VOLTAGE/FREQUENCY

SETTINGS
CHECK THE STARTER IS CONFIGURED TO MATCH SITE
SUPPLY VOLTAGE. IF NOT, SET THE STARTER/MOTOR
PROTECTION DEVICES AS OUTLINED BELOW AND IN TABLE 1

1) TRANSFORMER TAPPING: CONNECT THE TRANSFORMER


(TX1) PRIMARY INPUT TO THE CORRECT TAPPING.

2) EOCR OVER CURRENT SETTING: SET THE OVER CURRENT


(OC) IN THE EOCR-FDM2 OVERLOAD RELAY (REFER TO THE
EOCR-FDM2 PROGRAMMING INSTRUCTIONS IN THE
CUSTOMER DATAPACK).

3) MAIN CIRCUIT BREAKER MAGNETIC TRIP: SET THE


MAGNETIC TRIP SETTING DIAL ON CB1 TO THE CORRECT
VALUE.
Table 1
75KW 380-440V 50Hz, 440-480V 60Hz
MULTI-VOLTAGE SETTING GUIDE
Operating TX1 EOCR-FDM2 CB1 CB1 CB2
Voltage Primary Over Current Magnetic trip Thermal trip Overload
Present On-site Tapping (OC) Setting current current Ith Setting
(Ue) Connection Setting Im Factor Setting
380V / 50Hz 380V 140A 7.8 (1404A) 180A 6.3A
400V / 50Hz 400V 132A 7.3 (1314A) 180A 6.3A
415V / 50Hz 415V 129A 7.2 (1296A) 180A 6.3A
440V / 50Hz 440V 126A 7.0 (1260A) 180A 6.3A
440V / 60Hz 440V 119A 6.6 (1188A) 180A 6.3A
460V / 60Hz 460V 115A 6.4 (1152A) 180A 6.3A
480V / 60Hz 460V 112A 6.2 (1116A) 180A 6.3A
(See note 1)

NOTE 1: ADJUST VR1 SETTINGS TO V min (%Ue) = 94% and V max (%Ue) =
114% FOR 480V ONLY