M35 Series
Safety Exhaust (Dump)
Control Reliable Double Valves
with or without EEZ-ON® (Soft-Start) Module
Operating Instructions
Pinouts - Solenoid
A C D
1 1 1
Sol B Sol A Sol B Sol A
2 5 4 2 5 4 2 5 4
Sol B + + Sol A + +
3 3 3
- - -
Pressure
1 Sensors
Pressure
Sensors
Pinouts - Pressure Sensor Sensor B
+
Sensor A
+
2
1
Sensor B Sensor A
2
+ +
A B C
+ - -
+ - -
1 + 1 + + 1 +
2 5 4 2 5 4 2 5 4
Sensor A
3
Sensor B Sensor A
-
3
-
-
Sensor B Sensor A
-
3
-
-
Sensor B
Application Examples
M35 Series Dump Valve
without Soft Start Flow Control
Pressure
Gauge
PRODUCT LABEL IDENTIFICATION
3
4 2
2
51 3
1
www.rosscontrols.com
Dual PO
M35 Series Dump Valve Check Valve Flow Control
with Soft Start
Pressure
Gauge
3 3 1 3 2
1 2 2
1
M35 Series Soft Start Adjustment - Flow vs Number of Turns and Inlet Pressure
DIMENSIONAL DRAWINGS 6000 220
D SI (4 LED'S)
N Liters/min
SCFM
C EXH
IN 3000 100
OUT EXH
C
IN 2000 80
OUT
A A
1000 40
F
F
0 0
0 2 4 6 8 10
E Turns (counterclockwise)
B
SSA E 30 psig (2 bar) 60 psig (4 bar) 90 psig (6 bar) 115 psig (8 bar) 145 psig (10 bar)
B
With EEZ-ON® Without EEZ-ON® Exhaust Time – Normal and Faulted Conditions (s)
Flow Rates module module
Operating Pressure
Port Basic CV Dimensions - Inches (mm) Volume Normal
Soft-Start or 30 psig (2 bar) 90 psig (6 bar) 145 psig (10 bar)
Size Size 1-2 2-3 A 10.31 (261.9) 7.03 (178.5) ft3 (L) to 15 psig to 7 psig to 15 psig to 7 psig to 15 psig to 7 psig
Faulted
1/2 8 With 4.1 7.5 B 4.30 (109.3) 4.30 (109.3) (1 bar) (0.5 bar) (1 bar) (0.5 bar) (1 bar) (0.5 bar)
C 3.73 (94.7) 3.73 (94.7) N 0.055 0.071 0.094 0.112 0.120 0.135
1/2 8 Without 4.3 7.5 0.071 (2)
D 0.64 (16.3) 0.64 (16.3) F 0.072 0.098 0.147 0.183 0.200 0.247
3/4 8 With 4.1 7.5
E 1.44 (36.5) 1.44 (36.5) N 0.131 0.208 0.317 0.393 0.424 0.507
3/4 8 Without 4.3 7.5 0.35 (10)
F 0.185 0.301 0.533 0.710 0.789 1.024
F 6.39 (162.3) 3.11 (79.0)
N 0.226 0.379 0.597 0.746 0.804 0.971
IN Inlet 0.71 (20)
F 0.326 0.555 1.016 1.368 1.526 1.997
OUT Outlet
N 0.416 0.721 1.155 1.451 1.564 1.899
EXH Exhaust 1.41 (40)
F 0.608 1.063 1.983 2.685 3.000 3.941
SI Status Indicator N 1.462 2.604 4.227 5.326 5.743 7.006
SSA Soft-Start Adjustment 5.30 (150)
F 2.160 3.855 7.298 9.929 11.107 14.635
2 www.rosscontrols.com
ROSS EUROPA GmbH • Robert-Bosch-Strasse 2 • D-63225 Langen ROSS EUROPA GmbH • Robert-Bosch-Strasse 2 • D-63225 Langen
Telefon: (06103) 7597- 0 • Fax: (06103) 74694 • e-mail: info@rosseuropa.com • www.rosseuropa.com Telefon: (06103) 7597- 0 • Fax: (06103) 74694 • e-mail: info@rosseuropa.com • www.rosseuropa.com
Sitz: Langen • AG: Langen, B412 • Geschäftsführer: Ralf W. Dinkel Sitz: Langen • AG: Langen, B412 • Geschäftsführer: Ralf W. Dinkel
www.rosscontrols.com
Declaration of CE Conformity CE-Konformitätserklärung
(Translation from German-language Original) (Originalfassung)
Dietrich Warmbier
M35 Series Operating Instructions
Dietrich Warmbier
Global Safety Product Manager Global Safety Product Manager
3
M35 Series Operating Instructions
4 www.rosscontrols.com
M35 Series Operating Instructions
Common cause failures can cause loss of the safety function, especially in dual channel • Supply the proper voltage as overvoltage situations can result in solenoid burnout.
circuits where both channels could fail simultaneously due to a single event. • Make sure that the silencer’s flow capacity is not restricted as this could affect
• Maintain compressed air quality, e.g., filtration, pressure regulation, lubrication. system performance.
