVA % 1.0387PU 4.95 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 406
34.276KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 12.2 -8.5 14.9 0.06 0.06
1 1
TO 3WNDTR IDT1_TR_4 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.65
TO 3WNDTR IDT2_TR_4 WND 1 1 -6.1 4.3 7.4 118 1.0000LK 0.15 0.65

BUS 407 LV1_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0067PU 9.91 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 407
0.6040KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 321 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 423INV1_IDT1_1 0.6000 1 -3.1 1.8 3.6 0.01 0.01


1 1
TO 439 HV_AUXTR1_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 408 LV2_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0068PU 9.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 408
0.6041KV MW MVAR
1 1
TO 424 INV2_IDT1_1 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 409 LV1_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0068PU 9.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 409
0.6041KV MW MVAR
1 1
TO 425 INV1_IDT2_1 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_1 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 410 LV2_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0068PU 9.91 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 410
0.6041KV MW MVAR
1 1
TO 426 INV2_IDT2_1 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 440 HV_AUXTR2_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_1 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 322 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 411 LV1_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 411
0.6040KV MW MVAR
1 1
TO 427 INV1_IDT1_2 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 441 HV_AUXTR1_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 412 LV2_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0067PU 9.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 412
0.6040KV MW MVAR
1 1
TO 428 INV2_IDT1_2 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 413 LV1_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0066PU 9.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 413
0.6040KV MW MVAR
1 1
TO 429 INV1_IDT2_2 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_2 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 414 LV2_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 414
0.6040KV MW MVAR
1 1
TO 430 INV2_IDT2_2 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 323 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 442 HV_AUXTR2_2 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_2 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 415 LV1_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 415
0.6039KV MW MVAR
1 1
TO 431INV1_IDT1_3 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 443 HV_AUXTR1_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 416 LV2_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0066PU 9.88 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 416
0.6040KV MW MVAR
1 1
TO 432 INV2_IDT1_3 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 417 LV1_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 417
0.6040KV MW MVAR
1 1
TO 433 INV1_IDT2_3 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_3 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 418 LV2_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 418

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 324 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6040KV MW MVAR
1 1
TO 434 INV2_IDT2_3 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 444 HV_AUXTR2_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_3 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.66

BUS 419 LV1_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0066PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 419
0.6040KV MW MVAR
1 1
TO 435 INV1_IDT1_4 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1
TO 445 HV_AUXTR1_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 420 LV2_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0067PU 9.90 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 420
0.6040KV MW MVAR
1 1
TO 436 INV2_IDT1_4 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 421 LV1_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0067PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 421
0.6040KV MW MVAR
1 1
TO 437 INV1_IDT2_4 0.6000 1 -3.1 1.8 3.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 325 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_4 WND 2 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 422 LV2_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0067PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 422
0.6040KV MW MVAR
1 1
TO 438 INV2_IDT2_4 0.6000 1 -3.1 1.8 3.6 0.01 0.00
1 1
TO 446 HV_AUXTR2_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_4 WND 3 1 3.1 -1.8 3.6 116 1.0000LK 0.15 0.65

BUS 423 INV1_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0077PU 10.05 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 423
FROM GENERATION 3.1 -1.8L 3.6 115 0.6046KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 424 INV2_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0076PU 10.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 424
FROM GENERATION 3.1 -1.8L 3.6 115 0.6046KV MW MVAR
1 1
TO 408 LV2_IDT1_1 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 425 INV1_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0078PU 10.06 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 425
FROM GENERATION 3.1 -1.8L 3.6 115 0.6047KV MW MVAR
1 1
TO 409 LV1_IDT2_1 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 326 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 426 INV2_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0075PU 10.03 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 426
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 427 INV1_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0076PU 10.02 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 427
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 428 INV2_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0075PU 10.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 428
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 412 LV2_IDT1_2 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 429 INV1_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0076PU 10.02 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 429
FROM GENERATION 3.1 -1.8L 3.6 115 0.6046KV MW MVAR
1 1
TO 413 LV1_IDT2_2 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 430 INV2_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0074PU 9.99 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 430

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 327 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR


1 1
TO 414 LV2_IDT2_2 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 431 INV1_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0076PU 10.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 431
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 432 INV2_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0074PU 9.99 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 432
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 416 LV2_IDT1_3 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 433 INV1_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0076PU 10.02 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 433
FROM GENERATION 3.1 -1.8L 3.6 115 0.6046KV MW MVAR
1 1
TO 417 LV1_IDT2_3 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 434 INV2_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0074PU 9.99 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 434
FROM GENERATION 3.1 -1.8L 3.6 115 0.6044KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 328 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 435 INV1_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0076PU 10.03 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 435
FROM GENERATION 3.1 -1.8L 3.6 115 0.6046KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 436 INV2_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0075PU 10.01 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 436
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 420 LV2_IDT1_4 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 437 INV1_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0077PU 10.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 437
FROM GENERATION 3.1 -1.8L 3.6 115 0.6046KV MW MVAR
1 1
TO 421 LV1_IDT2_4 0.6000 1 3.1 -1.8 3.6 0.01 0.01
1 1

BUS 438 INV2_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0075PU 10.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 438
FROM GENERATION 3.1 -1.8L 3.6 115 0.6045KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 3.1 -1.8 3.6 0.01 0.00
1 1

BUS 439 HV_AUXTR1_1 0.6000 CKT MW MVAR MVA % 1.0067PU 9.91 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 439

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 329 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6040KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 447 LV_AUXTR1_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 440 HV_AUXTR2_1 0.6000 CKT MW MVAR MVA % 1.0068PU 9.91 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 440
0.6041KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 448 LV_AUXTR2_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 441 HV_AUXTR1_2 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 441
0.6040KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 449 LV_AUXTR1_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 442 HV_AUXTR2_2 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 442
0.6040KV MW MVAR
1 1
TO 414 LV2_IDT2_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 330 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 450 LV_AUXTR2_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 443 HV_AUXTR1_3 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 443
0.6039KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 451 LV_AUXTR1_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 444 HV_AUXTR2_3 0.6000 CKT MW MVAR MVA % 1.0066PU 9.87 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 444
0.6040KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 452 LV_AUXTR2_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 445 HV_AUXTR1_4 0.6000 CKT MW MVAR MVA % 1.0066PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 445
0.6040KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 453 LV_AUXTR1_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 446 HV_AUXTR2_4 0.6000 CKT MW MVAR MVA % 1.0067PU 9.89 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 446

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 331 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.6040KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 454 LV_AUXTR2_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 447 LV_AUXTR1_1 0.4150 CKT MW MVAR MVA % 0.9986PU 8.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 447
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 439 HV_AUXTR1_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 448 LV_AUXTR2_1 0.4150 CKT MW MVAR MVA % 0.9987PU 8.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 448
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 440 HV_AUXTR2_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 449 LV_AUXTR1_2 0.4150 CKT MW MVAR MVA % 0.9985PU 8.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 449
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 441 HV_AUXTR1_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 332 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 450 LV_AUXTR2_2 0.4150 CKT MW MVAR MVA % 0.9985PU 8.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 450
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 442 HV_AUXTR2_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 451 LV_AUXTR1_3 0.4150 CKT MW MVAR MVA % 0.9985PU 8.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 451
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 443 HV_AUXTR1_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 452 LV_AUXTR2_3 0.4150 CKT MW MVAR MVA % 0.9985PU 8.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 452
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 444 HV_AUXTR2_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 453 LV_AUXTR1_4 0.4150 CKT MW MVAR MVA % 0.9985PU 8.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 453
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 445 HV_AUXTR1_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 333 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 454 LV_AUXTR2_4 0.4150 CKT MW MVAR MVA % 0.9986PU 8.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 454
0.4144KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 446 HV_AUXTR2_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 460 HV_AUXTR33 33.000 CKT MW MVAR MVA % 1.0377PU 4.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 460
34.243KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 461 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 461 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 1.0333PU 3.92 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 461
0.4288KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 460 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 334 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

11.4 Grid voltage=0.9 p.u- Active Power and Reactive Power Flow Re-
sults

This section provides the detailed power flow results for the operating scenario when 220kV
pooling station of the solar park is subjected to grid voltage=0.9 p.u. These results include MW,
MVAr, MVA, Losses MW, Losses MVAr in each feeder of the network along with the voltage (in
kV).

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 335 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 1 220KVPGCILSS220.00 CKT MW MVAR MVA % 0.9000PU 0.00 X--- LOSSES ---X X-
--- AREA -----X X---- ZONE -----X 1
FROM GENERATION -242.1 -74.6R 253.3 72 198.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 -242.1 -74.6 253.3 0.00 0.00
1 1

BUS 2 220KVPOOLING220.00 CKT MW MVAR MVA % 0.9000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 2
198.00KV MW MVAR
1 1
TO 1 220KVPGCILSS220.00 1 242.1 74.6 253.3 0.00 0.00
1 1
TO 3 HV_POWERTR-1220.00 1 -60.6 -18.8 63.5 0.00 0.00
1 1
TO 4 HV_POWERTR-2220.00 1 -60.6 -18.7 63.4 0.00 0.00
1 1
TO 5 HV_POWERTR-3220.00 1 -60.5 -18.6 63.3 0.00 0.00
1 1
TO 6 HV_POWERTR-4220.00 1 -60.4 -18.5 63.2 0.00 0.00
1 1

BUS 3 HV_POWERTR-1220.00 CKT MW MVAR MVA % 0.9000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 3
198.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.6 18.8 63.5 0.00 0.00
1 1
TO 7 LV_POWERTR-133.000 1 -60.6 -18.8 63.5 1.0000LK 0.10 7.40
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 336 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 4 HV_POWERTR-2220.00 CKT MW MVAR MVA % 0.9000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 4
198.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.6 18.7 63.4 0.00 0.00
1 1
TO 8 LV_POWERTR-233.000 1 -60.6 -18.7 63.4 1.0000LK 0.10 7.38
1 1

BUS 5 HV_POWERTR-3220.00 CKT MW MVAR MVA % 0.9000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 5
198.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.5 18.6 63.3 0.00 0.00
1 1
TO 9 LV_POWERTR-333.000 1 -60.5 -18.6 63.3 1.0000LK 0.10 7.36
1 1

BUS 6 HV_POWERTR-4220.00 CKT MW MVAR MVA % 0.9000PU 0.00 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 6
198.00KV MW MVAR
1 1
TO 2 220KVPOOLING220.00 1 60.4 18.5 63.2 0.00 0.00
1 1
TO 10 LV_POWERTR-433.000 1 -60.4 -18.5 63.2 1.0000LK 0.10 7.34
1 1

BUS 7 LV_POWERTR-133.000 CKT MW MVAR MVA % 0.9378PU 6.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 7
30.946KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 337 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3 HV_POWERTR-1220.00 1 60.7 26.2 66.1 1.0000UN 0.10 7.40


1 1
TO 11 33KMAINHTPNL33.000 1 -60.7 -26.2 66.1 0.02 0.02
1 1

BUS 8 LV_POWERTR-233.000 CKT MW MVAR MVA % 0.9376PU 6.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 8
30.941KV MW MVAR
1 1
TO 4 HV_POWERTR-2220.00 1 60.7 26.1 66.0 1.0000UN 0.10 7.38
1 1
TO 11 33KMAINHTPNL33.000 1 -60.7 -26.1 66.0 0.02 0.03
1 1

BUS 9 LV_POWERTR-333.000 CKT MW MVAR MVA % 0.9374PU 6.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 9
30.935KV MW MVAR
1 1
TO 5 HV_POWERTR-3220.00 1 60.6 26.0 65.9 1.0000UN 0.10 7.36
1 1
TO 11 33KMAINHTPNL33.000 1 -60.6 -26.0 65.9 0.03 0.04
1 1

BUS 10 LV_POWERTR-433.000 CKT MW MVAR MVA % 0.9372PU 6.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 10
30.928KV MW MVAR
1 1
TO 6 HV_POWERTR-4220.00 1 60.5 25.8 65.8 1.0000UN 0.10 7.34
1 1
TO 11 33KMAINHTPNL33.000 1 -60.5 -25.8 65.8 0.04 0.05
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 338 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 11 33KMAINHTPNL33.000 CKT MW MVAR MVA % 0.9381PU 6.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 11
30.956KV MW MVAR
1 1
TO 7 LV_POWERTR-133.000 1 60.7 26.2 66.1 0.02 0.02
1 1
TO 8 LV_POWERTR-233.000 1 60.7 26.0 66.0 0.02 0.03
1 1
TO 9 LV_POWERTR-333.000 1 60.6 25.9 65.9 0.03 0.04
1 1
TO 10 LV_POWERTR-433.000 1 60.6 25.8 65.8 0.04 0.05
1 1
TO 12 50MWBLK2_1 33.000 1 -24.3 -10.3 26.4 0.01 0.01
1 1
TO 13 50MWBLK2_2 33.000 1 -24.3 -10.6 26.5 0.01 0.01
1 1
TO 70 HV_AUXTRPSS 33.000 1 0.1 0.0 0.1 0.00 0.00
1 1
TO 101 50MWBLK4_1 33.000 1 -24.3 -10.7 26.6 0.01 0.01
1 1
TO 102 50MWBLK4_2 33.000 1 -24.3 -10.8 26.6 0.01 0.01
1 1
TO 201 50MWBLK3_1 33.000 1 -24.3 -10.3 26.3 0.01 0.01
1 1
TO 202 50MWBLK3_2 33.000 1 -24.3 -10.6 26.5 0.01 0.01
1 1
TO 301 50MWBLK1_1 33.000 1 -24.3 -10.4 26.4 0.01 0.01
1 1
TO 302 50MWBLK1_2 33.000 1 -24.2 -10.2 26.3 0.01 0.01
1 1
TO 401 50MWBLK5_1 33.000 1 -24.2 -9.9 26.2 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 339 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 402 50MWBLK5_2 33.000 1 -24.2 -10.0 26.2 0.01 0.01


1 1

BUS 12 50MWBLK2_1 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 12
30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 10.3 26.4 0.01 0.01
1 1
TO 14 HV_IDT1_16 33.000 1 -12.1 -5.1 13.2 0.04 0.04
1 1
TO 16 HV_IDT1_17 33.000 1 -12.1 -5.2 13.2 0.03 0.03
1 1

BUS 13 50MWBLK2_2 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 13
30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 10.6 26.5 0.01 0.01
1 1
TO 18 HV_IDT1_18 33.000 1 -12.1 -5.2 13.2 0.03 0.03
1 1
TO 20 HV_IDT1_19 33.000 1 -12.2 -5.3 13.3 0.02 0.02
1 1

BUS 14 HV_IDT1_16 33.000 CKT MW MVAR MVA % 0.9425PU 6.23 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 14
31.101KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 12.2 5.0 13.2 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_16 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.62

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 340 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 1 1 -6.1 -2.5 6.6 104 1.0000LK 0.14 0.62

BUS 16 HV_IDT1_17 33.000 CKT MW MVAR MVA % 0.9417PU 6.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 16
31.077KV MW MVAR
1 1
TO 12 50MWBLK2_1 33.000 1 12.2 5.1 13.2 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_17 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_17 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63

BUS 18 HV_IDT1_18 33.000 CKT MW MVAR MVA % 0.9410PU 6.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 18
31.053KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 12.2 5.2 13.2 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_18 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_18 WND 1 1 -6.1 -2.6 6.6 1.0000LK 0.14 0.63

BUS 20 HV_IDT1_19 33.000 CKT MW MVAR MVA % 0.9403PU 6.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 20
31.031KV MW MVAR
1 1
TO 13 50MWBLK2_2 33.000 1 12.2 5.3 13.3 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_19 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.64
TO 3WNDTR IDT2_TR_19 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.64

