Professional Documents
Culture Documents
Detailing of
Clay Masonry
This publication updates and
supersedes the publication of the same
name published by the Clay Brick and
Paver Institute and in May 2000.
1 Introduction 7
2 Roof Anchorage 8
3 Wall Supports 10
4 Prevention of Dampness 13
4.6 Weepholes 15
5 Lintels 16
5.1 General 16
5.2 Definitions 16
5.5.1 General 24
5.6.1 Notation 25
6 Movement Gaps
27
6.1.1 Thermal 27
6.2.1 General 28
7 References 34
Figures
Click on any entry
Where specific dimensions are given on details in this manual, they should
be regarded as indicative only. The use of terms such as low wind, high wind
or earthquake loading should be interpreted as necessarily vague – specific
dimensions for roof tie-downs, anchorages for earthquake resistance and
so on should be designed by a structural engineer to suit the particular
circumstances, the local loading and soil conditions, and the requirements
of the local authorities. The diagrams should not be taken as a substitute
for engineering detail drawings.
Durability considerations are not covered in this manual and are included
in TBA Manual 7: Design of Clay Masonry for Serviceability6.
Roof anchorages are required to regions a continuous tie-down rod Figure 2. Roof – cavity wall
resist not only uplift from wind carried through to the footing (high wind)
forces, but also lateral shear from would be required. Such a detail is Strap attached to
truss/rafter
wind and earthquake forces. not shown here.
Requirements vary widely for
different regions, depending on the Where resistance to significant
level of wind and earthquake risk. earthquake forces is also required,
Where the term high wind is used, a detail such as that shown in
it should not be taken to include Figure 3 can be used. This detail 25 x 1 mm
cyclonic wind conditions, but only mobilises both leaves of masonry gal.straps at
600 mm min.
1200 crs max.
a comparatively higher level of for resistance to uplift forces and
wind than that referred to as low includes positive tying of the roof
wind. Some typical arrangements structure and the top plate to the Strap attached
to 10 mm bar
are indicated for cavity walls, top of the wall so that resistance embedded
veneer walls and single-skin walls. to horizontal shear forces is 50 mm min.
in each leaf
provided.
2.1 Cavity walls
Figure 1. Roof – cavity wall
For cavity walls, three common (low wind)
details are shown. The detail in Figure 3. Roof – cavity wall
Figure 1 is suitable for low wind (high wind and earthquake)
loads and uses a galvanised steel ‘TripleGrip’ fastener between wall plate
strap to tie the top plate to the and truss/rafter
Top plate
bolted to
bond beam Anchor bar
hooked over
reinforcing
bar in bond
beam
There are many different types of Figure 9 shows an alternative 3.2 Veneer walls
supports for walls, including detail for a cavity wall, supported
footings, slabs and shelf angles. on a strip footing with a floor slab For a veneer wall on a raft slab, as
Requirements for residential slabs founded on compacted fill. In this shown in Figure 11, the step down
and footings are covered by case the flashing does not extend can be any convenient dimension
AS 2870. Typical details are shown across the cavity; proper drainage of at least 20 mm, but the flashing
here for cavity walls, veneer walls, is ensured by an outward-sloping must extend up at least 150 mm
single-skin walls, internal walls, fill of mortar at the base of the above the base and be attached to
support of walls on slabs and cavity. The damp-proof course in the timber framing. The flashing
supports for the tops of internal the outer leaf should be at least also acts as a damp-proof course
walls. Some details for the support 150 mm above the finished ground for the masonry. The waterproofing
of walls on nibs and shelf angles level (if not paved) and the membrane for the slab must extend
are shown in Section 6. sub-floor membrane should extend above the finished ground level.
around the front of the slab and be
Weepholes (see Section 4.6) should embedded beneath the inner leaf. Figure 11. Base of a veneer wall on a
be provided above all flashings. raft slab
Termite protection measures Figure 9. Base of a cavity wall on a
might also be required but are strip footing with slab on fill Flashing/DPC Timber frame
omitted here for clarity. Sub-floor
DPC membrane Weep holes
wrapped around at 1200 crs
3.1 Cavity walls Weep holes slab edge max. 150 mmm min.
at 1200 crs 20 mm
The detail shown in Figure 8 is for max. Compacted fill min.
supporting a cavity masonry wall 150 mm min.
on a raft slab. The step down at the
edge of the slab can be any
convenient height but must be at Membrane under slab Compacted fill
least one course of brickwork to Strip footing
DPC
Weep Mortar behind
holes at DPC Weep holes at
1200 crs 1200 crs max.
max. 86 mm min.
