Design, simulation and implementation of a UPFC (unified power flow


controller) for transmission line model

Conference Paper · April 2017


DOI: 10.1109/IPACT.2017.8245053

CITATIONS READS

7 904

6 authors, including:

Dilum Hettiarachchi K T M U Hemapala


Curtin University University of Moratuwa
6 PUBLICATIONS   29 CITATIONS    94 PUBLICATIONS   338 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Microgrid Control View project

MicroDrainage View project

All content following this page was uploaded by K T M U Hemapala on 07 February 2018.

The user has requested enhancement of the downloaded file.


International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

Design, Simulation and Implementation of a UPFC


(Unified Power Flow Controller) for Transmission
Line Model
T.P.G.T.A. Priyankara, M.J.L.R. Fernando, I.A.K.Sandeepa, N.M.K.D Bandara, H.W.D.Hettiarachchi,
K.T.M.U.Hemapala.
Department of Electrical Engineering
University of Moratuwa
Katubadda, Sri Lanka.

Abstract—Generally the power system is frequently faced and other static equipment that provide control of one or
various disturbances. These disturbances will cause to more AC transmission system and increase the capacity
create harmonics and oscillations in the system which lead of power transfer”
to operate protection relays. Further this will cause to create
a total system failure. Different techniques and devices are As Fig. 1 depicts, FACTS devices can be subdivided
used in order to control these power system oscillations and
improve the power quality. One of the techniques is use of
in to two categories based on the power electronic
FACT (flexible alternating current transmission system) devices used in the control. They are Voltage Source
devices. FACT devices improve controllability of power Converter (VSC) based FACTS and Thyristor valve base
system operation. The unified power flow controller (UPFC) FACTS. UPFC is modern FACTS device which was
is one of the recently founded FACT device which is developed based on VSC control technology. Different
constructed using modern power electronics technology to
control the active and reactive power of the power system.
FACTS controllers are used to provide corrective actions
Developing an UPFC for transmission line model and for different steady-state operating problems in power
analyzing impact on power quality on transmission line in system. Table 1 shows some applications of the FACTS
abnormal conditions would be presented in this paper. devices.
Moreover, MATLAB/Simulink models for subsystems of the
UPFC are also developed to create a simulation model of
UPFC with transmission line model.

Keywords—UPFC, FACTS, STATCOM, SSSC

I.INTRODUCTION
Dynamic nature of the power system causes to
frequent disturbances in the system which can drive the
system to an unstable state. This continues failures will
lower the power system reliability and power quality
index of the system. Power quality is a combination of
voltage quality and current quality. The UPFC is one of Fig. 1.Classification of FACTS devices
the modern FACTS device that can be used to improve
power quality and reliability. UPFC also increases TABLE I. FACTS CONTROLLERS FOR STEADY- STATE
OPERATING PROBLMES
transient and dynamic grid stability of the system by
controlling both active and reactive power flow through a Operating problem Corrective action FACTS controller
Voltage limits:
transmission line. With the increasing demand, the Low voltage at Supply reactive
SVC, STATCOM
existing transmission network should be used optimally heavy load power
rather than constructing new transmission lines. UPFC High voltage at low Absorb reactive SVC, STATCOM,
load power TCR
provide better utilization of transmission system assets Thermal limits:
which already exist and provide environmental benefits. Transmission circuit
Reduce overload
TCSC,
overload SSSC,UPFC,PS
FACTS technology concept was introduced by Tripping of parallel
Limit circuit loading TCSC,SSSC,UPFC,PS
Electric Power Research Institute (EPRI) in the late circuit
Power flows:
1980’s. This concept is used in worldwide to improve the
Parallel line load Adjust series
system quality, reliability, stability and power flow with sharing reactance
TCSC,SSSC,UPFC
the existing power systems [1]. FACTS technology is Power flow direction
defined by the IEEE as "a power electronic based system Adjust phase angle TCSC, SSSC,PS
reversal

1
978-1-5090-5682-8 /17/$31.00 ©2017 IEEE
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