BUS 22 LV1_IDT1_16 0.6000 CKT MW MVAR MVA % 0.9974PU 40.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 22

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 341 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5984KV MW MVAR
1 1
TO 38 INV1_IDT1_160.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 54 HV_AUXTR1_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 2 1 3.1 1.5 3.5 111 1.0000LK 30.00LK 0.14 0.62

BUS 23 LV2_IDT1_16 0.6000 CKT MW MVAR MVA % 0.9979PU 40.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 23
0.5987KV MW MVAR
1 1
TO 39 INV2_IDT1_160.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_16 WND 3 1 3.1 1.6 3.5 112 1.0000LK 30.00LK 0.14 0.62

BUS 24 LV1_IDT2_16 0.6000 CKT MW MVAR MVA % 0.9974PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 24
0.5984KV MW MVAR
1 1
TO 40 INV1_IDT2_160.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_16 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 25 LV2_IDT2_16 0.6000 CKT MW MVAR MVA % 0.9979PU 10.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 25
0.5987KV MW MVAR
1 1
TO 41 INV2_IDT2_160.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 55 HV_AUXTR2_160.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 342 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_16 WND 3 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.62

BUS 26 LV1_IDT1_17 0.6000 CKT MW MVAR MVA % 0.9974PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 26
0.5984KV MW MVAR
1 1
TO 42 INV1_IDT1_170.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 56 HV_AUXTR1_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 2 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.63

BUS 27 LV2_IDT1_17 0.6000 CKT MW MVAR MVA % 0.9979PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 27
0.5987KV MW MVAR
1 1
TO 43 INV2_IDT1_170.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_17 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 28 LV1_IDT2_17 0.6000 CKT MW MVAR MVA % 0.9974PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 28
0.5984KV MW MVAR
1 1
TO 44 INV1_IDT2_170.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_17 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 29 LV2_IDT2_17 0.6000 CKT MW MVAR MVA % 0.9979PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 29
0.5987KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 343 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 45 INV2_IDT2_170.6000 1 -3.1 -1.6 3.5 0.01 0.00


1 1
TO 57 HV_AUXTR2_170.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_17 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 30 LV1_IDT1_18 0.6000 CKT MW MVAR MVA % 0.9974PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 30
0.5984KV MW MVAR
1 1
TO 46 INV1_IDT1_180.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 58 HV_AUXTR1_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 31 LV2_IDT1_18 0.6000 CKT MW MVAR MVA % 0.9979PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 31
0.5987KV MW MVAR
1 1
TO 47 INV2_IDT1_180.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_18 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 32 LV1_IDT2_18 0.6000 CKT MW MVAR MVA % 0.9974PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 32
0.5984KV MW MVAR
1 1
TO 48 INV1_IDT2_180.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_18 WND 2 1 3.1 1.6 3.5 1.0000LK 0.14 0.63

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 344 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 33 LV2_IDT2_18 0.6000 CKT MW MVAR MVA % 0.9979PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 33
0.5987KV MW MVAR
1 1
TO 49 INV2_IDT2_180.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 59 HV_AUXTR2_180.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_18 WND 3 1 3.1 1.6 3.5 1.0000LK 0.14 0.63

BUS 34 LV1_IDT1_19 0.6000 CKT MW MVAR MVA % 0.9974PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 34
0.5984KV MW MVAR
1 1
TO 50 INV1_IDT1_190.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 60 HV_AUXTR1_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.64

BUS 35 LV2_IDT1_19 0.6000 CKT MW MVAR MVA % 0.9979PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 35
0.5987KV MW MVAR
1 1
TO 51 INV2_IDT1_190.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_19 WND 3 1 3.1 1.6 3.5 114 1.0000LK 0.14 0.64

BUS 36 LV1_IDT2_19 0.6000 CKT MW MVAR MVA % 0.9974PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 36
0.5984KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 345 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 52 INV1_IDT2_190.6000 1 -3.1 -1.6 3.5 0.01 0.01


1 1
TO 3WNDTR IDT2_TR_19 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.64

BUS 37 LV2_IDT2_19 0.6000 CKT MW MVAR MVA % 0.9979PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 37
0.5987KV MW MVAR
1 1
TO 53 INV2_IDT2_190.6000 1 -3.1 -1.7 3.5 0.01 0.00
1 1
TO 61 HV_AUXTR2_190.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_19 WND 3 1 3.1 1.6 3.5 114 1.0000LK 0.14 0.64

BUS 38 INV1_IDT1_160.6000 CKT MW MVAR MVA % 1.0000PU 40.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 38
FROM GENERATION 3.1 1.5R 3.5 112 0.6000KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 39 INV2_IDT1_160.6000 CKT MW MVAR MVA % 1.0000PU 40.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 39
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 23 LV2_IDT1_16 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 40 INV1_IDT2_160.6000 CKT MW MVAR MVA % 1.0000PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 40
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 346 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 24 LV1_IDT2_16 0.6000 1 3.1 1.5 3.5 0.01 0.01


1 1

BUS 41 INV2_IDT2_160.6000 CKT MW MVAR MVA % 1.0000PU 10.57 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 41
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 42 INV1_IDT1_170.6000 CKT MW MVAR MVA % 1.0000PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 42
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 43 INV2_IDT1_170.6000 CKT MW MVAR MVA % 1.0000PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 43
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 27 LV2_IDT1_17 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 44 INV1_IDT2_170.6000 CKT MW MVAR MVA % 1.0000PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 44
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 28 LV1_IDT2_17 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 347 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 45 INV2_IDT2_170.6000 CKT MW MVAR MVA % 1.0000PU 10.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 45
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 29 LV2_IDT2_17 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 46 INV1_IDT1_180.6000 CKT MW MVAR MVA % 1.0000PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 46
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 47 INV2_IDT1_180.6000 CKT MW MVAR MVA % 1.0000PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 47
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 31 LV2_IDT1_18 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 48 INV1_IDT2_180.6000 CKT MW MVAR MVA % 1.0000PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 48
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 32 LV1_IDT2_18 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 49 INV2_IDT2_180.6000 CKT MW MVAR MVA % 1.0000PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 49
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 348 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 33 LV2_IDT2_18 0.6000 1 3.1 1.6 3.5 0.01 0.00


1 1

BUS 50 INV1_IDT1_190.6000 CKT MW MVAR MVA % 1.0000PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 50
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 51 INV2_IDT1_190.6000 CKT MW MVAR MVA % 1.0000PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 51
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 35 LV2_IDT1_19 0.6000 1 3.1 1.7 3.5 0.01 0.00
1 1

BUS 52 INV1_IDT2_190.6000 CKT MW MVAR MVA % 1.0000PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 52
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 36 LV1_IDT2_19 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 53 INV2_IDT2_190.6000 CKT MW MVAR MVA % 1.0000PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 53
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 3.1 1.7 3.5 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 349 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 54 HV_AUXTR1_160.6000 CKT MW MVAR MVA % 0.9974PU 40.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 54
0.5984KV MW MVAR
1 1
TO 22 LV1_IDT1_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 62 LV_AUXTR1_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 55 HV_AUXTR2_160.6000 CKT MW MVAR MVA % 0.9979PU 10.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 55
0.5987KV MW MVAR
1 1
TO 25 LV2_IDT2_16 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 63 LV_AUXTR2_160.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 56 HV_AUXTR1_170.6000 CKT MW MVAR MVA % 0.9974PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 56
0.5984KV MW MVAR
1 1
TO 26 LV1_IDT1_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 64 LV_AUXTR1_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 57 HV_AUXTR2_170.6000 CKT MW MVAR MVA % 0.9979PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 57
0.5987KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 350 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 29 LV2_IDT2_17 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 65 LV_AUXTR2_170.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 58 HV_AUXTR1_180.6000 CKT MW MVAR MVA % 0.9974PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 58
0.5984KV MW MVAR
1 1
TO 30 LV1_IDT1_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 66 LV_AUXTR1_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 59 HV_AUXTR2_180.6000 CKT MW MVAR MVA % 0.9979PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 59
0.5987KV MW MVAR
1 1
TO 33 LV2_IDT2_18 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 67 LV_AUXTR2_180.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 60 HV_AUXTR1_190.6000 CKT MW MVAR MVA % 0.9974PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 60
0.5984KV MW MVAR
1 1
TO 34 LV1_IDT1_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 68 LV_AUXTR1_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 351 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 61 HV_AUXTR2_190.6000 CKT MW MVAR MVA % 0.9979PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 61
0.5987KV MW MVAR
1 1
TO 37 LV2_IDT2_19 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 69 LV_AUXTR2_190.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 62 LV_AUXTR1_160.4150 CKT MW MVAR MVA % 0.9891PU 39.15 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 62
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 54 HV_AUXTR1_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 63 LV_AUXTR2_160.4150 CKT MW MVAR MVA % 0.9897PU 9.15 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 63
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 55 HV_AUXTR2_160.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 64 LV_AUXTR1_170.4150 CKT MW MVAR MVA % 0.9892PU 9.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 64
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 56 HV_AUXTR1_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 352 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 65 LV_AUXTR2_170.4150 CKT MW MVAR MVA % 0.9897PU 9.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 65
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 57 HV_AUXTR2_170.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 66 LV_AUXTR1_180.4150 CKT MW MVAR MVA % 0.9892PU 9.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 66
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 58 HV_AUXTR1_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 67 LV_AUXTR2_180.4150 CKT MW MVAR MVA % 0.9897PU 9.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 67
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 59 HV_AUXTR2_180.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 68 LV_AUXTR1_190.4150 CKT MW MVAR MVA % 0.9892PU 9.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 68
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 60 HV_AUXTR1_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 353 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 69 LV_AUXTR2_190.4150 CKT MW MVAR MVA % 0.9897PU 9.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 69
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 61 HV_AUXTR2_190.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 70 HV_AUXTRPSS 33.000 CKT MW MVAR MVA % 0.9381PU 6.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 70
30.956KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 -0.1 -0.0 0.1 0.00 0.00
1 1
TO 71 LV_AUXTRPSS 0.4150 1 0.1 0.0 0.1 1.0000LK 0.00 0.00
1 1

BUS 71 LV_AUXTRPSS 0.4150 CKT MW MVAR MVA % 0.9339PU 5.37 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 71
0.3876KV MW MVAR
1 1
TO LOAD-PQ 0.1 0.0 0.1
TO 70 HV_AUXTRPSS 33.000 1 -0.1 -0.0 0.1 1.0000UN 0.00 0.00
1 1

BUS 101 50MWBLK4_1 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 101
30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 10.7 26.6 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 354 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 103 HV_IDT1_11 33.000 1 -12.2 -5.3 13.3 0.02 0.02


1 1
TO 104 HV_IDT1_14 33.000 1 -12.2 -5.4 13.3 0.01 0.01
1 1

BUS 102 50MWBLK4_2 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 102
30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 10.8 26.6 0.01 0.01
1 1
TO 105 HV_IDT1_15 33.000 1 -12.2 -5.4 13.3 0.01 0.01
1 1
TO 106 HV_IDT1_20 33.000 1 -12.2 -5.4 13.3 0.01 0.01
1 1

BUS 103 HV_IDT1_11 33.000 CKT MW MVAR MVA % 0.9404PU 6.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 103
31.033KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 12.2 5.3 13.3 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_11 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.64
TO 3WNDTR IDT2_TR_11 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.64

BUS 104 HV_IDT1_14 33.000 CKT MW MVAR MVA % 0.9396PU 6.16 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 104
31.005KV MW MVAR
1 1
TO 101 50MWBLK4_1 33.000 1 12.2 5.4 13.3 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_14 WND 1 1 -6.1 -2.7 6.7 106 1.0000LK 0.14 0.64

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 355 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_14 WND 1 1 -6.1 -2.7 6.7 106 1.0000LK 0.14 0.64

BUS 105 HV_IDT1_15 33.000 CKT MW MVAR MVA % 0.9391PU 6.15 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 105
30.991KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 12.2 5.4 13.3 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_15 WND 1 1 -6.1 -2.7 6.7 106 1.0000LK 0.14 0.64
TO 3WNDTR IDT2_TR_15 WND 1 1 -6.1 -2.7 6.7 106 1.0000LK 0.14 0.64

BUS 106 HV_IDT1_20 33.000 CKT MW MVAR MVA % 0.9399PU 6.17 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 106
31.018KV MW MVAR
1 1
TO 102 50MWBLK4_2 33.000 1 12.2 5.3 13.3 0.01 0.01
1 1
TO 3WNDTR IDT1_TR_20 WND 1 1 -6.1 -2.7 6.6 105 1.0000LK 0.14 0.64
TO 3WNDTR IDT2_TR_20 WND 1 1 -6.1 -2.7 6.6 105 1.0000LK 0.14 0.64

BUS 107 LV1_IDT1_11 0.6000 CKT MW MVAR MVA % 0.9974PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 107
0.5984KV MW MVAR
1 1
TO 123 INV1_IDT1_110.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 139 HV_AUXTR1_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.64

BUS 108 LV2_IDT1_11 0.6000 CKT MW MVAR MVA % 0.9979PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 108

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 356 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5987KV MW MVAR
1 1
TO 124 INV2_IDT1_110.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_11 WND 3 1 3.1 1.6 3.5 114 1.0000LK 0.14 0.64

BUS 109 LV1_IDT2_11 0.6000 CKT MW MVAR MVA % 0.9974PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 109
0.5984KV MW MVAR
1 1
TO 125 INV1_IDT2_110.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_11 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.64

BUS 110 LV2_IDT2_11 0.6000 CKT MW MVAR MVA % 0.9979PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 110
0.5987KV MW MVAR
1 1
TO 126 INV2_IDT2_110.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 140 HV_AUXTR2_110.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_11 WND 3 1 3.1 1.6 3.5 114 1.0000LK 0.14 0.64

BUS 111 LV1_IDT1_14 0.6000 CKT MW MVAR MVA % 0.9973PU 10.44 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 111
0.5984KV MW MVAR
1 1
TO 127 INV1_IDT1_140.6000 1 -3.1 -1.7 3.5 0.01 0.01
1 1
TO 141 HV_AUXTR1_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 357 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT1_TR_14 WND 2 1 3.1 1.6 3.5 114 1.0000LK 0.14 0.64

BUS 112 LV2_IDT1_14 0.6000 CKT MW MVAR MVA % 0.9978PU 10.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 112
0.5987KV MW MVAR
1 1
TO 128 INV2_IDT1_140.6000 1 -3.1 -1.7 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_14 WND 3 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 113 LV1_IDT2_14 0.6000 CKT MW MVAR MVA % 0.9973PU 10.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 113
0.5984KV MW MVAR
1 1
TO 129 INV1_IDT2_140.6000 1 -3.1 -1.7 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_14 WND 2 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 114 LV2_IDT2_14 0.6000 CKT MW MVAR MVA % 0.9978PU 10.44 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 114
0.5987KV MW MVAR
1 1
TO 130 INV2_IDT2_140.6000 1 -3.1 -1.7 3.5 0.01 0.00
1 1
TO 142 HV_AUXTR2_140.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_14 WND 3 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 115 LV1_IDT1_15 0.6000 CKT MW MVAR MVA % 0.9973PU 10.43 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 115
0.5984KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 358 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 131INV1_IDT1_150.6000 1 -3.1 -1.7 3.5 0.01 0.01


