Professional Documents
Culture Documents
Modelling and Performance Prediction of
Modelling and Performance Prediction of
DOI 10.1007/s12273-013-0104-0
Research Article
Vahid Vakiloroaya1 (), Jafar Madadnia1, Bijan Samali2
1. Center for Built Infrastructure Research, School of Electrical, Mechanical and Mechatronic Systems, University of Technology Sydney, PO
Box 123, Broadway, Sydney, NSW, 2007, Australia
2. Center for Built Infrastructure Research, School of Civil and Environmental Engineering, University of Technology Sydney, PO Box 123,
Broadway, Sydney, NSW, 2007, Australia
Abstract Keywords
The aim of this paper is to explore methods to reduce the energy consumption of a central cooling central cooling plant,
plant. To achieve this, we have developed a new design for heating, ventilating and air conditioning design improvement,
(HVAC) efficiency improvement. A storage tank together with an immersed heat exchanger is energy saving,
installed in the discharge line between the compressor and condenser. The heat exchanger uses the modelling,
make-up water of the cooling tower to reduce the refrigerant temperature entering the condenser. performance prediction
To investigate the potential of energy savings, we used a real-world commercial building with a
central cooling plant, located in a hot and dry climate, for our case study. The energy consumption
Article History
Received: 4 October 2012
and relevant data of the existing central cooling plant were acquired over the course of a typical
Revised: 2 December 2012
week in summer. The integrated system has been modeled and analyzed to achieve energy
Accepted: 18 December 2012
conservation. The performance of the proposed cooling system was simulated using a transient
simulation software package. Comparison of the proposed system with existing cooling plant is
© Tsinghua University Press and
included in this paper to demonstrate the advantages of our new configuration. Results show that
Springer-Verlag Berlin Heidelberg
up to 18% power saving can be obtained by using our design.
2013
List of symbols
pump could work at higher coefficient of performance. Jeon CO2. Their results demonstrated that the new proposed
et al. (2010) analyzed the performance of a hybrid cooling system can meet the year-around cooling and heating
system that combines a screw water chiller with a ground demand. However, no research has been done on whether
source heat pump. Their results showed that the hybrid the performance of a vapor comparison central cooling plant
cooling system was able to stably provide the required cooling (CCP) is improved if the storage tank is installed after its
capacity at high-load conditions. A hybrid air conditioning compressor to reduce the refrigerant temperature using the
plant obtained by combining an air dehumidification make-up water of the cooling tower. This modified design
system that uses a hygroscopic solution and hydrophobic is the focus of our study.
mamberanes with an inverse cycle vapor compression This study provides a new design for the vapor com-
device was analyzed by Bergero and Chiari (2011). Their pression air conditioning systems to increase the refrigeration
results showed that up to 60% power saving was possible system’s overall efficiency. Sub-cooling increases the system’s
based on indoor latent load conditions. Deng et al. (2012) efficiency by reducing compressor power and increasing
evaluated the performance of the hybrid solar-assisted CO2 the system’s refrigeration effect. Simply stated, sub-cooling
heat pump in which a solar thermal driven absorption chiller lessens the amount of energy that is required to operate a
was combined with the heat pump. In their system, a gas refrigeration system and, therefore, results in a cost saving
cooler was located between the compressor of the heat pump for the operator. There are various traditional methods to
and evaporator of the chiller to decrease the temperature of achieve sub-cooling, all of which require additional power
Vakiloroaya et al. / Building Simulation 3
and thus result in additional system costs. In this study, the higher sub-cool temperature after the refrigerant passes
make-up water of the cooling tower is used to reduce the through the water-cooled condenser, significantly increasing
temperature of the superheated refrigerant gas before it the overall system coefficient of performance.
enters the condenser. In this system, the make-up water of
the cooling tower is first used to reduce the refrigerant 2 System description
temperature entering the condenser: a horizontal cylindrical
storage tank, together with an immersed heat exchanger, The schematic of the central cooling system with integrated
is used to reduce the temperature of refrigerant through water storage tank is shown in Fig. 1 and its operation cycle
the energy transfer between the superheated refrigerant is shown in Fig. 2. As detailed above, the system comprises
vapor and make-up water of the cooling tower. The cooled a water-cooled screw chiller, an open circuit cooling tower,
refrigerant then enters the condenser where an additional heat an air-handling unit, chilled water and condenser water
reduction occurs. As a result, the refrigerant temperature pumps, water storage tank with its immersed heat exchanger,
leaving the condenser decreases and the refrigerant subcool valves and connection tubes. The cycle starts with a mixture
temperature increases resulting in energy savings of 5%–18%. of liquid and vapor refrigerant entering the evaporator
An exact figure is dependent on the condensing and (point 1). The heat from the water returning from the
evaporator temperatures of the individual’s refrigeration air-handling unit is absorbed by the evaporator coil. During
system. this process, the state of the refrigerant changes from a
The objective of this project is to minimize the energy liquid to a gas and becomes superheated at the evaporator
consumption of building cooling systems while still satisfying exit. The superheated vapor enters the compressor (point 2),
occupant comfort conditions. For this purpose, we used the where increasing pressure raises the refrigerant temperature.