150 mm mm
150 min. Ant cap if
Flashing/ min. required
DPC
Mortar fill
Compacted fill Strip footing in cavity
Membrane under slab
Compacted
An alternative detail for single-skin Strip footing
fill
walls is shown in Figure 13. In this 3.5 Nibs and shelf angles
case the wall is seated on a strip
When non-loadbearing masonry
footing. It is usual to pour the slab
cladding is supported on nibs and
and grout the lower courses of the
shelf-angles it is essential to allow
wall in one operation. Other points
for sufficient movement to
are the same as for the previous 3.4 Internal walls –
accommodate long-term
detail. raft slab expansion and to provide adequate
For the support of internal walls, flashing to exclude water. The
Engineer’s details should be
a raft slab must be stiffened or at arrangements for flashing of these
obtained for single-skin walls that
least strengthened. Two typical supports are shown in Section 6,
utilise high wind tie-down rods.
details are shown in Figure 14 and where other aspects are discussed.
Figure 12. Base of a single-skin wall Figure 15. With single-storey walls
on a raft slab this can usually be achieved within
the slab thickness but for two-
storey construction the slab will
Waterproof require additional thickening.
coating Engineer’s details should be
obtained for the slab.
Starter bar
hooked into Figure 14. Internal wall support –
footing single storey
Membrane
Cornice fixed
to ceiling Allowance for
truss deflection
15 mm min.
Gap to
accommodate
movement
Problems relating to water such a wall. Most free water found used below the floor level DPC is
penetration into masonry in this location enters through not of a type known to be highly
buildings happen all too often, gaps in the joints due to bed resistant to salt attack, the
but they can be prevented. furrowing, tip jointing or other provision of an additional DPC close
Construction methods exist which, poor bricklaying practices. Defects to ground level is recommended.
if carefully followed, will ensure a in flashings can also be a cause.
durable and watertight building. Membrane-type DPCs must be laid
Cavity wall construction, which across the full width of the wall or
Where dampness or deterioration operates on the principle that the leaf and should be visible on either
due to water occurs in walls, it is cavity provides a break between a side when the brickwork is
common to find that the cause of wet outside leaf and a dry inside completed to show that the
failure is a poor architectural leaf, is usually an effective barrier operation of tooling the joint has
detail, unsuitable materials, bad to penetration of rainwater falling not provided a bridge of mortar
workmanship or a combination of on the face of the wall unless large across the membrane. If the
them all. Any of these causes gaps allow water to enter and membrane is carried across the
might arise from a lack of either blow or splash across the cavity to form a flashing, it should
understanding of the properties of cavity. The effectiveness of the incorporate a step-up of two
the materials involved, although cavity will be greatly reduced if it courses from the outside to the
carelessness or building down to a is bridged by mortar droppings or inside leaf (see Section 3).
price will sometimes be the cause poorly designed or installed wall
of bad workmanship. ties. Free drainage of the cavity 4.3 Cavity flashings
must occur if water transmission
In order to be effective, a wall
The BCA (Housing Provisions) to the inner leaf is to be avoided.
cavity must act as an uninterrupted
includes various details of
gap between a wet external leaf
construction practice for flashings The porous nature of both bricks
and a dry internal leaf. Whenever it
and damp-proof courses that are and mortar makes a major
is bridged or interrupted by other
deemed to be acceptable and contribution to the water
parts of the building, for example
should be read in conjunction with tightness of a wall. Their blotting
by frames in openings or structural
this manual. paper action of soaking up free
elements such as columns, beams,
water considerably reduces the
shelf angles or haunches, special
4.1 Prevention of water load on flashings and other
precautions are required to prevent
penetration through waterproofing elements and the
the transfer of moisture across the
water-holding capacity of
walls cavity. The flashing details given in
brickwork is seldom exceeded by
Section 3 and Section 6.4 (for nibs
Bricks and mortar both contain the volume of water delivered to it
and shelf angles) set out the
fine pores or capillaries of irregular during a period of rain.
general principles applicable to
shape and size extending for
4.2 Damp-proof courses waterproofing of interruptions to
various distances and directions.
the cavity.