The UPFC is the most versatile device which B. STATCOM


designed based on the combination of both series and
shunt FACTS devices. Shunt FACTS device (Shunt STATCOM is also a VSC based FACTS device which is
Converter) or STATCOM (Static Synchronous shunt connected with transmission line. Current flowing
Compensator) is used to control the reactive power flow through converter is controlled to adjust the bus voltage,
in the transmission line. Series FACTS device (Series i.e. reactive power flow of the transmission line.
Converter) or SSSC (Static Synchronous Series STATCOM has many advantages over a SVC (Static Var
Compensator) is used to control the series injecting Compensator). Some of them are listed below. [2]
voltage and phase angle which is injected to the
¾ Quick response.
transmission line through series transformer. These two
¾ Space requirement is less because STATCOM
converters are combined with a common dc link. This
doesn’t use bulky passive components such as
capacitor has small energy storing capacity. So, active
capacitors and reactors.
power generated by the series converter should be equal
¾ STATCOM can be interfaced with real power
to the active power flow through the shunt converter [1].
sources.
Fig.2 shows schematic diagram of the UPFC.
UPFC is come with advantages of both SSSC and
II.FACTS DEVICES
STATCOM. And has technological edge from
Many research have been done in the field of FACTS. controllability and flexibility aspect over the other
Since UPFC is one of the modern FACTS device, FACTS devices.
fewresearch have published with reference to UPFC. Lot
of them are simulation models and it is hard to find actual C. D-Q axis control strategy
harware design of a UPFC. Based on the control strategy
Three phase voltage and current is converted in to
used, UPFC has the flexibility to control anyoperation
two axes (D and Q) in this strategy for controlling
functions.D-Q control strategy is used in this research
purposes. Here, measured voltage and current of the
among different control strategies. Operation of UPFC,
transmission line is split into two components which are
main two components of the UPFC, i.e. SSSC (static
in phase with D axis and Q axis using abc to dq0
synchronous series compensator strategy) and
transformation method. These two components provide
STATCOM(static synchronous compensator)and
details about three phase voltage and current. According
different control strategies would bediscussed here.
to these readings, D and Q axis component of the
A. SSSC required injecting voltage can be calculated. It should be
added to the transmission line to maintain the system
SSSC is one of the voltage source converter(VSC) based stability. Then dq0 to abc transformation gives the
FACTS device which is connected in series with required three phase injecting voltage which should be
transmission line. SSSC provides advanced series injected to the line through series transformer. Switching
compensation. This has several advantages over a TCSC signals for the power switching devices should be
(Thyristor Controlled Series Compensator). Some of the generated according to that. In series converter, Real
advantages are listed below [2]. power of the transmission line can be controlled using D
¾ SSSC doesn’t use bulky passive components axis voltage by adjusting D axis current. Reactive power
such as capacitors and reactors. of the transmission line can be controlled using Q axis
¾ Operation capability in both inductive and voltage by adjusting Q axis current component. [3-5]
capacitive mode.
¾ Improved technical characteristics. In shunt converter, D-axis shunt current component is
¾ Real power exchange is possible between DC related with DC capacitor voltage and Q-axis shunt
side and AC network. i.e. energy source can be current component is related with reactive power.
connected on the DC side.
D. Phase Shifter Strategy(PS)

In this strategy, injecting voltage is maintained in


quadrature with UPFC bus voltage which shunt converter
is connected. Phase angle of the transmission line sending
end voltage can be varied to obtain specific active power
flow. [7-9].

E. Operation of the UPFC

The UPFC consist of mainly three parts. They are


converter circuit, inverter circuit and controller circuits.
Inverter circuit provide the main function of the UPFC.
Fig. 2.Schematic diagram of the UPFC
2
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