central cooling plant of a real-world commercial building A storage tank together with a serpentine tube heat exchanger
located in a hot and dry climate. Field tests were conducted installed after the compressor uses the cooling tower’s
to quantify and determine the operational variables of the make-up water to cool down the refrigerant. The refrigerant
central cooling plant. First, the mathematical model of the from the compressor goes through the copper coil inside
system components and assumptions at which the study the tank and undertakes a heat exchange (point 3). In this
was undertaken were developed. New modules for the design, temperature of high pressure superheated refrigerant
proposed system were developed by using collected gas can be decreased by exchanging heat with the make-up
experimental data and were implemented in the transient water of the cooling tower. A storage tank is located in the
tool using a FORTRAN code. An iterative numerical discharge line between the compressor and condenser for
procedure was used to solve simultaneous heat transfer this purpose. The incoming cold water is generally between
equations for the various system components. The 20℃ and 30℃ depending on the time of the year and the
experimental results were then compared with the geographical location. The make-up cold water then passes
theoretical prediction from the mathematical model of through the storage tank and thus reduces the temperature
the system to ensure that it can be used for the intended of refrigerant entering the condenser. This results in a more
purpose. Because of the nonlinear, time-varying and substantial sub-cooling at the condenser outlet and therefore
building-dependent dynamics of the system, the transient reductions of refrigerant temperature entering the evaporator,
software package, TRANSYS 16, was used to simulate and enhancing the system refrigeration effect and, in turn, its
predict the energy usage on an hourly and sub-hourly basis coefficient of performance (COP). On the other hand, this
for the building using the HVAC system. On the basis of modification reduces the refrigerant temperature leaving
mathematical models and by using test data, simulation the condenser by pre-cooling the refrigerant before it
modules for the central cooling plant were developed goes through the condenser for the final heat rejection. The
and embedded for the building. The system integration additional pre-cooling of the refrigerant then results in higher
encompassed the water-cooled screw chiller, the counter flow sub-cooling temperature at the condenser outlet and thus
cooling tower, the air-handling unit and the storage tank reduction of refrigerant temperature entering the evaporator.
with immersed heat exchanger. The energy consumption of The pre-cooling of the refrigerant means de-superheating the
the existing central cooling plant in the building was refrigerant entering the condenser using make-up water to
measured in a typical week of summer to compare the reduce its temperature below the condensation point at the
project data with the simulation results in order to analyze corresponding vapor pressure after the condenser resulting in
the performance and feasibility of the proposed newly- higher sub-cooling temperature at the condenser outlet.
configured system. Results demonstrated that the benefits After leaving the storage tank, the refrigerant undergoes
of the new design lie in the system’s ability to operate at a a further temperature reduction in the condenser, causing
4 Vakiloroaya et al. / Building Simulation
where hfg,w is the latent heat of the evaporation of the water 3.3 Rotary compressor
vapor and Tw is the mean temperature of the cooling tower
water. In a cooling tower, water enters the sump reservoir Since the compressor can reach operating speed instant-
from a water make-up source and operating tower cells. aneously, its transient characteristics can be neglected (Chen
The level of the sump is assumed to be constant in this and Deng 2006) and thus it can be modelled using algebraic
study because of its negligible effect on the cooling tower equations (Diaz 2007). Therefore, the compressor is modelled
performance. Therefore, the flow of the water make-up will with the use of an iterative procedure described by the
be equal to the total water loss from the cells. Furthermore, following equations for the polytropic work input to the
the water volume of the sump is assumed to be fully-mixed in compressor, the refrigerant mass flow rate of the compressor
all the cells so that the energy balance can be expressed as and the refrigerant enthalpy at the compressor exit. The
compressor mass flow rate is given by
dTsump é N cell ù
M w,ct = ê å( m w,o,ct (Tw,o,ct - Tsump ) )k ú VDηv
dt êë k =1 úû m r = (6)
vsuc
é N cell ù
+ ê m w,i,ct - å (m w,o,ct )k ( Tm,o,st - Tsump ) ú (2)
( )
ê ú The work input to the compressor is given by
ë k =1 û
where Ta,o,tp is the air temperature leaving the two-phase zone dTa,cc Tsup - Ta,i,cc
and can be calculated from (
ρaVsup Cp,a
dt
+ Cp,a (vel )a
l
= -Qcc) (25)
Vakiloroaya et al. / Building Simulation 7
In the steady-state condition, Tw,cc and Ta,cc are constant year. The data file distributed with TRNSYS 16 is generated
and thus by employing the method proposed in (Wang et using “Meteonorm” including Synthetic hourly weather data.
