Coordinaide™-The S&C Protection and Coordination Assistant 250 Kva
Coordinaide™-The S&C Protection and Coordination Assistant 250 Kva
Connection: Delta-Grd.Y
Primary_kV/Full Load Amps: 33/4.37
Secondary_kV/Full Load Amps: 13.2/10.93
Xfmr Rating: 250kVA
Impedence: 5%
Phase-Grd. Fault Current: 40000A
Phase-Grd. TPI: 362%
3-Phase Fault Current: 87.29A
3-Phase TPI: 3917%
Magnetizing Inrush:
@ .01 Second = 109.35A
@ .10 Second = 52.49A
Cold-Load Pickup Inrush:
@ 1 Second = 26.24A
@ 10 Seconds = 13.12A
@ 900 Seconds = 8.75A