By using inverter circuit, controllable ac voltage with a III.SIMULATION MODEL OF UPFC AND TRANSMISSION
magnitude of ܸ௦ ሺͲ ൑ ܸ௦ ൑ ܸ௦ሺ୫ୟ୶ሻ ሻ and phase angle of LINE
‫׎‬ሺͲ ൑ ‫ ׎‬൑ ͵͸Ͳሻcan be injectedto the transmission line In order to develop Simulink model of the UPFC,
through series transformer. Fig.3 and Fig.4 shows the Total system have been sub divided in to several sub
single line diagram and voltage and current phasor systems and develop Simulink models. Sub systems are
diagram of UPFC respectively. simulated separately and integrated these subsystems as a
one system.
The series injecting voltage which has magnitude of
ܸ௦ and phase angle of ‫ ׎‬can be controlled by controlling A. Transmission line model
the converter and inverter circuit operation. It implies that
ܸଶ and ߜ can be controlled. Active and reactive power Transmission line model is designed to test the operation
flow through transmission line can be calculated using of the UPFC. As Fig.5 UPFC is connected in between
following equation. transmission line 2 and 3. By using this configuration,
active power and reactive power flow through the
ܸଶ ܸଷ ܵ݅݊ሺߜሻ transmission line 3 can be controlled.
‫ݓ݋݈݂ݎ݁ݓ݋݌݁ݒ݅ݐܿܣ‬ሺܲሻ ൌ
ܺ
In this Simulink model, different loads are connected
ܸଶ ሺܸଶ െ ܸଷ ‫ݏ݋ܥ‬ሺߜሻሻ to switch from the system at different times. UPFC is to
ܴ݁ܽܿ‫ݓ݋݈݂ݎ݁ݓ݋݌݁ݒ݅ݐ‬ሺܲሻ ൌ 
ܺ be connected between bus 3 and bus 4 as Fig. 6.
According to that, by adjusting magnitude of B. Inverter & Converter circuits
ܸ௦ and phase angle of ‫ ׎‬, both active and reactive power
flows through transmission line can be controlled. Inverter circuit controls the magnitudeሺܸ௦ ሻand phase
angle ሺ‫׎‬ሻof the injecting voltage. By controlling the gate
The main function of converter is to absorb or signals of the IGBT, the series injecting voltage can be
supply real power to inverter circuit through dc link. It controlled.
can also absorb generated adjustable reactive power if it Converter circuit control the DC link voltage input to
can provide bidirectional operation. By disconnecting the inverter circuit. Active power flow through converter-
from DC link and connecting to the DC source, converter inverter circuit can be controlled by controlling the gate
and inverter can operate independently. (i.e. as signals of the IGBTs.
STATCOM and SSSC)

Bus 1 Bus 2

Bus 3 Bus 4 Bus 5

Fig. 5. Demonstration model of UPFC


Fig.3.Single line diagram of the UPFC

Fig.4.Phasor diagram Fig.6.Simulink Model of the Transmission Line Model

3
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

IV.CONTROLLING OF UPFC B. Series controller


In this model, it calculates the required voltage Voltage at bus 3 & 4(V3 & V4) and line current
magnitude and the phase angle of the injecting voltage flowing through the bus 4 (I4) are used as inputs in series
which need to maintain desired condition of the system. controller. Here also d-q axis control method is used. By
D-Q control strategy is used to calculate this injecting taking reference active and reactive power as inputs (Pref
voltage. and Qref), it calculates the reference d-axis and q-axis
A. Shunt controller current component (Idref and Iqref) which should be
maintained in the system.
In here, Voltage at DC link (Vdc) and bus 3 voltage
(V3) are taken as inputs to shunt controller. In that PI controller is used to get required voltage
controller, first three phase voltage is converted to d-q which should inject in series with line to maintain the
axis values. Vdc and V3 are used to calculate reference d- stability and quality of the power flow. Fig .8 shows the
axis current (Id) and q- axis current (Iq) values. Then Simulink model for the series controller with necessary
current regulator is used to calculate required voltage and control blocks.
required phase angle. Fig .7 shows the Simulink model.

Fig 7: Simulink model of the shunt controller

Fig.8. Simulink model of series controller


4
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

V.SIMULATION RESULTS AND ANALYSIS TABLE II. STAT ICAL DATA OF SIMULATION

Validity of the simulation is tested using the designed STANDARD


DEVIATION(KV) MEAN VOLTAGE(KV)
transmission model under several circumstances to ensure
the reliability and better performance of the UPFC over UPFC 0.486 2.85
other power electronic devices for voltage compensation.
As shown in Fig.9, at t=0.2 s large reactive load is STATCOM 0.624 2.76
parallelly connected to the transmission line before the SSSC 0.711 2.66
UPFC and followed by the another load connected at
t=0.4s after the UPFC while those are disconnected at
t=0.6s and t=0.7s respectively. Transmission line voltage is Reactive Power Reference
observed under two scenarios where UPFC connected and
SSSC is connected. Same type of analysis has been done
using a comparative study of UPFC and shunt device
STATCOM which is shown in Fig.10.
In both cases, it is clearly seen that voltage suppression is
better represented by the UPFC device under the
perturbation of the loads connection and disconnection.
With the statical data shown in Table 2. this is further
proved as the standard deviation of the voltage get reduced
and the mean voltage gets enhanced with the replacement
of UPFC.

Voltage Variation
Fig.11. Comparative analysis of reactive power reference of
UPFC and SSSC

Fig.11 depicts the variation of reactive power reference


signal generation of the control system of UPFC and
SSSC. When the reactive power reference of the
transmission line is set up to 0.5 at t=0.5 s UPFC controller
responds to it quickly where it shows the rising time of
0.1s only.

