DSEGenset®

DSE8610 MKII
SPECIFICATIONS

DC SUPPLY
CONTINUOUS VOLTAGE RATING

SYNCHRONISING & LOAD SHARING


5 V to 35 V Continuous

CRANKING DROPOUTS

AUTO START CONTROL MODULE Able to survive 0 V for 100 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is
achieved without the need for internal
batteries. LEDs and backlight will not be
maintained during cranking.
EXPANSION DEVICES
• DSE124 CAN/MSC Extender MAXIMUM OPERATING CURRENT
• DSE2130 Input Expansion 530 mA at 12 V, 280 mA at 24 V

Module MAXIMUM STANDBY CURRENT


• DSE2131 Ratio-metric Input 320 mA at 12 V, 160 mA at 24 V
Expansion Module CHARGE FAIL/EXCITATION RANGE
• DSE2133 RTD & Thermo-couple 0 V to 35 V
Expansion Module GENERATOR & BUS
• DSE2152 Ratio-metric Output VOLTAGE RANGE
Expansion Module 15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
• DSE2157 Output Expansion
Module FREQUENCY RANGE
3.5 Hz to 75 Hz
• DSE2548 LED Expansion
MAGNETIC PICKUP
VOLTAGE RANGE
+/- 0.5 V to 70 V
KEY FEATURES • 2 configurable volt-free relay • Redundant MSC communication FREQUENCY RANGE
• Comprehensive synchronising & outputs wired to CAN ports 10,000 Hz (max)
loadsharing capabilities • 4 configurable analogue/digital • True manual breaker control when
• Built in governor and AVR control inputs in CAN mode INPUTS
DIGITAL INPUTS A TO L
• Base load (kW export) control • Built in sensors to support 0 V to 10 • Water in fuel digital input Negative switching
• Positive & negative kVAr export V & 4 mA to 20 mA • Fuel tank bund alarm digital input
control • 12 configurable digital inputs • Separate ramp up and ramp down ANALOGUE INPUTS A TO D
• Mains (Utility) decoupling protection • Configurable 5 stage dummy load rates configurable via PLC Configurable as:
Negative switching digital input
• 4-Line back-lit LCD text display and load shedding outputs • Configurable CAN message time- 0 V to 10 V sensor
• Multiple Display Languages • CAN, MPU and alternator frequency outs 4 mA to 20 mA sensor
• Five key menu navigation speed sensing in one variant • In-built SNMP 0 Ω to 480 Ω sensor
• LCD alarm indication • Real time clock • Configurable CAN transmit &
OUTPUTS
• Heated display option available • Manual and automatic fuel pump receive OUTPUT A & B (FUEL & StART)
• Customisable power-up text and control • Battery chargers on DSENet® 15 A DC at supply voltage
images • Engine run-time scheduler • Persistent governor & AVR outputs
• DSENet expansion compatibility • Fuel usage monitor and low fuel • Filter generator voltage display OUTPUTS C & D
8 A AC at ­­­250 V AC (Volt-free)
• Data logging & trending facility level alarms • Filter bus voltage display
• Advanced PLC editor • Simultaneous use of all • Inhibit remote start AUXILIARY OUTPUTS E to L
• Protections disable feature communication ports • Power & reactive power control 2 A DC at supply voltage
• Fully configurable via PC using • Remote SCADA monitoring via • Remote start on load demand
BUILT IN AVR GOVERNOR CONTROL
USB, RS232, RS485 & Ethernet various DSE software applications • Configurable engine icons MINIMUM LOAD IMPEDANCE
communication • MODBUS RTU & TCP support with • Alternative load demand schemes 500 Ω
• Front panel configuration with configurable MODBUS pages for • Variable speed generator support Fully isolated
PIN protection integration into building • CAN AVR support
GAIN VOLTAGE
• Power save mode management systems (BMS) 0 V to 10 V DC
• 3 phase generator sensing and • Advanced SMS messaging Fully isolated
protection (additional external modem required)
• Generator current and power • Start & stop capability via SMS OFFSET VOLTAGE
0 V to 10 V DC
monitoring (kW, kvar, kVA, pf) messaging Fully isolated
• kW and kvar overload alarms • 3 configurable maintenance alarms
• Reverse power alarms • Compatible with a wide range of DIMENSIONS
• Over current protection CAN engines, including tier 4 OVERALL
245 mm x 184 mm x 51 mm
• Unbalanced load protection engine support 9.6” x 7.2” x 2.0”
• Independent earth fault protection • Uses DSE Configuration Suite PC
• Breaker control via fascia buttons Software for simplified configuration PANEL CUT-OUT
• Fuel and start outputs configurable • Power modes for when in parallel 220 mm x 160 mm
8.7” x 6.3”
when using CAN with the mains
• 8 configurable DC outputs MAXIMUM PANEL THICKNESS
8 mm
0.3”