al. 2004), the cooling coil capacity can be obtained as The hourly meteorological data used in this study include
information about the month of the year, hour of the month,
b0Cp,w m sup
Qcc = ( Tsup - Tw,o,cc ) (26) direct normal solar radiation, global solar radiation, dry-bulb
m sup temperature, humidity ratio, and wind speed.
1 + b1( )
m w,cc The central cooling plant installed in the building consists
of one water-cooled chiller, one cooling tower, one air-
where coefficients b0 and b1 can be determined from the handling unit, two chilled water pumps, and two condenser
data set collected experimentally. The advantage of the heat water pumps. The chiller has two screw compressors, each
transfer model for the cooling coil expressed in Eq. (26) is with a nominal capacity of 175 kW, and uses refrigerant
that in this model no geometric data of the cooling coil are R407C. For the shell and tube evaporator, the evaporator
required. In order to estimate their values, a large number temperature is set to be 4℃. The temperature of the supply
of data points are required, often more than those given in chilled water is taken at 7℃ at design conditions. The chiller
typical product catalogs and should be determined by real- comprises two refrigeration circuits in parallel in which
world test data. each circuit includes one thermostatic expansion valve and
Finally, a quadratic form for the air-handling unit VAV one screw compressor. The chiller can operate down to about
fan is proposed to represent the total power consumption
10% of its rated full load capacity via a modulating slide valve
in terms of the supply air temperature Tsup and chilled water
in the compressor. The design airflow rate and the electric
temperature Tw,o,ch:
power input of variable speed cooling tower fan at maximum
airflow rate are 10.4 kg/s and 1.5 kW, respectively. The
Eahu,f = c0 + c1Tw,o,ch + c2Tw,o,ch
2
+ c3Tsup design airflow rate of the air-handling unit with variable air
+ c4Tsup
2
+ c5Tw,o,chTsup (27) volume fan is 13.5 kg/s and its rated power input is 12.8 kW.
The design water flow rate and electric power of each chilled
where coefficients c0 to c5 are constant and can be determined water pump is 11.4 kg/s and 1.7 kW, respectively. The design
by regression of the field-test data collected. water flow of the condenser water pump is 13.8 kg/s and its
electric power is 2.3 kW. All circulator pumps operate at a
4 Case study constant speed. Photos of the screw chiller, air-handling
unit, and cooling tower are in the Electronic Supplementary
The simulation object is a commercial building together Materials (ESM1, ESM2 and ESM3) of this paper.
with its central cooling plant. The gross floor area of the
building is 2500 square meters and the usable floor area is 4.1 Experimental rig
1700 square meters. The building is three meters high. The
ground area to be occupied by the building is rectangular In order to determine the variables of the cooling system, a
in shape and stands in south-north direction. The building number of tests under different running conditions were
is open from 8:00 a.m. to 10:00 p.m. The walls, windows, conducted. The test field procedure has been carried out
floor and roof are modeled according to ASHRAE transfer on-site. The cooling tower and air-handling unit are located
function approach. The occupant density in the building is outside close to the building and the cooled air is carried
about one person per 5 m2 and the associated heat gain is to the building using the ducting system. High precision
95 W and 90 W for sensible and latent loads, respectively. sensors/transducers were used for measuring all operating
The mechanical ventilation rate for acceptable indoor air variables. Manometers were used for obtaining supply
quality is two air changes per hour (ACH). The infiltration is airflow rate readings. The temperature sensor for supply air
selected to be 1.5 ACH. Lighting power density is 20 W/m2, is of platinum resistance type with ±0.1℃ accuracy. Water
a common value used in practice for a commercial building. temperatures were measured by mercury thermometers
We assume the heat gain from the lights is 40% convective. of ±0.2℃ precision. Five platinum resistance thermometers
The equipment load inside the building is taken as 16 W/m2, of PT100 type with a calibrated accuracy of ±0.5℃ for a
corresponding to a medium load type. The clothing factor temperature range from –50℃ to +260℃ are used to
for people in the building is specified as 0.5 clo and relative measure the refrigerant temperature before and after of
air velocity is fixed at 0.1 m/s. The metabolic rate is 1.2 met each component. These sensors are in direct contact with
and no external work is assumed. The weather data that drive the refrigerant to achieve high accuracy.
