Professional Documents
Culture Documents
03244
MFR–11
Multi Function Relay
Mains Protection
APPLICATIONS DESCRIPTION
The MFR Series 1 is a family of The Multi Function Relay MFR–11 features
• True RMS sensing
microprocessor based protective relays & functions include: • Digital input for
that offer multiple protective features in a
blocking or remote
single package. • Microprocessor based design.
• Adjustable trip set points acknowledgement
Using a new digital procedure to measure
• Adjustable time delays for each function • Discrete Out
rms values – enabling a high measuring
• Front panel programmable
accuracy – the MFR Series 1 is insensitive permissive
• Programmable relays outputs
to harmonics, transients or disturbing
pulses.
• Two-line display • PC configurable
and Front panel
The MFR–11 is equipped with a DIN MFR–11 / MP
housing for front installation (front
configurable
Protective Functions
protection IP 54) or for snap on rail
• Over Voltage relay (59)
• Phase/phase or
installation. This simplifies the design of
• Under Voltage relay (27) phase/neutral
the switchgear cabinet, facilitates the
commissioning, ensures that the operation • Over frequency (81O) monitoring
• Under frequency (81U)
of the system is user friendly and
• Voltage asymmetry (47) • Microprocessor
increases the overall availability of the
technology for
system.
MFR–11 / G59 accurate,
Protective Functions repeatable and
U, f
MCB
• Over Voltage relay (59) reliable operation
• Under Voltage relay (27) • Programmable
• Over frequency (81O)
3
Switch • Under frequency (81U)
relay outputs
OFF
alternatively
• Voltage asymmetry (57) • Programmable two
Binary • Phase Shift monitoring (78)
control signals
Switch step threshold set
MFR 11 OFF GCB • df/dt (rocof) (81RL)
points with
individual time
delays
PLC
Controller G
PART NUMBERS AND OPTION PACKAGES
MFR–11 /MP
MFR 11 /G59
OPTION DESCRIPTIONS
Option Description
U Over-/Under voltage, Over-/Under frequency, and voltage asymmetry monitoring
DIMENSIONS
Front view
Parameterizing plug
35
72
65
27
Parameterizing plug
1 16
96
90
130
• Current.......................................................................................metallically separated
- Current-carrying capacity....................................................................................4.0 × IN
- Power consumption ........................................................................................< 0.15 VA
- Rated short time current (1 s).............................. [../1 A] 100.0 × IN ,[../5 A] 20.0 × IN
MFR–11/MP MFR–11/G59
01/08/F