1 1
TO 143 HV_AUXTR1_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 2 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 116 LV2_IDT1_15 0.6000 CKT MW MVAR MVA % 0.9978PU 10.44 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 116
0.5987KV MW MVAR
1 1
TO 132 INV2_IDT1_150.6000 1 -3.1 -1.7 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_15 WND 3 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 117 LV1_IDT2_15 0.6000 CKT MW MVAR MVA % 0.9973PU 10.44 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 117
0.5984KV MW MVAR
1 1
TO 133 INV1_IDT2_150.6000 1 -3.1 -1.7 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_15 WND 2 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 118 LV2_IDT2_15 0.6000 CKT MW MVAR MVA % 0.9978PU 10.43 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 118
0.5987KV MW MVAR
1 1
TO 134 INV2_IDT2_150.6000 1 -3.1 -1.7 3.6 0.01 0.00
1 1
TO 144 HV_AUXTR2_150.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_15 WND 3 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 359 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 119 LV1_IDT1_20 0.6000 CKT MW MVAR MVA % 0.9974PU 10.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 119
0.5984KV MW MVAR
1 1
TO 135 INV1_IDT1_200.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 145 HV_AUXTR1_200.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.64

BUS 120 LV2_IDT1_20 0.6000 CKT MW MVAR MVA % 0.9978PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 120
0.5987KV MW MVAR
1 1
TO 136 INV2_IDT1_200.6000 1 -3.1 -1.7 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_20 WND 3 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 121 LV1_IDT2_20 0.6000 CKT MW MVAR MVA % 0.9974PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 121
0.5984KV MW MVAR
1 1
TO 137 INV1_IDT2_200.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_20 WND 2 1 3.1 1.6 3.5 114 1.0000LK 0.14 0.64

BUS 122 LV2_IDT2_20 0.6000 CKT MW MVAR MVA % 0.9978PU 10.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 122
0.5987KV MW MVAR
1 1
TO 138 INV2_IDT2_200.6000 1 -3.1 -1.7 3.5 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 360 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 146 HV_AUXTR2_200.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_20 WND 3 1 3.1 1.7 3.5 114 1.0000LK 0.14 0.64

BUS 123 INV1_IDT1_110.6000 CKT MW MVAR MVA % 1.0000PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 123
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 124 INV2_IDT1_110.6000 CKT MW MVAR MVA % 1.0000PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 124
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 108 LV2_IDT1_11 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 125 INV1_IDT2_110.6000 CKT MW MVAR MVA % 1.0000PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 125
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 109 LV1_IDT2_11 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 126 INV2_IDT2_110.6000 CKT MW MVAR MVA % 1.0000PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 126
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 3.1 1.7 3.5 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 361 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 127 INV1_IDT1_140.6000 CKT MW MVAR MVA % 1.0000PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 127
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 3.1 1.7 3.5 0.01 0.01
1 1

BUS 128 INV2_IDT1_140.6000 CKT MW MVAR MVA % 1.0000PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 128
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 112 LV2_IDT1_14 0.6000 1 3.1 1.7 3.5 0.01 0.00
1 1

BUS 129 INV1_IDT2_140.6000 CKT MW MVAR MVA % 1.0000PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 129
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 113 LV1_IDT2_14 0.6000 1 3.1 1.7 3.5 0.01 0.01
1 1

BUS 130 INV2_IDT2_140.6000 CKT MW MVAR MVA % 1.0000PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 130
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 3.1 1.7 3.6 0.01 0.00
1 1

BUS 131 INV1_IDT1_150.6000 CKT MW MVAR MVA % 1.0000PU 10.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 131
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 362 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 115 LV1_IDT1_15 0.6000 1 3.1 1.7 3.5 0.01 0.01


1 1

BUS 132 INV2_IDT1_150.6000 CKT MW MVAR MVA % 1.0000PU 10.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 132
FROM GENERATION 3.1 1.7R 3.6 114 0.6000KV MW MVAR
1 1
TO 116 LV2_IDT1_15 0.6000 1 3.1 1.7 3.6 0.01 0.00
1 1

BUS 133 INV1_IDT2_150.6000 CKT MW MVAR MVA % 1.0000PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 133
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 117 LV1_IDT2_15 0.6000 1 3.1 1.7 3.5 0.01 0.01
1 1

BUS 134 INV2_IDT2_150.6000 CKT MW MVAR MVA % 1.0000PU 10.45 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 134
FROM GENERATION 3.1 1.7R 3.6 114 0.6000KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 3.1 1.7 3.6 0.01 0.00
1 1

BUS 135 INV1_IDT1_200.6000 CKT MW MVAR MVA % 1.0000PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 135
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 363 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 136 INV2_IDT1_200.6000 CKT MW MVAR MVA % 1.0000PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 136
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 120 LV2_IDT1_20 0.6000 1 3.1 1.7 3.5 0.01 0.00
1 1

BUS 137 INV1_IDT2_200.6000 CKT MW MVAR MVA % 1.0000PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 137
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 121 LV1_IDT2_20 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 138 INV2_IDT2_200.6000 CKT MW MVAR MVA % 1.0000PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 138
FROM GENERATION 3.1 1.7R 3.5 113 0.6000KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 3.1 1.7 3.5 0.01 0.00
1 1

BUS 139 HV_AUXTR1_110.6000 CKT MW MVAR MVA % 0.9974PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 139
0.5984KV MW MVAR
1 1
TO 107 LV1_IDT1_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 147 LV_AUXTR1_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 140 HV_AUXTR2_110.6000 CKT MW MVAR MVA % 0.9979PU 10.47 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 140

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 364 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5987KV MW MVAR
1 1
TO 110 LV2_IDT2_11 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 148 LV_AUXTR2_110.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 141 HV_AUXTR1_140.6000 CKT MW MVAR MVA % 0.9973PU 10.44 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 141
0.5984KV MW MVAR
1 1
TO 111 LV1_IDT1_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 149 LV_AUXTR1_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 142 HV_AUXTR2_140.6000 CKT MW MVAR MVA % 0.9978PU 10.44 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 142
0.5987KV MW MVAR
1 1
TO 114 LV2_IDT2_14 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 150 LV_AUXTR2_140.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 143 HV_AUXTR1_150.6000 CKT MW MVAR MVA % 0.9973PU 10.43 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 143
0.5984KV MW MVAR
1 1
TO 115 LV1_IDT1_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 365 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 151 LV_AUXTR1_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 144 HV_AUXTR2_150.6000 CKT MW MVAR MVA % 0.9978PU 10.43 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 144
0.5987KV MW MVAR
1 1
TO 118 LV2_IDT2_15 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 152 LV_AUXTR2_150.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 145 HV_AUXTR1_200.6000 CKT MW MVAR MVA % 0.9974PU 10.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 145
0.5984KV MW MVAR
1 1
TO 119 LV1_IDT1_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 153 LV_AUXTR1_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 146 HV_AUXTR2_200.6000 CKT MW MVAR MVA % 0.9978PU 10.46 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 146
0.5987KV MW MVAR
1 1
TO 122 LV2_IDT2_20 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 154 LV_AUXTR2_200.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 147 LV_AUXTR1_110.4150 CKT MW MVAR MVA % 0.9892PU 9.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 147

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 366 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 139 HV_AUXTR1_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 148 LV_AUXTR2_110.4150 CKT MW MVAR MVA % 0.9897PU 9.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 148
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 140 HV_AUXTR2_110.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 149 LV_AUXTR1_140.4150 CKT MW MVAR MVA % 0.9892PU 9.05 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 149
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 141 HV_AUXTR1_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 150 LV_AUXTR2_140.4150 CKT MW MVAR MVA % 0.9897PU 9.05 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 150
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 142 HV_AUXTR2_140.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 151 LV_AUXTR1_150.4150 CKT MW MVAR MVA % 0.9892PU 9.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 151

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 367 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 143 HV_AUXTR1_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 152 LV_AUXTR2_150.4150 CKT MW MVAR MVA % 0.9897PU 9.04 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 152
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 144 HV_AUXTR2_150.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 153 LV_AUXTR1_200.4150 CKT MW MVAR MVA % 0.9892PU 9.06 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 153
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 145 HV_AUXTR1_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 154 LV_AUXTR2_200.4150 CKT MW MVAR MVA % 0.9897PU 9.06 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 154
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 146 HV_AUXTR2_200.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 201 50MWBLK3_1 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 201

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 368 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 10.2 26.3 0.01 0.01
1 1
TO 203 HV_IDT1_5 33.000 1 -12.1 -5.1 13.1 0.04 0.04
1 1
TO 204 HV_IDT1_6 33.000 1 -12.1 -5.2 13.2 0.03 0.03
1 1

BUS 202 50MWBLK3_2 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 202
30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 10.5 26.5 0.01 0.01
1 1
TO 205 HV_IDT1_7 33.000 1 -12.1 -5.2 13.2 0.03 0.03
1 1
TO 206 HV_IDT1_9 33.000 1 -12.2 -5.3 13.3 0.02 0.02
1 1

BUS 203 HV_IDT1_5 33.000 CKT MW MVAR MVA % 0.9427PU 6.24 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 203
31.109KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 12.2 4.9 13.1 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_5 WND 1 1 -6.1 -2.5 6.6 104 1.0000LK 0.14 0.62
TO 3WNDTR IDT2_TR_5 WND 1 1 -6.1 -2.5 6.6 104 1.0000LK 0.14 0.62

BUS 204 HV_IDT1_6 33.000 CKT MW MVAR MVA % 0.9417PU 6.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 204

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 369 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

31.077KV MW MVAR
1 1
TO 201 50MWBLK3_1 33.000 1 12.2 5.1 13.2 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_6 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_6 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63

BUS 205 HV_IDT1_7 33.000 CKT MW MVAR MVA % 0.9412PU 6.20 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 205
31.058KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 12.2 5.2 13.2 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_7 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_7 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.63

BUS 206 HV_IDT1_9 33.000 CKT MW MVAR MVA % 0.9406PU 6.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 206
31.039KV MW MVAR
1 1
TO 202 50MWBLK3_2 33.000 1 12.2 5.2 13.2 0.02 0.02
1 1
TO 3WNDTR IDT1_TR_9 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_9 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.63

BUS 207 LV1_IDT1_5 0.6000 CKT MW MVAR MVA % 0.9974PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 207
0.5984KV MW MVAR
1 1
TO 223 INV1_IDT1_5 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 370 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 239 HV_AUXTR1_5 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT1_TR_5 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 208 LV2_IDT1_5 0.6000 CKT MW MVAR MVA % 0.9979PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 208
0.5987KV MW MVAR
1 1
TO 224INV2_IDT1_5 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_5 WND 3 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.62

BUS 209 LV1_IDT2_5 0.6000 CKT MW MVAR MVA % 0.9974PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 209
0.5984KV MW MVAR
1 1
TO 225 INV1_IDT2_5 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_5 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 210 LV2_IDT2_5 0.6000 CKT MW MVAR MVA % 0.9979PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 210
0.5987KV MW MVAR
1 1
TO 226 INV2_IDT2_5 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 240 HV_AUXTR2_5 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_5 WND 3 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.62

BUS 211 LV1_IDT1_6 0.6000 CKT MW MVAR MVA % 0.9974PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 211

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 371 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5984KV MW MVAR
1 1
TO 227 INV1_IDT1_6 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 241 HV_AUXTR1_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 2 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.63

BUS 212 LV2_IDT1_6 0.6000 CKT MW MVAR MVA % 0.9979PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 212
0.5987KV MW MVAR
1 1
TO 228 INV2_IDT1_6 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_6 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 213 LV1_IDT2_6 0.6000 CKT MW MVAR MVA % 0.9974PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 213
0.5984KV MW MVAR
1 1
TO 229 INV1_IDT2_6 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_6 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 214 LV2_IDT2_6 0.6000 CKT MW MVAR MVA % 0.9979PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 214
0.5987KV MW MVAR
1 1
TO 230 INV2_IDT2_6 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 242 HV_AUXTR2_6 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 372 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_6 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 215 LV1_IDT1_7 0.6000 CKT MW MVAR MVA % 0.9974PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 215
0.5984KV MW MVAR
1 1
TO 231 INV1_IDT1_7 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 243 HV_AUXTR1_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 216 LV2_IDT1_7 0.6000 CKT MW MVAR MVA % 0.9979PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 216
0.5987KV MW MVAR
1 1
TO 232 INV2_IDT1_7 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_7 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 217 LV1_IDT2_7 0.6000 CKT MW MVAR MVA % 0.9974PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 217
0.5984KV MW MVAR
1 1
TO 233 INV1_IDT2_7 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_7 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 218 LV2_IDT2_7 0.6000 CKT MW MVAR MVA % 0.9979PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 218
0.5987KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 373 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 234INV2_IDT2_7 0.6000 1 -3.1 -1.6 3.5 0.01 0.00


1 1
TO 244 HV_AUXTR2_7 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_7 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 219 LV1_IDT1_9 0.6000 CKT MW MVAR MVA % 0.9974PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 219
0.5984KV MW MVAR
1 1
TO 235 INV1_IDT1_9 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 245 HV_AUXTR1_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 220 LV2_IDT1_9 0.6000 CKT MW MVAR MVA % 0.9979PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 220
0.5987KV MW MVAR
1 1
TO 236 INV2_IDT1_9 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_9 WND 3 1 3.1 1.6 3.5 114 1.0000LK 0.14 0.63

BUS 221 LV1_IDT2_9 0.6000 CKT MW MVAR MVA % 0.9974PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 221
0.5984KV MW MVAR
1 1
TO 237 INV1_IDT2_9 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_9 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 374 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 222 LV2_IDT2_9 0.6000 CKT MW MVAR MVA % 0.9979PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 222
0.5987KV MW MVAR
1 1
TO 238 INV2_IDT2_9 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 246 HV_AUXTR2_9 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_9 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 223 INV1_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 223
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 207 LV1_IDT1_5 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 224 INV2_IDT1_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 224
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 208 LV2_IDT1_5 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 225 INV1_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 225
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 209 LV1_IDT2_5 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 375 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 226 INV2_IDT2_5 0.6000 CKT MW MVAR MVA % 1.0000PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 226
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 227 INV1_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 227
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 228 INV2_IDT1_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 228
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 212 LV2_IDT1_6 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 229 INV1_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 229
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 213 LV1_IDT2_6 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 230 INV2_IDT2_6 0.6000 CKT MW MVAR MVA % 1.0000PU 10.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 230
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 376 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 214 LV2_IDT2_6 0.6000 1 3.1 1.6 3.5 0.01 0.00


1 1

BUS 231 INV1_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 231
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 232 INV2_IDT1_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 232
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 216 LV2_IDT1_7 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 233 INV1_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 233
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 217 LV1_IDT2_7 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 234 INV2_IDT2_7 0.6000 CKT MW MVAR MVA % 1.0000PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 234
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 377 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 235 INV1_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 235
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 236 INV2_IDT1_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 236
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 220 LV2_IDT1_9 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 237 INV1_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 237
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 221 LV1_IDT2_9 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 238 INV2_IDT2_9 0.6000 CKT MW MVAR MVA % 1.0000PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 238
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 222 LV2_IDT2_9 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 239 HV_AUXTR1_5 0.6000 CKT MW MVAR MVA % 0.9974PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 239
0.5984KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 378 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 207 LV1_IDT1_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 247 LV_AUXTR1_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 240 HV_AUXTR2_5 0.6000 CKT MW MVAR MVA % 0.9979PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 240
0.5987KV MW MVAR
1 1
TO 210 LV2_IDT2_5 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 248 LV_AUXTR2_5 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 241 HV_AUXTR1_6 0.6000 CKT MW MVAR MVA % 0.9974PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 241
0.5984KV MW MVAR
1 1
TO 211 LV1_IDT1_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 249 LV_AUXTR1_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 242 HV_AUXTR2_6 0.6000 CKT MW MVAR MVA % 0.9979PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 242
0.5987KV MW MVAR
1 1
TO 214 LV2_IDT2_6 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 250 LV_AUXTR2_6 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 379 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 243 HV_AUXTR1_7 0.6000 CKT MW MVAR MVA % 0.9974PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 243
0.5984KV MW MVAR
1 1
TO 215 LV1_IDT1_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 251 LV_AUXTR1_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 244 HV_AUXTR2_7 0.6000 CKT MW MVAR MVA % 0.9979PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 244
0.5987KV MW MVAR
1 1
TO 218 LV2_IDT2_7 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 252 LV_AUXTR2_7 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 245 HV_AUXTR1_9 0.6000 CKT MW MVAR MVA % 0.9974PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 245
0.5984KV MW MVAR
1 1
TO 219 LV1_IDT1_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 253 LV_AUXTR1_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 246 HV_AUXTR2_9 0.6000 CKT MW MVAR MVA % 0.9979PU 10.48 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 246
0.5987KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 380 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 222 LV2_IDT2_9 0.6000 1 -0.0 -0.0 0.0 0.00 0.00


