Ethernet Connections
If you received this message while trying to connect over Ethernet, verify you have the correct
IP address in the Meter Directory record. If the meter is to assign the IP address, make sure the
IP address is set to 192.168.135.100 and that the switch S2 Position 2 is in the CLOSED
position on the CPU board. If the meter has a fixed IP address, verify the IP address, Subnet,
and Gateway are correct in the meter. Verify your wiring to make sure you have a crossed-over
cable for a direct connection between the meter and the computer. If going through a hub, verify
that the computer and meter are connected to the hub with straight through patch cables.
Pág. 261
For Ethernet Connections: If you are connecting to the meter over an Ethernet port, you should
be able to connect with the same IP address as normal. If this is unsuccessful, the meter may
have defaulted to 192.168.135.100 with a subnet of 255.255.255.0. Make sure your PC has a
compatible address and attempt a connection using this IP address.