Water lodging on one surface of a
The correct locations for ground
wall made of these materials will
and floor-level damp-proof courses Weep-holes are necessary to drain
be drawn into the pores by
(DPCs) are shown in Section 3. In any water that may be collected by
capillary force and, if sufficient
some regions in the past, it has the cavity flashings to the outside
water is present over a long
been the practice to provide two of the wall. Particular precautions
enough time, it may eventually
DPCs below timber floor level, but are required in walls exposed to
penetrate through the full
a single membrane is now often high winds, because air pressure on
thickness of the wall to appear as
recommended. The combination of the external face can prevent the
dampness on the inside. This is a
a DPC and a termite shield in this water from escaping through the
possible cause of dampness in
location will be necessary in many weep holes. When there is such a
walls with no cavity, but capillary
regions. Where there is any risk risk, the step across the cavity
action will not result in water
that surrounding ground may be should be increased.
running down the inside face of
waterlogged and the brick to be
5.1 General the ability of brickwork to form an 5.3 Using the design tables
arch over openings has been
Lintels are necessary to support allowed for. The function of the The design tables in Section 5.4
brickwork over door and window lintel is to provide support for the can be used for openings in
openings in walls. There are many triangle of brickwork above the internal, external and gable walls.
types of lintels and no one type opening, which does not form part Reference need not be made to
is best in all circumstances. of the arch, and it must be strong Section 5.6 (Design by Calculation)
Questions of performance, and stiff enough to prevent unless verification of the
economy, appearance and separation of the triangle from the determined lintel size is required.
durability must be considered adjoining brickwork. When the This manual considers the support
when specifying lintels. This height of brickwork over the of single leaf walls only; cavity
section gives structural opening is too small to form an walls should be treated as two
requirements that can be used to arch of adequate strength, the single-leaf walls, each requiring
specify any type of commercially lintel must be able to carry all of support.
made lintel. The requirements are the loads acting above the Point loads are not covered in the
given in tabular form for situations opening. design tables. For the design of
where clay brickwork is to be
lintels to carry point loads,
supported over openings up to There is no need to create a high reference should be made to
4.2 m in span and the brickwork is shear capacity in the brickwork Section 5.6. It is also possible in
either non-loadbearing or because all the forces acting some circumstances where wind
supports domestic floor or roof through the brickwork are resolved loads are high and, for example, a
loads. The design assumptions and into compressive stresses. Any light metal roof is used, that net
methods of calculation are brick and mortar combination that uplift forces will occur on a lintel.
described. is suitable for the conditions can Such cases are not provided for in
be used. the tables.
A full examination of the structural
behaviour of brickwork supported 5.2 Definitions The two most significant factors
by lintels is beyond the scope of
A number of terms used affecting the choice of lintels are
this manual and a number of
throughout this section have been strength and stiffness. A lintel
conservative assumptions have
given specific meanings to simplify must have both adequate strength
therefore been used. Lintel
the determination and selection of and stiffness and the factor that
manufacturers usually provide
lintels. For the purposes of this imposes the more severe
load tables for their products,
section the terms have the requirement controls the choice of
some of which assume composite
following meanings: lintel size. Usually the stiffness
action between the lintel and the
requirement is the more severe.
masonry. This is a very efficient
structural action, which uses the Stiffness (EI) – the stiffness of a
lintel is expressed in terms of the To determine the required strength
brickwork and the lintel together
Modulus of Elasticity (E) and the and stiffness of a lintel the
as a beam to resist the loads. This
Moment of Inertia (I) for which the following data must be known –
action cannot be achieved for all
materials and has not been unit is MN.mm2.
(i) the clear span of the opening
assumed in the tables presented
Strength (M) – the strength of a (L);
here. When using manufacturers’
tables it is essential to check lintel is expressed in terms of
bending moment capacity for (ii) the height of the brickwork
that the underlying assumptions
which the unit is kN.m. above the lintel (h); and,
are compatible with the
circumstances of the particular (iii) the type and magnitude of the
building being designed. loads acting upon the lintel.
