Name of Project: TAMPIPI Residence

Title : Compliance report


Area : Architectural

Documentary
Description of Non-
Item No. Requirements Evidences/Reference
Conformity
No.
External masonry wall thickness Fire resistive standards of a hollow masonry
1 is less than the requirements for external wall minimum thickness is 150mm in Annex 1.a/Section 603
fire resistive standards. 1hr fire resistance.

Eaves over required windows shall not be less


Eaves over required windows is
2 than 750 millimeters from the side and rear Annex 1.b/Section 704
less than the requirements.
property lines.
Every required exit doorway shall be of a size
as to permit the
Entrance and exit doors width is
3 installation of a door not less than 900 Annex 1.c/Section 1207
lesser than the requirements.
millimeters in width and not less than 2.00
meters in height.

Height from ffl to beam is lesser A residential occumpancy has a maximum


4 Annex 1.d/Section 707
than the requirements. height of 3m above established grade.

The setback of front, side, and


The minimum setback of residential building
5 rear of the building is lesser than Annex 1.e/Section 804
in front, side ,and rear is 4.5m, 2m, and 2m.
the requirements.