You are on page 1of 1

General Information Device #1 Device #2 Device #3 Device #4 Results Help

(Click on [Results] to exit this page) - (9/8/2016 10:44:34 AM)


Device#1(Source) Device#2 Device#3 Device#4(Load)

Date: 9/8/2016 10:44:34 AM

System Voltage: 33kV


Available Fault Current: 40000.A

1) DEVICE# 1: Fuse Link

Manufacturer: Cooper (Kearney)


Speed: K
Ampere Rating: 6K

2) DEVICE# 2: Transformer (Damage Curve)

Connection: Delta-Grd.Y
Primary_kV/Full Load Amps: 33/4.37
Secondary_kV/Full Load Amps: 13.2/10.93
Xfmr Rating: 250kVA
Impedence: 5%
Phase-Grd. Fault Current: 40000A
Phase-Grd. TPI: 362%
3-Phase Fault Current: 87.29A
3-Phase TPI: 3917%
Magnetizing Inrush:
@ .01 Second = 109.35A
@ .10 Second = 52.49A
Cold-Load Pickup Inrush:
@ 1 Second = 26.24A
@ 10 Seconds = 13.12A
@ 900 Seconds = 8.75A

3) DEVICE# 3: Fuse Link

Manufacturer: Cooper (Kearney)


Speed: K
Ampere Rating: 15K

4) DEVICE# 4: Not Selected