1 1
TO 254 LV_AUXTR2_9 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 247 LV_AUXTR1_5 0.4150 CKT MW MVAR MVA % 0.9892PU 9.16 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 247
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 239 HV_AUXTR1_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 248 LV_AUXTR2_5 0.4150 CKT MW MVAR MVA % 0.9897PU 9.16 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 248
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 240 HV_AUXTR2_5 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 249 LV_AUXTR1_6 0.4150 CKT MW MVAR MVA % 0.9892PU 9.12 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 249
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 241 HV_AUXTR1_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 250 LV_AUXTR2_6 0.4150 CKT MW MVAR MVA % 0.9897PU 9.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 250

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 381 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 242 HV_AUXTR2_6 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 251 LV_AUXTR1_7 0.4150 CKT MW MVAR MVA % 0.9892PU 9.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 251
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 243 HV_AUXTR1_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 252 LV_AUXTR2_7 0.4150 CKT MW MVAR MVA % 0.9897PU 9.11 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 252
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 244 HV_AUXTR2_7 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 253 LV_AUXTR1_9 0.4150 CKT MW MVAR MVA % 0.9892PU 9.08 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 253
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 245 HV_AUXTR1_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 254 LV_AUXTR2_9 0.4150 CKT MW MVAR MVA % 0.9897PU 9.09 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 254

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 382 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 246 HV_AUXTR2_9 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 301 50MWBLK1_1 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 301
30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.3 10.4 26.4 0.01 0.01
1 1
TO 303 HV_IDT1_10 33.000 1 -12.1 -5.3 13.2 0.03 0.03
1 1
TO 304 HV_IDT1_8 33.000 1 -12.1 -5.1 13.2 0.04 0.04
1 1

BUS 302 50MWBLK1_2 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 302
30.973KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 10.2 26.3 0.01 0.01
1 1
TO 305 HV_IDT1_13 33.000 1 -12.1 -5.1 13.2 0.04 0.04
1 1
TO 306 HV_IDT1_12 33.000 1 -12.1 -5.1 13.2 0.04 0.04
1 1
TO 360 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 303 HV_IDT1_10 33.000 CKT MW MVAR MVA % 0.9409PU 6.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 303

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 383 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

31.050KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 12.2 5.2 13.2 0.03 0.03
1 1
TO 3WNDTR IDT1_TR_10 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_10 WND 1 1 -6.1 -2.6 6.6 105 1.0000LK 0.14 0.63

BUS 304 HV_IDT1_8 33.000 CKT MW MVAR MVA % 0.9419PU 6.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 304
31.083KV MW MVAR
1 1
TO 301 50MWBLK1_1 33.000 1 12.2 5.0 13.2 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_8 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_8 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63

BUS 305 HV_IDT1_13 33.000 CKT MW MVAR MVA % 0.9420PU 6.22 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 305
31.085KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 12.2 5.0 13.2 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_13 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63
TO 3WNDTR IDT2_TR_13 WND 1 1 -6.1 -2.5 6.6 105 1.0000LK 0.14 0.63

BUS 306 HV_IDT1_12 33.000 CKT MW MVAR MVA % 0.9425PU 6.23 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 306
31.104KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 12.2 5.0 13.1 0.04 0.04
1 1
TO 3WNDTR IDT1_TR_12 WND 1 1 -6.1 -2.5 6.6 104 1.0000LK 0.14 0.62

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 384 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_12 WND 1 1 -6.1 -2.5 6.6 104 1.0000LK 0.14 0.62

BUS 307 LV1_IDT1_10 0.6000 CKT MW MVAR MVA % 0.9974PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 307
0.5984KV MW MVAR
1 1
TO 323 INV1_IDT1_100.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 339 HV_AUXTR1_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 308 LV2_IDT1_10 0.6000 CKT MW MVAR MVA % 0.9979PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 308
0.5987KV MW MVAR
1 1
TO 324 INV2_IDT1_100.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_10 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 309 LV1_IDT2_10 0.6000 CKT MW MVAR MVA % 0.9974PU 10.50 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 309
0.5984KV MW MVAR
1 1
TO 325 INV1_IDT2_100.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_10 WND 2 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 310 LV2_IDT2_10 0.6000 CKT MW MVAR MVA % 0.9979PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 310
0.5987KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 385 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 326INV2_IDT2_100.6000 1 -3.1 -1.6 3.5 0.01 0.00


1 1
TO 340 HV_AUXTR2_100.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_10 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 311 LV1_IDT1_8 0.6000 CKT MW MVAR MVA % 0.9974PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 311
0.5984KV MW MVAR
1 1
TO 327 INV1_IDT1_8 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 341 HV_AUXTR1_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 2 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.63

BUS 312 LV2_IDT1_8 0.6000 CKT MW MVAR MVA % 0.9979PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 312
0.5987KV MW MVAR
1 1
TO 328 INV2_IDT1_8 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_8 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 313 LV1_IDT2_8 0.6000 CKT MW MVAR MVA % 0.9974PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 313
0.5984KV MW MVAR
1 1
TO 329 INV1_IDT2_8 0.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_8 WND 2 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.63

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 386 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 314 LV2_IDT2_8 0.6000 CKT MW MVAR MVA % 0.9979PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 314
0.5987KV MW MVAR
1 1
TO 330 INV2_IDT2_8 0.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 342 HV_AUXTR2_8 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_8 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 315 LV1_IDT1_13 0.6000 CKT MW MVAR MVA % 0.9974PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 315
0.5984KV MW MVAR
1 1
TO 331 INV1_IDT1_130.6000 1 -3.1 -1.6 3.5 0.01 0.01
1 1
TO 343 HV_AUXTR1_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 2 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.63

BUS 316 LV2_IDT1_13 0.6000 CKT MW MVAR MVA % 0.9979PU 10.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 316
0.5987KV MW MVAR
1 1
TO 332 INV2_IDT1_130.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_13 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 317 LV1_IDT2_13 0.6000 CKT MW MVAR MVA % 0.9974PU 10.54 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 317
0.5984KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 387 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 333 INV1_IDT2_130.6000 1 -3.1 -1.6 3.5 0.01 0.01


1 1
TO 3WNDTR IDT2_TR_13 WND 2 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.63

BUS 318 LV2_IDT2_13 0.6000 CKT MW MVAR MVA % 0.9979PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 318
0.5987KV MW MVAR
1 1
TO 334INV2_IDT2_130.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 344 HV_AUXTR2_130.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_13 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.63

BUS 319 LV1_IDT1_12 0.6000 CKT MW MVAR MVA % 0.9974PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 319
0.5984KV MW MVAR
1 1
TO 335 INV1_IDT1_120.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 345 HV_AUXTR1_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 320 LV2_IDT1_12 0.6000 CKT MW MVAR MVA % 0.9979PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 320
0.5987KV MW MVAR
1 1
TO 336 INV2_IDT1_120.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_12 WND 3 1 3.1 1.6 3.5 113 1.0000LK 0.14 0.62

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 388 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 321 LV1_IDT2_12 0.6000 CKT MW MVAR MVA % 0.9974PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 321
0.5984KV MW MVAR
1 1
TO 337 INV1_IDT2_120.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_12 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 322 LV2_IDT2_12 0.6000 CKT MW MVAR MVA % 0.9979PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 322
0.5987KV MW MVAR
1 1
TO 338 INV2_IDT2_120.6000 1 -3.1 -1.6 3.5 0.01 0.00
1 1
TO 346 HV_AUXTR2_120.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_12 WND 3 1 3.1 1.6 3.5 112 1.0000LK 0.14 0.62

BUS 323 INV1_IDT1_100.6000 CKT MW MVAR MVA % 1.0000PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 323
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 324 INV2_IDT1_100.6000 CKT MW MVAR MVA % 1.0000PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 324
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 308 LV2_IDT1_10 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 389 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 325 INV1_IDT2_100.6000 CKT MW MVAR MVA % 1.0000PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 325
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 309 LV1_IDT2_10 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 326 INV2_IDT2_100.6000 CKT MW MVAR MVA % 1.0000PU 10.51 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 326
FROM GENERATION 3.1 1.6R 3.5 113 0.6000KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 327 INV1_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 327
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 328 INV2_IDT1_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 328
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 312 LV2_IDT1_8 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 329 INV1_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.57 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 329
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 390 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 313 LV1_IDT2_8 0.6000 1 3.1 1.6 3.5 0.01 0.01


1 1

BUS 330 INV2_IDT2_8 0.6000 CKT MW MVAR MVA % 1.0000PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 330
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 331 INV1_IDT1_130.6000 CKT MW MVAR MVA % 1.0000PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 331
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

BUS 332 INV2_IDT1_130.6000 CKT MW MVAR MVA % 1.0000PU 10.56 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 332
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 316 LV2_IDT1_13 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 333 INV1_IDT2_130.6000 CKT MW MVAR MVA % 1.0000PU 10.57 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 333
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 317 LV1_IDT2_13 0.6000 1 3.1 1.6 3.5 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 391 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 334 INV2_IDT2_130.6000 CKT MW MVAR MVA % 1.0000PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 334
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 335 INV1_IDT1_120.6000 CKT MW MVAR MVA % 1.0000PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 335
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 336 INV2_IDT1_120.6000 CKT MW MVAR MVA % 1.0000PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 336
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1
TO 320 LV2_IDT1_12 0.6000 1 3.1 1.6 3.5 0.01 0.00
1 1

BUS 337 INV1_IDT2_120.6000 CKT MW MVAR MVA % 1.0000PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 337
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 321 LV1_IDT2_12 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 338 INV2_IDT2_120.6000 CKT MW MVAR MVA % 1.0000PU 10.57 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 338
FROM GENERATION 3.1 1.6R 3.5 112 0.6000KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 392 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 322 LV2_IDT2_12 0.6000 1 3.1 1.6 3.5 0.01 0.00


1 1

BUS 339 HV_AUXTR1_100.6000 CKT MW MVAR MVA % 0.9974PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 339
0.5984KV MW MVAR
1 1
TO 307 LV1_IDT1_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 347 LV_AUXTR1_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 340 HV_AUXTR2_100.6000 CKT MW MVAR MVA % 0.9979PU 10.49 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 340
0.5987KV MW MVAR
1 1
TO 310 LV2_IDT2_10 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 348 LV_AUXTR2_100.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 341 HV_AUXTR1_8 0.6000 CKT MW MVAR MVA % 0.9974PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 341
0.5984KV MW MVAR
1 1
TO 311 LV1_IDT1_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 349 LV_AUXTR1_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 342 HV_AUXTR2_8 0.6000 CKT MW MVAR MVA % 0.9979PU 10.52 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 342

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 393 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5987KV MW MVAR
1 1
TO 314 LV2_IDT2_8 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 350 LV_AUXTR2_8 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 343 HV_AUXTR1_130.6000 CKT MW MVAR MVA % 0.9974PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 343
0.5984KV MW MVAR
1 1
TO 315 LV1_IDT1_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 351 LV_AUXTR1_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 344 HV_AUXTR2_130.6000 CKT MW MVAR MVA % 0.9979PU 10.53 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 344
0.5987KV MW MVAR
1 1
TO 318 LV2_IDT2_13 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 352 LV_AUXTR2_130.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 345 HV_AUXTR1_120.6000 CKT MW MVAR MVA % 0.9974PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 345
0.5984KV MW MVAR
1 1
TO 319 LV1_IDT1_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 394 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 353 LV_AUXTR1_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 346 HV_AUXTR2_120.6000 CKT MW MVAR MVA % 0.9979PU 10.55 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 346
0.5987KV MW MVAR
1 1
TO 322 LV2_IDT2_12 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 354 LV_AUXTR2_120.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 347 LV_AUXTR1_100.4150 CKT MW MVAR MVA % 0.9892PU 9.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 347
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 339 HV_AUXTR1_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 348 LV_AUXTR2_100.4150 CKT MW MVAR MVA % 0.9897PU 9.10 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 348
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 340 HV_AUXTR2_100.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 349 LV_AUXTR1_8 0.4150 CKT MW MVAR MVA % 0.9892PU 9.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 349
0.4105KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 395 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 341 HV_AUXTR1_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 350 LV_AUXTR2_8 0.4150 CKT MW MVAR MVA % 0.9897PU 9.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 350
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 342 HV_AUXTR2_8 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 351 LV_AUXTR1_130.4150 CKT MW MVAR MVA % 0.9892PU 9.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 351
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 343 HV_AUXTR1_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 352 LV_AUXTR2_130.4150 CKT MW MVAR MVA % 0.9897PU 9.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 352
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 344 HV_AUXTR2_130.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 353 LV_AUXTR1_120.4150 CKT MW MVAR MVA % 0.9892PU 9.15 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 353
0.4105KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 396 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO LOAD-PQ 0.0 0.0 0.0


TO 345 HV_AUXTR1_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 354 LV_AUXTR2_120.4150 CKT MW MVAR MVA % 0.9897PU 9.16 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 354
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 346 HV_AUXTR2_120.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 360 HV_AUXTR33 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 360
30.973KV MW MVAR
1 1
TO 302 50MWBLK1_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 361 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 361 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 0.9337PU 5.25 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 361
0.3875KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 360 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 401 50MWBLK5_1 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 401

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 397 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

30.972KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 9.9 26.2 0.01 0.01
1 1
TO 403 HV_IDT1_1 33.000 1 -12.1 -4.9 13.1 0.06 0.06
1 1
TO 404 HV_IDT1_2 33.000 1 -12.1 -5.0 13.1 0.05 0.05
1 1

BUS 402 50MWBLK5_2 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 402
30.972KV MW MVAR
1 1
TO 11 33KMAINHTPNL33.000 1 24.2 9.9 26.2 0.01 0.01
1 1
TO 405 HV_IDT1_3 33.000 1 -12.1 -5.0 13.1 0.05 0.05
1 1
TO 406 HV_IDT1_4 33.000 1 -12.1 -5.0 13.1 0.05 0.05
1 1
TO 460 HV_AUXTR33 33.000 1 0.0 0.0 0.0 0.00 0.00
1 1

BUS 403 HV_IDT1_1 33.000 CKT MW MVAR MVA % 0.9441PU 6.28 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 403
31.154KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 12.2 4.7 13.1 0.06 0.06
1 1
TO 3WNDTR IDT1_TR_1 WND 1 1 -6.1 -2.4 6.5 104 1.0000LK 0.14 0.61
TO 3WNDTR IDT2_TR_1 WND 1 1 -6.1 -2.4 6.5 104 1.0000LK 0.14 0.61

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 398 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 404 HV_IDT1_2 33.000 CKT MW MVAR MVA % 0.9434PU 6.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 404
31.133KV MW MVAR
1 1
TO 401 50MWBLK5_1 33.000 1 12.2 4.8 13.1 0.05 0.05
1 1
TO 3WNDTR IDT1_TR_2 WND 1 1 -6.1 -2.4 6.6 104 1.0000LK 0.14 0.62
TO 3WNDTR IDT2_TR_2 WND 1 1 -6.1 -2.4 6.6 104 1.0000LK 0.14 0.62