the project simulations are based on a typical meteorological Two pressure transmitters with a calibrated accuracy of
8 Vakiloroaya et al. / Building Simulation
1% are respectively installed in suction line and discharge is compliant with the requirements of the ANSI/ASHRAE
line. The measuring range for pressure transmitter located Standard 140 (2007). The model included a subroutine to
in suction line is between zero to 2000 kPa and for pressure evaluate the thermodynamic properties of the refrigerant
transmitters located in discharge line is zero to 3500 kPa. R407C. This simulation code was then used to calculate the
Powers of components were measured by a digital AC/DC parameters of main interest such as the temperature of
power clamp multimeter of ±3.5% tolerance. refrigerant leaving the DX evaporator, compressor, water
All of temperature sensors, pressure transmitter, and storage tank, air-cooled condenser and expansion valve as
power clamp multimeter are integrated with a computer well as water temperature in the water storage tank. The idea
based data-logger. Therefore the data of system power is to compare the behavior of the models with the observed
consumption and other variables were logged for each behavior of the real system.
ten-minute period. Then the variables were stored and The module of the screw chiller has been developed
arranged in database files so that the process performance to consider its different components separately. For this
can be assessed using the proposed approach. purpose, the aforementioned mathematical model for each
part of the chiller, i.e., evaporator, compressor, condenser,
5 TRNSYS development expansion valve, and water storage tank are coded and
implemented on the chiller module using FORTRAN. In
The mathematical model of the system components is this module, a numerical algorithm is embedded to call the
coded into the fully integrated visual interface known as determined parameters from the first component (evaporator)
TRNSYS simulation studio using FORTRAN. Under real and transfer them respectively to the next component in
conditions there are many factors that can influence the each iteration. To begin the simulation, the program reads
HVAC system performance. In this study, all dimensions the first set of operating data, such as the evaporative and
of the system components and the dimension of connected condensing pressure of the refrigerant and the temperature
pipes are included in program code. The experimental of superheated refrigerant vapor leaving the evaporator.
obtained data were entered through a dedicated visual The enthalpy and temperature of the refrigerant leaving the
interface. The simulation information flow diagram is shown evaporator are calculated by using the evaporator model. The
in Fig. 3, where the icon “commercial building” involved the algorithm continues until all enthalpies and temperatures
building information file has been created by PREBID and of refrigerant are collected after it travels through each
Fig. 3 Central cooling plant simulation information flow diagram in TRNSYS workspace
Vakiloroaya et al. / Building Simulation 9
component of the system. In each iteration, the compressor operated continuously from 8:00 a.m. to 10:00 p.m. Only 12%
work, refrigerant sub-cool temperature and power con- of the total predicted data deviate from the actual data by
sumption of each component are calculated and stored in a more than 10% and all of modeled data have a prediction
separate file. These data are then compared with the error of less than 15%, as shown in Fig. 4.
conventional central cooling plant to measure comparative
system efficiency.
refrigeration effect h2 - h1
RMSE COP = = (32)
CV = ´100% (31) compressor work h3 - h2
y data,m
From Eq. (32), it is clear of two possible modifications to
where N is the number of collected data, ypred,i is the improve the system performance, namely, by increasing the
predicted variable, ydata,i is the measured variable and ydata,m refrigeration effect or decreasing the compressor power. In
is the average value of the measured variables. this study, as the refrigerant temperature in the condenser
The integrated simulation tool was validated by comparing outlet drops, the refrigerant temperature in the evaporator
the predicted and measured power consumption of the inlet also drops and the enthalpy of the refrigerant entering
chiller for the first week of July, during which the chiller the evaporator is lowered. This reduction allows the
10 Vakiloroaya et al. / Building Simulation
air conditioning system is significantly less than the power efficiency due to the higher refrigeration effect in the direct
usage of conventional plant. expansion evaporator which allows for a performance gain.
Thus, the new design is promising for an improvement of
the system performance while fulfilling the cooling demand
with guaranteed energy efficiency. The modified system can
save electricity up to 18%.