(Unit is kN.m)
Height of
brickwork Clear span of opening, L (m)
above lintel,
h (mm) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
300 0.06 0.12 0.20 0.29 0.4 0.5 0.7 0.8 1.0 1.2 1.4 1.6
600 0.08 0.18 0.33 0.52 0.7 1.0 1.3 1.6 2.0 2.3 2.8 3.2
900 0.08 0.18 0.35 0.61 0.9 1.3 1.8 2.2 2.8 3.4 4.0 4.7
1200 0.08 0.18 0.35 0.61 1.0 1.4 2.0 2.7 3.4 4.2 5.0 5.9
1500 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.7 4.7 5.7 6.9
1800 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.1 7.5
2100 or more 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
Height of
brickwork Clear span of opening, L (m)
above lintel,
h (mm) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
300 1.9 4.7 9.4 16.6 26.6 40 57 78 105 136 188 252
600 2.1 6.5 16.0 29.7 49.1 75 109 151 203 265 367 496
900 2.1 6.5 15.9 32.9 63.7 101 150 212 289 381 530 720
1200 2.1 6.5 15.9 32.9 61.0 104 177 256 355 475 670 917
1500 2.1 6.5 15.9 32.9 61.0 104 167 254 397 543 777 1076
1800 2.1 6.5 15.9 32.9 61.0 104 167 254 372 527 844 1188
2100 or more 2.1 6.5 15.9 32.9 61.0 104 167 254 372 527 786 1138
(Unit is kN.m)
Height of
brickwork Load Clear span of opening, L (m)
above lintel, width
h (mm) (m) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
1.8 0.18 0.44 0.79 1.24 1.8 2.4 3.1 4.0 4.9 5.9 7.0 8.2
3.0 0.26 0.65 1.18 1.86 2.7 3.7 4.8 6.1 7.5 9.1 10.8 12.6
300 4.2 0.34 0.86 1.58 2.49 3.6 4.9 6.4 8.2 10.1 12.2 14.5 17.0
5.4 0.42 1.07 1.97 3.12 4.5 6.2 8.1 10.3 12.7 15.3 18.3 21.4
6.6 0.50 1.28 2.36 3.75 5.4 7.4 9.7 12.4 15.3 18.5 22.0 25.8
1.8 0.08 0.18 0.53 0.99 1.6 2.3 3.0 4.0 5.0 6.1 7.4 8.7
3.0 0.08 0.18 0.66 1.30 2.1 3.1 4.2 5.5 7.0 8.6 10.4 12.4
600 4.2 0.08 0.18 0.79 1.62 2.7 3.9 5.4 7.1 9.0 11.1 13.5 16.1
5.4 0.08 0.18 0.92 1.93 3.2 4.8 6.6 8.7 11.0 13.7 16.6 19.7
6.6 0.08 0.18 1.05 2.25 3.8 5.6 7.8 10.2 13.0 16.2 19.6 23.4
1.8 0.08 0.18 0.35 0.61 1.2 1.9 2.8 3.8 4.9 6.2 7.6 9.1
3.0 0.08 0.18 0.35 0.61 1.4 2.4 3.5 4.9 6.4 8.1 9.9 12.0
900 4.2 0.08 0.18 0.35 0.61 1.6 2.8 4.2 5.9 7.8 10.0 12.3 14.9
5.4 0.08 0.18 0.35 0.61 1.8 3.2 4.9 6.9 9.2 11.8 14.7 17.9
6.6 0.08 0.18 0.35 0.61 1.9 3.6 5.6 8.0 10.7 13.7 17.1 20.8
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.4 3.4 4.7 6.0 7.6 9.2
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.6 4.0 5.5 7.3 9.3 11.4
1200 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.8 4.5 6.4 8.6 11.0 13.6
5.4 0.08 0.18 0.35 0.61 1.0 1.4 3.1 5.0 7.3 9.8 12.7 15.8
6.6 0.08 0.18 0.35 0.61 1.0 1.4 3.3 5.5 8.1 11.1 14.4 18.0
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.1 5.6 7.3 9.1
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.4 6.3 8.3 10.6
1500 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.7 6.9 9.3 12.0
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 5.0 7.5 10.3 13.5
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 5.3 8.1 11.4 14.9
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.7 8.6
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.0 9.3
1800 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.3 10.1
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.7 10.8
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 8.0 11.5
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
2100 or more 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
Height of
brickwork Load Clear span of opening, L (m)
above lintel width
(mm) (m) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
1.8 4.7 15 33 62 103 160 235 329 446 587 819 1112
3.0 6.6 21 49 92 155 240 353 496 673 888 1239 1686
