Professional Documents
Culture Documents
Power up the router with 24VAC power supply, press the service pin
and access the router through FTT10 network then down load
application image to the router and configure it to communicate
with backbone network. Same procedure will be applied to all
routers in each roomBy commissioning the router in each room will
be enable to establish the communication link between rooms,
after completing router commissioning activity for all rooms then
the system will be ready to connect with the MACRO server
Sequence of Operation :
Fume Hood Monitor: Low face velocity alarm status from hood
monitor will send to the controller and via the integration between
LCS and BAS the operator will monitor the alarm.
Exhaust Air Valve (EAV): The exhaust air valve shall modulate with
the Supply air valve and the hood air valve to achieve the
requirements of hood demand and ventilation demand whichever
is higher.
Supply Air Valve (SAV): The minimum supply flow is sized to satisfy
the unoccupied ventilation rate and the maximum supply flow is
sized to satisfy the minimum occupied ventilation requirement,
maximum hood demand and maximum thermal demand. The
supply valve flow command shall be generated by comparing the
minimum ventilation demand, the makeup air for hood demand,
and the cooling demand and selecting the highest of these three
settings.
Temperature Control
https://methodstatementhq.com/method-statement-for-testing-and-commissioning-of-laboratory-air-flow-control-system-fumes-hood-monitoring.html 10/12
4/22/2021 Method Statement For Testing And Commissioning Of Laboratory Air Flow Control System & Fumes Hood Monitoring – Method Stateme…
The Lab Controls system will control the temperature of the space
by measuring the space and/or a duct mounted temperature
sensor(s), comparing it to one or more temperature set points and
A rise in temperature above the room set point flow causes the
supply valve to increase the airflow into the room linearly from
cooling/heating minimum flow setting to cooling maximum flow
setting. Negative or Positive zone pressurization is maintained by
controlling the exhaust valve to a flow equal to the supply valve’s
feedback plus the design offset entering the space [Exhaust Flow =
Supply Flow + (Offset)]. A drop in temperature to the room set
point causes the supply and exhaust valves to decrease flow until
https://methodstatementhq.com/method-statement-for-testing-and-commissioning-of-laboratory-air-flow-control-system-fumes-hood-monitoring.html 11/12
4/22/2021 Method Statement For Testing And Commissioning Of Laboratory Air Flow Control System & Fumes Hood Monitoring – Method Stateme…
Copyright 2011-2021. All rights reserved. Construction method statements and editable project documents. Serving
Construction Industry from 10 years.
https://methodstatementhq.com/method-statement-for-testing-and-commissioning-of-laboratory-air-flow-control-system-fumes-hood-monitoring.html 12/12