FUNCTIONAL DESCRIPTION:
The AC drive is equipped with the cooling fan. Cooling air enters the drive through the
air inlets in the door. The direction of the airflow is upwards. The dissipation power of
the switchboard is about 2% of the rated power of the switchboard.
REASONS FOR THE CHANGE:
The manufacturers estimation for the operational time of the cooling fan (2410ML-
05W-B60-EQ5) is about 70 000 hours @ 40 degrees Celsius. The major problems are
caused by the failure of the bearings.
WHERE USED:
ACS800-x1/x4 IP 21, R2 and R2i
ACS800-x1/x4-0001-2 to -0005-2 ACS800-x1/x4/104-0003-3 to ACS800-x1/x4/104-0004-5 to
-0009-3 -0011-5