300 4.2 8.4 28 64 122 206 321 472 663 901 1189 1660 2259
5.4 10.3 35 80 152 257 401 590 831 1128 1490 2081 2832
6.6 12.2 41 96 182 308 481 709 998 1356 1791 2502 3406
1.8 2.1 6.5 24 52 95 155 236 339 468 626 883 1212
3.0 2.1 6.5 29 67 126 209 320 464 645 867 1228 1690
600 4.2 2.1 6.5 34 82 157 262 405 590 822 1108 1572 2168
5.4 2.1 6.5 40 97 187 316 490 715 999 1348 1916 2646
6.6 2.1 6.5 45 112 218 369 574 841 1176 1589 2261 3123
1.8 2.1 6.5 15.9 33 79 141 227 338 478 651 932 1293
3.0 2.1 6.5 15.9 33 89 168 277 421 605 832 1200 1676
900 4.2 2.1 6.5 15.9 33 99 195 328 505 731 1012 1468 2058
5.4 2.1 6.5 15.9 33 110 222 379 588 857 1193 1735 2440
6.6 2.1 6.5 15.9 33 120 248 430 672 984 1373 2003 2822
1.8 2.1 6.5 15.9 33 61 104 202 319 469 656 957 1347
3.0 2.1 6.5 15.9 33 61 104 219 361 545 776 1148 1633
1200 4.2 2.1 6.5 15.9 33 61 104 236 403 621 897 1339 1920
5.4 2.1 6.5 15.9 33 61 104 253 445 697 1017 1530 2207
6.6 2.1 6.5 15.9 33 61 104 270 486 773 1137 1722 2493
1.8 2.1 6.5 15.9 33 61 104 167 254 435 633 949 1362
3.0 2.1 6.5 15.9 33 61 104 167 254 460 693 1064 1554
1500 4.2 2.1 6.5 15.9 33 61 104 167 254 486 753 1178 1745
5.4 2.1 6.5 15.9 33 61 104 167 254 511 814 1293 1936
6.6 2.1 6.5 15.9 33 61 104 167 254 536 874 1408 2127
1.8 2.1 6.5 15.9 33 61 104 167 254 372 527 901 1332
3.0 2.1 6.5 15.9 33 61 104 167 254 372 527 939 1427
1800 4.2 2.1 6.5 15.9 33 61 104 167 254 372 527 977 1523
5.4 2.1 6.5 15.9 33 61 104 167 254 372 527 1016 1618
6.6 2.1 6.5 15.9 33 61 104 167 254 372 527 1054 1714
1.8 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
3.0 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
2100 or more 4.2 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
5.4 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
6.6 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
(Unit is kN.m)
Height of
brickwork Load Clear span of opening, L (m)
above lintel, width
h (mm) (m) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
1.8 0.13 0.30 0.54 0.83 1.2 1.6 2.1 2.6 3.2 3.9 4.6 5.4
3.0 0.18 0.42 0.76 1.19 1.7 2.3 3.0 3.8 4.7 5.7 6.8 7.9
300 4.2 0.22 0.54 0.98 1.55 2.2 3.0 4.0 5.0 6.2 7.5 8.9 10.4
5.4 0.27 0.66 1.21 1.91 2.8 3.8 4.9 6.2 7.7 9.3 11.0 12.9
6.6 0.31 0.78 1.43 2.27 3.3 4.5 5.9 7.4 9.1 11.1 13.2 15.5
1.8 0.08 0.18 0.44 0.79 1.2 1.7 2.3 2.9 3.7 4.5 5.4 6.4
3.0 0.08 0.18 0.52 0.97 1.5 2.2 3.0 3.8 4.8 5.9 7.1 8.5
600 4.2 0.08 0.18 0.59 1.15 1.8 2.7 3.6 4.7 6.0 7.4 8.9 10.5
5.4 0.08 0.18 0.67 1.33 2.2 3.1 4.3 5.6 7.1 8.8 10.6 12.6
6.6 0.08 0.18 0.74 1.51 2.5 3.6 5.0 6.5 8.3 10.2 12.4 14.7
1.8 0.08 0.18 0.35 0.61 1.1 1.7 2.4 3.1 4.0 5.0 6.0 7.2
3.0 0.08 0.18 0.35 0.61 1.2 1.9 2.8 3.7 4.8 6.0 7.4 8.9
900 4.2 0.08 0.18 0.35 0.61 1.3 2.2 3.2 4.3 5.6 7.1 8.7 10.5
5.4 0.08 0.18 0.35 0.61 1.4 2.4 3.6 4.9 6.5 8.2 10.1 12.2
6.6 0.08 0.18 0.35 0.61 1.5 2.6 4.0 5.5 7.3 9.3 11.5 13.9
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.2 3.1 4.1 5.2 6.5 7.8
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.4 3.4 4.6 5.9 7.4 9.1
1200 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.5 3.7 5.1 6.7 8.4 10.3
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.6 4.0 5.6 7.4 9.4 11.6
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.8 4.3 6.1 8.1 10.3 12.8
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.0 5.2 6.6 8.1
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.1 5.6 7.2 9.0
1500 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.3 5.9 7.8 9.8
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.4 6.3 8.4 10.6