BUS 405 HV_IDT1_3 33.000 CKT MW MVAR MVA % 0.9434PU 6.26 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 405
31.131KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 12.2 4.8 13.1 0.05 0.05
1 1
TO 3WNDTR IDT1_TR_3 WND 1 1 -6.1 -2.4 6.6 104 1.0000LK 0.14 0.62
TO 3WNDTR IDT2_TR_3 WND 1 1 -6.1 -2.4 6.6 104 1.0000LK 0.14 0.62

BUS 406 HV_IDT1_4 33.000 CKT MW MVAR MVA % 0.9437PU 6.27 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 406
31.141KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 12.2 4.8 13.1 0.05 0.05
1 1
TO 3WNDTR IDT1_TR_4 WND 1 1 -6.1 -2.4 6.5 104 1.0000LK 0.14 0.62
TO 3WNDTR IDT2_TR_4 WND 1 1 -6.1 -2.4 6.5 104 1.0000LK 0.14 0.62

BUS 407 LV1_IDT1_1 0.6000 CKT MW MVAR MVA % 0.9974PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 407
0.5985KV MW MVAR
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 399 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 423INV1_IDT1_1 0.6000 1 -3.1 -1.5 3.5 0.01 0.01


1 1
TO 439 HV_AUXTR1_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 2 1 3.1 1.5 3.4 111 1.0000LK 0.14 0.61

BUS 408 LV2_IDT1_1 0.6000 CKT MW MVAR MVA % 0.9979PU 10.61 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 408
0.5987KV MW MVAR
1 1
TO 424 INV2_IDT1_1 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_1 WND 3 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.61

BUS 409 LV1_IDT2_1 0.6000 CKT MW MVAR MVA % 0.9974PU 10.61 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 409
0.5985KV MW MVAR
1 1
TO 425 INV1_IDT2_1 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_1 WND 2 1 3.1 1.5 3.5 111 1.0000LK 0.14 0.61

BUS 410 LV2_IDT2_1 0.6000 CKT MW MVAR MVA % 0.9979PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 410
0.5987KV MW MVAR
1 1
TO 426 INV2_IDT2_1 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1
TO 440 HV_AUXTR2_1 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_1 WND 3 1 3.1 1.5 3.5 111 1.0000LK 0.14 0.61

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 400 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 411 LV1_IDT1_2 0.6000 CKT MW MVAR MVA % 0.9974PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 411
0.5984KV MW MVAR
1 1
TO 427 INV1_IDT1_2 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 441 HV_AUXTR1_2 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 2 1 3.1 1.5 3.5 111 1.0000LK 0.14 0.62

BUS 412 LV2_IDT1_2 0.6000 CKT MW MVAR MVA % 0.9979PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 412
0.5987KV MW MVAR
1 1
TO 428 INV2_IDT1_2 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_2 WND 3 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 413 LV1_IDT2_2 0.6000 CKT MW MVAR MVA % 0.9974PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 413
0.5985KV MW MVAR
1 1
TO 429 INV1_IDT2_2 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_2 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 414 LV2_IDT2_2 0.6000 CKT MW MVAR MVA % 0.9979PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 414
0.5987KV MW MVAR
1 1
TO 430 INV2_IDT2_2 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 401 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 442 HV_AUXTR2_2 0.6000 1 0.0 0.0 0.0 0.00 0.00


1 1
TO 3WNDTR IDT2_TR_2 WND 3 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 415 LV1_IDT1_3 0.6000 CKT MW MVAR MVA % 0.9974PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 415
0.5984KV MW MVAR
1 1
TO 431INV1_IDT1_3 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 443 HV_AUXTR1_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 2 1 3.1 1.5 3.5 111 1.0000LK 0.14 0.62

BUS 416 LV2_IDT1_3 0.6000 CKT MW MVAR MVA % 0.9979PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 416
0.5987KV MW MVAR
1 1
TO 432 INV2_IDT1_3 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_3 WND 3 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 417 LV1_IDT2_3 0.6000 CKT MW MVAR MVA % 0.9974PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 417
0.5984KV MW MVAR
1 1
TO 433 INV1_IDT2_3 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 3WNDTR IDT2_TR_3 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 418 LV2_IDT2_3 0.6000 CKT MW MVAR MVA % 0.9979PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 418

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 402 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5987KV MW MVAR
1 1
TO 434 INV2_IDT2_3 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1
TO 444 HV_AUXTR2_3 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_3 WND 3 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 419 LV1_IDT1_4 0.6000 CKT MW MVAR MVA % 0.9974PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 419
0.5985KV MW MVAR
1 1
TO 435 INV1_IDT1_4 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1
TO 445 HV_AUXTR1_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 2 1 3.1 1.5 3.5 111 1.0000LK 0.14 0.62

BUS 420 LV2_IDT1_4 0.6000 CKT MW MVAR MVA % 0.9979PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 420
0.5987KV MW MVAR
1 1
TO 436 INV2_IDT1_4 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1
TO 3WNDTR IDT1_TR_4 WND 3 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 421 LV1_IDT2_4 0.6000 CKT MW MVAR MVA % 0.9974PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 421
0.5985KV MW MVAR
1 1
TO 437 INV1_IDT2_4 0.6000 1 -3.1 -1.5 3.5 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 403 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 3WNDTR IDT2_TR_4 WND 2 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 422 LV2_IDT2_4 0.6000 CKT MW MVAR MVA % 0.9979PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 422
0.5987KV MW MVAR
1 1
TO 438 INV2_IDT2_4 0.6000 1 -3.1 -1.5 3.5 0.01 0.00
1 1
TO 446 HV_AUXTR2_4 0.6000 1 0.0 0.0 0.0 0.00 0.00
1 1
TO 3WNDTR IDT2_TR_4 WND 3 1 3.1 1.5 3.5 112 1.0000LK 0.14 0.62

BUS 423 INV1_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 423
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 424 INV2_IDT1_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.64 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 424
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 408 LV2_IDT1_1 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

BUS 425 INV1_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.65 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 425
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 409 LV1_IDT2_1 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 404 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 426 INV2_IDT2_1 0.6000 CKT MW MVAR MVA % 1.0000PU 10.63 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 426
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

BUS 427 INV1_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 427
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 428 INV2_IDT1_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 428
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 412 LV2_IDT1_2 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

BUS 429 INV1_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 429
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 413 LV1_IDT2_2 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 430 INV2_IDT2_2 0.6000 CKT MW MVAR MVA % 1.0000PU 10.61 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 430

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 405 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR


1 1
TO 414 LV2_IDT2_2 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

BUS 431 INV1_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.61 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 431
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 432 INV2_IDT1_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.61 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 432
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 416 LV2_IDT1_3 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

BUS 433 INV1_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 433
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 417 LV1_IDT2_3 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 434 INV2_IDT2_3 0.6000 CKT MW MVAR MVA % 1.0000PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 434
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 406 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 435 INV1_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 435
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 436 INV2_IDT1_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.63 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 436
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 420 LV2_IDT1_4 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

BUS 437 INV1_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.63 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 437
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 421 LV1_IDT2_4 0.6000 1 3.1 1.5 3.5 0.01 0.01
1 1

BUS 438 INV2_IDT2_4 0.6000 CKT MW MVAR MVA % 1.0000PU 10.62 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 438
FROM GENERATION 3.1 1.5R 3.5 111 0.6000KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 3.1 1.5 3.5 0.01 0.00
1 1

BUS 439 HV_AUXTR1_1 0.6000 CKT MW MVAR MVA % 0.9974PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 439

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 407 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5985KV MW MVAR
1 1
TO 407 LV1_IDT1_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 447 LV_AUXTR1_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 440 HV_AUXTR2_1 0.6000 CKT MW MVAR MVA % 0.9979PU 10.60 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 440
0.5987KV MW MVAR
1 1
TO 410 LV2_IDT2_1 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 448 LV_AUXTR2_1 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 441 HV_AUXTR1_2 0.6000 CKT MW MVAR MVA % 0.9974PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 441
0.5984KV MW MVAR
1 1
TO 411 LV1_IDT1_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 449 LV_AUXTR1_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 442 HV_AUXTR2_2 0.6000 CKT MW MVAR MVA % 0.9979PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 442
0.5987KV MW MVAR
1 1
TO 414 LV2_IDT2_2 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 408 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

TO 450 LV_AUXTR2_2 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00


1 1

BUS 443 HV_AUXTR1_3 0.6000 CKT MW MVAR MVA % 0.9974PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 443
0.5984KV MW MVAR
1 1
TO 415 LV1_IDT1_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 451 LV_AUXTR1_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 444 HV_AUXTR2_3 0.6000 CKT MW MVAR MVA % 0.9979PU 10.58 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 444
0.5987KV MW MVAR
1 1
TO 418 LV2_IDT2_3 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 452 LV_AUXTR2_3 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 445 HV_AUXTR1_4 0.6000 CKT MW MVAR MVA % 0.9974PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 445
0.5985KV MW MVAR
1 1
TO 419 LV1_IDT1_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 453 LV_AUXTR1_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 446 HV_AUXTR2_4 0.6000 CKT MW MVAR MVA % 0.9979PU 10.59 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 446

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 409 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

0.5987KV MW MVAR
1 1
TO 422 LV2_IDT2_4 0.6000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 454 LV_AUXTR2_4 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 447 LV_AUXTR1_1 0.4150 CKT MW MVAR MVA % 0.9892PU 9.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 447
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 439 HV_AUXTR1_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 448 LV_AUXTR2_1 0.4150 CKT MW MVAR MVA % 0.9897PU 9.21 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 448
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 440 HV_AUXTR2_1 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 449 LV_AUXTR1_2 0.4150 CKT MW MVAR MVA % 0.9892PU 9.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 449
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 441 HV_AUXTR1_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 410 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 450 LV_AUXTR2_2 0.4150 CKT MW MVAR MVA % 0.9897PU 9.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 450
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 442 HV_AUXTR2_2 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 451 LV_AUXTR1_3 0.4150 CKT MW MVAR MVA % 0.9892PU 9.18 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 451
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 443 HV_AUXTR1_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 452 LV_AUXTR2_3 0.4150 CKT MW MVAR MVA % 0.9897PU 9.19 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 452
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 444 HV_AUXTR2_3 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 453 LV_AUXTR1_4 0.4150 CKT MW MVAR MVA % 0.9892PU 9.20 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 453
0.4105KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 445 HV_AUXTR1_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 411 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

BUS 454 LV_AUXTR2_4 0.4150 CKT MW MVAR MVA % 0.9897PU 9.20 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 454
0.4107KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 446 HV_AUXTR2_4 0.6000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

BUS 460 HV_AUXTR33 33.000 CKT MW MVAR MVA % 0.9386PU 6.13 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 460
30.972KV MW MVAR
1 1
TO 402 50MWBLK5_2 33.000 1 -0.0 -0.0 0.0 0.00 0.00
1 1
TO 461 LV_AUXTR33 0.4150 1 0.0 0.0 0.0 1.0000LK 0.00 0.00
1 1

BUS 461 LV_AUXTR33 0.4150 CKT MW MVAR MVA % 0.9337PU 5.25 X--- LOSSES ---X
X---- AREA -----X X---- ZONE -----X 461
0.3875KV MW MVAR
1 1
TO LOAD-PQ 0.0 0.0 0.0
TO 460 HV_AUXTR33 33.000 1 -0.0 -0.0 0.0 1.0000UN 0.00 0.00
1 1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 412 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

11.5 Short Circuit Study Results

This section provides the results of the calculations for three phase short circuit study at all
locations in the network.

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 413 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
1 [220KVPGCILSS220.00] 3PH 5099.30 13382.2 -83.59 32541.5 35266.9 555.8
8419.5 8437.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/10.441/83.586, 8.89610

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
2 [220KVPOOLING220.00] 3PH 5098.32 13379.6 -83.59 32534.7 35258.9 555.4
8419.0 8437.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/10.443/83.586, 8.89497

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 414 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
3 [HV_POWERTR-1220.00] 3PH 5098.32 13379.6 -83.59 32534.7 35258.9 555.4
8419.0 8437.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/10.443/83.586, 8.89497

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
4 [HV_POWERTR-2220.00] 3PH 5098.32 13379.6 -83.59 32534.7 35258.9 555.4
8419.0 8437.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/10.443/83.586, 8.89497

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
5 [HV_POWERTR-3220.00] 3PH 5098.32 13379.6 -83.59 32534.7 35258.9 555.4
8419.0 8437.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/10.443/83.586, 8.89497

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 415 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
6 [HV_POWERTR-4220.00] 3PH 5098.32 13379.6 -83.59 32534.7 35258.9 555.4
8419.0 8437.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/10.443/83.586, 8.89497

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
7 [LV_POWERTR-133.000] 3PH 1891.15 33086.6 -86.83 93583.0 89368.0 8366.8
30012.1 31156.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.633/86.827, 18.04007

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 416 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
8 [LV_POWERTR-233.000] 3PH 1888.07 33032.6 -86.75 93430.4 89057.8 8074.0
29972.6 31041.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.634/86.754, 17.63065

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
9 [LV_POWERTR-333.000] 3PH 1884.55 32971.1 -86.67 93256.5 88706.5 7765.3
29927.5 30918.5
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.636/86.670, 17.18760

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 417 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

10 [LV_POWERTR-433.000] 3PH 1880.61 32902.2 -86.58 93061.5 88315.2 7448.8


29876.8 30791.4
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.637/86.577, 16.71827

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
11 [33KMAINHTPNL33.000] 3PH 1897.34 33194.9 -86.98 93889.4 89996.2 9022.4
30091.5 31415.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.631/86.976, 18.92674

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
12 [50MWBLK2_1 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 418 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
13 [50MWBLK2_2 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
14 [HV_IDT1_16 33.000] 3PH 1299.96 22743.4 -72.25 51604.4 45497.4 1.4
21818.4 21818.4
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.921/72.251, 3.12421

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 419 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
16 [HV_IDT1_17 33.000] 3PH 1384.20 24217.3 -74.18 56670.7 50061.7 4.7
23062.3 23062.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.865/74.181, 3.52941

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
18 [HV_IDT1_18 33.000] 3PH 1478.08 25859.8 -76.38 62816.7 55623.7 18.2
24418.4 24418.4
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.810/76.375, 4.12563

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 420 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
20 [HV_IDT1_19 33.000] 3PH 1570.57 27477.9 -78.59 69484.2 61687.4 69.2
25723.4 25723.5
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.763/78.588, 4.95410

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
22 [LV1_IDT1_16 0.6000] 3PH 44.72 43032.6 -82.29 101803.9 101898.4 870.5
43032.6 43041.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.288, 7.38492

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
23 [LV2_IDT1_16 0.6000] 3PH 46.77 45002.1 -82.28 106447.4 106527.6 901.7
45002.1 45011.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.281, 7.37792

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 421 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
24 [LV1_IDT2_16 0.6000] 3PH 44.72 43029.2 -82.30 101816.8 101890.5 870.4
43029.2 43038.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.298, 7.39446

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
25 [LV2_IDT2_16 0.6000] 3PH 46.77 45005.4 -82.27 106434.4 106535.4 901.7
45005.4 45014.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.272, 7.36884

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 422 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
26 [LV1_IDT1_17 0.6000] 3PH 44.81 43117.8 -82.38 102189.8 102285.0 915.4
43117.8 43127.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.375, 7.46979

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
27 [LV2_IDT1_17 0.6000] 3PH 46.86 45095.4 -82.37 106869.4 106950.3 950.4
45095.4 45105.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.372, 7.46653

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
28 [LV1_IDT2_17 0.6000] 3PH 44.81 43114.5 -82.38 102202.8 102277.1 915.3
43114.5 43124.2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 423 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.385, 7.47954