References
Fig. 7 Central cooling plant average monthly power consumption
ANSI/ASHRAE Standard 140 (2007). Standard method of test for
6.1 Effect of storage tank area variation the evaluation of building energy analysis computer program.
Atlanta, USA: American Society of Heating, Refrigeration and
Figure 8 shows the variation of the system energy con- Air-Conditioning.
sumption as a function of the water storage tank volume Beghi A, Cecchinato L (2011). Modelling and adaptive control of
for summer. From this figure it can be seen that with the small capacity chillers for HVAC applications. Applied Thermal
increasing storage tank volume and therefore the amount Engineering, 31: 1125 1134.
of the make-up water, the electricity usage decreases quite Bergero S, Chiari A (2011). On the performance of a hybrid air-
rapidly initially and then more slowly subsequently. It is conditioning system in different climatic conditions. Energy, 36:
interesting to note that the storage tank volume greater than 5261 5273.
50 m3 does not have influence on the system energy usage. Chen W, Deng S (2006). Development of a dynamic model for a DX
VAV air conditioning system. Energy Conversion and Management,
47: 2900 2924.
Diaz G (2007). Controllability of cross-flow two-phase heat exchanger.
International Journal of Heat and Mass Transfer, 50: 4559 4567.
Deng S, Dai YJ, Wang RZ (2012). Performance study on hybrid solar-
assisted CO2 heat pump system based on the energy balance of
net zero energy apartment. Energy and Buildings, 54: 337 349.
DoE (2001). Energy Information Administration, Table US-1, Electricity
consumption by end use in U.S. households. U.S. Department of
Energy.
Fig. 8 Variation of the system power consumption versus storage DoE (2006). Energy Information Administration, International Energy
tank area Outlook. U.S. Department of Energy.
Huang G, Wang S, Xu X (2009). A robust model predictive control
strategy for improving the control performance of air-conditioning
7 Conclusions
system. Energy Conversion and Management, 50: 2650 2658.
IEA (2008). International Energy Agency, Online Energy Statistics,
In this paper a new configuration for the central cooling
Energy Balances. Available at http://www.iea.org/stats/.
plant has been developed, successfully demonstrating a
Jeon J, Lee S, Hong D, Kim Y (2010). Performance evaluation and
significant improvement in the system performance. In this modeling of a hybrid cooling system combining a screw water
design, a storage tank is implemented in the discharge line chiller with a ground source heat pump in a building. Energy, 35:
between the compressor and condenser. The storage tank 2006 2012.
uses the make-up water of the cooling tower to reduce the Jin GY, Cai WJ, Wang YW, Yao Y (2006). A simple dynamic model
temperature of refrigerant entering the condenser. The of cooling coil unit. Energy Conversion and Management, 47:
performance of the proposed system is then analyzed by 2659 2672.
using a well-validated building transient simulation code. Kusiak A, Xu G, Tang F (2011). Optimization of an HVAC system
The experimental results for the newly-configured system with strength multi-objective particle-swarm algorithm. Energy,
demonstrated that the new design delivers higher system 36: 5935 5943.
12 Vakiloroaya et al. / Building Simulation
Lee TS, Lu WC (2010). An evaluation of empirically-based models for a carbon dioxide transcritical vapor compression cycle refrigeration
predicting energy performance of vapor-compression chillers. system. Master degree thesis, Maryland University, USA.
Applied Energy, 87: 3486 3493. Soylemez MS (2004). On the optimum performance of forced draft
Lin JL, Yeh TJ (2007). Modeling, identification and control of air- counter flow cooling towers. Energy Conversion and Management,
conditioning systems. International Journal of Refrigeration, 30: 45: 2335 2341.
209 20. Stene J (2005). Residential CO2 heat pump system for combined space
Mortada S, Zoughaib A, Clodic D, Arzano-Daurelle C (2012). Dynamic heating and hot water heating. International Journal of Refrigeration,
modeling of an integrated air-to-air heat pump using Modelica. 28: 1259 1265.
International Journal of Refrigeration, 35: 1335 1348. Tashtoush B, Moihim M, Al-Rousan M (2005). Dynamic model of an
Mossolly M, Ghali K, Ghaddar N (2009). Optimal control strategy for HVAC system for control analysis. Energy, 30: 1729 1745.
a multi-zone air conditioning system using a genetic algoruthm. Wang YW, Cai WJ, Soh YC, Li SJ, Lu L, Xie L (2004). A simplified
Energy, 34: 58 66. modeling of cooling coils for control and optimization of HVAC
Schoenfeld JM (2008). Integration of a thermoelectric subcooler into systems. Energy Conversion and Management, 45: 2915 2930.