You are on page 1of 1

College of Technology of Taif

Bachelor of Electrical Technology


Subject: Power systems control

Correction Example 10B

1. Compute the change in frequency.

PL
   0.001317 pu  0.001317  60  0.07902 Hz
1 1
  D1  D2
R1 R2

f new  60  0.07902  59.92Hz

2. Compute the change in tie flow.

 1 
Ptie     D2   0.0671 pu  0.0671 500  33.6MW
 R2 

3. Compute the change in prime movers powers.


Pmech1    0.13175 pu  0.13175  500  65.87 MW
R1

Pmech 2    0.06587 pu  0.06587  500  32.93MW
R2