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.6 6.7 8.9 11.5
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.4 8.1
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.6 8.6
1800 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.8 9.0
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.0 9.4
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.2 9.8
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
2100 or more 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
Height of
brickwork Load Clear span of opening, L (m)
above lintel width
(mm) (m) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
1.8 3.3 9.9 21.6 39.8 66 102 149 208 281 369 513 696
3.0 4.3 13.3 29.6 55.3 93 143 210 294 398 524 730 991
300 4.2 5.2 16.8 37.7 70.9 119 185 271 380 515 679 947 1287
5.4 6.2 20.2 45.8 86.4 145 226 332 466 632 834 1164 1583
6.6 7.2 23.7 53.9 101.9 172 267 393 552 750 989 1381 1878
1.8 2.1 6.5 20.1 41.3 73 117 174 248 340 451 633 865
3.0 2.1 6.5 22.8 49.1 89 144 218 313 431 575 811 1111
600 4.2 2.1 6.5 25.5 56.9 105 172 262 377 522 699 988 1358
5.4 2.1 6.5 28.1 64.6 120 199 305 442 613 824 1166 1604
6.6 2.1 6.5 30.8 72.4 136 227 349 507 705 948 1343 1850
1.8 2.1 6.5 15.9 32.9 72 122 190 277 386 520 737 1016
3.0 2.1 6.5 15.9 32.9 77 136 216 320 452 613 876 1213
900 4.2 2.1 6.5 15.9 32.9 82 150 242 363 517 706 1014 1410
5.4 2.1 6.5 15.9 32.9 87 163 268 406 582 799 1152 1607
6.6 2.1 6.5 15.9 32.9 93 177 294 449 647 892 1290 1804
1.8 2.1 6.5 15.9 32.9 61 104 190 289 414 568 818 1138
3.0 2.1 6.5 15.9 32.9 61 104 198 310 453 630 916 1286
1200 4.2 2.1 6.5 15.9 32.9 61 104 207 332 492 693 1015 1434
5.4 2.1 6.5 15.9 32.9 61 104 216 353 531 755 1113 1582
6.6 2.1 6.5 15.9 32.9 61 104 225 375 571 817 1212 1729
1.8 2.1 6.5 15.9 32.9 61 104 167 254 417 589 865 1224
3.0 2.1 6.5 15.9 32.9 61 104 167 254 430 620 925 1322
1500 4.2 2.1 6.5 15.9 32.9 61 104 167 254 443 651 984 1421
5.4 2.1 6.5 15.9 32.9 61 104 167 254 456 682 1043 1519
6.6 2.1 6.5 15.9 32.9 61 104 167 254 469 713 1102 1618
1.8 2.1 6.5 15.9 32.9 61 104 167 254 372 527 873 1262
3.0 2.1 6.5 15.9 32.9 61 104 167 254 372 527 893 1311
1800 4.2 2.1 6.5 15.9 32.9 61 104 167 254 372 527 913 1361
5.4 2.1 6.5 15.9 32.9 61 104 167 254 372 527 932 1410
6.6 2.1 6.5 15.9 32.9 61 104 167 254 372 527 952 1459
1.8 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
3.0 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
2100 or more 4.2 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
5.4 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
6.6 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
(Unit is kN.m)
Table 8. Stiffness requirements (EI) for lintels supporting walls and timber floors
1.8 14.2 35.3 72 130 215 334 495 704 971 1304 1857 2579
3.0 22.3 54.5 110 195 318 488 713 1004 1370 1823 2571 3540
4.2 30.4 73.7 147 260 421 642 932 1304 1770 2341 3285 4500
5.4 38.5 92.9 185 325 524 795 1151 1604 2169 2860 4000 5461
6.6 46.6 112.1 222 389 627 949 1370 1904 2568 3378 4714 6422
and –
All building materials change size 6.1.2 Short term wetting and which they are made. It is now
as their temperature varies, or as drying generally accepted that the rate of
they are loaded or unloaded. Some All masonry units expand on expansion diminishes with time
materials (such as concrete and wetting and contract on drying, and can be accurately represented
cement products) shrink as they but these changes are usually not by a linear relationship with the
dry out after being placed in sufficient to require consideration logarithm of time.