In case of a large reactive load(30 Mvar) connected


transmission line, behavior of the system voltage with and
without UPFC is studied in Fig.12. At t=0.1 s UPFC is
bypassed where it shows serious voltage unitability of the
system and then at t-0.3s it is reconnected to the line,
Fig.9. Comparative analysis of UPFC and SSSC where it shows responsive stability of voltage despite of
load switching at t=0.6s.

Voltage Variation
Voltage Variation

Fig.10. Comparative analysis of UPFC and STATCOM


Fig.12. Disconnection and reconnection of UPFC

5
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

VI.CONCLUSION [4] S. Tara Kalyani and G. Tulasiram Das. “SIMULATION OF D-Q


CONTROL SYSTEM FOR A UNIFIED POWER FLOW
UPFC is one of the modern technology use in the world CONTROLLER”. ARPN Journal of Engineering and Applied
to maintain the power quality. The concept is still in Sciences. vol. 2, no. 6, december 2007.
developing stage and most of research are still in [5] Mirjana Milosevic. “Decoupling Control of d and q Current
Components in Three-Phase Voltage Source Inverter”.
simulation level. It uses modern power electronic [6] Acha, Enrique. FACTS. 1st ed. Chichester: Wiley, 2004. Print.
concepts and power system theories to achieve its [7] MubeenSaminaElyas, Nema RK, AgnihotriGayatri. Power flow
optimum operation in the system. control with UPFC in power transmission system. World
AcadSciEngTechnol 2008;2:287e91.
MATLAB/Simulink was used for simulation purpose [8] Padiyar KR. FACTS: controllers in power transmission and
in this research. This paper provides a detailed discussion distribution. New Age 2007. ISBN No. 9788122425413.
[9] Lerch E, Povh D, Witzmann R, Hlebcar R, Mihalic R. Simulation
about UPFC and its operation. Addition to that, and performance analysis of unified power flow controller. CIGRE
importance of FACTS devices to increase the power August 1994.
quality and reliability of power transmission is also [10]VaishaliKuralkar, “Active and Reactive Power control using
included here. Furthermore, the paper discussed about UPFC”, International Journal of Engineering Research and General
Science Volume 2, Issue 6, October-November, 2014
control strategies of UPFC, transmission line model [11]S. Muthukrishnan, Dr. A. Nirmal Kumar, “Comparison of
design, series and shunt controller designs. Simulation and Experimental Results of UPFC used for Power
Quality Improvement”, International Journal of Computer and
ACKNOWLEDGEMENT Electrical Engineering, Vol. 2, No. 3, June, 2010.
[12]Prof.KishorPorate, N Santhosh Kumar, “Experimental Verification
The authors gratefully acknowledge the support provided and Matlab Simulation of UPFC for Power Quality Improvement”,
by the Senate Research Council, University of Moratuwa IOSR Journal of Electrical and Electronics Engineering (IOSR-
(SRC/LT/2015/04). JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 2
Ver. VII (Mar – Apr. 2014).
[13]S. Muthukrishnan,Dr. A.Nirmalkumar, G. Murugananth, “Modeling
REFERENCES and Simulation Five Level Inverter based UPFC System” ,
[1] Shraddha S. Khonde, S. S. Dhamse, Dr. A. G. Thosar, “Power International Journal of Computer Applications (0975 – 8887)
Quality Enhancement of Standard IEEE 14 Bus System using Volume 12– No.11, January 2011.
Unified Power Flow Controller” International Journal of [14] B. Kawkabani, B. Kawkabani, J. Simond, “Modeling and Transient
Engineering Science and Innovative Technology (IJESIT) Volume Simulation of Unified Power Flow Controllers (UPFC) in
3, Issue 5, September 2014. PowerSystem Studies”.
[2] Padiyar, K. R. FACTS Controllers In Power Transmission And [15]K.Suresh, P.Venkatesh, “Modelling and Controlling of
Distribution. 1st ed. New Delhi: New Age International, 2007.
Print.
Unified Power Flow Controller (Upfc)” ,International
[3] M. R. Qader, "Design and simulation of a different innovation Journal of Modern Engineering Research (IJMER)Vol.2,
controller-based UPFC (unified power flow controller) for the Issue.4, July-Aug 2012 pp-2574-2577
enhancement of power quality," Energy, vol. 89, pp. 576–592, Sep. [16] Alok Kumar Mohanty, Amar Kumar Barik, “Power System
2015. Stability Improvement Using FACTS Devices”, International
Journal of Modern Engineering Research (IJMER).