STORAGE TEMPERATURE RANGE


RELATED MATERIALS -40 °C to +85 °C
TITLE PART NO. -40 °F to +185 °F
DSE8610 MKII Installation Instructions 053-182 OPERATING TEMPERATURE RANGE
DSE8610 MKII Operator Manual 057-254 -30 °C to +70 °C
-40 °F to +185 °F
DSE8610 MKII PC Configuration Suite Manual 057-238
DSE8610 MKII Data Sheet 055-204 HEATED DISPLAY VARIANT
DSE8610 Data Sheet 055-083 -40 °C to +70 °C
-40 °F to +158 °F

DEEP SEA ELECTRONICS LTD DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com EMAIL sales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com

Deep Sea Electronics Ltd maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-204/06/20 (3)
DSEGenset®

DSE8610 MKII
ENVIRONMENTAL TESTING STANDARDS

ELECTRO MAGNETIC COMPATIBILITY


BS EN 61000-6-2

SYNCHRONISING & LOAD SHARING EMC Generic Immunity Standard for the
Industrial Environment

AUTO START CONTROL MODULE


BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment

ELECTRICAL SAFETY
The DSE8610 MKII is a market- features are included. KEY LOAD SHARE FEATURES: BS EN 60950
Safety of Information Technology Equipment,
leading Synchronising Auto Start Designed to offer increased built • Peak lopping/sharing (with including Electrical Business Equipment
Control Module suitable for use in a in support for active sensors for appropriate DSE mains controller)
multi-generator loadshare system, 0 V to 10 V & 4 mA to 20 mA. • Sequential set start TEMPERATURE
BS EN 60068-2-1
designed to synchronise up to 32 Comprehensive communication • Manual voltage/frequency Ab/Ae Cold Test -30 oC
generators including electronic and and system expansion options are adjustment BS EN 60068-2-2
non-electronic engines. available. • R.O.C.O.F. and vector shift Bb/Be Dry Heat +70 oC
protection
VIBRATION
The DSE8610 MKII monitors the Using the DSE PC Configuration Suite • Generator load demand BS EN 60068-2-6
generator and indicates operational Software allows easy alteration of the • Automatic hours run balancing Ten sweeps in each of three major axes
status and fault conditions, operational sequences, timers and • Mains (Utility) decoupling 5 Hz to 8 Hz at +/-7.5 mm, 8 Hz to 500 Hz
at 2 gn
automatically starting or stopping alarms. With all communication ports • Mains (Utility) decoupling
the engine on load demand or fault capable of being active at the same test mode HUMIDITY
conditions. time, the DSE8610 MKII is ideal for a • Dead bus sensing BS EN 60068-2-30
wide variety of demanding load share • Bus failure detection Db Damp Heat Cyclic 20/55 oC at 95% RH
48 Hours
System alarms are annunciated on applications. • Direct governor and AVR control BS EN 60068-2-78
the LCD screen (multiple language • Volts and frequency matching Cab Damp Heat Static 40 oC at 93% RH
options available), illuminated LED The Advanced PLC tool within • kW and kvar load sharing 48 Hours
and audible sounder.­­ Configuration Suite provides • Dead bus synchronising SHOCK
users with an extremely powerful BS EN 60068-2-27
The event log records 250 events to configuration tool for the most Three shocks in each of three major axes
15 gn in 11 mS
facilitate easy maintenance, and an demanding applications.
extensive number of fixed and flexible DEGREES OF PROTECTION
monitoring, metering and protection PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE


VARIETY OF LOAD SHARE APPLICATIONS
DSE2130
DSE2131 MODEM MODBUS PC
DSE2133
DSE2152 2 12 8 4
DSE2157
DSE2548 232 485

DSENET® RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
+
ETHERNET

DEUTZ DETROIT

DSE8610 MKII MSC


ISUZU
PERKINS
CATERPILLAR
IVECO
JOHN DEERE
LOMBARDINI
MTU SISU
7 VOLVO JCB DIESELMAX
55xx 75xx 8xxx 8xxx MKII
CUMMINS YANMAR
OTHER SCANIA AND OTHERS

BUS VOLT FREE GENERATOR SENSING FUEL & START CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
CURRENT VOLTS D+
+ W/ L

1ph 2 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E/N N

ISSUE 3