position in a building and shrink in clay brickwork.
further as they cure. Clay bricks Experience shows that if control
6.1.3 Long term permanent gaps are provided, with widths
expand slowly over a long period of
expansion calculated on the basis of the
time. When different materials are
Expansion of fired clay units begins coefficient of expansion of the
used together, their different
as soon as they have cooled after particular brick used in the
responses to changing loads,
firing and takes place in all three structure, stresses due to the
temperatures and moisture
directions. This expansion is due to restraint of further growth are
contents will lead to size
reaction with moisture and is unlikely to cause distress during
differences between them. The
sometimes referred to as the remaining practical life of
resulting differential movements
‘permanent moisture expansion’. the building.
must be taken into account if
All fired clay products, including
damage to the structure is to be
bricks, are subject to chemical 6.1.4 Coefficient of expansion
avoided and this is done by the
reactions between water and The coefficient of expansion is an
provision of movement gaps
certain of their constituent estimate of the amount bricks will
between parts of the structure.
minerals that cause them to grow in the first fifteen years after
6.1 Dimensional changes in expand. The reactions begin when they are made. Values are
clay masonry units bricks in the kiln cool below about generally lower than they were in
400ºC, they are not hastened by the past because of a better
There are a number of potential wetting and, for practical understanding of the factors
sources of dimensional change in purposes, are irreversible. influencing expansion and better
clay masonry. All except long-term control over the manufacturing
expansion are cyclic, reversible Any atmosphere in which people
can live and breathe contains processes, particularly the firing
changes. temperature. When it is required,
sufficient water to cause clay
brick expansion and neither the the coefficient of expansion for
6.1.1 Thermal
magnitude nor the rate of particular units can be obtained
The thermal expansion of clay
expansion is measurably changed from the manufacturer.
bricks varies slightly depending
upon their colour and the method when bricks are used internally Coefficient of expansion is now
of manufacture, but the value is rather than externally. However, given the symbol em, but it was
unlikely to be greater than total movement is made often formerly referred to simply
0.008 mm/m/ºC. Thermal appreciably less by the absence of as the 'e' value. The value is
expansion can be taken into significant temperature changes determined by subjecting a brick
account in calculating the and, consequently, gaps to fresh from the kiln to saturated
spacings of movement gaps in accommodate movements are steam at atmospheric pressure.
external brickwork (see later) but often not required in internal This expansion has been shown to
no particular account need be walls. correlate well with natural
taken of thermal expansion in expansion over a longer period.
most internal brickwork. The magnitude of long-term The test procedure is given in the
permanent change in the standard test procedures for clay
dimensions of clay bricks (growth) masonry units (AS 4456.11)8.
depends upon the material from
(c) High exceeding 1.6 up to The Masonry Structures Code (a) Temperature movements
2.4 mm/m (AS 3700) includes overall limits The building frame will usually
on joint width and movement but be internal and will remain
However, it must be remembered does not specify a method of comparatively unchanged in its
that: design for gap spacings. Such a temperature. An allowance of
method is outlined in this section. 0.35 mm/m for temperature
• There is no pattern in the movements due to heating and
coefficients of expansion based 6.2.2 Sources of movement cooling of the masonry
on brick colour or manufacturing cladding is recommended, to
method that enables general Masonry units provide for temperature
figures to be produced. Details on how to obtain data on differences of up to 40ºC
the magnitude of growth between the frame and its
• Within a single brick type the (coefficient of expansion) have cladding.