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
29 [LV2_IDT2_17 0.6000] 3PH 46.87 45098.7 -82.36 106856.3 106958.1 950.4
45098.7 45108.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.362, 7.45725

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
30 [LV1_IDT1_18 0.6000] 3PH 44.90 43203.3 -82.46 102578.5 102674.4 962.8
43203.3 43214.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.462, 7.55695

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 424 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
31 [LV2_IDT1_18 0.6000] 3PH 46.96 45189.0 -82.46 107294.7 107376.2 1001.9
45189.0 45200.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.463, 7.55764

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
32 [LV1_IDT2_18 0.6000] 3PH 44.89 43200.0 -82.47 102591.7 102666.5 962.7
43200.0 43210.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.472, 7.56692

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 425 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

33 [LV2_IDT2_18 0.6000] 3PH 46.97 45192.3 -82.45 107281.5 107384.0 1001.9


45192.3 45203.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.453, 7.54815

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
34 [LV1_IDT1_19 0.6000] 3PH 44.98 43279.6 -82.54 102926.5 103023.0 1007.1
43279.6 43291.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.540, 7.63643

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
35 [LV2_IDT1_19 0.6000] 3PH 47.05 45272.4 -82.54 107675.4 107757.6 1050.2
45272.4 45284.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.544, 7.64081

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 426 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
36 [LV1_IDT2_19 0.6000] 3PH 44.97 43276.2 -82.55 102939.7 103015.1 1007.0
43276.2 43288.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.549, 7.64659

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
37 [LV2_IDT2_19 0.6000] 3PH 47.05 45275.7 -82.53 107662.1 107765.4 1050.3
45275.7 45287.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.534, 7.63112

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 427 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
38 [INV1_IDT1_160.6000] 3PH 43.68 42026.9 -81.04 106983.1 96997.5 421.7
42026.9 42029.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.037, 6.34013

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
39 [INV2_IDT1_160.6000] 3PH 45.84 44109.9 -81.22 112285.3 102160.6 487.3
44109.8 44112.5
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.218, 6.47303

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
40 [INV1_IDT2_160.6000] 3PH 43.67 42024.2 -81.05 106976.2 96993.7 422.0
42024.2 42026.3

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 428 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.048, 6.34802

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
41 [INV2_IDT2_160.6000] 3PH 45.84 44113.6 -81.21 112295.0 102174.8 488.1
44113.6 44116.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.211, 6.46808

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
42 [INV1_IDT1_170.6000] 3PH 43.76 42109.6 -81.12 107193.5 97349.2 442.5
42109.6 42111.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.119, 6.39972

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 429 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
43 [INV2_IDT1_170.6000] 3PH 45.93 44200.8 -81.30 112516.7 102550.7 512.6
44200.8 44203.7
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.305, 6.53847

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
44 [INV1_IDT2_170.6000] 3PH 43.76 42106.6 -81.13 107185.8 97342.2 442.5
42106.6 42108.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.129, 6.40682

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 430 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
45 [INV2_IDT2_170.6000] 3PH 45.94 44203.8 -81.30 112524.4 102557.7 512.7
44203.8 44206.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.295, 6.53140

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
46 [INV1_IDT1_180.6000] 3PH 43.85 42192.5 -81.20 107404.6 97703.5 464.4
42192.5 42195.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.201, 6.46065

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 431 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
47 [INV2_IDT1_180.6000] 3PH 46.03 44291.9 -81.39 112748.8 102943.7 539.4
44291.9 44295.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.391, 6.60549

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
48 [INV1_IDT2_180.6000] 3PH 43.84 42189.5 -81.21 107396.9 97696.5 464.3
42189.5 42192.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.211, 6.46788

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
49 [INV2_IDT2_180.6000] 3PH 46.03 44294.9 -81.38 112756.5 102950.8 539.4
44294.9 44298.2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 432 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.382, 6.59829

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
50 [INV1_IDT1_190.6000] 3PH 43.92 42266.4 -81.27 107592.7 98020.5 484.8
42266.4 42269.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.275, 6.51598

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
51 [INV2_IDT1_190.6000] 3PH 46.11 44373.2 -81.47 112955.7 103295.5 564.4
44373.2 44376.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.469, 6.66645

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 433 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
52 [INV1_IDT2_190.6000] 3PH 43.92 42263.4 -81.28 107585.0 98013.5 484.7
42263.4 42266.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.285, 6.52332

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
53 [INV2_IDT2_190.6000] 3PH 46.12 44376.2 -81.46 112963.4 103302.6 564.4
44376.2 44379.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.460, 6.65912

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 434 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
54 [HV_AUXTR1_160.6000] 3PH 44.72 43032.6 -82.29 101803.9 101898.4 870.5
43032.6 43041.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.288, 7.38492

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
55 [HV_AUXTR2_160.6000] 3PH 46.77 45005.4 -82.27 106434.4 106535.4 901.7
45005.4 45014.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.272, 7.36884

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 435 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

56 [HV_AUXTR1_170.6000] 3PH 44.81 43117.8 -82.38 102189.8 102285.0 915.4


43117.8 43127.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.375, 7.46979

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
57 [HV_AUXTR2_170.6000] 3PH 46.87 45098.7 -82.36 106856.3 106958.1 950.4
45098.7 45108.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.362, 7.45725

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
58 [HV_AUXTR1_180.6000] 3PH 44.90 43203.3 -82.46 102578.5 102674.4 962.8
43203.3 43214.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.462, 7.55695

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 436 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
59 [HV_AUXTR2_180.6000] 3PH 46.97 45192.3 -82.45 107281.5 107384.0 1001.9
45192.3 45203.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.453, 7.54815

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
60 [HV_AUXTR1_190.6000] 3PH 44.98 43279.6 -82.54 102926.5 103023.0 1007.1
43279.6 43291.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.540, 7.63643

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 437 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
61 [HV_AUXTR2_190.6000] 3PH 47.05 45275.7 -82.53 107662.1 107765.4 1050.3
45275.7 45287.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.534, 7.63112

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
62 [LV_AUXTR1_160.4150] 3PH 0.36 501.3 -88.60 1276.2 1415.8 685.5
501.3 849.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.603, 41.01744

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
63 [LV_AUXTR2_160.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.2 686.7
501.5 850.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.606, 41.10163

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 438 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
64 [LV_AUXTR1_170.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.7 685.8
501.3 849.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.604, 41.03788

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
65 [LV_AUXTR2_170.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.3 687.0
501.5 850.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.607, 41.12576

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 439 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
66 [LV_AUXTR1_180.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.8 686.1
501.3 849.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.605, 41.06194

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
67 [LV_AUXTR2_180.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.3 687.3
501.5 850.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.608, 41.14993

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
68 [LV_AUXTR1_190.4150] 3PH 0.36 501.3 -88.61 1276.1 1415.8 686.4
501.3 850.0

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 440 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.606, 41.08334

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
69 [LV_AUXTR2_190.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.4 687.6
501.5 851.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.609, 41.17144

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
70 [HV_AUXTRPSS 33.000] 3PH 1897.34 33194.9 -86.98 87145.8 89996.2 9022.4
30091.5 31415.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.631/86.976, 18.92674

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 441 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
71 [LV_AUXTRPSS 0.4150] 3PH 5.40 7512.5 -89.32 19123.7 21245.8 10572.4
7512.5 12969.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.033/89.323, 84.57716

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
101 [50MWBLK4_1 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 442 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
102 [50MWBLK4_2 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
103 [HV_IDT1_11 33.000] 3PH 1558.52 27267.0 -78.30 68576.5 60860.1 58.2
25555.0 25555.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.769/78.296, 4.82730

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
104 [HV_IDT1_14 33.000] 3PH 1685.82 29494.1 -81.43 78834.8 70240.8 370.2
27306.7 27309.2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 443 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.711/81.428, 6.63416

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
105 [HV_IDT1_15 33.000] 3PH 1755.29 30709.6 -83.19 85152.6 76050.7 1031.5
28238.5 28257.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.682/83.191, 8.37502

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
106 [HV_IDT1_20 33.000] 3PH 1626.65 28459.1 -79.96 73874.6 65696.5 156.1
26499.8 26500.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.736/79.958, 5.64694

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 444 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
107 [LV1_IDT1_11 0.6000] 3PH 44.97 43270.0 -82.53 102882.8 102979.3 1001.4
43270.0 43281.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.530, 7.62639

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
108 [LV2_IDT1_11 0.6000] 3PH 47.04 45262.0 -82.53 107627.7 107709.8 1044.0
45262.0 45274.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.534, 7.63030

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 445 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
109 [LV1_IDT2_11 0.6000] 3PH 44.96 43266.7 -82.54 102896.1 102971.4 1001.4
43266.7 43278.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.540, 7.63653

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
110 [LV2_IDT2_11 0.6000] 3PH 47.04 45265.3 -82.52 107614.4 107717.6 1044.1
45265.3 45277.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.524, 7.62064

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
111 [LV1_IDT1_14 0.6000] 3PH 45.07 43365.5 -82.63 103320.6 103417.8 1059.6
43365.5 43378.5

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 446 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.627, 7.72818

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
112 [LV2_IDT1_14 0.6000] 3PH 47.15 45366.6 -82.64 108106.9 108189.7 1107.5
45366.6 45380.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.635, 7.73693

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
113 [LV1_IDT2_14 0.6000] 3PH 45.06 43362.2 -82.64 103333.9 103409.9 1059.5
43362.2 43375.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.637, 7.73857

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 447 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
114 [LV2_IDT2_14 0.6000] 3PH 47.15 45369.8 -82.63 108093.4 108197.5 1107.6
45369.8 45383.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.626, 7.72702

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
115 [LV1_IDT1_15 0.6000] 3PH 45.12 43413.4 -82.68 103540.8 103638.5 1090.0
43413.4 43427.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.676, 7.78025

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 448 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

116 [LV2_IDT1_15 0.6000] 3PH 47.20 45418.9 -82.69 108348.0 108431.2 1140.8
45419.0 45433.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.686, 7.79155

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
117 [LV1_IDT2_15 0.6000] 3PH 45.11 43410.1 -82.69 103554.2 103630.5 1089.9
43410.1 43423.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.686, 7.79078

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
118 [LV2_IDT2_15 0.6000] 3PH 47.20 45422.2 -82.68 108334.5 108439.0 1140.9
45422.2 45436.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.677, 7.78150

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 449 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
119 [LV1_IDT1_20 0.6000] 3PH 45.02 43322.5 -82.58 103123.2 103220.1 1033.0
43322.5 43334.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.583, 7.68199

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
120 [LV2_IDT1_20 0.6000] 3PH 47.10 45319.5 -82.59 107890.7 107973.2 1078.4
45319.5 45332.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.590, 7.68853

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 450 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
121 [LV1_IDT2_20 0.6000] 3PH 45.02 43319.2 -82.59 103136.4 103212.1 1032.9
43319.2 43331.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.593, 7.69227

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
122 [LV2_IDT2_20 0.6000] 3PH 47.10 45322.7 -82.58 107877.4 107981.0 1078.5
45322.8 45335.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.580, 7.67873

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
123 [INV1_IDT1_110.6000] 3PH 43.92 42257.5 -81.27 107570.0 97984.1 482.5
42257.5 42260.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.267, 6.50997

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 451 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
124 [INV2_IDT1_110.6000] 3PH 46.10 44363.8 -81.46 112931.7 103258.8 562.0
44363.8 44367.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.462, 6.66088

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
125 [INV1_IDT2_110.6000] 3PH 43.91 42254.5 -81.28 107562.3 97977.1 482.5
42254.5 42257.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.277, 6.51730

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 452 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
126 [INV2_IDT2_110.6000] 3PH 46.11 44366.8 -81.45 112939.4 103265.9 562.1
44366.8 44370.4
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.453, 6.65357

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
127 [INV1_IDT1_140.6000] 3PH 44.01 42350.1 -81.36 107805.8 98382.8 509.3
42350.1 42353.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.359, 6.58057

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 453 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
128 [INV2_IDT1_140.6000] 3PH 46.21 44465.6 -81.56 113191.1 103701.5 594.9
44465.6 44469.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.559, 6.73881

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
129 [INV1_IDT2_140.6000] 3PH 44.01 42347.1 -81.37 107798.1 98375.8 509.2
42347.1 42350.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.369, 6.58804

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
130 [INV2_IDT2_140.6000] 3PH 46.21 44468.7 -81.55 113198.7 103708.6 594.9
44468.7 44472.6

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 454 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.550, 6.73133

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
131 [INV1_IDT1_150.6000] 3PH 44.06 42396.5 -81.41 107924.0 98583.4 523.2
42396.5 42399.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.406, 6.61655

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
132 [INV2_IDT1_150.6000] 3PH 46.26 44516.7 -81.61 113321.0 103924.3 612.1
44516.7 44520.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.608, 6.77858

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 455 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
133 [INV1_IDT2_150.6000] 3PH 44.06 42393.5 -81.42 107916.3 98576.4 523.2
42393.5 42396.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.415, 6.62410

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
134 [INV2_IDT2_150.6000] 3PH 46.27 44519.7 -81.60 113328.7 103931.3 612.1
44519.7 44523.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.599, 6.77103

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 456 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
135 [INV1_IDT1_200.6000] 3PH 43.97 42308.4 -81.32 107699.6 98203.0 497.0
42308.4 42311.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.318, 6.54858

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
136 [INV2_IDT1_200.6000] 3PH 46.16 44419.8 -81.52 113074.3 103501.9 579.9
44419.8 44423.5
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.515, 6.70348

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 457 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
137 [INV1_IDT2_200.6000] 3PH 43.97 42305.4 -81.33 107691.9 98196.0 497.0
42305.4 42308.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.327, 6.55598

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
138 [INV2_IDT2_200.6000] 3PH 46.17 44422.8 -81.51 113081.9 103508.9 579.9
44422.8 44426.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.506, 6.69608

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
139 [HV_AUXTR1_110.6000] 3PH 44.97 43270.0 -82.53 102882.8 102979.3 1001.4
43270.0 43281.6

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 458 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.530, 7.62639

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
140 [HV_AUXTR2_110.6000] 3PH 47.04 45265.3 -82.52 107614.4 107717.6 1044.1
45265.3 45277.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.524, 7.62064

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
141 [HV_AUXTR1_140.6000] 3PH 45.07 43365.5 -82.63 103320.6 103417.8 1059.6
43365.5 43378.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.627, 7.72818

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 459 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
142 [HV_AUXTR2_140.6000] 3PH 47.15 45369.8 -82.63 108093.4 108197.5 1107.6
45369.8 45383.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.626, 7.72702

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
143 [HV_AUXTR1_150.6000] 3PH 45.12 43413.4 -82.68 103540.8 103638.5 1090.0
43413.4 43427.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.676, 7.78025

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 460 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

144 [HV_AUXTR2_150.6000] 3PH 47.20 45422.2 -82.68 108334.5 108439.0 1140.9


45422.2 45436.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.677, 7.78150

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
145 [HV_AUXTR1_200.6000] 3PH 45.02 43322.5 -82.58 103123.2 103220.1 1033.0
43322.5 43334.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.583, 7.68199

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
146 [HV_AUXTR2_200.6000] 3PH 47.10 45322.7 -82.58 107877.4 107981.0 1078.5
45322.8 45335.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.580, 7.67873

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 461 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
147 [LV_AUXTR1_110.4150] 3PH 0.36 501.3 -88.61 1276.1 1415.8 686.3
501.3 849.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.606, 41.08067

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
148 [LV_AUXTR2_110.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.4 687.5
501.5 851.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.609, 41.16875

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 462 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
149 [LV_AUXTR1_140.4150] 3PH 0.36 501.3 -88.61 1276.2 1415.9 686.7
501.3 850.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.606, 41.10744