• Avoid compressor oils that can cause valve seals to swell, soften, or otherwise • If required, replace the silencer with high-flow, non-clogging silencers, available
deteriorate. from ROSS®
• Operate within prescribed temperature limits.
• Install the valve such that the normal stroke travel of the valve elements are 7. Assembly and Installation
perpendicular to the main direction of machine vibration and/or mechanical shock.
• Do not use a test pulse longer than allowed by the Technical Specifications.
• Avoid external magnetic fields.
CAUTIONS
• Do not plug the valve exhaust port. Risk of injury due to installation while pressurized or with live parts!
• Use only high-flow, non-clogging silencers, available from ROSS®. Installation while pressurized or with electrical power switched on can result in
injuries due to sudden pressure build-up or electric shock.
6.1.3. Diagnostic Coverage
ff De-energize and de-pressurize the relevant system parts before installing the valves.
A diagnostic coverage of 99% is achievable through appropriate integration of the M35 ff Secure the system to prevent it being switched back on again.
Series valve into the safety control system. The monitoring system must check for the
proper change of state of each valve pressure sensor (S1 & S2) with each change ATTENTION
of state of the safety control system outputs to the valve solenoids (Sol 1 & Sol 2).
Detection of a fault by the safety control system must trigger a shut-off of the safety Destruction of components!
controller’s outputs to the valve solenoids (Sol 1 & Sol 2), see section 8. Chemical substances can damage the surface, the markings and the seals of the device.
ff Install the valve such that it is protected against the effects of chemicals.
6.1.4. Fault Modes Damage to the device through storage at incorrect temperatures!
Note that normal operation requires that Sol 1 & Sol 2 be energized simultaneously The storage temperature represents the permissible ambient temperature and de-
for switching the M35 Series valve on, and de-energizing both Sol 1 and Sol 2 pends on the type of valve in question.
simultaneously for switching the M35 Series valve off. Faults that could occur during ff Observe the temperature information in chapter 10 “Technical Specifications.”
normal operation:
Sol 1 & Sol 2 energized simultaneously 7.1. Mechanical Installation
S1 ON, S2 OFF
If attaching to an installed ROSS MD3TM or MD4TM Air Preparation Unit, use (2) ROSS
S1 OFF, S2 ON
connection clamps. If installing as a stand-alone unit, use either (2) ROSS connection
S1 OFF, S2 OFF
clamp and bracket sets or install fittings directly into the inlet and outlet ports.
Sol 1 & Sol 2 de-energized simultaneously Visit www.rosscontrols.com for more information.
S1 ON, S2 OFF
S1 OFF, S2 ON 7.2. Pneumatic Installation
S1 ON, S2 ON
Connect the compressed air supply to port 1. Connect port 2 to the downstream
6.1.5. Foreseeable Misuse portion of the circuit.
www.rosscontrols.com 5
M35 Series Operating Instructions
Failure of the valve to shift synchronously leads to a fault in the M35 Series valve.
This could happen for a variety of reasons, such as:
• Defective piston seals,
• Main valve elements experiencing a switching delay due to dirt or resinous oil,
• Insufficient electrical signals to valve solenoids; suitable voltage not available,
• Receipt of signals at solenoids not synchronous,
• Pilot valves experiencing a switching delay due to damaged components, dirt, or
resinous oil,
• Excessive water build-up in the valve.
11. Disposal
Dispose of the valve in accordance with the applicable statutory regulations in your
country.
6 www.rosscontrols.com
M35 Series Operating Instructions
POWER PRESSES
10. Mechanical power presses and other potentially hazardous machinery using a
pneumatically controlled clutch and brake mechanism must use a press control double
valve with a monitoring device. A double valve without a self-contained monitoring
device should be used only in conjunction with a control system which assures
monitoring of the valve. All double valve installations involving hazardous applications
should incorporate a monitoring system which inhibits further operation of the valve
and machine in the event of a failure within the valve mechanism.
www.rosscontrols.com 7