coefficient of expansion can vary been given in Section 6.1.4.
considerably at different It must be remembered that (b) Frame shortening
production times. In some expansion takes place in the Modern framed structures
instances, a halving or doubling height and width as well as the usually have a frame of
of em values has been observed length of the units. reinforced concrete, with high
from bricks sold under the same creep and shrinkage
name but manufactured six Foundation and footing characteristics, and the
months apart. movements masonry cladding is a two-leaf
Uniform movements of the wall with one leaf within the
For these reasons designers should footings of a building should not frame. The outer leaf is
obtain current expansion data for affect masonry walls. However, connected to it only by wire
the particular brick they propose differential movements due to ties across a cavity and is
to use. uneven settlement or moisture carried at floor level by a
change in the foundation can lead concrete nib or steel shelf-
6.2 Design of control gaps to cracking of masonry. Where angle. In these circumstances
6.2.1 General these movements are expected to it is imperative that proper
The common use of reinforced be significant, the structure can be provision be made to
concrete frames in buildings, designed as articulated masonry. accommodate the differences
together with the availability of a In general, the control joints between the movement of the
wider range of bricks, have incorporated by a prudent frame and the cladding, even if
contributed to making the control designer to articulate brickwork the frame is of steel where
of movements more complex than against damage from footing frame shortening is small.
before. Locations and widths of movement can normally also act
control gaps to accommodate as gaps to control movements For reinforced concrete frames
long-term moisture expansion can associated with expansion of the it is possible to use techniques
be determined based on the units. Design of articulated such as those suggested by
characteristic expansion of the masonry is covered in TBA Fintel and Khan9 to calculate
units. In many instances these Manual 7. column shortening for the
gaps will be in the same locations particular building and to use
Sv /2 max.
1/3 to 1/5
wall height Sv Sv
Slip joint at
min. re-entrant
corner
Sv /2 max.
Gaps close to corner to
enable panels to be tied to
the supporting frame
Consideration should also be given If the spacing of vertical gaps is Sv, full-height gaps in the run of wall
to providing control joints at wall the total closure at each gap and parapet would be at around
openings and at changes in wall would be: 16.5 m centres, with an extra gap
thickness (other than for piers, in the parapet half way between
buttresses or other members that each of the full-height gaps.
provide support). where 0.35 mm/m is the
allowance for thermal movement In many instances, it may be
In developing a method for in the wall. convenient to locate gaps at some
calculating the spacing of vertical line or lines occurring on the
gaps, the following notation is If the closure is to be limited to facade, for example behind
used: 15 mm, then: downpipes. Wider spacing than
that calculated might be adopted
Sv = Maximum spacing of vertical with more safety on south and
gaps in walls (in metres). east-facing walls where the
movement from temperature
Svp = Maximum spacing of changes will be less.
vertical gaps in parapets A similar approach to parapets
(in metres). gives: A nearly invisible joint can be
provided at a re-entrant angle by
em = The coefficient of expansion the provision of a straight joint
of the clay unit used in the that permits the long wall to slide
construction (mm/m). For example, consider a clay brick behind the shorter return (see
where em = 1.6 mm/m. Figure 31).
It has been recommended practice
for many years to design spacings Then, Vertical movement
of vertical control gaps in walls Horizontal gaps to control vertical
based on half the 5-year expansion movement are required only in
value. It is known that expansion and buildings where the external leaf
varies with the logarithm of time10 of masonry is non-loadbearing and
and the 5-year expansion is about The first gap in the main wall is supported by a frame or floor
70% of the 15-year expansion (em). should be no more than 8 m from slabs. In these situations, provision
The design movement for walls is the corner and, in the parapet, is required for the shortening of
therefore; 5 m from the corner. However, it is the supporting frame or walls, for
probably best to put the first gap the growth of the clay bricks and
close to the corner and run it for movements associated with
Double this amount is used for through both the wall and
parapets. parapet. Then, for this example,
Δh = closing movement in a
horizontal gap included in a
wall (mm).
Use of biscuit
bricks is NOT
recommended