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
150 [LV_AUXTR2_140.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.4 687.9
501.5 851.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.609, 41.19566

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
151 [LV_AUXTR1_150.4150] 3PH 0.36 501.3 -88.61 1276.2 1415.9 686.9
501.3 850.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.607, 41.12086

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 463 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
152 [LV_AUXTR2_150.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.5 688.1
501.5 851.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.610, 41.20912

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
153 [LV_AUXTR1_200.4150] 3PH 0.36 501.3 -88.61 1276.2 1415.8 686.5
501.3 850.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.606, 41.09539

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 464 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
154 [LV_AUXTR2_200.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.4 687.7
501.5 851.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.609, 41.18354

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
201 [50MWBLK3_1 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 465 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

202 [50MWBLK3_2 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
203 [HV_IDT1_5 33.000] 3PH 1273.82 22286.1 -71.66 50108.7 44153.4 1.0
21427.3 21427.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.940/71.659, 3.01653

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
204 [HV_IDT1_6 33.000] 3PH 1384.20 24217.3 -74.18 56670.7 50061.7 4.7
23062.3 23062.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.865/74.181, 3.52941

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 466 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
205 [HV_IDT1_7 33.000] 3PH 1456.33 25479.1 -75.86 61340.8 54285.6 13.3
24106.9 24106.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.823/75.862, 3.97005

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
206 [HV_IDT1_9 33.000] 3PH 1534.84 26852.7 -77.73 66828.6 59268.6 41.3
25222.8 25222.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.780/77.726, 4.59661

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 467 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
207 [LV1_IDT1_5 0.6000] 3PH 44.69 43004.2 -82.26 101675.8 101770.1 856.0
43004.2 43012.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.260, 7.35711

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
208 [LV2_IDT1_5 0.6000] 3PH 46.74 44971.1 -82.25 106307.4 106387.4 886.0
44971.1 44979.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.251, 7.34892

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 468 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

209 [LV1_IDT2_5 0.6000] 3PH 44.69 43000.8 -82.27 101688.7 101762.2 856.0
43000.8 43009.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.269, 7.36659

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
210 [LV2_IDT2_5 0.6000] 3PH 46.74 44974.4 -82.24 106294.4 106395.2 886.1
44974.4 44983.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.242, 7.33991

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
211 [LV1_IDT1_6 0.6000] 3PH 44.81 43117.8 -82.38 102189.8 102285.0 915.4
43117.8 43127.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.375, 7.46979

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 469 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
212 [LV2_IDT1_6 0.6000] 3PH 46.86 45095.4 -82.37 106869.4 106950.3 950.4
45095.4 45105.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.372, 7.46653

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
213 [LV1_IDT2_6 0.6000] 3PH 44.81 43114.5 -82.38 102202.8 102277.1 915.3
43114.5 43124.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.385, 7.47954

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 470 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
214 [LV2_IDT2_6 0.6000] 3PH 46.87 45098.7 -82.36 106856.3 106958.1 950.4
45098.7 45108.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.362, 7.45725

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
215 [LV1_IDT1_7 0.6000] 3PH 44.88 43184.3 -82.44 102491.9 102587.6 952.0
43184.3 43194.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.443, 7.53738

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
216 [LV2_IDT1_7 0.6000] 3PH 46.94 45168.2 -82.44 107199.9 107281.3 990.2
45168.2 45179.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.442, 7.53717

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 471 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
217 [LV1_IDT2_7 0.6000] 3PH 44.88 43181.0 -82.45 102505.0 102579.7 951.9
43181.0 43191.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.452, 7.54730

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
218 [LV2_IDT2_7 0.6000] 3PH 46.94 45171.5 -82.43 107186.7 107289.1 990.2
45171.5 45182.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.433, 7.52773

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 472 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
219 [LV1_IDT1_9 0.6000] 3PH 44.95 43251.0 -82.51 102795.7 102892.0 990.2
43251.0 43262.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.510, 7.60640

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
220 [LV2_IDT1_9 0.6000] 3PH 47.02 45241.1 -82.51 107532.3 107614.3 1031.8
45241.1 45252.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.513, 7.60937

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
221 [LV1_IDT2_9 0.6000] 3PH 44.94 43247.6 -82.52 102808.9 102884.1 990.2
43247.6 43259.0

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 473 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.520, 7.61649

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
222 [LV2_IDT2_9 0.6000] 3PH 47.02 45244.4 -82.50 107519.1 107622.1 1031.9
45244.4 45256.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.504, 7.59976

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
223 [INV1_IDT1_5 0.6000] 3PH 43.65 41999.7 -81.01 106913.9 96884.0 415.3
41999.7 42001.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.011, 6.32146

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 474 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
224 [INV2_IDT1_5 0.6000] 3PH 45.81 44080.4 -81.19 112210.3 102038.4 479.9
44080.4 44083.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.192, 6.45353

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
225 [INV1_IDT2_5 0.6000] 3PH 43.64 41996.7 -81.02 106906.2 96877.0 415.3
41996.7 41998.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.021, 6.32840

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 475 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
226 [INV2_IDT2_5 0.6000] 3PH 45.81 44083.4 -81.18 112218.0 102045.4 480.0
44083.4 44086.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.183, 6.44663

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
227 [INV1_IDT1_6 0.6000] 3PH 43.76 42109.9 -81.12 107194.4 97352.5 442.8
42109.9 42112.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.120, 6.40065

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
228 [INV2_IDT1_6 0.6000] 3PH 45.94 44201.5 -81.31 112518.6 102558.0 513.4
44201.5 44204.5

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 476 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.307, 6.54051

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
229 [INV1_IDT2_6 0.6000] 3PH 43.76 42106.9 -81.13 107186.7 97345.5 442.8
42106.9 42109.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.130, 6.40775

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
230 [INV2_IDT2_6 0.6000] 3PH 45.94 44204.5 -81.30 112526.4 102565.0 513.5
44204.5 44207.5
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.298, 6.53343

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 477 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
231 [INV1_IDT1_7 0.6000] 3PH 43.83 42174.4 -81.18 107358.5 97627.9 459.7
42174.4 42176.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.184, 6.44794

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
232 [INV2_IDT1_7 0.6000] 3PH 46.01 44272.4 -81.37 112699.1 102863.5 534.1
44272.4 44275.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.375, 6.59253

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 478 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
233 [INV1_IDT2_7 0.6000] 3PH 43.83 42171.4 -81.19 107350.8 97620.9 459.7
42171.4 42173.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.194, 6.45514

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
234 [INV2_IDT2_7 0.6000] 3PH 46.01 44275.4 -81.37 112706.8 102870.5 534.1
44275.4 44278.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.366, 6.58536

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 479 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
235 [INV1_IDT1_9 0.6000] 3PH 43.90 42239.0 -81.25 107523.0 97904.7 477.4
42239.0 42241.7
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.249, 6.49606

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
236 [INV2_IDT1_9 0.6000] 3PH 46.08 44343.4 -81.44 112880.0 103170.7 555.7
44343.4 44346.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.443, 6.64555

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
237 [INV1_IDT2_9 0.6000] 3PH 43.89 42236.0 -81.26 107515.3 97897.7 477.3
42236.0 42238.7

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 480 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.258, 6.50336

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
238 [INV2_IDT2_9 0.6000] 3PH 46.09 44346.5 -81.43 112887.7 103177.8 555.7
44346.5 44350.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.433, 6.63826

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
239 [HV_AUXTR1_5 0.6000] 3PH 44.69 43004.2 -82.26 101675.8 101770.1 856.0
43004.2 43012.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.260, 7.35711

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 481 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
240 [HV_AUXTR2_5 0.6000] 3PH 46.74 44974.4 -82.24 106294.4 106395.2 886.1
44974.4 44983.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.242, 7.33991

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
241 [HV_AUXTR1_6 0.6000] 3PH 44.81 43117.8 -82.38 102189.8 102285.0 915.4
43117.8 43127.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.375, 7.46979

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 482 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
242 [HV_AUXTR2_6 0.6000] 3PH 46.87 45098.7 -82.36 106856.3 106958.1 950.4
45098.7 45108.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.362, 7.45725

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
243 [HV_AUXTR1_7 0.6000] 3PH 44.88 43184.3 -82.44 102491.9 102587.6 952.0
43184.3 43194.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.443, 7.53738

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
244 [HV_AUXTR2_7 0.6000] 3PH 46.94 45171.5 -82.43 107186.7 107289.1 990.2
45171.5 45182.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.433, 7.52773

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 483 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
245 [HV_AUXTR1_9 0.6000] 3PH 44.95 43251.0 -82.51 102795.7 102892.0 990.2
43251.0 43262.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.510, 7.60640

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
246 [HV_AUXTR2_9 0.6000] 3PH 47.02 45244.4 -82.50 107519.1 107622.1 1031.9
45244.4 45256.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.504, 7.59976

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 484 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
247 [LV_AUXTR1_5 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.6 685.4
501.3 849.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.603, 41.00586

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
248 [LV_AUXTR2_5 0.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.2 686.6
501.5 850.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.606, 41.09359

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
249 [LV_AUXTR1_6 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.7 685.8
501.3 849.5

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 485 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.604, 41.03788

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
250 [LV_AUXTR2_6 0.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.3 687.0
501.5 850.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.607, 41.12576

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
251 [LV_AUXTR1_7 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.7 686.0
501.3 849.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.605, 41.05659

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 486 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
252 [LV_AUXTR2_7 0.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.3 687.2
501.5 850.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.608, 41.14455

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
253 [LV_AUXTR1_9 0.4150] 3PH 0.36 501.3 -88.61 1276.1 1415.8 686.3
501.3 849.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.605, 41.07531

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 487 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

254 [LV_AUXTR2_9 0.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.4 687.5
501.5 850.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.608, 41.16337

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
301 [50MWBLK1_1 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
302 [50MWBLK1_2 33.000] 3PH 1851.91 32400.0 -85.72 91641.0 85148.1 4404.1
29506.4 29833.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35155

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 488 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
303 [HV_IDT1_10 33.000] 3PH 1489.16 26053.6 -76.64 63581.0 56317.2 21.4
24576.3 24576.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.804/76.637, 4.20969

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
304 [HV_IDT1_8 33.000] 3PH 1364.69 23875.9 -73.73 55462.1 48971.1 3.6
22776.4 22776.4
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.878/73.731, 3.42655

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 489 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
305 [HV_IDT1_13 33.000] 3PH 1355.11 23708.3 -73.51 54876.6 48443.2 3.1
22635.6 22635.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.884/73.510, 3.37818

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
306 [HV_IDT1_12 33.000] 3PH 1291.14 22589.2 -72.05 51096.1 45040.5 1.2
21686.7 21686.7
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.928/72.051, 3.08705

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 490 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
307 [LV1_IDT1_10 0.6000] 3PH 44.91 43212.9 -82.47 102621.9 102717.9 968.2
43212.9 43223.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.472, 7.56678

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
308 [LV2_IDT1_10 0.6000] 3PH 46.97 45199.4 -82.47 107342.1 107423.8 1007.8
45199.4 45210.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.473, 7.56792

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
309 [LV1_IDT2_10 0.6000] 3PH 44.90 43209.5 -82.48 102635.0 102710.0 968.1
43209.5 43220.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.481, 7.57678

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 491 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
310 [LV2_IDT2_10 0.6000] 3PH 46.98 45202.7 -82.46 107328.9 107431.5 1007.9
45202.7 45214.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.463, 7.55841

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
311 [LV1_IDT1_8 0.6000] 3PH 44.79 43098.9 -82.36 102103.8 102198.8 905.2
43098.9 43108.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.356, 7.45073

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 492 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
312 [LV2_IDT1_8 0.6000] 3PH 46.84 45074.7 -82.35 106775.4 106856.1 939.3
45074.7 45084.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.352, 7.44663

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
313 [LV1_IDT2_8 0.6000] 3PH 44.79 43095.5 -82.37 102116.8 102190.9 905.1
43095.5 43105.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.366, 7.46044

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
314 [LV2_IDT2_8 0.6000] 3PH 46.85 45078.0 -82.34 106762.3 106863.9 939.4
45078.0 45087.8

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 493 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.342, 7.43740

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
315 [LV1_IDT1_13 0.6000] 3PH 44.78 43089.4 -82.35 102060.8 102155.8 900.1
43089.4 43098.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.346, 7.44125

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
316 [LV2_IDT1_13 0.6000] 3PH 46.83 45064.3 -82.34 106728.4 106809.0 933.8
45064.3 45074.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.342, 7.43672

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 494 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
317 [LV1_IDT2_13 0.6000] 3PH 44.78 43086.0 -82.36 102073.8 102147.9 900.1
43086.0 43095.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.356, 7.45093

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
318 [LV2_IDT2_13 0.6000] 3PH 46.84 45067.6 -82.33 106715.3 106816.8 933.9
45067.6 45077.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.332, 7.42751

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 495 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

319 [LV1_IDT1_12 0.6000] 3PH 44.71 43023.1 -82.28 101761.1 101855.6 865.6
43023.1 43031.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.279, 7.37561

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
320 [LV2_IDT1_12 0.6000] 3PH 46.76 44991.8 -82.27 106400.7 106480.8 896.4
44991.8 45000.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.271, 7.36822

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
321 [LV1_IDT2_12 0.6000] 3PH 44.71 43019.7 -82.29 101774.1 101847.7 865.5
43019.7 43028.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.289, 7.38514

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 496 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
322 [LV2_IDT2_12 0.6000] 3PH 46.76 44995.1 -82.26 106387.7 106488.6 896.5
44995.1 45004.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.262, 7.35917

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
323 [INV1_IDT1_100.6000] 3PH 43.86 42202.1 -81.21 107428.9 97746.3 467.2
42202.1 42204.7
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.212, 6.46846

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 497 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
324 [INV2_IDT1_100.6000] 3PH 46.04 44302.8 -81.40 112776.6 102994.9 543.2
44302.8 44306.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.404, 6.61513

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
325 [INV1_IDT2_100.6000] 3PH 43.85 42199.0 -81.22 107421.2 97739.3 467.2
42199.0 42201.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.222, 6.47570

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
326 [INV2_IDT2_100.6000] 3PH 46.04 44305.8 -81.39 112784.3 103002.0 543.3
44305.8 44309.2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 498 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.395, 6.60791

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
327 [INV1_IDT1_8 0.6000] 3PH 43.74 42091.5 -81.10 107147.5 97274.1 438.1
42091.5 42093.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.102, 6.38728

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
328 [INV2_IDT1_8 0.6000] 3PH 45.91 44181.3 -81.29 112467.2 102471.0 507.7
44181.3 44184.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.288, 6.52582

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 499 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
329 [INV1_IDT2_8 0.6000] 3PH 43.74 42088.5 -81.11 107139.8 97267.1 438.1
42088.5 42090.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.112, 6.39436

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
330 [INV2_IDT2_8 0.6000] 3PH 45.92 44184.3 -81.28 112474.9 102478.1 507.7
44184.3 44187.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.279, 6.51877

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 500 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
331 [INV1_IDT1_130.6000] 3PH 43.73 42082.3 -81.09 107124.1 97235.0 435.8
42082.3 42084.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.093, 6.38063

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
332 [INV2_IDT1_130.6000] 3PH 45.90 44171.2 -81.28 112441.4 102427.6 504.8
44171.2 44174.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.278, 6.51850

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 501 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
333 [INV1_IDT2_130.6000] 3PH 43.73 42079.3 -81.10 107116.4 97228.0 435.7
42079.3 42081.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.103, 6.38769

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
334 [INV2_IDT2_130.6000] 3PH 45.91 44174.2 -81.27 112449.2 102434.6 504.8
44174.2 44177.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.269, 6.51147

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
335 [INV1_IDT1_120.6000] 3PH 43.67 42018.1 -81.03 106960.5 96961.8 419.8
42018.1 42020.2

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 502 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.029, 6.33450

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
336 [INV2_IDT1_120.6000] 3PH 45.83 44100.5 -81.21 112261.6 102124.6 485.3
44100.5 44103.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.211, 6.46784

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
337 [INV1_IDT2_120.6000] 3PH 43.66 42015.0 -81.04 106952.8 96954.8 419.7
42015.0 42017.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/81.039, 6.34147

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 503 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
338 [INV2_IDT2_120.6000] 3PH 45.83 44103.5 -81.20 112269.3 102131.6 485.4
44103.5 44106.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.202, 6.46091

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
339 [HV_AUXTR1_100.6000] 3PH 44.91 43212.9 -82.47 102621.9 102717.9 968.2
43212.9 43223.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.472, 7.56678

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 504 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
340 [HV_AUXTR2_100.6000] 3PH 46.98 45202.7 -82.46 107328.9 107431.5 1007.9
45202.7 45214.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.463, 7.55841

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
341 [HV_AUXTR1_8 0.6000] 3PH 44.79 43098.9 -82.36 102103.8 102198.8 905.2
43098.9 43108.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.356, 7.45073

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
342 [HV_AUXTR2_8 0.6000] 3PH 46.85 45078.0 -82.34 106762.3 106863.9 939.4
45078.0 45087.8

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 505 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.342, 7.43740

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
343 [HV_AUXTR1_130.6000] 3PH 44.78 43089.4 -82.35 102060.8 102155.8 900.1
43089.4 43098.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.346, 7.44125

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
344 [HV_AUXTR2_130.6000] 3PH 46.84 45067.6 -82.33 106715.3 106816.8 933.9
45067.6 45077.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.332, 7.42751

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 506 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
345 [HV_AUXTR1_120.6000] 3PH 44.71 43023.1 -82.28 101761.1 101855.6 865.6
43023.1 43031.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.279, 7.37561

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
346 [HV_AUXTR2_120.6000] 3PH 46.76 44995.1 -82.26 106387.7 106488.6 896.5
44995.1 45004.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.262, 7.35917

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 507 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

347 [LV_AUXTR1_100.4150] 3PH 0.36 501.3 -88.61 1276.1 1415.8 686.1


501.3 849.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.605, 41.06461

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
348 [LV_AUXTR2_100.4150] 3PH 0.36 501.5 -88.61 1276.6 1416.3 687.3
501.5 850.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.608, 41.15261

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
349 [LV_AUXTR1_8 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.7 685.7
501.3 849.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.604, 41.03254

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 508 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
350 [LV_AUXTR2_8 0.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.3 686.9
501.5 850.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.607, 41.12040

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
351 [LV_AUXTR1_130.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.7 685.7
501.3 849.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.604, 41.02987

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 509 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
352 [LV_AUXTR2_130.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.3 686.9
501.5 850.5
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.607, 41.11772

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
353 [LV_AUXTR1_120.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.7 685.4
501.3 849.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.603, 41.01119

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
354 [LV_AUXTR2_120.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.2 686.6
501.5 850.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.606, 41.09895

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 510 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
360 [HV_AUXTR33 33.000] 3PH 1851.91 32400.0 -85.72 82604.6 85148.1 4404.1
29506.4 29833.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35155

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
361 [LV_AUXTR33 0.4150] 3PH 2.30 3200.9 -89.21 8148.1 9052.5 4513.0
3200.9 5532.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.079/89.210, 72.52402

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 511 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
401 [50MWBLK5_1 33.000] 3PH 1851.91 32400.0 -85.72 91640.9 85148.0 4404.1
29506.4 29833.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35164

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
402 [50MWBLK5_2 33.000] 3PH 1851.91 32400.0 -85.72 91641.0 85148.1 4404.1
29506.4 29833.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35155

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 512 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

403 [HV_IDT1_1 33.000] 3PH 1141.72 19974.9 -68.71 43027.6 37813.8 0.1
19413.1 19413.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/1.049/68.713, 2.56653

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
404 [HV_IDT1_2 33.000] 3PH 1200.69 21006.6 -70.02 46095.3 40555.7 0.3
20319.9 20319.9
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.998/70.019, 2.75034

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
405 [HV_IDT1_3 33.000] 3PH 1208.44 21142.3 -70.19 46509.5 40926.4 0.4
20438.2 20438.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.991/70.192, 2.77639

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 513 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
406 [HV_IDT1_4 33.000] 3PH 1177.95 20608.7 -69.51 44895.4 39482.4 0.2
19971.6 19971.6
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/1.017/69.514, 2.67656

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
407 [LV1_IDT1_1 0.6000] 3PH 44.52 42843.9 -82.10 100956.1 101049.2 778.9
42843.9 42851.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.097, 7.20404

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 514 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
408 [LV2_IDT1_1 0.6000] 3PH 46.55 44795.8 -82.08 105520.9 105599.6 802.7
44795.8 44802.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.081, 7.18944

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
409 [LV1_IDT2_1 0.6000] 3PH 44.52 42840.5 -82.11 100968.9 101041.3 778.8
42840.5 42847.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.107, 7.21315

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 515 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

410 [LV2_IDT2_1 0.6000] 3PH 46.56 44799.1 -82.07 105508.1 105607.4 802.8
44799.1 44806.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.072, 7.18079

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
411 [LV1_IDT1_2 0.6000] 3PH 44.60 42919.2 -82.17 101293.6 101387.2 814.2
42919.2 42926.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.174, 7.27514

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
412 [LV2_IDT1_2 0.6000] 3PH 46.64 44878.1 -82.16 105889.6 105968.9 840.8
44878.1 44886.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.161, 7.26348

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 516 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
413 [LV1_IDT2_2 0.6000] 3PH 44.60 42915.9 -82.18 101306.4 101379.3 814.1
42915.9 42923.6
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.183, 7.28443

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
414 [LV2_IDT2_2 0.6000] 3PH 46.64 44881.4 -82.15 105876.8 105976.7 840.9
44881.4 44889.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.152, 7.25466

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 517 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
415 [LV1_IDT1_3 0.6000] 3PH 44.61 42928.6 -82.18 101335.9 101429.6 818.7
42928.6 42936.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.183, 7.28414

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
416 [LV2_IDT1_3 0.6000] 3PH 46.65 44888.5 -82.17 105935.9 106015.3 845.7
44888.5 44896.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.171, 7.27286

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
417 [LV1_IDT2_3 0.6000] 3PH 44.61 42925.3 -82.19 101348.8 101421.7 818.7
42925.3 42933.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.193, 7.29345

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 518 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
418 [LV2_IDT2_3 0.6000] 3PH 46.65 44891.8 -82.16 105923.0 106023.0 845.8
44891.8 44899.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.162, 7.26402

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
419 [LV1_IDT1_4 0.6000] 3PH 44.57 42890.9 -82.14 101166.8 101260.2 800.8
42890.9 42898.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.145, 7.24829

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 519 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
420 [LV2_IDT1_4 0.6000] 3PH 46.61 44847.2 -82.13 105751.0 105830.1 826.3
44847.2 44854.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.131, 7.23551

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
421 [LV1_IDT2_4 0.6000] 3PH 44.57 42887.6 -82.15 101179.6 101252.3 800.7
42887.6 42895.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.155, 7.25751

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
422 [LV2_IDT2_4 0.6000] 3PH 46.61 44850.5 -82.12 105738.2 105837.9 826.4
44850.5 44858.1

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 520 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.122, 7.22676

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
423 [INV1_IDT1_1 0.6000] 3PH 43.49 41844.4 -80.86 106518.4 96227.6 379.5
41844.4 41846.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.857, 6.21317

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
424 [INV2_IDT1_1 0.6000] 3PH 45.63 43909.6 -81.03 111775.5 101310.8 436.4
43909.6 43911.7
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.030, 6.33489

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 521 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
425 [INV1_IDT2_1 0.6000] 3PH 43.48 41841.3 -80.87 106510.6 96220.6 379.4
41841.3 41843.1
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.867, 6.21990

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
426 [INV2_IDT2_1 0.6000] 3PH 45.64 43912.6 -81.02 111783.2 101317.8 436.4
43912.6 43914.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.020, 6.32822

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 522 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
427 [INV1_IDT1_2 0.6000] 3PH 43.56 41917.4 -80.93 106704.2 96535.4 395.9
41917.4 41919.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.929, 6.26358

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
428 [INV2_IDT1_2 0.6000] 3PH 45.72 43989.8 -81.11 111979.8 101651.9 456.3
43989.8 43992.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.106, 6.39007

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 523 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

429 [INV1_IDT2_2 0.6000] 3PH 43.56 41914.3 -80.94 106696.5 96528.4 395.9
41914.3 41916.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.939, 6.27041

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
430 [INV2_IDT2_2 0.6000] 3PH 45.72 43992.9 -81.10 111987.5 101659.0 456.4
43992.9 43995.2
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.097, 6.38330

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
431 [INV1_IDT1_3 0.6000] 3PH 43.57 41926.5 -80.94 106727.5 96574.0 398.0
41926.5 41928.4
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.938, 6.26995

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 524 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
432 [INV2_IDT1_3 0.6000] 3PH 45.73 43999.9 -81.12 112005.4 101694.7 458.9
43999.9 44002.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.115, 6.39705

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
433 [INV1_IDT2_3 0.6000] 3PH 43.57 41923.5 -80.95 106719.8 96567.0 398.0
41923.5 41925.4
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.948, 6.27679

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 525 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
434 [INV2_IDT2_3 0.6000] 3PH 45.73 44002.9 -81.11 112013.1 101701.8 458.9
44002.9 44005.3
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.106, 6.39026

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
435 [INV1_IDT1_4 0.6000] 3PH 43.53 41890.0 -80.90 106634.5 96419.7 389.6
41890.0 41891.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.902, 6.24456

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 526 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
436 [INV2_IDT1_4 0.6000] 3PH 45.68 43959.7 -81.08 111903.1 101523.8 448.7
43959.7 43962.0
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.077, 6.36925

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
437 [INV1_IDT2_4 0.6000] 3PH 43.53 41886.9 -80.91 106626.7 96412.8 389.6
41886.9 41888.8
Note - ip(B) currents include safety factor multiplier (1.15).
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.009/80.912, 6.25135

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
438 [INV2_IDT2_4 0.6000] 3PH 45.69 43962.7 -81.07 111910.9 101530.8 448.8
43962.7 43965.0

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 527 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

Note - ip(B) currents include safety factor multiplier (1.15).


THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/81.068, 6.36251

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
439 [HV_AUXTR1_1 0.6000] 3PH 44.52 42843.9 -82.10 100956.1 101049.2 778.9
42843.9 42851.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.097, 7.20404

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
440 [HV_AUXTR2_1 0.6000] 3PH 46.56 44799.1 -82.07 105508.1 105607.4 802.8
44799.1 44806.2
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.072, 7.18079

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 528 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym


Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
441 [HV_AUXTR1_2 0.6000] 3PH 44.60 42919.2 -82.17 101293.6 101387.2 814.2
42919.2 42926.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.174, 7.27514

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
442 [HV_AUXTR2_2 0.6000] 3PH 46.64 44881.4 -82.15 105876.8 105976.7 840.9
44881.4 44889.3
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.152, 7.25466

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 529 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

443 [HV_AUXTR1_3 0.6000] 3PH 44.61 42928.6 -82.18 101335.9 101429.6 818.7
42928.6 42936.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.183, 7.28414

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
444 [HV_AUXTR2_3 0.6000] 3PH 46.65 44891.8 -82.16 105923.0 106023.0 845.8
44891.8 44899.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.162, 7.26402

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
445 [HV_AUXTR1_4 0.6000] 3PH 44.57 42890.9 -82.14 101166.8 101260.2 800.8
42890.9 42898.4
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.145, 7.24829

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 530 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
446 [HV_AUXTR2_4 0.6000] 3PH 46.61 44850.5 -82.12 105738.2 105837.9 826.4
44850.5 44858.1
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.008/82.122, 7.22676

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
447 [LV_AUXTR1_1 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.6 684.8
501.3 848.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.602, 40.96058

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 531 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

X------------ BUS ------------X MVA AMP DEG AMP AMP AMP


AMP AMP
448 [LV_AUXTR2_1 0.4150] 3PH 0.36 501.5 -88.60 1276.5 1416.1 686.0
501.5 849.7
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.604, 41.04810

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
449 [LV_AUXTR1_2 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.6 685.1
501.3 848.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.602, 40.98187

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
450 [LV_AUXTR2_2 0.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.2 686.3
501.5 849.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.605, 41.06949

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 532 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
451 [LV_AUXTR1_3 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.6 685.1
501.3 848.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.602, 40.98454

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
452 [LV_AUXTR2_3 0.4150] 3PH 0.36 501.5 -88.61 1276.5 1416.2 686.3
501.5 850.0
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.605, 41.07217

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 533 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

/I/ AN(I) /I/ /I/ /I/


/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
453 [LV_AUXTR1_4 0.4150] 3PH 0.36 501.3 -88.60 1276.1 1415.6 685.0
501.3 848.8
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.602, 40.97388

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
454 [LV_AUXTR2_4 0.4150] 3PH 0.36 501.5 -88.60 1276.5 1416.2 686.2
501.5 849.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.502/88.605, 41.06147

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.10, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
460 [HV_AUXTR33 33.000] 3PH 1851.91 32400.0 -85.72 82604.6 85148.1 4404.1
29506.4 29833.3

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 534 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.647/85.717, 13.35155

------------------------------------------------------------------------------------------------------
---------
VOLTAGE FACTOR C= 1.05, NOMINAL FREQUENCY=50.0 Hz, BREAKING CURRENT at TIME= 0.100 seconds
<-SCMVA-> <-Sym I''k rms--> <-ip(B)-> <-ip(C)-> <DC Ib(C)> <Sym
Ib-> <Asym Ib>
/I/ AN(I) /I/ /I/ /I/
/I/ /I/
X------------ BUS ------------X MVA AMP DEG AMP AMP AMP
AMP AMP
461 [LV_AUXTR33 0.4150] 3PH 2.30 3200.9 -89.21 8148.1 9052.5 4513.0
3200.9 5532.9
THEVENIN IMPEDANCE, X/R (OHM) Z+:/0.079/89.210, 72.52402

------------------------------------------------------------------------------------------------------
---------

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 535 of 536
Ayana Renewable Power Private Limited
PSS®E Model of 250MW Solar Power Plant, Anantapur,
Andhra Pradesh

12 Literature & References


[1] https://www.srldc.org/Downloads/Procedure_for_Integration_of_Power_System_Ele-
ments.pdf
[2] Guideline for exchange of data for modelling Solar farms.pdf: Document by POSOCO
[3] CEA Technical Standards for Connectivity to the Grid, dated 6th February, 2019
[4] Manual of CEA Transmission Planning Criteria- January 2013
[5] Overall SLD - Ananthapur 250MW.pdf
[6] User Manual for Inverter Model: “Generic Modeling of Sungrow SG3125HV Photovoltaic
Inverter.pdf”, Sungrow Power Supply Co., Ltd., V10, 2019/05/30
[7] SG3125HV-20 CEA Test Report.pdf
[8] SUNGROW Harmonic Test Report for SG3125HV-20.pdf
[9] PV Power Plant Controller User Manual.pdf, Document by Adaptive Engineering PVT LTD.
[10] Cable Schedule GTP
[11] IDT GTP
[12] Power Transformers GTP
[13] Auxiliary Transformers GTP

Restricted

Project Reference: 3006880923 Technical Report Version 1


Siemens Ltd, SI DG SW PTI 2020-09-30 Page 536 of 536